Detcon 610-N4X-SA User Manual

Model 610-N4X-SA
NEMA 4 X Control Enclosure
Model 610-N4X www.detcon.com
Detcon Inc.
Detcon Inc.
Gas Detection Control System
www.detcon.com
www.detcon.com
d e t co n I n c .
RESET/ACK
BUTTON
Operator’s Installation and Instruction Manual
Covers 3 and 5 relay, Stainless and Fiberglass Enclosures
DETCON, Inc.
3200 Research Forest Dr.,
The Woodlands, Texas 77387
Ph.281.367.4100 / Fax 281.298.2868
www.detcon.com
July 15, 2005• Document #3001• Revision 0.1
This page left intentionally blank
Model 610-N4X-SA
610-N4X-SA Instruction Manual ii
Model 610-N4X-SA
Table of Contents
1.0 Introduction.............................................................................................................................................. 1
1.1 Description ........................................................................................................................................... 1
1.2 Specifications ....................................................................................................................................... 1
1.3 Relay Logic Description....................................................................................................................... 2
1.4 Front Panel Alarm Reset ...................................................................................................................... 2
2.0 Installation................................................................................................................................................ 3
2.1 Start Up ................................................................................................................................................ 6
3.0 Maintenance & Repair ............................................................................................................................ 6
4.0 Spare Parts List........................................................................................................................................ 8
5.0 Warranty .................................................................................................................................................. 8
Table of Figures
Figure 1 Mounting................................................................................................................................................ 3
Figure 2 Motherboard Schematic Wiring Diagram.............................................................................................. 4
Figure 3 Component Layout................................................................................................................................. 5
Figure 4 Alarm Wiring......................................................................................................................................... 5
Figure 5 Typical Dry Contact Connections.......................................................................................................... 6
Figure 6 Input Power Connections....................................................................................................................... 6
Figure 7 Backplane Configuration Jumpers......................................................................................................... 7
610-N4X-SA Instruction Manual iii
Model 610-N4X-SA
This page left intentionally blank
Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 •
610-N4X-SA Instruction Manual iv
www.detcon.comsales@detcon.com
Model 610-N4X-SA
1.0 Introduction
Detcon Model 610-N4X-SA Gas Detection System consists of 3 major assemblies:
1. The 610-N4X-SA Fiberglass or Stainless Steel control enclosure.
2. The Model 10 single channel digital control modules.
3. The remote mount gas sensor assemblies.
The NEMA 4X control enclosure is detailed in this manual, the Model 10 digital control modules are detailed in the Detcon Model 10 Operators Installation and Instruction Manual, and applicable sensor assemblies in their corresponding Operators Installation and Instruction Manual.
1.1 Description
Detcon Model 610-N4X-SA control enclosure, along with Model 10 digital control modules, is designed to serve as a host assembly for up to six remote mount gas detection sensor assemblies. The control enclosure is rated NEMA 4X, which is by definition rain tight and therefore suitable for outdoor location in electrically non-hazardous environments. The single channel modular design supports application flexibility wherein one or two gas detection systems are configured dependent on the three or five alarm relay model. All control modules are plug-in front panel accessible for easy maintenance and repair. The system is powered by 120VAC unless otherwise specified at the time of order.
Discrete output terminal strips located on the controller motherboard are provided for sensor terminations. The 4-20 mA outputs for remote recording devices and an RS-485 serial ModBus™ output are located on the motherboard. The VDC power in, and remote alarm reset terminations are also provided on the Motherboard. Din Rail mounted terminal block outputs are provided for two or four alarm and one fault relays. Terminations for AC power-in are also provided on a Din Rail.
All Relays on the Model 10 digital control modules are configured as Latched, Normally Energized in No­Alarm/No-Fault condition. These relays control the state of the Alarm Relays mounted on the motherboard. Each Alarm Relay is a DPDT relay with one set of contacts for annunciator power and one set of dry contacts for customer use. Three – 5Amp Fuse Blocks are provided for each alarm, providing the ability to connect up to three annunciators for each alarm condition (including Fault).
1.2 Specifications
Electrical Classification
NEMA 4X
Dimensions
24''W x 24''H x 10 1/2''D
Capacity
6 single channels
Power Input
220VAC/117VAC/24VDC
Power Consumption
<5 watts per channel (includes gas sensor and control modules. Does not include annunciators.)
