Dometic DX Remote & Self-Contained A/C Installation And Operation Manual

Page 1
DX Remote & Self-Contained A/C v
INSTALLATION • OPERATION
Direct Expansion Systems Revised: 20170710
L-2086
v
English
Page 2
Page 3
v
English
L-2086
Table of Contents
DX Remote & Self-Contained A/C Systems
• Introduction
Drawings and Diagrams ..................................................................4
Air Conditioning Basics ....................................................................4
The Effect of Seawater Temperature ...............................................4
Types of DX Systems .......................................................................4
Subsystems ....................................................................................5
System Controls ..............................................................................5
Condensate Drain ............................................................................5
DX Remote & Self-Contained A/C Systems
• Installation
Installation Procedures ...................................................................6
Electrical System .............................................................................6
Installing The Self-Contained A/C Unit 6
Selecting the Site .............................................................................6
Site Location Checklist ....................................................................7
Mounting the Self-Contained Unit ....................................................7
Installing The Condensing Unit 7
Selecting the Site ............................................................................7
Site Location Checklist ....................................................................7
Mounting the Remote Condensing Unit ...........................................7
Installing The Cooling/Heating Unit 8
Selecting the Site ............................................................................8
Site Location Checklist ....................................................................8
Mounting the Cooling/Heating Unit ..................................................8
Installing the Refrigerant Tubing ......................................................8
Installing the Seawater Cooling System 9
Importance of a Self-Draining System .............................................9
Through-Hull Inlet Fitting .................................................................9
Seacock ...........................................................................................9
Strainer ............................................................................................9
Seawater Pump ...............................................................................9
Manifolds .......................................................................................10
Overboard Discharge .....................................................................10
Seawater Piping ............................................................................10
Bonding ......................................................................................... 10
Installing The Air Distribution System 10
Return Air Grill (RA Grills) .............................................................10
Ducts .............................................................................................10
Discharge Air Grill .......................................................................... 11
Installing the Control Unit 11
The SMX Control ......................................................................... 11
The Rotary Knob Switch Assembly ................................................ 11
Installing the Pump Relay 11
Location ......................................................................................... 11
Voltage and Triggers ......................................................................12
Electrical Connections 12
Three Phase Power ....................................................................... 12
Final Inspection 13
Inspecting the Seawater Cooling System ......................................13
Inspecting the Self Contained Unit ................................................13
Inspecting the Condensing Unit
(Remote Condensing Unit Systems Only) ..................................13
Inspecting the Cooling/Heating Unit
(Remote Condensing Unit Systems Only) ..................................13
Inspecting the Refrigerant Connections
(Remote Condensing Unit Systems Only) ..................................13
Inspecting the Air Distribution System ...........................................13
Inspecting the Control/Switch Assembly and Electrical Wiring ...... 13
Charging the System with Refrigerant 14
Charging a New System ................................................................ 14
Field Charging the System.............................................................14
Removing Refrigerant from the System .........................................15
Initial Start Up 15
DX Remote & Self-Contained A/C Systems
• Operation
Operating Instructions - Rotary Controls 16
SA & SSA Models ..........................................................................16
Operation Instructions - SMX Controls 16
SMX II/SMX Net Operation ............................................................16
Power On .......................................................................................16
System Off ..................................................................................... 16
Selecting Setpoint..........................................................................16
Displaying Temperature ................................................................. 16
Cool Mode ..................................................................................... 17
Heat Mode ..................................................................................... 17
Automatic Changeover ................................................................ 17
Manual Fan Speed Control ............................................................ 17
Automatic Fan Speed Control .......................................................17
Adjusting Brightness ...................................................................... 17
Using The Humidity Control Routine ........................................... 17
Anti-Ice Routine ............................................................................. 17
Owner Maintenance - Routine 18
Condensate Drains ........................................................................18
Air Filters ........................................................................................18
Seawater Connections ...................................................................18
Seawater Pump .............................................................................18
Seawater Strainer ..........................................................................18
Refrigerant Gas ............................................................................. 18
Winterizing the System .................................................................. 18
Trouble Shooting Limited
Descriptions of Figures
18
19
Copyright 2004 Dometic Corporation, All Rights Reserved - Every precaution has been taken in the preparation of this manual to insure its accuracy. However, Dometic Corporation assumes no
responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of this product and information contained herein.
Page 4
v
English
L-2086 Introduction
DX Remote & Self-Contained A/C Systems • Introduction
Warning
This manual contains essential information concerning the safe and proper installation and operation of your Cruisair air conditioning system. If there are any state­ments or procedures in this manual that you do not un­derstand, contact the Dometic Corporation Applications Department for assistance. Phone 804-746-1313 (8 am - 5 pm US Eastern Time), Fax 804-746-7248, or email sales@tmenviro-va.com.
Notice
US federal law prohibits the intentional release of refrig­erant gases into the environment, including the R -22 re­frigerant used in most Cruisair air conditioning systems. Special care must be taken when installing, charging, and servicing Cruisair equipment to prevent any loss of equipment. Only EPA certied technicians with the prop­er equipment should perform service on the refrigerant circuit of the system.
Drawings and Diagrams
The gures that are referenced throughout this manual can be found immediately after the warranty section of the manual. In addition, some Cruisair equipment will be shipped with specic installation sheets or wiring diagrams that may supercede the information located in this manual.
Air Conditioning Basics
The basic principle of an air conditioner is the movement of heat. In a direct expansion (DX) water-cooled air conditioner, heat is transferred from the cabin air to the refrigerant gas, which then releases the heat into the seawater. In reverse cycle heating (heat pump), the refrigerant ow is reversed and heat is extracted from the seawater and then discharged into the cabin.
The heat exchange process relies on the movement of both cabin air and seawater to effectively work. If air ow or seawa ter ow is compromised, the efficiency of the system will drop, and the unit could eventually be damaged, or at least shut down on one of its safety protection devices.
Part of the cooling process, in addition to lowering the air tem perature, is the removal of moisture from the air. This lowers the humidit helps keep the boat dry, reducing mold growth and other mois ture related problems.
y, which makes the area feel more comfortable and
-
-
-
best when the seawater temperature is below 90°F (32°C). At higher water temperatures the unit will operate, but at reduced capacity. As the water temperature rises, so does the refriger ant gas pressure. A high-pressure safety switch will shut the
wn if the water temperature gets too hot, or there is a
unit do loss of cooling water ow.
In heat mode, the opposite is true. As the seawater tem perature gets colder, there is less heat available and heating perf
ormance drops. Full heating capacity is available in water temperatures as low as 55°F (13°C), but drops to about 50% capacity in 40°F (4.4°C) water. Below this, the refrigerant pres sure can be so low that the unit will not produce heat, (or may shut do
wn on low-pressure fault, if this option is installed).
-
-
-
Types of DX Systems
Self-contained units have all major mechanical compo­nents of an air conditioning system mounted on one chassis, including the compr blower, electrical box and related parts.
The self-contained unit is normally mounted low in the living area - under a settee or berth, or in a closet or locker. Cabin air is pulled into the unit, where it is cooled or heated, then dis charged through ducting to a grill usually located on a bulkhead high in the compartment.
The refrigerant circuit in a self-contained unit is pre-charged and sealed at the factory, and no additional charging is needed at installation. A typical self-contained unit is shown in Figure 1.
Remote systems, also called split-gas, have the air condition ing components mounted on two separate chassis that are installed in different locations and are connected by copper refrigerant tubing.
The condensing unit consists of the compressor, seawater condenser, and electrical components, and is mounted in the engine room or other mechanical space.
The cooling/heating unit includes the evaporator coil and a fan or blower mounted on a drip pan. It is installed in the living area in a similar manner to a self-contained unit. Two or three cooling/heating units can be connected to one condensing unit so that multiple or large cabins can be cooled.
