Dometic SMX II, SMXir Description And Installation Manual

DX Modulating A/C System
INSTALLATION • OPERATION
For DX Modulating SMX II Control Systems using SMXII and SMXir displays
Revised: 08-29-06 L-0952 English
Part Number: LP-28
Table of Contents
Modulating A/C Systems • Introduction
Drawings and Diagrams ................................................................... 4
Air Conditioner Basics ...................................................................... 4
The Effect of Seawater Temperature ................................................ 4
The Modulating System .................................................................... 4
How it Works in General ...................................................................4
How it Works in Detail ...................................................................... 5
Subsystems ..................................................................................... 6
Condensate Drain ............................................................................ 6
Modulating A/C System • Installation
Installation Procedures ..................................................................... 7
Electrical System ............................................................................. 7
Voltage and Frequency ..................................................................... 7
Installing The Condensing Unit
Selecting the Site ............................................................................. 7
Site Location Checklist ..................................................................... 7
Mounting the Condensing Unit ......................................................... 7
Installing the Seawater Cooling System
Importance of a Self-Draining System .............................................. 8
Through-Hull Inlet Fitting .................................................................. 8
Seacock ........................................................................................... 8
Strainer ............................................................................................. 8
Seawater Pump ................................................................................8
Manifolds ..........................................................................................8
Overboard Discharge ....................................................................... 9
Seawater Piping ............................................................................... 9
Bonding ............................................................................................ 9
Installing The Cooling/Heating Unit
Selecting the Site ............................................................................. 9
Site Location Checklist ..................................................................... 9
Mounting the Cooling/Heating Unit ................................................. 10
Installing the Refrigerant Tubing ......................................................10
Installing The Air Distribution System
Return Air Grill ............................................................................... 10
Ducts .............................................................................................. 10
Ducting Guidelines .........................................................................10
Discharge Air Grill .......................................................................... 11
Installing the Cooling Unit Control
SMX II Control System ...................................................................11
Installing the Power/Logic Box ........................................................ 11
Installing the SMXir Keypad/Display ...............................................11
SMX Interconnect Cable ................................................................ 11
Installing the Temperature Sensor .................................................. 12
Installing the Pump Relay
Location .......................................................................................... 12
Operation ....................................................................................... 12
Voltage and Triggers .......................................................................12
Electrical Connections
General Electrical Notes ................................................................ 12
Three Phase Power ........................................................................13
Final Inspection
Inspecting the Seawater Cooling System ....................................... 13
Inspecting the Condensing Unit ...................................................... 13
Inspecting the Cooling/Heating Unit ............................................... 13
Inspecting the Refrigerant Connections ..........................................14
Inspecting the Air Distribution System ............................................ 14
Inspecting the Control and Electrical Wiring ...................................14
Charging the System with Refrigerant
Initial Charging, New System ......................................................... 14
Adjusting the Charge ...................................................................... 15
Removing Refrigerant from the System ..........................................16
Initial Start Up ................................................................................. 16
Modulating A/C Systems • Operation
Operating Instructions - SMX II Control Systems
The SMX Keypad/Display............................................................... 17
The SMXir Remote Control ............................................................ 18
Basic Operation
Power On .......................................................................................19
System Off .....................................................................................19
Selecting Setpoint .......................................................................... 19
Displaying Temperature .................................................................. 19
Cool Mode ...................................................................................... 19
Heat Mode ...................................................................................... 19
Automatic Changeover ...................................................................19
Manual Fan Speed Control ............................................................. 19
Automatic Fan Speed Control .........................................................19
Adjusting Brightness ...................................................................... 19
Using The Humidity Control Routine...............................................19
Custom Programming Record ........................................................ 20
Programming the SMX II System
Programming Summary Table ........................................................ 21
Factory Memory Reset ................................................................... 21
Auxiliary (Electric) Heat .................................................................. 21
Fahrenheit/Celsius Display ............................................................. 21
Setpoint Differential ........................................................................21
Fan Response Differential .............................................................. 21
Continuous Or Intermittent Fan ...................................................... 22
Low Fan Speed Adjustment............................................................22
High Fan Speed Adjustment ........................................................... 22
Temperature Calibration ................................................................. 22
Humidity Control Program
Programming The Time Period ....................................................... 23
Programming The Dehumidification Time .......................................23
Recommended Humidity Control Settings ...................................... 23
Fault Shutdowns and Error Messages
Software Error ................................................................................ 23
Determining Your Software Version Number ................................... 24
Compressor Time Delay 24
Owner Maintenance
Condensate Drains .........................................................................24
Air Filters ........................................................................................ 24
Seawater Connections ................................................................... 24
Seawater Pump .............................................................................. 24
Seawater Strainer ........................................................................... 24
Refrigerant Gas .............................................................................. 24
Winterizing the System .................................................................. 24
Trouble Shooting 24
Limited Warranty Periods 26
Owner’s Limited Warranty 27
Description of Figures 29
Cruisair Worldwide Service Dealer Locator 41
L-0952
3
English
Modulating A/C Systems • Introduction
Warning
This manual contains essential information concerning the safe and proper installation and operation of your Cruisair air conditioning system. If there are any statements or procedures in this manual that you do not understand, contact the Dometic Applications Department for assistance. Phone 804-746-1313 (8am - 5pm US Eastern Time), Fax 804-746-7248, or email sales@dometicenviro.com, attention applications department.
Notice
US federal law prohibits the intentional release of refrigerant gases into the environment, including the R-22 refrigerant used in most Cruisair air conditioning systems. Special care must be taken when installing, charging, and servicing Cruisair equipment to prevent any loss of refrigerant. Only EPA certified technicians with the proper equipment should perform service on the refrigerant circuit of the system.
Drawings and Diagrams
The figures that are referenced throughout this manual can be found immediately after the warranty section of the manual. In addition, some Cruisair equipment will be shipped with specific installation sheets or wiring diagrams that may supercede the information located in this manual.
Air Conditioner Basics
The basic principle of an air conditioner is the movement of heat. In a direct expansion (DX) water-cooled air conditioner, heat is transferred from the cabin air to the refrigerant in the cooling unit. The refrigerant is routed back to the condensing unit where the heat is transferred to the seawater.
