DMTech FP9000L-4, FP9000L-2, FP9000L-6, FP9000L-8 Installation, Setup And Operation

Page 1
ISO 9001:2008 Certified Company
Tel./Fax : +359 64 801 597 e-mail : office@dm-teh.com web : www.dm-teh.com Address : Pleven,Bulgaria 5800
34 “Gen. Lt. Atanas Stefanov” Str.
"DMTeh" Ltd. Pleven
Fire conventional panel
FP 9000L - 2/4/6/8
Installation, setup and operation.
Rev 02:16
“DMTeh” Ltd., Pleven, Bulgaria, 34 “Gen Atanas Stefanov” Str., office 7, Tel. +359 64 801 597
e-mail: office@dm-teh.com Page 1 of 21
,
Page 2
Instructions for installation, setup and operation - FP9000L-2/4/6/8
3
INTRODUCTION
3
TECHNICAL PARAMETERS
5
CONTROLS AND INDICATION
6
FACTORY SET PARAMETERS
7
INSTALLATION AND PANEL SETUP
12
LEVELS OF ACCESS
13
PANEL CONDITIONS
15
CONDITIONS FOR USE, STORAGE AND TRANSPORT
16
CONTENT AND COMPLEX OF DELIVERY
16
WARRANTY
P. CONTENTS:
Page 2 of 16
Page 3
Instructions for installation, setup and operation - FP9000L-2/4/6/8
LINES
Lines:
Number of lines
2,4,6 or 8
Optional
Maximum number of fire detectors in a line
32
Type of the joining line
biconductional
Plume maximum resistance
100 Current thresholds in the lines:
Interruption
from 1 to 4 mA
Duty mode
from 4 to 16 mA
Fire
from 17 to 70 mA
Fire direct /without delay outputs/
from 40 to 70 mA
Short circuit
> 70 mA
Lines functional characteristics:
Verification quantity before entering Fire
mode:
2
Verification and regestrating fault in a earth
conductor
yes
selectively
OUTPUTS
Independent relay output in case of fire alarm:
Quantity
1
Type
switching
NC / NO
Electrical characteristics
3А/125V AC, 3A/30V DC
Controllable output in case of fire alarm:
Quantity
2
Type
potentional relay
Electrical characteristics
(19-28)VDC/ 0,5A
Additional relay outputs (modul M9000R 2/4/6/8) in case of fire alarm:
Quantity
2/4/6/8
Type
potentional-free
NO
1. INTRODUCTION
FP9000L-2/4/6/8 is a conventional Fire alarm panel with 2, 4, 6 or 8 lines. Certified to standards EN 54-2 and EN 54-4. Each line can be connected to 32 detectors. The panel has 4 relay outputs, 2 of which are controllable and one relay. The outputs may have a delay of seven minutes. Panel to add and expansion relay module M9000R - 2/4/6/8.All the panel conditions information is LED indicators.
Quick and easy - installation, setup and starting. Simple and clear procedures for operation and maintenance of the system.