A remote system must be charged with refrigerant after instal lation by a certied technician. A typical condensing unit is shown in Figure 2, and Figure 3 is a typical draw-through type cooling/heating unit.
essor, seawater condenser, evaporator coil,
-
-
-
The Effect of Seawater Temperature
The efficiency of the system is dependent on both the seawater and cabin temperatures. In cooling, the air conditioner works
Page 5
v
English
L-2086 Introduction
Subsystems
Both self-contained units and remote condensing systems require subsystems that are purchased separately because of the many variations and options available. These include the seawater, air distribution, and control subsystems.
Seawater System
The seawater cooling system consists of an inlet through-hull tting, seacock (water shut-off valve), strainer, pump, and overboard discharge tting all connected by hose or piping. If multiple air conditioning units are served by a single seawater pump, then a pump relay and water manifold are required.
Air Distribution System
Cabin air is drawn into the self-contained unit or cooling/heat­ing unit through a return air grill. It is then cooled or warmed and b
lown back into the cabin through a ducting system. The air should be discharged high in the cabin and away from the return air grill to ensure good circulation. An air lter is locat ed on the cooling unit or on the return air grill and must be cleaned r
egularly.
-
System Controls
Two different types of controls are available, either an electro­mechanical rotary knob switch assembly or one of the Cruisair SMX ser
The electromechanical switch assemblies are typically 3-knob switches that control mode (OFF, FAN, RUN), thermostat (temperature setting), and fan speed. Other versions include 1 and 2 knob switches for control of “slave” cooling units, and a 4-knob switch for use on systems with auxiliary electric heat.
ies of microprocessor controls.
grammable functions allow the user to customize the system to suit the specic needs of their boat and boating en
The two SMX control systems available are SMX II and the SMX Net. Each system consists of:
Power/Logic (P/L) board - Monitors and controls all func tions of the air conditioning unit. SMX II and SMX Net hav different P/L boards and are not interchangeable.
Keypad/Display - The SMXir is a 10-button user interface with a digital readout and LED indicators. It is used with SMX II or SMX Net systems.
Temperature-Sensing Element - Air temperature is moni tored by a temperature-sensing element (TSEP) that plugs into the power/logic board.
Connecting Cable - The keypad/display connects to the P/L board with a CX or CXP connecting cable.
SMX Net systems may also have additional network cables and an outside temperature sensor that plug into the P/L board.
vironment.
-
Condensate Drain
When the air conditioner is running in the cooling mode, mois­ture is removed from the air by the evaporator coil. This con­densation is then caught in a drain pan and must be drained of
f to a sump or overboard. In humid climates the system can produce a large amount of condensate water that could cause signicant damage to your boat if the drain system doesn’t work properly.
-
Cruisair SMX controls are advanced microprocessor systems that provide a more comfortable environment and better system protection than mechanical controls. In addition, over 20 pro
-
Page 6
v
English
L-2086 Installation
DX Remote & Self-Contained A/C Systems • Installation
Installation Procedures
This rst section covers installation procedures for Cruisair direct expansion (DX) air conditioning systems, both self-con­tained units and remote systems. Please read and understand the man
ual before attempting to install any equipment.
SMX Installation
For installation instructions for your SMX Control, refer to SMXII Control Systems (L-2066) or the SMX Net Control Sys­tems (L-2067) manuals.
Electrical System
Cruisair air conditioning systems are available for use with common power supplies throughout the world. In the United States and most of North and South America, the systems are 115V or 230V, 60Hz, single phase AC (alternating current). In Europe and most of Asia, power systems are typically 230V 50Hz single phase.
Compressors larger than 20,000 Btu/hr are only available in 230V single phase, 230V or 380/460V 3 phase. On 380/460V 3-phase units there is often a separate, lower voltage circuit for the controls and blower, either 115V or 230V. On some power systems this can be supplied by using one input line and the neutral. If not, a separate control power feed or a transformer will be required.
Running and starting loads of an air conditioning system are of ten the largest electrical loads on a boat. It is important that the po
wer supply system is large enough to handle these loads, and is installed properly. Contact an electrician if you are not sure about the proper wiring procedures. Always follow local codes or ABYC codes for proper wiring guidelines.
Voltage and Frequency
The voltage rating of a unit is a nominal rating. The actual voltage in a given location may be higher or lower by as much as 10% and the system will still operate ne. For example, at 60 Hz, you will sometimes see 110VAC to 120VAC, or 208VAC to 240VAC, or 440VAC to 480VAC. In a 50Hz environment, common voltages range from 220V to 240V, or 380V to 415V.
When choosing a system, the voltage and frequency must be known. While standard 60Hz equipment can often be run at 50Hz, it will experience a 17% drop in performance, however, 50Hz equipment can not be run at 60Hz because the 50Hz motor will run too fast and cause damage. Seawater pumps will lose even more performance at 50 Hz due to the nature of centrifugal pumps.
at 50Hz. If a boat is traveling in 50Hz and 60Hz environments, then 60Hz equipment should be installed, with special attention to sizing (especially the pumps) so that the system performs up to expectations. When running 60Hz equipment at 50Hz, the voltage should be reduced 17% to prevent overheating a motor.
Installing The Self-Contained A/C Unit
Safety Warning
A Cruisair self-contained unit should never be placed such that it can circulate carbon monoxide, fuel vapors or other noxious fumes into the boat’s living spaces. Do not install or operate a self-contained unit in the engine room or near an internal combustion engine. Failure to follow this precaution could result in serious injury or death.
Selecting the Site
Self-contained units are designed for built-in installation low in a closet, under a dinette seat or bunk, or any other convenient location, with discharge air ducted to a grill high in the com partment. See Figure 4 for a typical installation.
-
Ignition Protection Warning
Self-contained units do not meet federal requirements for ignition protection. Do not install in spaces containing gasoline engines, tanks, LPG/CPG cylinders, regulators, valves or fuel line ttings. Failure to comply may result in injury or death.
The self-contained unit must be mounted in a space large enough to provide clearance on all sides for air circulation. It is not necessary that the coil be placed directly behind the return air grill, but an unobstructed path must be provided for the air to get to the coil. A 2” (50 mm) space in front of the evaporator coil must be maintained.
Measure carefully for horizontal and vertical clearance prior to proceeding with installation. It is a good practice to place each component physically in the area you have selected to ensure that there is enough space and that connections can be easily made.
Note that some Cruisair self-contained units have a detachable electrical box, which can be remotely mounted to save space in the installation.
-
Dedicated 50Hz units will give full performance at 50Hz, and should be used when the system is going to be run exclusively
Page 7
v
English
L-2086 Installation
Site Location Checklist
• Unit is not located in an engine room or near an internal
combustion engine
• There is no obstruction of airow from return air grill to coil
• Seawater can be piped to the unit with no loops, dips, or
kinks
• Accessible for service and maintenance, including the return
air lter
• Adequate space for seawater and condensate drain connec
tions
Flat, horizontal and sturdy mounting location
• Condensate drain can be run continuously downhill from
unit to overboard tting or sump
• Space is sealed from the bilge or outside air
Mounting the Self-Contained Unit
Before mounting the unit, rotate the blower for discharge in the desired direction by removing the screws from the blower mounting ange and any supporting the rear of the blower, then replacing all screws and remounting the electrical box (if needed).
Mount the unit on a horizontal surface, and fasten securely with the hold-down clips provided. If the unit has a detachable electrical box and you wish to mount it remotely, it should be securely fastened to a bulkhead or deck.
Route the condensate drain so that it ows freely to an over board tting or sump. Do not permit condensate to puddle in the bilge condensate drains, one at each end. It is recommended that you use both drains for best results, but if you choose to use only one condensate drain, place the included plug in the other hole.
Once the unit is correctly mounted, proceed to section titled
“Installing The Seawater Cooling System.”
. Note that most Cruisair self-contained units have two
-
Installing The Condensing Unit
This section applies only to remote condensing unit systems. If you are installing a self-contained unit, skip this section and go to “Installing The Seawater Cooling System.”