The heat exchange process relies on the movement of both cabin air and seawater to work effectively. If airflow or seawater flow is compromised, the efficiency of the system will drop, and the unit could shut down on one of its safety protection devices, or eventually become damaged.
Part of the cooling process, in addition to lowering the air temperature, is the removal of moisture from the air. This lowers the humidity, which makes the area feel more comfortable, and helps keep the boat dry, reducing mold growth and other moisture related problems.
The Effect of Seawater Temperature
The efficiency of the system is dependent on both the seawater and cabin temperatures. The air conditioner works best when the seawater temperature is below 90°F (32°C). The unit will operate at higher water temperatures, but at reduced capacity. As the water temperature rises, so does the refrigerant pressure. A high-pressure safety switch will shut the unit down if the water temperature gets too hot, or if there is a loss of cooling water flow.
Warning
Do not operate your A/C unit in water that is colder than 38°F (3.3°C). Doing so could lead to water freezing in the condenser coil, which can cause damage to the unit.
The Modulating System
Unlike a standard DX remote condensing unit system, the Cruisair modulating system allows independent thermostatic control of up to five cooling units, all run by one compressor. The FM type modulating condensing unit is cooling only. If heat is desired, the cooling units should be ordered with the optional electric heating element. One advantage to this is that an individual unit can be in heating mode even when the rest of the system is cooling.
How it Works in General
The Modulating System air conditioner consists of a special condensing unit and multiple evaporators (cooling/heating units), connected by copper refrigerant lines. The cooling/ heating unit, located in the cabin or area to be cooled, consists of a blower, an evaporator coil and an optional electric heater. Each area has an SMX microprocessor control which allows independent control over that zone.
The condensing unit, located in the engine room or machin­ery space, consists of a compressor, seawater condenser, compressor relay, and other electrical and refrigeration components.
Refrigerant lines connect the condensing unit to each cooling unit, and a pair of signal wires run from each cooling unit to the compressor relay on the condensing unit to signal the compressor to run.
The cooling/heating unit blower draws warm humid cabin air across the fins on the evaporator where the heat from the air is transferred to the refrigerant in the evaporator coil. As this happens, moisture in the air is captured on the evaporator coil in the form of condensation and drips into the base pan. As the refrigerant absorbs the heat from the cabin air, it evaporates from a liquid into a gas. The compressor then compresses the hot gas and pumps it through the outer tube
L-0952 Introduction
4
English
in the condenser coil. The seawater pump circulates rela­tively cool seawater through the inner tube in the condenser coil. The heat from the refrigerant is exchanged to the seawater and discharged overboard. This cools the refriger­ant and condenses it into a liquid. The liquid refrigerant is then passed through the evaporator coil and the cycle repeats. Removing heat and moisture from the cabin air lowers its temperature and humidity levels. In the electric heat mode, a solenoid valve on the cooling/heating unit closes and stops the flow of refrigerant through that one unit while the blower remains on. The electric heater energizes, warming the cabin air as it is drawn over the heating ele­ments. The conditioned air is blown through the ducting and out the supply air grill(s).
The Modulating system can operate up to five independently controlled cooling/heating units at one time. Unlike the typical “split” system, the Modulating system adjusts to the number of cooling/heating units that are on line and operational. The control and setpoint of any zone can be set to the desired temperature, heating or cooling, and the Modulating system will condition that zone accordingly. Note that the cooling units must have the optional electric heaters to heat the cabin.
The cabin controls are independent of each other and relay a signal to the condensing unit, turning it on in the cooling mode. If the cabin control is set for heating, a solenoid valve stops the flow of refrigerant through the cooling/heating unit’s evaporator coil and energizes the electric heater. The Modulating system is designed to provide the most flexibility in independent zone control of any split refrigerant-based system by providing heating or cooling at the same time, but in different cabins.
How it Works in Detail
The Condensing Unit
The modulating condensing unit consists of the compressor, the receiver, the heat exchanger or condenser coil, a hot gas by-pass valve and a “de-superheat” valve, the associated electrical components, and the system service valves. These parts work together to compress the expanded refrigerant, flowing back from the cooling unit to the compressor, into a high-pressure state. The compressed refrigerant then passes through the heat exchanger (condenser coil) where it gives up the heat that was absorbed in the cooling (evapora­tor) coil. It is then condensed to a liquid state as it flows to the liquid receiver. The process is repeated as the refrigerant flows back to the cooling unit. The bypass valve senses the increased pressure when a cooling unit is removed from the system, such as when an area is thermostatically satisfied, and allows the refrigerant to flow back to the suction side of the compressor.
When cooling is called for by the thermostat control of one of the cooling/heating units, a signal is sent to the
relay
. This signal relays power to the compressor allowing it to operate. As the system comes on, low-pressure refrigerant gas flows back from the cooling/heating units to the
lator.
The accumulator is a storage place for the refrigerant and ensures that only gas, and not liquid, refrigerant makes it back into the compressor. The presses the refrigerant into a high-pressure gas and dis­charges it into the refrigerant gas is cooled and condenses into a high-pressure liquid as it passes through the outer tube of the condenser coil. The heat from the refrigerant gas is exchanged to the seawater, which flows through the inner tube of the con­denser coil, and is pumped overboard. The refrigerant then flows into the way back to the cooling/heating units.
If all cooling/heating units (up to five) are on and running then the system operates just like standard remote DX equipment. However, as cooling/heating units cycle off and the suction pressure coming back from those units starts to get lower, the Modulating System starts to compensate for the changes in refrigerant pressure and temperature extremes. The two unique components on the condensing unit that serve to balance the system are the
Bypass Valve
The Hot Gas Bypass Valve is positioned between the suction line leading into the accumulator and the discharge line coming out of the compressor. If the
low
(<55psi) then the Hot Gas Bypass Valve opens and
helps to raise the suction side pressure.