2. TECHNICAL PARAMETERS
Page 3 of 16
Page 4
Instructions for installation, setup and operation - FP9000L-2/4/6/8
Electrical characteristics
3А/125V AC, 3A/30V DC
Independent relay output in case of failure:
Quantity
1
Type
potentional-free, switching
NC / NO
Electrical characteristics
3А/125V AC, 3A/30V DC
Delay outputs:
Time delay of switching outputs
0 ÷ 7 minutes
POWER SUPPLY
Mains power
Voltage
(187-252)V AC
Frequency
50/60 Hz
Maximum power to mains power
38W / AC
Battery power
Battery quantity
2
Type of the battery
Lead, gel
Battery rated voltage
12V DC
Reted power C20
1.3Ah, 4.5Ah, 5 Ah
Charger voltage
27,6 VDC
temperature compensated
Consumption of battery power in standby mode
Configuration with 2 lines
< 40 mA to 24 VDC
Configuration with 4 lines
< 50 mA to 24 VDC
Configuration with 6 lines
< 60 mA to 24 VDC
Configuration with 8 lines
< 70 mA to 24 VDC
Time needed in security mode when mains power supply is down with battery 12V/ 5Ah
Configuration with 2 lines
120h
Configuration with 4 lines
90h
Configuration with 6 lines
80h
Configuration with 8 lines
72h
Time needed in security mode when mains power supply is down with battery 12V/1.3Ah
Configuration with 2 lines
32h
Executive devicess powering
Voltage
(19-28)V DC
Maximal current (including the controllable
outputs current)
1А
Fuses
Mains power 230V AC
4,0 A fusible
Battery power
4,0 А fusible
Powering external devices
1,85 А automatic
Controllable outputs
1,1 А automatic
Functional characteristics
Control of the lines and controllable outputs for fault conditions (short circuit and
Page 4 of 16
Page 5
Instructions for installation, setup and operation - FP9000L-2/4/6/8
interruption) and automatic reset;
Ability to delay controllable and general outputs for fire for a period of 0 to 7 minutes
after the registration of state Fire,with DIP switch.;
Built-in sounder in case of fire – monotonal, continuous with the possibility of exclusion;
Test mode of each (fire alarm) lines;
Ability to Disable each of the fire alarm lines;
Ability to Disable controllable outputs for fire;
Interface for communication with external devices RS485 and networking / optional /;
Possibility for GPRS communication and remote control and monitoring / optional /;
Possibility Ability to add module relay M9000R-2/4/6/8. The module expands the outputs
of the Panel.
Over all size
310х240х80 mm
Weight without batteries
1,25 kg
Safety degree
IP30/ EN 60529
The panel meets standarts:
EN 54-2:1997
EN 54-2:1997/A1:2006
EN 54-2:1997/AC:1999
EN 54-4:1997
EN 54-4:1997/A1:2002
EN 54-4:1997/A2:2006
EN 54-4:1997AC:1999
EN 50130-4:2011
EN 55022:2006/А1:2007
EN 60950-1:2006/А11:2009
Indicators
Function
“POWER”
Constant green light
FIRE
Common indicator - flashing or constant red light in Fire condition
“DIST FIRE
Flashing or continuous red light in case of a remote station Fire while working in a network of more than one panel.
“FAULT”
A common failure indicator. Upon failure of any type a yellow light will start flashing
“SYS FAULT”
A system failure due to stoppage of the CPU. A constant yellow light will light up. Needs to be repaired at an authorized service.
“POWER FAULT”
In case of fault or loss of an AC or battery power supply a steady yellow light will light up.
“TEST”
When in line test condition a constant yellow light will light up.
3. CONTROLS AND INDICATION
LED indicators
Page 5 of 16
Page 6
Instructions for installation, setup and operation - FP9000L-2/4/6/8
“DISABLE”
When in Disabled component / line or controllable output / a steady yellow light will light up.
“OUTS”
Illuminates with steady yellow light at short or interruption of output devices power supply line
“DEL OUTS”
Continuous yellow light at preset delay of connected outputs
“BUZZER SILENCE”
Indicator to the button "BUZZER SILENCE", in suppressing local telltale, a steady red light will light up.
“SOUND SILENCE”
Indicator to the button "SOUND SILENCE", when suppressing Fire outputs, a steady red light will light up.
LALEVEL ACCESS
Indicator to visualize the level of access. If the lights have access level 2. If no lights Access Level 1.
EARTH
Indicator case of damage grounded conductor.
1 2” “1 2 3 4” “1 2 3 4 5 6” “1 2 3 4 5 6 7 8
Individual indicators for Fire and line failure - Fire is lit with red light, fault lights up with yellow light. When disabled and line test there is an indication of the respective condition.
Button
Panel condition
Access
level
Действие на органа за управление
RESET
Fire
Level 2
Exit from Fire condition.
SOUND
SILENCE”
Fire
Level 2
Where activated outputs for Fire - silence of the same outputs.