Selecting the Site
Cruisair condensing units are designed to be installed in any convenient location. The unit is normally placed in the engine room or other machinery space, but it can be located in the living areas. The condensing unit will produce condensation so a drip pan may be needed. The space around the unit can be insulated to reduce noise if desired. The unit is internally cooled and does not require ventilation.
-
Ignition Protection Warning
Most Cruisair remote condensing units meet federal requirements for ignition protection. However, there are some condensing units, such as those with 3 -phase compressors, that are not ignition protected. Do not install non-ignition protected units in spaces containing gasoline engines, tanks, LPG/CPG cylinders, regulators, valves or fuel line ttings. Failure to comply may result in injury or death.
Site Location Checklist
• Adequate space for access to refrigerant, and seawater and electrical connections
• Accessible for service and maintenance
• Flat, horizontal surface
• Away from direct spray from engine air intakes or water washdown
• Maximum refrigerant tube run is 50ft (15m)
Mounting the Remote Condensing Unit
Orient the unit so the refrigerant, electrical connections and service ports are accessible.
On models with a plywood base, simply drill 4 mounting holes through the base in appropriate locations and fasten the unit with screws or bolts. Do not remove the plywood base or shock mounts as they are part of the vibration and noise isolation built into the unit.
Some models utilize a drain pan with bottom or side conden sate drains. Screw or bolt through all corner holes of the pan to mount the unit.
Do not remove any covers, caps or ttings that may expose any wiring or refrigerant. Only remove these items when you are ready to complete the installation. Removal of any covers may result in damage to the electrical components. Removal of the caps or ttings may result in refrigerant loss.
-
Page 8
v
English
L-2086 Installation
Installing The Cooling/Heating Unit
This section applies only to remote condensing unit systems. If you are installing a self-contained unit, skip this section and go to “Installing The Seawater Cooling System”.
Safety Warning
A Cruisair cooling/heating unit should never be placed such that it can circulate carbon monoxide, fuel vapors or other noxious fumes into the boat’s living spaces. Failure to follow this precaution could result in serious injury or death.
Ignition Protection Warning
Cooling/heating units do not meet federal requirements for ignition protection. Do not install in spaces containing gasoline engines, tanks, LPG/CPG cylinders, regulators, valves or fuel line ttings. Failure to comply may result in injury or death.
Safety Warning
Do not terminate air handler condensate drain lines with­in 3 feet (1m) of any outlet of engine exhaust systems, nor in a compartment housing an engine or generator, nor in a bilge, unless the drain is properly connected to a sealed condensate or shower sump pump. Exhaust and/ or bilge fumes can travel up a drain line and mix with the return air blowing into living areas.
Selecting the Site
Because of the diversity of available cooling/heating units, there is a great deal of exibility in selecting the location. Typi­cally the unit is located low in the cabin, with the discharge grill as high as possib from the return air for proper air circulation.
There are basically 2 types of cooling/heating units, draw­through and blow-through. Figures 5 and 6 show typical cool ing/heating unit installations.
. Draw-through units typically have squirrel-cage blowers
that are strong enough to push air through ducting to the discharge grill.
2. Blow-through units use a fan or blower to blow air across the evaporator coil for direct discharge through a grill. The discharge air from these units should not be ducted.
le for good cooling performance and away
-
It is not necessary for the evaporator coil to be placed directly in front of the return air grill, but an unobstructed path must be available for the air to get to the coil. A 2” (50mm) space in front of the evaporator coil must be maintained.
Site Location Checklist
• Unit is not located in an engine room or near an internal combustion engine
• There is no obstruction of airow from return air grill to coil
• Accessible for service and maintenance, including the return air lter
• Adequate space for and condensate drain connections
• Flat, horizontal and sturdy mounting location
• Condensate drain can be run continuously downhill from unit to overboard tting or sump
• Space is sealed from the bilge or outside air
• Maximum copper tubing run between condensing unit and cooling unit is 50 ft. (15m)
Mounting the Cooling/Heating Unit
Mount the cooling/heating unit so that the condensate drip pan is beneath the unit. Some models require a mounting frame or mounting leg kit, which is supplied separately. Other models have integral mounting frames or the condensate pan itself is the mounting base. See individual spec sheets for specic guidelines.
Route the condensate drain hose steadily downhill so that the condensate ows freely to an overboard tting or sump. Do not permit condensate to puddle in the bilge. Some Cruisair cool ing/heating units have two condensate drains, one at each end. It is recommended that you use both drains for best results. If you choose to use only one condensate drain, plug the other.
Be careful when bending the extension tubes on the evapora tors. Do not allow the tubing to kink and do not twist or bend the tubing at the connection point close t may crack. If bending by hand make large radius bends. Use a tube bender if a tight bend is required.
o the coil or the joints
-
-
Installing the Refrigerant Tubing
Use refrigerant-grade soft copper tubing of the correct sizes to connect the cooling/heating unit to the condensing unit. Note that tee-joints will be needed if more than one cooling/heat ing unit is used with a single condensing unit. The tees must be properly oriented to provide best efficiency. (See Figure 7, Refrigerant Line Size Chart.)
-
Some cooling/heating units are designed for overhead use, and may be mounted below a ybridge console or seating. This setup will draw return air through the overhead, with discharge air either directly blown back down into the area or ducted to overhead grills.
Only use refrigerant-grade seamless soft copper tubing. Never use any type of plastic or rubber hose or tubing.
The refrigerant tubes can run uphill, downhill or sloping as re quired and can have as many bends as necessary. Avoid sharp bends that could result in kinks in the tubing. The cooling/heat-
-
Page 9
v
English
L-2086 Installation
ing unit has additional tubing to help with installation. Take care when bending this tubing as it can easily kink or crack a weld joint resulting in refrigerant loss.
A self-draining seawater system will allow air in the piping to rise naturally through the pump and then be expelled. It will also make winterizing the system much easier.
Both refrigerant lines should be insulated individually.
When putting the recommended closed cell foam insulation over the tubes, cover the ends of the copper tubes to prevent foreign material and moisture from getting inside the copper tubing. After checking for leaks, insulate the connecting are nut joints and tee-joints to prevent secondary condensation. Secure tubing every 3 feet (1m) as necessary for support.
The copper tubing is connected to the condensing unit and cooling/heating unit with are joints. To prevent refrigerant leaks, ares must be formed correctly with the proper aring tool. Only 45-degree single ares should be used.
Flares should be made following the instructions of the partic ular aring tool. Make sure to slide the are nut onto the tube before aring. A drop of oil on the tube can ease the aring process. The surface of the are face must be smooth and free of defects to ensure that the joint won’t leak. The are should be large enough in diameter to ll the are nut completely.
Once you have completed installing the cooling/heating unit and have made the refrigerant connections between the cool ing/heating unit and the condensing unit, proceed to on to the next section “Installing The Seawater Cooling System.”
-
-
Installing the Seawater Cooling System
The following installation instructions apply to both self-con­tained and remote condensing units.
Importance of a Self-Draining Sys­tem
Along with restricted ducting, a poorly plumbed seawater system is one of the most common installation problems on marine air conditioners. When water ow is lost, not only will the air conditioning units no longer cool or heat, the units and the pump could be damaged from running with no water ow.
When using a centrifugal seawater pump, it is imperative that the seawater piping be routed continually uphill from the through-hull inlet to pump and to the condenser, then smoothly up or down to the overboard discharge, without any dips or loops, and with only one high point in the system. This is said to be self-draining because all water would drain out of the piping if the boat were lifted out of the water.
Whenever air gets into the system, which can happen in heavy seas or a sharp turn, it can become trapped in the pump. Because a centrifugal pump cannot pump air, ow through the system is lost.
Figure 8 shows a properly plumbed system and some common mistakes.
Through-Hull Inlet Fitting
A separate through-hull tting must be installed for each air conditioning seawater pump. Do not attempt to draw water from an engine, generator, or other through-hull tting.
A scoop-type through hull should be installed facing forward, and as far below the water line and close to the keel as possi ble.
Drill a properly sized hole for the through-hull tting. Bed the scoop with marine sealant designed for underwater use, and tighten the nut onto the through-hull to secure it.