The TX Valve is positioned between the receiver and the accumulator and senses the temperature of the suction line leading into the compressor. If the
too high
from the receiver to the accumulator, lowering the tempera­ture of the gas going into the compressor. If the suction side pressure drops below 35psi then the low-pressure switch will open. The condensing unit is also equipped with a high­pressure switch that opens when the discharge pressure rises above 425psi. (See Figure 12)
then the TX Valve opens and flashes cool refrigerant
condenser coil.
receiver
and the
that stores the liquid refrigerant on its
“De-Superheat” TX Valve
compressor
The high-pressure hot
suction pressure gets to
suction temperature gets
compressor
accumu-
then com-
Hot Gas
.
The Refrigerant Lines and Manifolds
The refrigerant lines are made of copper tube that is sized for the BTU load of the system. The suction lines are always larger than the discharge lines. The suction lines must be insulated. They supply both liquid and gas refrigerant to and from the evaporators and the condensing unit. Typically, the condensing unit lines are larger and will connect to a refrigerant manifold. At the manifold, the lines will reduce in size to supply the independent evaporators. (See Figure 11.)
L-0952 Introduction
5
English
The Cooling/Heating Units
The cooling/heating units are independently controlled and are located in the cabin areas. They consist of a blower, air heat exchanger, electric heat element, solenoid valve and control. In the cooling mode, the control sends a signal to the condensing unit to operate. The solenoid valve opens allowing the refrigerant to pass through the air exchanger. The fan’s control and setpoint operation are typical to any thermostatically controlled system. Once the setpoint is reached, the unit slows, and then closes the solenoid valve automatically. As the temperature rises, the unit will turn on again and continue this cycle maintaining the desired room temperature.
If heat is needed, the solenoid valve closes, stopping the flow of refrigerant through the evaporator coil. The electric heat elements are energized and the fan turns on. Once the setpoint is reached, the unit slows, and then turns off automatically. This cycle will continue also, maintaining the desired room temperature.
The SMX Control
The SMX control is a microprocessor cabin control that works in conjunction with the condensing unit’s compressor relay. Once the control is set for either cooling or heating mode and the setpoint is selected, the SMX will automati­cally maintain the desired room temperature. It will cycle the blower on and off, conditioning the cabin air. It will also send a signal to the condensing unit energizing the compressor in the cooling mode. In the heating mode, the signal is relayed from the compressor to the electric heating elements in the air handler, heating the air in the cabin.
seawater pump serves multiple condensing units, then a pump relay and water manifold are required.
Air Distribution System
Cabin air is drawn into the cooling unit through a return air grill. It is then cooled (or warmed if the electric heat option is installed) and blown back into the cabin through a ducting system. The air should be discharged high in the cabin and away from the return air grill to ensure good circulation. An air filter is located on the cooling unit or on the return air grill and must be cleaned regularly.
System Controls
The SMX II microprocessor circuit board, controlled by the SMXir keypad/display, provides a comfortable environment and ensures overall system protection. With over 22 pro­grammable functions, the SMX can be customized to suit any environmental application. The SMX monitors incoming line voltage and extremes in refrigerant pressure, and will shut the system down to prevent damage if necessary.
Condensate Drain
When the air conditioner is running in the cooling mode, moisture is removed from the air by the evaporator coil. This condensation is then caught in a drain pan and must be drained off to a sump or overboard. In humid climates the system can produce a large amount of condensate water that could cause significant damage to your boat if the drain system doesn’t work properly.
The Compressor Relay
The compressor relay is located on the condensing unit and is the hub for the evaporators. It has a series of relays (called “triggers”), one for each evaporator in the system. As the evaporators call for cooling, a signal is sent to the relay box. This signal energizes a trigger, which in turn relays current to the compressor. Any number of triggers can be energized at the same time commanding the compressor to run. The triggers are independent components and can be added or replaced as needed. This control box is in addition to the standard start components required for the compressor.
Subsystems
Subsystems are purchased separately because of the many variations and options available. These include the seawater, air distribution, and control subsystems.
Seawater System
The seawater system consists of an inlet through-hull fitting, water shut-off valve, strainer, pump, and overboard dis­charge fitting, all connected by hose or piping. If a single
L-0952 Introduction
6
English
Modulating A/C System • Installation
Installation Procedures
This section covers the installation procedures for the Cruisair Modulation System, including electrical connections and SMXir control installation. Please read and understand this manual before attempting to install any equipment.
Electrical System
Cruisair air conditioning systems are available for use with common power supplies throughout the world. In the United States and most of North and South America, the systems are 115V or 230V, 60Hz, single phase AC (alternating current). In Europe and most of Asia, power systems are typically 230V 50Hz single phase.
The compressors used in Cruisair Modulating condensing units are only available in 230V single phase, 230V 3-phase, or 380/460V 3-phase. On 380/460V 3-phase units there is a separate lower voltage circuit for the controls, either 115V or 230V. On some power systems this can be supplied by using one input line and the neutral. If not, a separate control power feed or a transformer will be required.
Running and starting loads of an air conditioning system are often the largest electrical loads on a boat. It is important that the power supply system is large enough to handle these loads. Contact an electrician if you are not sure about the proper wiring procedures. Always follow local and ABYC codes for proper wiring guidelines.
Voltage and Frequency
The voltage rating of a unit is a nominal rating. The available power supply voltage may be higher or lower by as much as 10% and the system will still operate properly. For example, at 60 Hz, voltages my range from 110VAC to 120VAC, or 208VAC to 240VAC, or 440VAC to 480VAC. In a 50Hz environment, common voltages range from 220V to 240V, or 380V to 415V.
When choosing a system, the voltage and frequency must be known. While standard 60Hz equipment can often be run at 50Hz, it will experience a 17% drop in performance. However, 50Hz equipment can not be run at 60Hz because the 50Hz motor will run too fast and become damaged. Seawater pumps will lose even more performance at 50Hz due to the nature of centrifugal pumps.
Dedicated 50Hz units will give full performance at 50Hz, and should be used when the system is going to be run exclu- sively at 50Hz. If a boat is traveling in 50Hz and 60Hz environments, then 60Hz equipment should be installed, with special attention to sizing (especially the pumps) so that the system performs to expectations. When running 60Hz
L-0952 Installation
equipment at 50Hz, the voltage should be reduced by 17% to prevent overheating a motor.