BUZZER SILENCE
Fire и Failure
All Levels
Suppression / activation of the local sounder
T
Led Test
Levels 1
and 2
Test LED indicators and sound indicator.
Confirmation
Levels 1
and 2
Confirmation of lines and outputs to test and disable
1
Information and
management
Level 1
and 2
Keyboard entry mode:
- Changing the access level;
- Disable mode;
- Test mode. Choice of line or controllable output in test and disable.
BUTTONS
Page 6 of 16
Page 7
Instructions for installation, setup and operation - FP9000L-2/4/6/8
2
Information and
management
Levels 1
and 2
Keyboard entry mode:
- Changing the access level;
- Disable mode;
- Test mode.
3
Information and
management
Levels 1
and 2
Keyboard entry mode:
- Changing the access level.
- Disable mode
- Test mode
5. PANEL INSTALATION AND SETUP
5.1 Panel assembly.
Unpack the panel; Mount the dowels at the appointed place for fixing the panel; Attach the panel to the dowels through the three holes on the chassis
It is recommended that the panel should not be installed near heat sources (radiators, air
conditioners, etc.).
The connecting wires are mounted, using the hole in the box.
5.2. Connecting Fire detectors.
Fire detectors are installed to the panel with the help of two-wire insulated line of total
resistance up to 100. The recommended conductor cross-section is depending on the length of the lines, which are:
Up to 1000 m cable 2 х 0,5 mm Up to 1500 m cable 2 х 1,0 mm
Upon accession to the Fire alarm line to the panel, a check on the resistance is recommended. In case of proper installation in one line (fitted with finite element) between the plus and minus of the cable entering the panel, resistance should be measured 4,7k (+/-10%). When measuring the two wires to "Earth", there should not be a link. The connection is made to the terminals of the relevant modules - "+Lx" and "-Lx" (where "x" is the line number) when observing the indicated polarity. (Fig.1)
2 2
Page 7 of 16
Page 8
Instructions for installation, setup and operation - FP9000L-2/4/6/8
Fig.1
One line can allow the installation of up to 32 Fire detectors generally, regardless of their type.
To the unused lines, directly to the terminals mount the final element "EOL", otherwise the lines will be able in Fault condition.
FIRE LINES - Parameters.
Current interruption
The factory setting is 4 mA.
Current Fire
The factory setting is 16 mA.
Current Fire-direct /without delay outputs/
The factory setting is 40 mA.
- It is used to distinguish between MCP and automatic fire detector.
- If a MCP to make alarm state over 40mA, the panel will recognize it and will include
sirens without delay.
Number of checks
The factory setting is for 2 checks.
- After the first activation, the panel resets the line for 3 seconds and awaits a second
response in the next 60 seconds. If there is a response in this period the panel enters Fire condition.This setting is recommended for lines with automatic Fire detectors the aim of ignoring false alarms.
Outputs
The panel has 3 outputs built in alarm mode.
- 2 controllable relay outputs for sirens
- 1 relay output C/NC/NO*
Additional relay outputs
Add module M9000R. The module has 2,4,6 or 8 relays. Accordingly, for plants FR9000L 2/4/6/8, mounted modules M9000R-2/4/6/8.
Page 8 of 16
Page 9
Delay Outputs
In the panel can be set to delay outputs with DIP switch on Level 3.
DIP-4
123S
000X - without delay outputs 001X - 1 minute delay 010X - 2 minute delay 011X - 3 minute delay 100X - 4 minute delay 101X - 5 minute delay 110X - 6 minute delay 111X - 7 minute delay
*Relay output for fire can be: XXX0 - without delay - where 0 the switch 4 of DIP switch XXX1 - with a delay - where 1 the switch 4 of DIP switch
Instructions for installation, setup and operation - FP9000L-2/4/6/8
5.3. Installation of the executive devices at panel
All connections are made by means of terminals, mounted on the printed circuit board (Fig.2).
Fig. 2
Total consumption of the voltage powering the external devices (terminal "+28 VDC") and the
consumption of the controllable outputs shall not exceed 1,0 A in the heaviest mode.