-
Seacock
A full ow seacock should be installed directly onto the through-hull tting. Use Threaded-seal tape or other sealant on the threads. The seacock must be accessible and easy to close in case of emergency, or to clean the strainer.
Strainer
A seawater strainer must be installed between the seacock and the pump, and should be situated to provide easy access for cleaning. The strainer must be located vertically above the seacock and below the pump so any air that gets into the strainer can get out.
Make sure the water ow through the strainer is in the correct direction. Some strainers have an arrow that shows correct ow direction.
Mount the strainer to a bulkhead so it is properly supported before connecting hoses. Use Threaded-seal tape or other sealant on pipe threads.
Seawater Pump
Centrifugal pumps are not self-priming, and must be mount­ed so that they are below the heeled waterline in any given operating condition. The pump should be accessible for future service.
Mount the pump so the outlet is directed upward so air can escape. The head on some pumps can be rotated to allow mounting on a vertical bulkhead. See Figure 9.
Self-priming pumps are available if the pump cannot be mount ed below the waterline.
Required seawater owrate is 4 gpm per ton (12,000 Btu/hr) of total system capacity.
-
Page 10
v
English
L-2086 Installation
Manifolds
If a pump is serving multiple units, then a seawater manifold will be needed to supply water to all units. This can be as simple as a TEE for 2 units, or a custom made manifold for up to 7 or 8 units.
It is very important to consider manifold orientation so that all air conditioning units get the proper ow of water. See Figure 10 for manifold information.
need to be larger than the outlet pipe size. Do not use pump connections to determine hose size.
The “Pump Inlet” recommended pipe size includes all
ttings and hose (through-hull, seacock, strainer, etc.) up to the pump inlet connection. The “Pump Discharge” includes all piping/hose and ttings from the pump to the air condi tioning unit or manifold, and to the overboard discharge.
Use larger hose when the run is longer than 16 feet (5m).
-
A manifold can also be used on the outlets of the air condition ing units when using a single overboard discharge.
Overboard Discharge
The overboard tting should be located between 1 to 2 inches (25 - 50 mm) above the water line. This is to facilitate visual conrmation of water ow, but also close enough to the water to minimize splashing noise.
If the overboard tting must be installed below the heeled water line, then a valve must be installed per ABYC standards.
Seawater Piping
Only use reinforced marine grade hose or other suitable piping (PVC, CPVC, Cupronickle, or Stainless steel).
Double clamp all hose connections.
Use only plastic, bronze, or stainless steel ttings (do not use brass).
Avoid loops or dips in the hose runs.
Make sure enough hose is used to allow future removal of components.
-
Bonding
Bond all metallic parts (through-hull ttings, valves, strainer, manifolds, etc.) that are in contact with seawater to the vessel’s bonding system in accordance with ABYC standards E-8 and E-9. Items should only be bonded or grounded once. If an item is in contact with an electrically grounded part (pump head or seawater condenser) then it should not be bonded again.
Installing The Air Distribution System
The following instructions apply to both self-contained units and remote condensing systems, except as noted. Refer to Figure 11 for proper grill and duct sizes.
Return Air Grill (RA Grills)
The return air grill should be located so there is unobstructed airow to the unit’s evaporator coils. Installing ducting between the return air grill and the air conditioning unit is not normally necessary and should be avoided. The grill may be located on a side opposite the evaporator coil so long as airow to the coil is unobstructed.
Use the correct size hose, ttings, and components. See the table below for proper seawater sizing. Note that the pump inlet piping (including through-hull and strainer) may
An air lter must be used to prevent the evaporator coil from collecting dirt and lint. The lter can be located at the evap orator coil or at the grill. Only one lter should be used. Most self-cont lter, but if the lter is not easily accessible, use a lter on the return air grill.
ained units and cooling units are supplied with an air
Ducts
Insulated exible ducting or built-in ducting may be used to route air from the blower to the discharge grill. Note that blow through cooling units are installed directly behind the discharge grill, and ducts are unnecessary. Likewise, with some overhead cooling/heating units, air is discharged directly into the com partment without ducts.
Ducting Guidelines
Secure duct to blower or transition box (plenum) with screws and duct tape. When using insulated exible ducting, make sure inner duct is secured and sealed to adapter before pulling insulation over connection.
10
-
-
Page 11
v
English
L-2086 Installation
Plenums, or transition boxes are used with exible ducting to split and route the discharge air as needed. Figure 12 shows several plenum congurations.
• Ducting must be properly sized for the airow. If the duct run is
longer than 10 feet (3m), use the next larger duct size.
• Use of insulated duct is recommended, and is mandatory when used in high heat areas or where condensation would be a problem.
• Run exible ducting tightly and smoothly, with as few bends as possible.
• Keep ducts as short as possible.
• Support ducting to prevent sagging during boat operation.
• Trim excess ducting before attaching to transition adapters.
• Make sure ducting is not crushed or kinked.
• Use a exible transition duct between blower and any built­in ducting.
• If possible, rotate blower to keep duct run as short and direct as possible.
Discharge Air Grill
When used with exible ducts, a grill plenum should be incor­porated behind the discharge grill. Location of this grill should be as high as possib ow between discharge and return encompasses as great an area as possible in the cabin. Care should be taken to avoid “short cycling,” a situation where the conditioned air is returned to the coil without being substantially affected by the cabin air.
le in the cabin, and oriented so that air
Installing the Control Unit
The SMX Control
If your system has SMX controls, refer to the appropriate SMX II or SMX Net Control System Installation/Operation Manual.
be rear access with sufficient clearance for the wiring and the protective cover. The thermostat bulb is on a 10 ft (3m) long capillary tube, and the switch assembly must be installed close enough to the unit so the bulb can be mounted in the return air path.
Remote condensing systems use SA type switches which have terminal strips that must be mounted to the back of the bulkhead where all eld wiring terminates. This location must be easily accessible for wiring connections and service.
One and two-knob slave switch assemblies should be installed in the cabin where the slave cooling unit is operating.
Mounting
Cut a hole in the bulkhead using the template shipped with the switch, or one from the back of this manual. See Figures 13a and 13b for templates and switch dimensions.
Attach the terminal strip to an accessible location on the back of the bulkhead (remote systems only). Self-contained systems have a 10-foot (3m) harness with a plug that connects to the self-contained unit.
Carefully route the thermostat bulb from the switch to the return air path of the unit so the capillary tube does not get kinked. The large bulb must sense the return air, and not touch the evaporator coil. If a second smaller “anticipator” bulb is attached to the main bulb, it should be installed into the dis charge duct.
After making all wire connections, install the protective plastic cover (remote systems only) over the terminal strip. Next install the plastic cover over the back of the switch assembly (remote and self-contained systems) and mount the switch to the bulk head with the 4 screws provided.
-
-
Installing the Pump Relay
The Rotary Knob Switch Assembly
The following instructions apply to both self-contained and remote condensing unit systems using a rotary-knob switch assembly.
Warning
The rotary knob switch assembly switches line voltage (115 or 230VAC) and in many case full power of the unit. The selected mounting location must be safe in regards to voltage as well as heat produced by the switch as­sembly.
Location
The switch assembly should be mounted on a vertical bulk­head where it can easily be seen and reached. There should
The following instructions apply to both self-contained and remote condensing unit systems that have multiple A/C units served by a single seawater pump. If you only have one A/C unit, or each unit has it’s own seawater pump, then skip to the next section.
Location
The pump relay is generally located in the engine room near the seawater pump, but it can be mounted anywhere that is convenient and accessible. It must be in a dry location, away from any possible water spray, with room for some heat dissi pation.
11
-
Page 12
v
English
L-2086 Installation
Warning
PR3X and PR8X pump relays are certied ignition protected. However, pump relays with electromechanical relays or contactors (such as 3-phase pump relays) are not ignition protected and must never be installed in spaces containing gasoline engines, tanks, LPG/CPG cylinders, regulators, valves or fuel line ttings. Failure to comply may result in injury or death.