Installing The Condensing Unit
Ignition Protection Warning
Most Cruisair remote condensing units meet federal requirements for ignition protection. However, there are some condensing units, such as those with 3-phase compressors, which are not ignition protected. Do not install non-ignition protected units in spaces containing gasoline engines, tanks, LPG/CPG cylinders, regulators, valves or fuel line fittings. Failure to comply may result in injury or death.
Selecting the Site
Cruisair condensing units are designed to be installed in any convenient location. The unit is normally placed in the engine room or other machinery space, but it can be located in the living areas. The condensing unit will produce condensation so a drain line from the drip pan is needed in these installa­tions. The space around the unit can be insulated to reduce noise if desired. The unit is internally cooled and does not require ventilation. The location selected should provide for access to refrigerant, seawater, and electrical connections and be accessible for service. It should be installed on a flat, horizontal surface away from direct spray from engine air intakes or water wash-down.
Site Location Checklist
• Adequate space for access to refrigerant, seawater and
electrical connections.
• Accessible for service and maintenance.
• Flat, horizontal surface.
• Away from direct spray from engine air intakes or water
wash-down.
Mounting the Condensing Unit
Orient the condensing unit (Figure 1) so the refrigerant, electrical connections and service ports are accessible. Use the supplied “L” brackets to bolt the unit down. Fasten the mounting base pan securely in such a way that the unit can be removed for future service if need be.
Do not remove any covers, caps or fittings that may expose any wiring or refrigerant. Only remove these items when you are ready to complete the installation. Removal of any covers may result in damage to the electrical components. Removal of the caps or fittings may result in refrigerant loss.
7
English
Installing the Seawater Cooling System
The seawater system consists of a scoop-type thru-hull fitting, water shut-off valve or seacock, strainer, seawater pump, water hose and overboard discharge fitting. If more than one condensing unit is using a single seawater pump, a water manifold and pump relay are also needed.
Importance of a Self-Draining System
Along with restricted ducting, a poorly plumbed seawater system is one of the most common installation problems on marine air conditioners. When water flow is lost, not only will the air conditioning units no longer cool or heat, the units and pump could be damaged from running dry.
When using a centrifugal seawater pump, it is imperative that the seawater piping be routed continually uphill from the through-hull inlet, valve, and strainer to the pump and then up to the condenser, then smoothly up or down to the overboard discharge, without any dips or loops, and with only one high point in the system (usually the condenser coil or the overboard discharge). This is said to be self-draining because all water would drain out of the piping if the boat were lifted out of the water.
Whenever air gets into the system, which can happen in heavy seas or during a sharp turn, it can become trapped in the pump. Because a centrifugal pump cannot pump air, water flow through the system is lost.
A self-draining seawater system will allow air in the piping to rise naturally through the pump and then be expelled overboard. It will also make winterizing the system much easier. Figure 6 shows a properly plumbed system and some common plumbing mistakes.
Seacock
A bronze, full flow seacock (ball valve type) should be installed directly onto the through-hull fitting. Use Teflon tape or other sealant on the threads. The seacock must be accessible and easy to close in case of emergency, or to clean the strainer.
Strainer
A seawater strainer must be installed between the seacock and the pump, and should be situated to provide easy access for cleaning. The strainer must be located vertically above the seacock and below the pump. Make sure the water flow through the strainer is in the correct direction. Some strainers have an arrow that shows correct flow direction.
Mount the strainer to a bulkhead so it is properly supported before connecting hoses. Use Teflon tape or other sealant on pipe threads.
Seawater Pump
Centrifugal pumps are not self-priming, and must be mounted so that they are below the heeled waterline in any given operating condition. The pump should be located so that it is accessible for future service.
Mount the pump so the outlet is above the pump and directed upward so air can escape thus preventing an air lock in the pump head. The head on some pumps can be rotated to allow mounting on a vertical bulkhead. (See Figure 4.)
Self-priming pumps are available if the pump cannot be mounted below the waterline.
Through-Hull Inlet Fitting
A separate thru-hull fitting and seacock should be used for each seawater pump. Do not attempt to draw seawater from the engine or generator thru-hull fitting. A scoop-type thru­hull is preferred for all installations. It should be installed facing forward and located as far below the water line and as close to the keel as possible, where it will always be under­water. Beware of the change of location of the thru hull fitting relative to the waterline, given the motion of the boat. The ideal location is ahead of the stuffing boxes and aft of the forward engine bulkhead.
To install the through-hull fitting, drill a properly sized hole for the fitting. Place a bead of marine, underwater sealant around the fitting and secure it through the hull. Tighten the nut onto the fitting.
L-0952 Installation
Required seawater flow rate is 4 gpm per ton (12,000 Btu/hr) of condensing unit capacity.
Manifolds
If one seawater pump is serving multiple condensing units, then a seawater manifold will be needed to supply water to each unit. This can be as simple as a TEE for two units, or a custom made manifold for three or more units. It is very important to consider manifold orientation so that all con­densing units get the proper flow of water.
See Figure 5 for manifold information. A manifold can also be used on the outlets of the condensing units when using a single overboard discharge.
8
English
Overboard Discharge
The overboard fitting should be located 1 to 2 inches (25-50 mm) above the vessel’s water line. This is to facilitate visual confirmation of water flow, but close enough to the water to minimize splashing noise. If the overboard discharge fitting must be installed below the heeled water line, then a seacock must be installed per ABYC standards.
Seawater Piping
• Use only reinforced marine grade hose or other suitable piping (PVC, CPVC, cupronickel, or stainless steel).
• Double clamp all hose connections, reversing clamps.
• Use only plastic, bronze, or stainless steel fittings (do not use brass).
• Avoid loops or dips in the hose runs.
• Make sure enough hose is used to allow future removal of components.
• Use the correct size hose, fittings, and components. See the table below for proper sizing. Note that the pump inlet piping (including through-hull and strainer) may need to be larger than the outlet pipe size. Do not use pump connections to determine hose size.
• Use larger hose when the run is longer than 16 feet (5m).
• Required seawater flow rate is 4 gpm per ton (12,000 Btu/ hr) of condensing unit capacity.