5.3.1. Installation of the executive devices to the panel’s controllable outputs.
Terminals "+ Out x", "-Out x" - controllable, potential outputs, responding at Fire condition, are used. At the end of the line a resistor 4,7k/0.5W (from the design of the panel) is mounted. It is recommended that in series with the power supply of the corresponding device to place a diode (Fig.3). We recommend 1N4001 diode or equivalent. The panel constantly monitors for failure (interruption or short circuit) power line devices.
Page 9 of 16
Page 10
Instructions for installation, setup and operation - FP9000L-2/4/6/8
Fig. 3
If controllable outputs are not used, directly to terminals "+Outx", "-Outx" a resistor 4,7k/0,5W is connected, otherwise the outputs will be in Fault condition.
5.3.2. Installation of the executive devices to RELAY OUTPUTS. Used:
- Terminal "+28VDC" - positive lead of the stabilized direct voltage for external devices (light and
sound signaling devices, executive devices, etc. );
- Terminal "GND" – (negative lead for supplying the external devices);
- Terminal of the corresponding relay outputs.
Relay outputs with changeover contacts for Fault (REL Fault) and Fire (REL Fire) conditions.
- When in Fault condition of the panel, output - REL Fault, is activated immediately, regardless of
the type of fault. The output may not be disabled or delayed.
- Upon entering the panels condition Fire, no matter what line, output - REL FIRE be activated
immediately. The output may not be disabled or delayed.
- REL Fault - terminals "REL Fault/C", "REL Fault/NO" and "REL Fault/NC" - potential free
relay contacts of the relay. In the absence of failure, there is a link between terminals "REL
Fault/C" and "REL Fault/NO", and in case of failure - between terminals "REL Fault/C" and
"REL Fault/NC".
- REL FIRE - terminals "REL FIRE/C", "REL FIRE/NO" and "REL FIRE/NC" - potential free
relay contacts of the relay. In standby mode there is a connection between terminals "REL
Fig. 4
Page 10 of 16
Page 11
Instructions for installation, setup and operation - FP9000L-2/4/6/8
FIRE/C" and "REL FIRE/NC " and in case of Fire - between terminals "REL FIRE/C" and "REL
FIRE/NO ".
If relay outputs are not used, then its terminals remain free (nothing is connected to them).
5.4. Power supply connection
To the terminal with mains fuse connect feeding cable observing the following positions.
- P - power wire " Phase";
- N - power wire " None ";
- "Earth" - safety ground wire.
The cable should be double insulated and section not less than 0,5 mm2 for power cables and 1,5 mm2 for the safety ground wire. The other end of the feeding cable is connected to the mains using a junction box. The mains power supply of the panel should be on a separate circuit.
6. PUTTING THE PANEL IN WORKING CONDITION
Check the connection to mains power supply. Check the correct connection of peripheral devices. Place the fuse in the terminal. Join the feeding cables to the batteries, where as the batteries are connected in series. To the
positive terminal of the battery join the red wire and the negative – to the blue wire. The overall voltage of both batteries must be greater than 17,6 V, otherwise the panel does not recognize them. Thermal sensor in the panel place in the battery. With it you monitor the temperature and control the mode battery charge.
If everything is done correctly and the lines parameters are within the factory settings, the panel
enters Duty Mode.
Set the accession of exits and the respective delays, if they are necessary.
7. LEVELS OF ACCESS
In panel FP9000L There are 4 LEVELS of access to the various indications and control functions.
Access Level 1
This level of access is for all persons, whom can be expected to identify and react to Fire alarm or fault. Visible are all light indicators.
Available are the following features:
suppression of built sounder; displaying suppressed messages for Fire, Fault and Disabled components; displaying the status of the lines;
Access Level 2
This is a level of access to persons, who are responsible for the safety and are trained and authorized to operate the panel in the conditions:
Security; Fire; Fault; Disabled component; Test.