Voltage and Triggers
PR3X and PR8X pump relays are identical in operation. When the rst A/C unit turns on, the pump relay will turn on the sea­water pump, and the pump will stay on until the last A/C unit shuts do
The PR3X can operate up to 3 A/C units, and the PR8X can operate up to 8 A/C units. Both can operate 115V and 230V pumps.
Triggers are used in the pump relays to isolate the signals from each A/C unit. Some pump relays come with pre-installed trig gers, or you can buy triggers separately. Triggers come in 115V and 230V Both 115V and 230V triggers can be used in a single pump relay if the system requires it.
wn.
-
, and must match the control voltage of the A/C unit.
• If there is only one a/c unit, the seawater pump does not re quire a separate breaker, but make sure the breaker is siz for the combined load of the unit and the pump. If multiple a/c units are supplied by a single pump, then a pump relay will be needed, and will require it’s own circuit breaker.
• All units must be grounded to minimize the potential hazard of electrical shock and personal injury.
• All metallic ttings in the seawater system that are isolated from the a/c unit or pump by rubber hose should be bonded per ABYC standards E-8 and E-9.
• On larger F-type condensing units a fuse can be added to protect the fan and control wires.
-
ed
The trigger is simply a relay that closes when the A/C unit turns on. Because each trigger is isolated, the polarity of the signals from the A/C units does not matter.
Electrical Connections
Warning
Make sure all power is off before opening any electrical box.
The following guidelines apply to both self-contained and remote condensing unit systems:
• Failure to properly ground and bond the system will void warranty.
• All electrical connections should be made within the electrical junction boxes supplied with the units. Most units have terminal strips that are labeled or have color-coded wiring. Open terminal strips (such as supplied with switch assemblies) require that the included terminal strip covers be installed over the strip and switch back after installation is complete.
• Wiring diagrams are included in the back of this manual and under the cover of the electrical boxes on all units. Contact Dometic Corporation if you are not sure if you have the correct diagrams.
• Each air conditioning unit requires it’s own dedicated circuit breaker, of the appropriate size. See the table below for suggested circuit breaker and wire sizing.
Note
Always follow ABYC guidelines or local codes when selecting breakers and wire sizes.
Three Phase Power
Some larger compressors and pumps have 3 phase motors that will run forwards or backwards depending on the wire connections. Reciprocating (piston type) compressors can run either way without any problem, but scroll compressors and centrifugal pumps are direction sensitive and must be wired so the motors run the correct direction. If running backwards, Scroll compressors will usually make loud, unusual noises and will not perform properly.
12
Page 13
v
English
L-2086 Installation
Safety Warning
To prevent a possible electrical shock in the event a component has an electrical breakdown, which could re­sult in serious injury or death, always ground the system in the following manner:
• Use proper wire size with a ground to feed power from the ship’s electrical panel to each cooling unit junction box. Make sure the ground wire is properly connected to the ground buss in the ship’s service distribution panel and to the ground lug in the cooling unit’s junction box
• Connect the junction box ground lug to the P/L box green wire (or to the switch assembly terminal strip).
• Use proper wire size with a ground to feed the power from the ship’s electrical panel to the condensing unit’s junction box. Make sure the ground wire is properly connected to the ground buss in the ship’s service distribution panel and to the condensing unit’s ground lug.
• Ground the seawater pump, and pump relay (if used) to the condensing unit’s ground lug.
• Bond the ground lug on the condensing unit to the ship’s grounding system.
• Check the continuity of the ground system before the system is energized.
Inspecting the Self Contained Unit
• Is the air conditioning unit securely mounted?
• Is the unit located so that it will not draw fumes from the engine room and discharge them into the compartment?
• Are condensate drains properly routed to an overboard discharge or sump?
• If only one condensate drain is being used, has the hole at the other end of the tray been plugged?
Inspecting the Condensing Unit
(Remote Condensing Unit Systems Only)
• Is the condensing unit mounted securely using the integral wooden baseboard or drain pan?
• Are the fasteners accessible if it is necessary to remove the unit for service later?
Inspecting the Cooling/Heating Unit
(Remote Condensing Unit Systems Only)
• Is the unit securely mounted?
• Are condensate drains properly routed to an overboard discharge or sump?
• If only one condensate drain is used, have any other drain holes in the drip tray been plugged?
Note
Always follow ABYC guidelines or local codes when selecting breakers and wire sizes. ABYC standards are available from: American Boat and Yacht Council, 3069 Solomon’s Island Rd., Edgewater, MD 21036, Telephone: (410) 956-1050.
Final Inspection
Prior to charging or energizing the system, conduct a nal inspection, using the following checklist.
Inspecting the Seawater Cooling System
• Is the seawater pump properly sized for the system?
• Is the pump oriented correctly and mounted securely with the pump outlet directed vertically upwards?
• Is the centrifugal seawater pump located so it is below the water line at all times?
• Are the inlet and outlet thru-hulls secure, properly sealed and properly oriented?
• Are all hose clamps tight?
• Are seawater hoses double clamped?
• Are there any loops or dips in the seawater plumbing that might cause the system to become air locked?
• Is the strainer located between the seacock and the pump, and is it correctly oriented?
• Are all metallic seawater ttings properly bonded?
Inspecting the Refrigerant Connec­tions
Only)
• Are are joints made with forged are nuts and properly
• Are are joints and tees properly insulated?
• Are copper refrigerant tubes individually insulated?
• Are tubes fastened securely to the boat every three feet or
(Remote Condensing Unit Systems
tightened?
as needed throughout their length?
Inspecting the Air Distribution Sys­tem
• Is there unobstructed airow from the return air grill to the coil?
• Is there a lint screen or lter in the return air path where it is accessible for regular cleaning?
• Have exible ducts been pulled tight to remove bends and constrictions?
• Are grills correctly sized for the system?
13
Page 14
v
English
L-2086 Installation
Inspecting the Control/Switch As­sembly and Electrical Wiring
• Is the thermostat sensor or thermistor properly located and secured in the return air path and not in direct contact with any metal objects? (For switch assemblies with two sensing bulbs, the large one goes in the return air path and the small one in the discharge air path.)
• Are all wiring harnesses properly secured?
• Are wiring connections made, color to color, correctly at terminal strips?
• Are plugs properly aligned and securely connected?
• Are all components properly grounded and bonded?
• Are proper sized circuit breakers used?
• Are terminal strips located in a dry, safe place and properly covered?
You will need the following tools to complete the charging procedure:
• R-22 container (typically the disposable-type container color-coded green for R-22)
• four-valve gauge manifold with self-closing ttings on the charging hoses
• vacuum pump
• base valve wrench and hand tools
• accurate thermometer
Proceed as follows:
1. Make sure all are joints are well made and tight.
2. Do not touch the condensing unit base valve stem covers
or white port caps. Remove the red port cap on the dis charge (right side) base valve (or on a eld-inst tee tting).
-
alled in-line
Charging the System with Re­frigerant
Self-contained units are precharged from the factory and do not need further charging. If you are installing a self-contained system, skip this section and proceed to “Initial Startup”.
The following instructions should be followed in evacuating and charging a Cruisair remote condensing unit system with R-22. Some special ordered units contain refrigerant other than R-22. Please follow the special charging procedures included with the unit.
Notice
US federal law prohibits the intentional release of refrig­erant gases into the environment, including the R -22 re­frigerant used in most Cruisair air conditioning systems. Special care must be taken when installing, charging, and servicing Cruisair equipment to prevent any loss of equipment. Only EPA certied technicians with the prop­er equipment should perform service on the refrigerant circuit of the system.
Charging a New System
There are three refrigerant circuit components in a Cruisair re­mote condensing unit system: the condensing unit, the cooling/ heating unit and the copper r unit is shipped from the factory charged with approximately the right amount of refrigerant needed for the whole system.