Bonding
All metallic parts in contact with seawater must be connected to the vessel’s bonding system. This includes the through­hulls, strainer, bronze pumps, manifolds, and the condensing unit(s).
2ECOMMENDED3EAWATER0IPE3IZES
Installing The Cooling/Heating Unit
Safety Warning
A Cruisair cooling/heating unit should never be placed such that it can circulate carbon monoxide, fuel vapors or other noxious fumes into the boat’s living spaces. Failure to follow this precaution could result in serious injury or death.
Ignition Protection Warning
Cooling/heating units do not meet federal requirements for ignition protection. Do not install in spaces containing gasoline engines, tanks, LPG/CPG cylinders, regulators, valves or fuel line fittings. Failure to comply may result in injury or death.
Safety Warning
Do not terminate air handler condensate drain lines within 3 feet (1m) of any outlet of engine exhaust systems, nor in a compartment housing an engine or generator, nor in a bilge, unless the drain is properly connected to a sealed condensate or shower sump pump. Exhaust and/or bilge fumes can travel up a drain line and mix with the return air blowing into living areas.
Selecting the Site
Typically the unit is located in the cabin under a bunk or in a locker. The discharge air must be ducted from the cooling unit to a grill as high as possible (minimum three feet [1m] above the floor) and away from the return air grill for good air circulation.
It is not necessary that the coil be placed directly behind the return air grill, but an unobstructed path must be provided for the air to get to the coil. A 2" (50mm) space in front of the coil must be maintained if it is not directly behind the return air grill.
&LOW2ATE 0UMP 0UMP
GPM )NLET $ISCHARGE
  
  
  
  
  
  
  
  
  
  
L-0952 Installation
Site Location Checklist
• Unit is not located in an engine room or near an internal combustion engine.
• There is no obstruction of airflow from return air grill to coil.
• Accessible for service and maintenance, including the return air filter.
• Adequate space for condensate drain connections.
• Flat, horizontal and sturdy mounting location.
• Condensate drain can be run continuously downhill from unit to overboard fitting or sump.
• Space is sealed from the bilge, engine room, exhaust fumes or outside air.
• Maximum copper tubing run between condensing unit and cooling unit is 50 ft. (15m)
9
English
Mounting the Cooling/Heating Unit
Mount the cooling/heating unit (Figure 2) so the condensate drip pan is beneath the unit. Use the integral mounting brackets to secure the unit in place. Make sure the unit has access for service. The blower, solenoid valve, and the heater elements should be accessible. The electrical junction box should be mounted in a location with easy access.
Route the condensate drain hose steadily downhill so that the condensate flows freely to an overboard fitting or sump. Do not permit condensation to puddle in the bilge. Cruisair cooling/heating units have two condensate drains on opposite corners. It is recommended to use both drains for best results. If only one condensate drain is used then plug the other fitting. Use Teflon tape on the hose barbs for a watertight seal. The two drains may be teed together, providing there is a minimum drop of 2" (50mm) from the drain pan to the tee fitting. After the condensate drain installation is complete, test the installation by pouring a quart of water into the pan and checking for good flow.
The copper tubing is connected to the condensing unit, distribution manifolds, and cooling units with flare joints. To prevent refrigerant leaks, flares must be formed correctly with the proper flaring tool. Only 45-degree single flares should be used. Flares should be made following the instructions of the particular flaring tool. Make sure to slide the flare nut onto the tube before flaring. A drop of oil on the tube can help the process. The surface of the flare must be smooth and free of defects to ensure that the joint won’t leak. The flare should be large enough in diameter to fill the nut completely.
Use only forged, long-stem flare nuts, such as supplied with Cruisair equipment. Flare nuts should be tightened until the nut ceases to offer resistance to tightening. This is the point where the flared portion of the copper tubing is beginning to flow under the force of the nut being tightened.
Installing The Air Distribution System
Installing the Refrigerant Tubing
Caution
Be careful when bending the extension tubes on the evaporators. Do not allow the tubing to kink and do not twist or bend the tubing at the connection point close to the coil or the joints may crack. If bending by hand make large radius bends. Use a tube bender if a tight bend is required.
Use refrigerant-grade soft copper tubing to connect the cooling units to the condensing unit. See Figure 11 for correct tubing sizes. Distribution manifolds or TEE connec­tions may be used to split the refrigerant lines from the condensing unit to the cooling units.
Only use refrigerant-grade seamless soft copper tubing. Never use any type of plastic or rubber hose.
The tubes can run uphill, downhill, or sloping as required, and can have as many bends as necessary. Avoid shard bends that could result in kinks in the tubing.
The refrigerant distribution manifolds or TEE connections should be located to provide (as close as possible) equal length tubing runs between the manifold and each of the cooling units. All flare connections should be made in an accessible location for future service.
The suction line must be insulated with closed-cell foam insulation. Do not insulate the suction and discharge lines together. When sliding the insulation over the tubes, cover the open ends to prevent debris and moisture from contami­nating the refrigerant circuit. After checking for leaks, insulate the flare joints at the condensing unit, distributors, and cooling units. Secure the tubing every 3 feet (1m) as neces­sary for support.
Refer to Figure 3 for a typical installation and to Figure 7 for proper grill and duct sizes.
Return Air Grill
The return air grill should be located so there is unobstructed airflow to the unit’s evaporator coil. Ducting between the return air grill and the cooling unit is not normally necessary and should be avoided. The grill may be located on a side opposite the evaporator coil so long as airflow to the coil is unobstructed. Cross sectional area of the airflow path must not be less than that of the evaporator coil face.
An air filter must be used to prevent the evaporator coil from collecting dirt and lint. The filter can be located on the evaporator coil or at the return air grill. Cooling units are supplied with an air filter, but if that filter is not easily acces­sible for periodic cleaning, then use a filter on the return air grill.
Ducts
Insulated flexible ducting or built-in ducting must be used to route air from the blower to the discharge grill.
Ducting Guidelines
Secure duct to blower or transition box (plenum) with screws and duct tape. When using insulated flexible ducting, make sure inner duct is secured and sealed to the adapter before pulling insulation over connection.