Page 11 of 16
Page 12
Instructions for installation, setup and operation - FP9000L-2/4/6/8
In access level 2 are available are following features:
Exit from Fire condition; suppression of the outputs, activated when Fire;
involuntary activation of the controllable outputs; suppression of built- in sounder.
Switching from Level 2 to Level 1 and vice versa happens after a combination of buttons and the relevant information on the led indicator "Level Access".
The selection happens with a combination of buttons 1-2-3. With this combination is passed from the access level 1 to 2 and vice versa.
LED indicator "LA" reflects the state respectively. In light we have access Level 2, if notq Access Level
1.
Access level 3
In Level 3 is reached by entering a opening the front cover of the panel.
Available are the following panel’s features:
all possibilities from Levels 1 and 2 Replacing a burnt fuse; on / off communication through interface RS485; delay outputs; Add additional relay module M9000R – 2/4/6/8.
Access Level 4
This is the level of access for persons who are trained and authorized by the manufacturer to repair the panel and modify the software.
Special means are required to enter this level.
8. CONDITIONS OF PANEL
FP9000L panel operates in five conditions: Duty, Fire, Fault, Disabled component and Test.
8.1. DUTY CONDITION
In Security condition, the panel is ready for indication and treatment of Fire and Fault conditions
in case of relevant events.
LED indication – light up the indicator: "POWER" and "DEL OUTS at preset delay of connected
output.
Beeper indication - off. Text message indication - displayed labeled " Security " and information about the current time. Active buttons - button 1,2,3 and T. When you press it the panel enters Information and Control
condition.
8.2. FIRE CONDITION
The panel may be in Fire condition in one or several lines.
- LED indication - light indicators:
- "FIRE"
- "1 2 /3 4 /5 6 /7 8" Local indicator(s) for Fire in a line.
Page 12 of 16
Page 13
Instructions for installation, setup and operation - FP9000L-2/4/6/8
Beeper indication - Sounder is constantly on. Active buttons
button "BUZZER SILENCE". Pressing it leads to:
- Disabling the embedded sounder, if it has responded to Fire or Fault;
- Activating the built-in sounder, if the panel is in Fire or Fault condition and the tale is
disabled by previous pressing of the same button.
button "SOUND SILENCE". Press it to :
- When suppressed outputs for Fire - forced activation of the outputs;
- When activated outputs for Fire - suppression of these outputs.
button "RESET". Press it to :
- the panel is forced to exit Fire condition and reset lines ( power down for 3 seconds).
8.3. Fault Condition
Panel enters Fault condition when registering any of the following events:
- Fatal system fault;
- Low power - diluted battery during droping in the mains supply;
- Fault in a line - removed Fire alarm detector, short circuit or break;
- Fault in a controllable output - short circuit or break;
- Damage to the mains;
- Fault in backup batteries;
- Short circuit or leakage to ground wire;
- Fault in power lines;
- Fault in power supply for external devices;
- Fault in network or transmission device.
When systemic failure processor can not continue. Exit for this kind of fault can only be accomplished by turning off the power and subsequent repair. All damage, except for the system kind, lead to switching off some periphery. Exiting this condition happens automatically to 100 seconds after dropping out (removal) of the fault. When in fault "Low power" the built-in sounder is activated with discontinuous signal.
LED indication – lights up the indicator : "FAULT" and depending on the fault :
- Upon System error - indicator "SYS FAULT" lights up in continuous yellow light;
- Upon fault in Fire alarm line - individual fault indicator flashes yellow light respectively
when:
short circuit - with a frequency of 1 Hz ( slow flashing ); interruption - a frequency of 4 Hz ( fast flashing ); removed Fire alarm detector - a frequency of 4 Hz, every one second (choppy rapidly
flashing).
- Upon fault in a controllable output - indicator "OUTS" lights up with flashing yellow
light;
- Upon fault in mains supply - indicator "POWER FAULT" lights up in continuous yellow
light;
- Fault in the local network or the transmission device - indicator "COMUN" lights up with
a steady yellow light.
- If the sound signal is suppressed by button "BUZZER SILENCE", LED indicator lights
up a constant red light.