The procedure will be to evacuate the nitrogen and air from the cooling unit and the copper tubing, then release the refrigerant from the condensing unit into the entire system. To facilitate this procedure, there is a special evacuation port (red cap) located on the base valve of the condensing unit .This port has a schrader valve so you can evacuate and vapor charge the lines and cooling unit without releasing the refrigerant in the condensing unit.
efrigerant lines. The condensing
3. Connect the vacuum pump hose to the vacuum pump.
Connect the refrigerant supply line to the refrigerant container (making sure the refrigerant container valve is OFF). Connect the low pressure gauge hose, to the red capped port. At this point, do not connect the high pressure charging hose to anything.
4. Close all four gauge manifold valves.
5. Energize the vacuum pump and open the manifold valves
for the vacuum pump, the refrigerant container and the red­capped access port.
6. As the pump operates, you will see the low pressure test
gauge fall to a vacuum. When the vacuum reaches 28 in. Hg close the vacuum pump valve and turn the vacu um pump off. Leave the system for 15 minut observe the gauge. If any vacuum has been lost, look for leaks, especially at are joints. Then return to step #3 above and re-evacuate the system.
7. Open the vacuum pump valve and leave the vacuum pump
operating for at least 6 hours, until a vacuum of at least 29 in. Hg is achieved. Close the vacuum pump valve and turn the vacuum pump off. Wait one hour. If no vacuum is lost, proceed with charging. If any leaks are indicated, reinspect are joints for leakage, and return to step #3 above to re-evacuate the system.
8. Open the refrigerant container valve slowly and allow gas
to enter the system until the low pressure gauge rises to zero. You have now vapor charged the evacuated lines and cooling/heating unit with refrigerant to a gauge pressure of zero. Close the refrigerant container valve.
9. Remove the low pressure gauge hose from the red capped
port. Replace and tighten the red cap.
es and then
-
14
Page 15
v
English
L-2086 Installation
10. Remove both condensing unit base valve stem caps. Open both base valves fully by turning the valve stems fully coun­terclockwise. This will allow the refrigerant in the condens­ing unit to enter the system. Replace and tighten the valv stem caps.
At this point, the system is basically charged and ready for nal gas charge adjustment once the boat is in the water.
Field Charging the System
To eld charge a new unit, which has been evacuated and basically charged, proceed as follows:
1. Remove both base valve stem caps and conrm that both valve stems are in the back-seated or full counterclockwise position.
2. Remove the white gauge port caps from both base valves. No gas should escape. If it does, retighten the cap and call Dometic Corporation for assistance.
Removing Refrigerant from the Sys­tem
When adjusting the charge in the refrigerant system, you may have to remove refrigerant. It is a violation of federal law to vent refrigerant to the atmosphere, and it is necessary that you capture any refrigerant that is removed from the system. There are two methods of doing this.
1. Use an approved refrigerant recovery unit and rellable refrigerant container.
2. Allow refrigerant to escape from the high pressure side into a rellable refrigerant container.
Initial Start Up
The following instructions apply to both self-contained and remote condensing systems.
3. Close all gauge manifold valves.
4. Attach the gauge manifold hoses to the gauge ports: high pressure on the right and low pressure on the left. Connect the hose to the refrigerant container.
5. Open both base valves to the test position by rotating the stems one turn clockwise.
6. Start the unit in the cooling mode, and observe the system pressures. Use the charging curves shown in Figure 29 to determine the proper pressures. These charts are to be used as a GUIDE to setting pressures. They are NOT designed to give EXACT pressure settings. There are conditions that may cause pressures to vary. Head pres sures may vary +10%. Accurate Suction Pressure settings are more critical f proper functioning of the system. Through the gauge manifold, adjust the gas charge to obtain the proper system pressures.
7. To remove the gauge manifold, backseat the base valves by turning the stems fully counterclockwise. Tighten the stem packing gland nuts. Replace and tighten the stem caps. Remove the gauge hoses and replace and tighten the port caps.
-
or
1. Open the seacock (seawater inlet valve).
2. Turn on the circuit breaker for the air conditioner. If a pump relay is installed, the breaker for the pump must also be turned on.
3. Following directions in the Operation manual, set the system for cooling or heating at the switch or SMX keypad, and adjust temperature setting so the unit will turn on.
4. Verify that water is owing from the overboard discharge. Check all overboards if more than one unit is installed.
5. Allow unit to run for 10 minutes at high fan speed. Check the temperature differential between discharge and return air by placing an accurate thermometer in front of the dis charge grill and then in front of the return air grill.
In cooling, the difference between the discharge and return should be 15 - 20°F (8.3 - 11.1°C), with normal ambient air and water temperatures. In the heating mode the differen tial can be as high as 25°F (13.9°C).
If e
verything checks out, the system is ready to go.
-
-
Note
It is recommended to charge the system in the cool mode (as described above). If conditions are such that charging must be done in the heat cycle, the gauge connections must be re versed on the base valves. Also note that in the heat mode the same pressures can be observed at two different charge levels. This could lead to an overcharge condition.
-
15
Page 16
v
English
L-2086 Operation
DX Remote & Self-Contained A/C Systems • Operation
Operating Instructions - Rotary Controls
SA & SSA Models
1. Open the seawater inlet valve.
2. Set the OFF -
3. Turn on the main circuit breakers on your boat’s electrical panel designated for the air conditioning unit. If there is more than one air conditioning system on board, you must also turn on the breaker for the seawater pump.
4. Set the thermostat by turning the COOLER) to the desired mode of operation.
5. Set the fan speed control to
6. Turn the top control knob to
7. Turn the top control knob to ON. The compressor will start, and the unit will begin to cool or heat, depending on which mode of operation you have selected. Verify that water is owing from the overboard discharge.
8. To set the thermostat, allow the unit to operate until the area is cooled or heated to the desired temperature. At
this point, turn the toward the center position until you hear it “click” once. The thermostat is now set to maintain the desired temperature.
9. Set the fan speed to provide the desired ow of air, using the center knob.
10. If you turn the system off, or if you wish to switch between cooling and heating, wait three minutes to allow the sys tem’s internal pressures to equalize before attempting t restart.
- ON knob to the OFF position.
knob (WARMER/
(HIGH).
to energize the blower.
knob (WARMER/COOLER) slowly
-
SMX II/SMX Net Operation
1. Open seacock (seawater inlet valve).
2. Turn on main circuit breakers for the air conditioning sys­tem. If there is more than one unit on board, you m turn on the breaker for the seawater pump.
3. Adjust SMX settings as desired.
ust also
Hint
It is good practice to check for seawater ow by observing the overboard discharge when the system is rst turned on. If you do not observe steady water ow, shut the system down and check the seawater system.
Power On
When AC power is applied to the system at the circuit breaker, the SMX microprocessor retrieves from permanent memory the last operating conguration. This process takes about four seconds, after which the system will begin operating just as it had been when power was last turned off.
System Off
Press the OFF key to turn the system off. Note that the data display remains energized even when the system is off. The fan can be turned on manually when the system is in the off mode.
Note
The SMX has built-in protection against sudden power interrup­tions. The system automatically stores the current operating congur changes. (The new operation mode must be in affect for 10 seconds before it is saved into permanent memory.) When AC power is lost, the SMX system retains these settings, and when AC power is restored it resumes operation using the same settings as before.
ation in permanent memory every time you make
Hint
It is good practice to check for seawater ow by observing the overboard discharge when the system is rst turned on. If you do not observe steady water ow, shut the system down and check for obstructions in the seawater cooling system.
Operation Instructions - SMX Controls
There are two different SMX control systems available, SMX II and SMX Net. The following are basic operation instructions for both systems. For complete installation and operation infor mation, consult the appropriate manual, L-2066 for SMX II or L-2067 for SMX Net.
Selecting Setpoint
Press the SET key and the current setpoint will be displayed. Press the UP or DOWN key to change the setpoint.
Displaying Temperature
To display cabin temperature, press the TEMP key.
SMX II Only
Press TEMP a second time for an alternating display of inside temperature and setpoint. Press a third time to return to inside
-
temperature only.