Plenums, or transition boxes are used with flexible ducting to split and route the discharge air as needed. Figure 8 shows several plenum configurations.
L-0952 Installation
10
English
• Ducting must be properly sized for the airflow. If the duct run is longer than 10 feet (3m), use the next larger duct size.
• Use of insulated duct is recommended, and is mandatory when used in high heat areas or where condensation might occur.
• Rotate blower in the direction of the duct run if possible.
• Install flexible ducting tightly and smoothly, with as few bends as possible.
• Keep duct runs as short as possible.
• Support ducting to prevent sagging during boat operation.
• Trim excess ducting before attaching to transition adapt­ers.
• Make sure ducting is not crushed or kinked.
• Use a flexible transition duct between blower and any built-in ducting.
Discharge Air Grill
Location of the discharge grill should be as high as possible in the cabin (minimum three feet (1m) above the floor), and oriented so that airflow between the discharge and return encompasses as great an area as possible. Care should be taken to avoid “short cycling,” a situation where the condi­tioned air is blown directly back to the evaporator coil without being substantially mixed with the cabin air.
A grill plenum should be incorporated behind the grill to provide a chamber for the air to expand and flow quietly into the living area. The plenum also provides a hose connector to attach the flexible duct behind the grill. (See Figure 8.)
Installing the Cooling Unit Control
Each independent cooling unit in the modulating system will have its own control. Refer to the wiring diagrams in the back of this manual.
SMX II Control System
The SMX II control system consists of:
Power/Logic (P/L) module - Monitors and controls all
functions of the cooling unit.
Keypad/Display - The SMXir is a 10-button user interface touch pad with a digital readout and LED indicators.
Warning
Make sure all power is off before opening any electrical box. Failure to do so may result in injury or death.
Installing the Power/Logic Box
The Power/Logic box has a 3 ft (.9m) wire harness that must be connected to the air handler junction box. These wires can be extended if needed. Refer to installation diagrams in back of this manual.
• It is very important that the P/L box is mounted in an accessible location.
• The SMX P/L board is ignition protected, enclosed, and operates in ambient temperatures up to 130°F (54°C).
• The P/L box may be installed in any position.
• The P/L board dissipates heat when operating, and must be installed in a ventilated location.
• The P/L box is NOT waterproof and must be placed where it will NOT get wet.
Installing the SMXir Keypad/Display
The SMXir keyboard/display should be installed so it is both visible and accessible. It should be placed in plain view and within easy reach of the operator.
Select a spot on an interior, vertical surface. This can be an inside wall, partition or other permanent structure with rear access for wiring. The SMXir control operates on low voltage DC and is certified ignition-protected. The space behind the SMXir control does not have to be ventilated since the control components do not produce heat.
The SMXir keypad is surface mounted, and only requires a hole for the CXP cable. Refer to Figure 10 in the back of this manual for installation instructions. Plug the interconnect cable in and route it to the Power/Logic (P/L) box.
SMX Interconnect Cable
Connection between the SMXir keypad and the Power/Logic board should be made with a CXP cable. This is a shielded cable with RJ12 (phone-type) 6-pin plugs on each end.
CXP cables are available in different lengths, from 2 feet (.6m) to 80 feet (24m). Route the cable from the power/logic board to the keypad. Cable runs should be as short as possible and should not be bundled with high voltabe or antenna cables. Plug the cable in at both ends, and secure per low DC voltage standards.
Temperature-Sensing Element - Air temperature is monitored by a temperature-sensing element (TSEP) that plugs into the power/logic board.
Connecting Cable - The keypad/display connects to the P/L board with a CXP connecting cable.
L-0952 Installation
11
Caution
The CXP interconnect cable transmits low voltage DC signals. It can be affected by outside interference from high voltage cables or other sources. Do not route the SMX interconnect cable beside AC power cables or other high voltage wiring.
English
Installing the Temperature Sensor
The TSEP temperature sensor measures the cabin air temperature and relays the information to the power/logic board. The sensor is 1" long by ¼” diameter (25mm x 7mm diameter) and is attached to a length of flat, 4-conductor cable with an RJ-11 (phone-type) plug at the end. Different lengths of TSEP cables are available, from 2 feet to 80 feet (.6m to 24m).
Operation
PR3X and PR8X pump relays are identical in operation. When any condensing unit turns on, the pump relay will turn the seawater pump on, and the pump will stay on until the last condensing unit shuts down. The PR3X can serve up to three condensing units, and the PR8X can serve up to eight condensing units. Both can operate either 115V or 230V, single phase pumps, with a maximum current of 15 amps.
For best results, the sensor should be placed in the return air path, in front of the system evaporator coil. Directly behind the return air grill is often a good location. The sensor must not touch the evaporator coil, or be placed in the discharge air.
With the TSEP in the return air path, use the default mode of continuous fan operation for the most accurate temperature control. If intermittent fan operation is desired (fan on and off with the setpoint), the sensor must be wall mounted on an INSIDE surface not subject to any influence from heat outside of the area (including direct sunlight). Thermistor covers are available from Cruisair for wall mounting.
The TSEP cable plugs into the RJ-11 jack on the P/L board marked “INSIDE TSE”. Coil up any excess cable, and tie out of the way.
Installing the Pump Relay
The following instructions apply to systems that have multiple condensing units served by a single seawater pump. If there is only one condensing unit on the vessel, or if each unit has its own seawater pump, then skip to the next section.
Location
The pump relay is generally located in the engine room near the seawater pump, but it can be mounted anywhere that is convenient and accessible. It must be mounted in a dry location, away from any possible water spray, with room for some heat dissipation.
Ignition Protection Warning
PR3X and PR8X pump relays are certified ignition protected. However, pump relays with electromechanical relays or contactors (such as 3-phase pump relays) are not ignition protected and must never be installed in spaces containing gasoline engines, tanks, LPG/CPG cylinders, regulators, valves or fuel line fittings. Failure to comply may result in injury or death.