Page 13 of 16
Page 14
Instructions for installation, setup and operation - FP9000L-2/4/6/8
Beeper indication – The built-in sounder is activated with a discontinuous signal. Active buttons
button "BUZZER SILENCE". Pressing it leads to:
- disabling the embedded sounder, if it is activated by Fire or Fault;
- activating the built- in sounder, if the panel is in Fire or Fault condition and the
annunciator is disabled by previous pressing the same button.
8.4. DISABLED COMPONENT CONDITION
Panel enters Disabled component condition after a manual operation of disabling a specific component - a Fire alarm line and/or controllable outputs. The condition is managed through the information and control screens.
Putting fire lines or controllable outputs in mode Disable is as follows.
1. Level Access 2;
2. Dials the keyboard combination 2222;
3. Led Disable indicator flashes;
4. With button “1” is selected the line or controllable outputs;
5. With button “Tis confirmed;
6. Combination 2222 out of the programming mode Disable;
LED indication - light indicators:
- "DISABLE" lights up with a constant yellow light
- "1 2 3 4 5 6 7 8" local line indicator lights up with flashing yellow light.
- "OUTS" flashes when a disabled controllable output.
Beeper indication - not affected by the disabled component condition.
8.5. TEST CONDITION
Panel enters Test condition through manual operation for setting a Fire alarm line in to test. The condition is managed through screens of Information and control condition. Menu «Test Lines» is fourth from the main menu.
Putting fire lines in mode Test is as follows.
1. Level Access 2;
2. Dials the keyboard combination 3333;
3. Led Disable indicator “TEST” flashes;
4. With button “1” is selected line;
5. With button “T” is confirmed;
6. Combination 3333 out of the programming mode TEST;
- The line is reset (shuts off its power supply for time 3sec) automatically every 60s.
Page 14 of 16
Page 15
Instructions for installation, setup and operation - FP9000L-2/4/6/8
Fire Station FP 9000L
1 qty.
EOL - resistor 4,7k/0,5W:
- for configuration with 2 lines /FP9000-2/
2 qty.
- for configuration with 4 lines /FP9000-4/
4 qty.
- for configuration with 6 lines /FP9000-6/
6 qty.
- for configuration with 8 lines /FP9000-8/
8 qty.
(EOL) End for controllable output - resistor 4,7k/0,5W;
2 qty.
Fuse 4,0А;
2 qty.
Connective bridge for batteries;
1 qty.
Packaging.
1 qty.
LED indication - light up indicators:
- "TEST" is lit with yellow light
- " 1 2 3 4 5 6 7 8 " local line indicator in Test lights up with flashing yellow and red light.
Beeper indication - is not affected by the of the Test condition lines.
8.5.1. TEST LED
Testing of LED indication the panel done by button «T».
9. CONDITIONS FOR USE, STORAGE AND TRANSPORT
Operation and storage
The panel is used and stored in closed rooms under the following conditions :
Temperature
- storage from 5оC to 35оC
- transport from -10оC to 50оC
- working from -5оC to 40оC
Relative humidity
- storage to 80%
- working to 93%
Transport
The panel is transported in covered vehicles, in factory packing and in the above atmospheric conditions.
10. DELIVEERY COMPOSITION AND COMPLEXITY/SET
11. WARRANTY
The manufacturer guarantees the product’s conformity with EN 54-2: 1997, A1: 2006, EN54-4: 1997, A1: 2002, A2: 2006. The warranty period is 24 months from the date of sale, provided that:
- the conditions of storage and transport were met;
Page 15 of 16
Page 16
Instructions for installation, setup and operation - FP9000L-2/4/6/8
- the startup has been done by authorized persons;
- The requirements for operation conditioned in this instruction were met;
- Defects are not caused by natural phenomena and accidents of thr plug socket.
DMTeh wishes you splendid work!
For any questions may contact the company's technical staff DMTeh, by email.
e-mail :office@dm-teh.com
Page 16 of 16
Loading...