16
Page 17
v
English
L-2086 Operation
SMX Net Series
If your boat is equipped with the optional outside thermistor, press TEMP a second time to display outside temperature. Press a third time for an alternating display of setpoint, inside temperature and outside temperature. Note that the inside and outside indicators show you which temperature is being displayed.
Cool Mode
To enter the COOL mode, press the COOL key. The Cool Mode Indicator will light to show that you have selected the cooling mode.
The Cooling Indicator will be lit whenever the system is in the cooling mode and the compressor is actually running. When the compressor cycles off, the Cooling Indicator goes off, but the Cool Mode Indicator stays on.
Heat Mode
Press the HEAT key to select HEAT Mode. The Heat Mode Indicator will light to show that you have selected the heating mode.
The Heating Indicator will be lit whenever the system is in the heating mode and the compressor is actually running. When the compressor cycles off, the Heating Indicator goes off, but the Heat Mode Indicator stays on.
Automatic Changeover
Press the COOL and HEAT keys simultaneously for AUTO­MATIC CHANGEOVER between COOL and HEAT Modes. The mode indicat automatic changeover mode.
For the SMXir Remote Control only - Press the Auto Switchover key to enter automatic changeover mode.
Note that the Cooling or Heating Indicator will come on when the compressor is running to show when the system is running in the cooling or heating mode.
ors will light, to show that the system is in the
Manual Fan Speed Control
Press the FAN key to select manual fan control. The Manual Fan Indicator will light to show that it is in the manual mode. Then use the SLOW and FAST keys to select the desired fan speed.
Note that you can use the manual fan control to circulate air even when the system is in the OFF mode.
speed automatically slows. Once setpoint is reached, the com pressor cycles off and the fan keeps running on low speed.
-
Adjusting Brightness
Pressing the SET key repetitively will dim the LED display. Keep pressing SET to return to full brightness.
Note
SMXLB keypads automatically adjust according to cabin light­ing.
Using The Humidity Control Rou­tine
When engaged, the SMX humidity control routine automati­cally turns the air conditioning system on at timed intervals to r
emove moisture from the air. The system is programmed at the factory for average values. To change the factory settings, see “Humidity Control Program”.
To start the dehumidication program:
• Press OFF.
• Press COOL, HEAT and FAN keys simultaneously.
For the SMXir Remote Control only - Pr key to enter dehumidication mode.
• The data display will ash HU, indicating that the program is
active.
• To halt the dehumidication program, press any key. The
HU message will stop ashing.
ess the Dehumid
Safety Note
Whenever the SMX system is in the dehumidication mode, all of the system safeguard controls remain active. If the seawater ow fails or if line voltage falls below preset limits, the system will automatically shut down. If AC power is interrupted, the system will automatically resume operation in the dehumidica tion mode when power is restored.
Anti-Ice Routine
The SMX control will occasionally shut down the compressor in the cooling mode to allow any ice that may have formed on the evaporator coil to melt. The anti-ice shutdown only occurs at inside temperatures lower than 70°F (21°C).
In a 10 minute cycle period, the compressor will shut off for 15 seconds per degree (°F) below 70°F. For example, if the inside temperature is 67°F, the compressor will shut off for 45 seconds every 10 minutes.
-
Automatic Fan Speed Control
If in manual fan mode, press FAN key to select automatic fan control. The Manual Fan Indicator goes off, and the system will automatically adjust fan speed as the actual cabin temperature deviates from the setpoint. As setpoint is approached, the fan
17
Page 18
v
English
L-2086 Operation
Owner Maintenance - Routine
Condensate Drains
Every three months, check the condensate drains for obstructions by pouring a quart of water rapidly into the condensate pan. If it does not drain completely within 30 seconds, check the drain outlets for clogging. Remember that many Cruisair systems have two drains and hoses, one at each end of the unit.
Air Filters
At least once a month, check the lint screen or lter behind the return air grill or on the face of the cooling/heating unit and clean if necessary.
The unit will not operate at all.
Solution
1. Blown fuse or tripped circuit breaker. Replace fuse with
time delay type or reset breaker. Check for correct sizing.
2. Low voltage to unit. Check shoreside power supply and
rating of electrical power cord to boat.
Situation
Air from the unit does not feel cool (or warm in the heating mode).
Solution
1. The selector switch is set for FAN only. Switch the system
into the cooling or heating mode.
Seawater Connections
Verify that all seawater connections are tight, and check for water ow from each unit’s overboard discharge.
Seawater Pump
If your system uses a rubber-impeller seawater pump, you should inspect the impeller after 300 hours of operation. Replace it if worn. If you have a centrifugal pump, regular main tenance is not needed.
Seawater Strainer
Check the seawater strainer daily. Remove any debris.
Refrigerant Gas
The refrigerant gas (most likely R-22) used in your Cruisair air conditioning system is adequate for the life of the system. Routine “seasonal” charging of the system is not typically necessary.
Winterizing the System
Close the seacock and remove the inlet water hose from the air conditioner. Allow all water to drain from the system. Loosen the screws on the pump head to allow the water to drain from the pump. Drain and clean the seawater strainer.
Trouble Shooting
Before you call for service, review this list. It may save you time and expense. This list contains common occurrences that are not a result of defective workmanship or materials. If you need service after trying these procedures, call your nearest Cruisair dealer.
2. The thermostat is set incorrectly. Set the thermostat for a
cooler or warmer setting.
3. Water ow is restricted. Clear restriction. Clean strainer.
Situation
The unit operates but the cabin fails to cool normally.
-
Solution
1. Dirty air lter. Clean lint screen or air lter.
2. The thermostat is set too high. Reset the thermostat to a
cooler setting.
3. The evaporator has iced. Turn the system to FAN only for 5
minutes, then restart.
Situation
Compressor cycles on and off.
Solution
1. Dirty air lter. Clean lint screen or air lter.
2. Water ow restriction. Clear restriction. Clean strainer.
Situation
Water dripping inside cabin.
Solution
1. Condensate drain is clogged. Clean out drain holes.
2. Blockage in hose. Clear hose. Check downhill routing of
hose.
Situation
18
Page 19
v
English
L-2086
Descriptions of Figures
Fig. 1 Typical Self-Contained Unit Fig. 2 Typical Remote Condensing Unit Fig. 3 Typical Draw-Through Cooling Unit Fig. 4 Typical Self-Contained Installation Fig. 5 Typical Draw-Through Cooling Unit Installation Fig. 6 Typical Blow-Through Cooling Unit Installation Fig. 7 Refrigerant Line Sizes Fig. 8 Seawater Piping, Proper System and Common Mistakes Fig. 9 Pump Head Orientation Fig. 10 Seawater Manifolds Fig. 11 Duct and Grill Sizes Fig. 12 Plenum Congurations Fig. 13 Switch Dimension and Templates Fig. 14 SHR5-16 StowAway Wiring, #082611 Fig. 15 SH24C StowAway Wiring, #080264 Fig. 16 SHF5-16-C StowAway Compact w/ 3-knob Control Wiring Fig. 17 SHF24-C StowAway Compact w/ 3-knob Control Wiring Fig. 18 SHUF18(C/CK)/1-HV StowAway Compact w/ 3-knob Control Wiring Fig. 19 SHUF5-16(C/CK)/1-HV StowAway Compact w/ 3-knob Control Wiring Fig. 20 WFAH6-16 Condensing Unit Wiring, #082201 Fig. 21 R/F20-60C 1-Ph. Cond. Unit Wiring, #082534 Fig. 22 R/F24-72 3-Ph. Cond. Unit Wiring, #082556 Fig. 23 SA3-Z Switch Wiring Fig. 24 SA5-Z Switch Wiring Fig. 25 PR3X Pump Relay Wiring Fig. 26 PR8X Pump Relay Wiring Fig. 27 WFAH System Wiring, 115V Fig. 28 WFAH System Wiring, 230V Fig. 29 WFAH System Wiring, 230V, w/ Aux. Heat Fig. 30 R/F Type System Wiring, SA3-Z Switch, 1Ph. Fig. 31 R/F Type System Wiring, SA3-B Switch, 1Ph. Fig. 32 R/F Type System Wiring, SA3-Z Switch, 3Ph. Fig. 33 Refrigerant Charging Curves (R22) Fig. 34 Charging Systems with Alternative Refrigerants
19
Page 20
Fig. 1 - Typical Self-Contained Unit
Fig. 4- Typical Self-Contained Installation
Fig. 2 - Typical Remote Condensing Unit
Fig. 3 - Typical Draw-through Cooling Unit
Fig. 5 Typical Cooling Unit Installation (draw-
through)
Fig. 6 Typical Cooling Unit Installation (blow-
through)
L-2086
20
Page 21
Fig.7 - Refrigeration Line Sizes
Notes:
• Maximum length of refrigerant line between condensing unit and cooling unit is 50 feet (15m).