Voltage and Triggers
Triggers are used in the pump relays to isolate the pump signal from each condensing unit. Some pump relays come with pre-installed triggers, or you can buy triggers separately. Triggers come in 115V and 230V, and must match the control voltage of the condensing unit. Both 115V and 230V triggers can be used together in a single pump relay if the system requires it. The trigger is simply a relay that closes when the condensing unit turns on. Because each trigger is isolated, the polarity of the signals from the condensing units does not matter.
Electrical Connections
Warning
Make sure all power is off before opening any electrical box. Failure to comply may result in injury or death.
General Electrical Notes
Failure to properly ground and bond the system will void the warranty, and may result in a dangerous installation.
All electrical connections should be made within the electrical junction boxes supplied with the units. Most units have terminal strips that are labeled or have color-coded wiring. Open terminal strips (such as supplied with switch assemblies) require that the included terminal strip cover be installed over the terminal strip and the back of the switch after installation is complete.
Wiring diagrams are included in the back of this manual and under the cover of the electrical boxes on all units. Contact Dometic if you have any questions about the wiring diagrams.
• Each A/C condensing unit requires its own dedicated circuit breaker of the appropriate size. See data plate on the unit for suggested breaker and wire sizes.
If there is only one A/C unit, the seawater pump can be wired in parallel with the compressor and doesn’t require it’s own circuit breaker (make sure the breaker is large enough for both the compressor and pump). If multiple A/ C units are served by a single pump, then a pump relay is needed, and will require a separate circuit breaker.
L-0952 Installation
12
English
• Each cooling unit that has electric heat should have its own separate circuit breaker. Cooling-only cooling units have only a blower and solenoid that require electrical power and draw very low current. If desired, multiple cooling-only cooling units can be run on one breaker.
The wiring from the cooling unit control to the condensing unit compressor relay is for signal power only. However, this control power is line voltage (230VAC).
All units must be grounded to minimize the potential hazard of electrical shock and personal injury.
• The condensing unit must be connected to the ship’s bonding system to prevent corrosion due to stray electri­cal current. All pumps, metallic valves and fittings in the seawater system that are isolated from the condensing unit by rubber hose or PVC plastic must be individually bonded also.
Use ring or locking fork type wire connection terminals.
Field wiring must comply with ABYC or local electrical codes.
Power to the unit must be within the operating voltage range indicated on the data plate.
Three Phase Power
Three phase motors will run forward or backward depending on the arrangement of the three wire connections. The scroll compressors used on Cruisair Modulating condensing units are direction sensitive. If the wire sequence is incorrect, the compressor will run backwards and not cool properly. It will also make unpleasant noises. Centrifugal pumps are also direction sensitive. Make sure 3-phase motors are running in the correct direction.
Safety Warning
To prevent a possible electrical shock in the event a component has an electrical breakdown, which could result in serious injury or death, always ground the system in the following manner:
• Bond the ground lug on the condensing unit to the ship’s grounding system.
• Check the continuity of the ground system before the system is energized.
Note
Always follow ABYC guidelines or local codes when selecting breakers and wire sizes. ABYC standards are available from: American Boat and Yacht Council, 3069 Solomon’s Island Rd., Edgewater, MD 21036, Telephone: (410) 956-1050
Final Inspection
Prior to charging or energizing the system, conduct a final inspection using the following checklist.
Inspecting the Seawater Cooling System
• Is the seawater pump properly sized for the system?
• Is the pump oriented correctly and mounted securely with the pump outlet above the inlet?
• Is the centrifugal seawater pump located so it is below the water line at all times?
• Are the inlet and outlet through-hulls secure, properly sealed and properly oriented?
• Are all hose clamps tight?
• Are seawater hoses double/reverse clamped?
• Are there any loops or dips in the seawater plumbing that might cause the system to become air-locked?
• Is the strainer located between the seacock and the pump, and is it correctly oriented?
• Are all metallic seawater fittings, the pump, condenser and manifold properly bonded?
Inspecting the Condensing Unit
• Is the condensing unit mounted securely?
• Are the fasteners accessible for future service?
• Use proper wire size with a ground to feed power from the ship’s electrical panel to each cooling unit junction box. Make sure the ground wire is properly connected to the ground buss in the ship’s service distribution panel and to the ground lug in the cooling unit’s junction box.
• Connect the junction box ground lug to the P/L box green wire (or to the switch assembly terminal strip).
• Use proper wire size with a ground to feed the power from the ship’s electrical panel to the condensing unit’s junction box. Make sure the ground wire is properly connected to the ground buss in the ship’s service distribution panel and to the condensing unit’s ground lug.
• Ground the seawater pump, and pump relay (if used) to the condensing unit’s ground lug.
L-0952 Installation
Inspecting the Cooling/Heating Unit
Is the unit securely mounted?
Are condensate drains properly routed to an overboard discharge or sump?
If only one condensate drain is used, have any other drain holes in the drip tray been plugged?
Inspecting the Refrigerant Connections
• Are flare joints made with forged flare nuts and properly tightened?
• Are flare joints and tees properly insulated?
• Are all suction lines individually insulated?
• Are tubes fastened securely to the boat every three feet or as needed throughout their length?
13
English
Inspecting the Air Distribution System
• Is there unobstructed airflow from the return air grill to the coil?
• Is there a lint screen or filter in the return air path where it is accessible for regular cleaning?
• Have flexible ducts been pulled tight to remove bends and constrictions?
• Are grills correctly sized for the system?
Inspecting the Control and Electrical Wiring
• Is the thermostat sensor or thermistor properly located and secured in the return air path and not in direct contact with any metal objects?
• Are all wiring harnesses properly secured?
• Are wiring connections made, color-to-color, correctly at terminal strips?
• Are all components properly grounded and bonded?
• Are proper sized circuit breakers installed?
• Are terminal strips located in a dry, safe place and properly covered?
Charging the System with Refrigerant
Special considerations when charging the Modulating system
All cooling units must be turned on and running (solenoid valve open) in the cool mode before evacuating the system or adjusting the refrigerant charge. To ensure that all evaporators are on in the cooling mode, and the solenoid valves are open, set each cabin control’s set point down to the lowest temperature setting. There is no need for the compressor to run while evacuating the system, so turn the condensing unit’s circuit breaker off before turning the cooling units on.
The modulating unit is different from a standard DX condens­ing unit in that it has two special refrigerant valves that allow partial loads to run safely: the hot gas bypass valve and the “de-superheat” valve. These valves are factory set and do not require any field adjustment. Any field adjustments could cause the valves to operate incorrectly, causing damage to the compressor or compromising the performance of the system.
As cooling units in the system shut down, the suction pressure at the modulating condensing unit will drop. The hot gas bypass valve senses the suction pressure and will open to allow discharge gas to flow into the accumulator if the suction pressure drops below 55 psi. This will raise the suction pressure and prevent liquid refrigerant from reaching the compressor.
As more hot (high-pressure) gas is dumped into the suction line (due to cooling units shutting down), the superheat (suction gas temperature going into the compressor) can rise to unsafe levels. A thermal expansion (TX) valve is installed which acts as a “de-superheat” valve. It senses the super­heat and will flash liquid refrigerant into the accumulator to cool the suction gas.
This process automatically balances the system as the load from the evaporators changes. This is why it is important to have all cooling units on and operating while charging the system. If one or two are off line, it will cause the refrigerant circuit to alter and make it impossible to correctly charge the system.
The following instructions should be followed in evacuating and charging a Cruisair modulating condensing system with R-22. Some special-order units may contain refrigerant other than R-22. Please follow the special charging procedures included with the unit.
Notice
US federal law prohibits the intentional release of refrigerant gases into the environment, including the R-22 refrigerant used in most Cruisair systems. Special care must be taken when installing, charging, and servicing Cruisair equipment to prevent any loss of refrigerant. Only EPA certified techni­cians with the proper equipment should perform service on the refrigerant circuit.
Initial Charging, New System
There are three refrigerant circuit components in a Cruisair Modulating System: the condensing unit, the cooling/heating unit (evaporator) and the copper refrigerant line-sets. The condensing unit is shipped from the factory charged with refrigerant gas.
It will be necessary to properly evacuate the cooling units and line-sets before releasing the refrigerant from the condensing unit into the system. To facilitate this evacuation procedure, there is a special vacuum port (aka: purge port, access port, evacuation port or service port) located on the condensing unit’s discharge base valve. This vacuum port has a red cap and a schrader valve, and is located at the 2:00 position on the base valve.
Required tools to charge a modulating system:
1. R-22 container (typically the disposable-type container color-coded green for R-22).
2. Gauge manifold with self-closing fittings on the charging hoses.
3. Vacuum pump.
4. Base valve wrench and hand tools.
L-0952 Installation
14
English
5. Accurate thermometer.
6. Thermometer to measure superheat.
Proceed as follows:
1. Turn the condensing unit’s circuit breaker OFF so the compressor will not run while the system is being evacuated.
2. Do not touch the condensing unit base valve stem covers or white port caps. Remove the red cap from the vacuum port on the discharge base valve (right side of unit, 2:00 position on base valve).
3. Connect the low side pressure gauge hose to the vacuum port on the base valve. Connect the vacuum pump hose from the center position on the gauge manifold to the vacuum pump. The high side hose is not used at this time.
11. Remove both condensing unit base valve stem caps from top of base valves. Ensure that both white gauge port caps, and the red vacuum port cap, are in place and tight. Open both base valves fully by turning the valve stems fully counter-clockwise. This will allow the refriger­ant in the condensing unit to enter the system. Replace and tighten the valve stem caps.
12. Turn all cooling units OFF.
The system is now partially charged and is ready for final adjustment.
Adjusting the Charge
After the system has been evacuated and is partially charged, the final charge must be added and adjusted. To correctly adjust the charge in a modulating system, the superheat must be measured.
4. Close all gauge manifold valves.
5. Energize (open) all cooling unit solenoid valves by turning each control on and setting the lowest possible set point.
6. Energize the vacuum pump. Open the manifold valves to the vacuum pump and the base valve vacuum port.
7. As the pump operates, the low-pressure gauge needle will fall to a vacuum. When the vacuum reaches 28 inches Hg close the vacuum pump valve and turn the vacuum pump off. Let the system sit untouched for 15 minutes and then observe the gauge. If any vacuum has been lost, look for leaks, especially at flare joints. Repair all leaks. Then return to step #4 above and evacuate the system again. Once the vacuum has been held at 28 inches Hg for at least 15 minutes, proceed to the next step.
8. Open the vacuum pump valve and leave the vacuum pump operating for at least six hours, and until a vacuum of at least 29 inches Hg is achieved. Close the vacuum pump valve and turn the vacuum pump off. Wait one hour. If no vacuum is lost, proceed with charging. If any leaks are indicated, inspect flare joints again. Repair all leaks. Then return to step #4 above and evacuate the system again. Once the vacuum has been held at 29 inches Hg for at least one hour, proceed to the next step.
9. Remove the low pressure gauge hose from the vacuum port, replace and tighten the red cap.
10. Turn off vacuum pump and disconnect that line from gauge manifold.
1. At this time, all cooling units should be OFF. Turn the condensing unit’s circuit breaker ON.
2. Remove the discharge port base valve stem cap, and make sure that the valve is in the back-seated (fully counter-clockwise) position.
3. Make sure the gauge manifold valves are closed.
4. Remove the white gauge port cap from the discharge base valve and connect the gauge manifold high side hose. Remove the port cap from the suction port near the low-pressure switch and connect the gauge manifold suction hose. Connect the refrigerant tank to the gauge manifold.
5. Attach the thermometer or temperature sensor to the suction line near the low-pressure switch. Wrap insula­tion over the sensor so that the ambient temperature does not affect it.
6. Open the discharge base valve to the test position by rotating the stem one turn clockwise. The high side gauge should now register a pressure reading.
7. Set all the cooling units to cooling, and the set points as low as possible to ensure that the solenoid valves are energized (open) and the blowers are on high speed. If need be, open exterior doors to ensure that the rooms do not achieve set point before charging is complete. The compressor should start as soon as the first unit is turned on.
NOTE: All the cooling units must be on so both the hot gas bypass valve and de-superheat (TX) valve do not open. The system cannot be charged properly if either valve is open.
L-0952 Installation
15
English
Loading...
+ 33 hidden pages