• Only use seamless refrigeration grade copper tubing.
• Insulate discharge and suction tubes separately.
• Use minimum 3/8” (10mm) thick closed cell insulation.
• Seal (glue and/or tape) all insulation seams.
• Use “dead-head” orientation of TEEs on multiple cooling unit sys tems to help ensure proper distribution of refrigerant.
-
L-2086
21
Page 22
Fig. 8 - Seawater Piping - Proper System and Common Mistakes
Fig.10 - Seawater manifoldsFig. 9 - Pump head orientation
L-2086
22
Page 23
Fig. 12 - Plenum CongurationsFig. 11 - Duct and Grill Sizes Tables
L-2086
23
Page 24
Fig. 13a - Switch Dimensions and Templates
L-2086
24
Page 25
Fig. 13b - Switch Dimensions and Templates
L-2086
25
Page 26
Fig. 14 - SHR5-16 StowAway Wiring, #082611
Fig. 15 - SH24C StowAway Wiring, #080264
L-2086
26
Page 27
Fig. 16 - SHF5-16-C StowAway Compact w/ 3-knob Control Wiring
Fig. 17 - SHF24-C StowAway Compact w/ 3-knob Control Wiring
L-2086
27
Page 28
Fig. 18 - SHUF18(C/CK)/1-HV StowAway Compact w/ 3-knob Control Wiring
Fig. 19 - SHUF5-16(C/CK)/1-HV StowAway Compact w/ 3-knob Control Wiring
L-2086
28
Page 29
Fig. 20- WFAH6-16 Condensing Unit Wiring, #082201
Fig. 21- R/F20-60C 1-Ph. Cond. Unit Wiring, #082534
L-2086
29
Page 30
Fig. 22- R/F24-72 3-Ph. Cond. Unit Wiring, #082556
Fig. 23- SA3-Z Switch Wiring
L-2086
30
Page 31
Fig. 24- SA5-Z Switch Wiring
Fig. 25- PR3X Pump Relay Wiring
L-2086
31
Page 32
Fig. 26- PR8X Pump Relay Wiring
Fig. 27- WFAH System Wiring, 115V
L-2086
32
Page 33
Fig. 28- WFAH System Wiring, 230V
Fig. 29- WFAH System Wiring, 230V, w/ Aux. Heat
L-2086
33
Page 34
Fig. 30- R/F Type System Wiring, SA3-Z Switch, 1Ph.
Fig. 31- R/F Type System Wiring, SA3-B Switch, 1Ph.
L-2086
34
Page 35
Fig. 32- R/F Type System Wiring, SA3-Z Switch, 3Ph.
L-2086
35
Page 36
Fig. 33- Refrigerant Charging Curves (R22)
L-2086
36
Page 37
Fig. 34 Charging Systems with Alternative Refrigerants
New A/C units are available from the factory with non-HCFC refrigerants. R-417A (also known as NU-22® or Isceon 59®) is a direct drop-in replace­ment for R22. It will work with Alkyl Benzene and mineral lubricants so standard compressors can be used. Note that some self-contained units (with rotary compressors) and chillers (with scroll compressors) might have R-407C with POE lubricant.
Both R-417A and R-407C are blended refrigerants, meaning they are made up from multiple component refrigerants. In most cases the user will not notice a change in operation or performance of these systems, but charging a system with a blend requires some special considerations.
• We currently don’t have charging curves for either gas. A system with a blend must be charged by superheat.
• The system should be charged with liquid refrigerant from the tank to prevent fractionation. Note that some tanks have a dip tube so the tank is used in the upright position, while other tanks will need to be turned upside down to get liquid. This should be clearly marked on the tank.
• A partial leak in the system doesn’t necessarily mean that the refrigerant needs to be removed and recharged. However, it is possible that enough fractionation can occur that would require a complete evacuation and recharge. This will be evident when trying to charge the system and the temperature/pressures will not respond correctly.
To charge a split system with a blend:
1. Evacuate lines and evaporator (cooling unit) as normal.
2. Open base valves to release the refrigerant in the condensing unit.
3. Attach an accurate thermometer or temperature sensor to the suction line near the base valve, at the 3 or 9 o’clock position on the line. Insu late over the sensor so that the ambient temperature does not aff
.
reading
4.
Open the suction base valve to the test position. The low-side gauge
should now register a pressure reading.
5. Turn on the system in the cooling mode, and set the thermostat to a low setting so the unit will stay on.
6. Allow the system to run for ve minutes so the pressures will stabilize, then measure the superheat. This must be done using the Dew Point for conversion.
Note: There is no ideal superheat temperature. It should be in the range of 10° to 20°F (5.6° to 11.1°C), depending on the heat load. On cool days, superheat will be lower, and on hot days it will be higher.
7. To reduce superheat, slowly add liquid refrigerant to the suction line. Do this in very small increments and allow the system to stabilize before taking another reading. DO NOT OVERCHARGE! If the system is overcharged, refrigerant must be removed from the liquid line, using an approved recovery cylinder.
Warning: You are charging with liquid refrigerant. To prevent liquid from “slugging” the compressor, open the manifold valve only a small amount to allow the refrigerant to ash from liquid to vapor in the charging hose. GO SLOWLY! A special valve is available for charging liquids.
8. Once the superheat is set properly, close the manifold gauge valves, and backseat the discharge base valve. Tighten the stem packing nuts, remove manifold gauges, and replace service port caps.
-
ect the
Glossary
Blend - A refrigerant that is made up of two or more single-component refrigerants.
Fractionation - Change in the composition of a blend because one (or more) of the component refrigerants is lost (or removed faster than the others). This happens because the components have different boiling points. It can occur in a tank or system that has lost gas, or locally in a system component such as a coil or accumulator.
Temperature Glide - Because of the different boiling temperatures of the components, a blend will evaporate over a range of temperatures (at a constant pressure). The difference between the Bubble Point and the Dew Point is the Temperature Glide.
Superheat - The “extra” heat (beyond what is required to fully evap­orate the refrigerant) that the refrigerant picks up in the evaporator. Superheat is determined by measuring the refrigerant temperature (at the suction line) and then subtracting the saturation temperature (found from the pressure-temperature chart using suction pressure). Use the Dew Point pressure for blends.
Bubble Point - The pressure at which a blend starts to boil. Listed in the pressure-temperature chart.
Dew Point - The pressure at which a blend nishes boiling. Listed in the pressure-temperature chart.
L-2086
37
Page 38
NOTES
Page 39
NOTES
Page 40
DOMETIC MARINE DIVISION 2000 N. Andrews Ave. Pompano Beach, FL 33069 USA Tel +1 954-973-2477 Fax +1 954-979-4414 Mail
marinesales@dometicusa.com
24/7 TECH SUPPORT FOR UNITED STATES AND CANADA 8:00 AM to 5:00 PM Eastern Time: 800-542-2477 After hours and weekends: 888-440-4494
INTERNATIONAL SALES AND SERVICES Europe and the Middle East: +44 (0) 870-330-6101 For all other areas visit our website to find your nearest distributor.
dometic.com
L-0384 | 07/10/17
Loading...