Outputs
Discrete Analog 4-20 mA DC Serial RS-485 Modbus™ Discrete or zoned alarm relays (Alarm 2 Timer(s))
Discrete alarm relays K1, K3 (and if applicable K4)
Resistive load: 7.5A, 240 VAC; 10A, 30 VDC
610-N4X-SA Instruction Manual Rev. 0.1 Page 1 of 8
Model 610-N4X-SA
Inductive load: 5A, 240 VAC; 7.5A, 30 VDC Max. operating current: 10A
Time delay relays K2 (and if applicable K5)
Resistive load: 10A, 240 VAC; 10A, 30 VDC Inductive load: 7A, 240 VAC; 7.5A, 30 VDC Max. operating current: 10A
Operating Temperature Range
-40°C to +175°C
Battery Backup (If applicable)
2ea. 12V 2.9Ah batteries in series; ½ hour minimum operating time
Warranty
One year
1.3 Relay Logic Description
Relay Assignments
The 610-N4X-SA comes with 3 or 5 Alarm Relays for use with one or two gases respectively. One or two of these relays are timer relays (Dependent on one or two gas). (Refer to Figure 3) In this typical system the Relays are:
K1 – Alarm 1 – H2S Low Relay K2 – Alarm 2 – H2S High Time delay relay K3 – Fault relay (Common Fault for three and five relay systems) K4 – Alarm 1 – LEL Low Relay (If applicable) K5 – Alarm 2 – LEL High Time delay Relay (If Applicable)
Alarm 1 – H2S/LEL Low
During Alarm 1 conditions, the Normally Energized coil(s) on the control modules will de-energize. This will energize Alarm 1 Relay, K1 (or K4 if applicable), applying power to annunciators attached to alarm 1 (H2S or LEL Low). Alarm 1 conditions can be Acknowledged and Reset via the RESET/ACK Switch on the front panel of the unit.
Alarm 2 – H2S/LEL High
During Alarm 2 conditions the Normally Energized coil(s) on the control modules will de-energize. This will energize the Alarm 2 Relay K2 (or K5 if applicable) applying power to annunciators attached to alarm 2 (H2S or LEL High). The time delay relay controlling the annunciators will energize for a number of minutes determined by the setting of the relay, and will then release. Alarm 2 conditions can be Acknowledged and Reset via the RESET/ACK Switch on the front panel of the unit.
Fault Alarm
During Fault conditions, when any controller goes into fault, or upon loss of power, the Normally Energized coil(s) on the control modules will de-energize. This will de-energize the Fault Relay K3, applying power to the annunciators attached to the Fault relay.
1.4 Front Panel Alarm Reset
A Front Panel mounted, normally open, momentary switch is used to reset the alarms of all Model 10 controllers. The reset function is effective when the Model 10’s respective alarms have been programmed in
610-N4X-SA Instruction Manual Rev. 0.1 Page 2 of 8
Model 610-N4X-SA
the latching position and alarm conditions have passed. Each Model 10 controller also has its own discrete alarm reset switch, which is discussed further in the Model 10 Instruction Manual.
2.0 Installation
1. Securely mount the 610-N4X-SA Enclosure in accordance with figure 1. Stainless Steel version mounting footprint is the same as that shown.
25.59in [649.94mm]
22.75in [577.85mm]
Model 610-N4X www.detcon.com
Detcon Inc.
Detcon Inc.
Gas Detection Control System
www.detcon.com
www.detcon.com
d et c o n I n c .
MODEL 10
MODEL 10
MODEL 10
MODEL 10
MODEL 10
MODEL 10
ALM 2
ALM2
ALM 2
ALM 2
ALM2
ALM 2
ALM 1
ALM1
ALM 1
ALM 1
ALM1
ALM 1
FAULT
FAULT
FAULT
FAULT
FAULT
FAULT
ALARM
ALARM
ALARM
ALARM
RESET
RESET
RESET
RESET
TEST
TEST
TEST
TEST
TEST
TEST
RESET/ACK
BUTTON
MODEL 10MODEL 10MODEL 10MODEL 10MODEL 10MODEL 10
ALM2
ALM 2
ALM 2
ALM2
ALM 2
ALM 2
ALM1
ALM 1
ALM 1
ALM1
ALM 1
ALM 1
FAULT
FAULT
FAULT
FAULT
FAULT
FAULT
ALARM
ALARM
ALARM
ALARM
ALARM RESET
RESET
ALARM
ALARM
ALARM
RESET
RESET
RESET
RESET
RESET
RESET
TEST
TEST
TEST
TEST
TEST
TEST
Reset/Ack Push Button
Houston Texas
Houston Texas
Mounting Holes R0.28in [R7.14mm]
26.8in [681.99mm]
10.4in [263.91mm]
27.8in [707.39mm]
Figure 1 Mounting
2. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in the Sensor Instruction Manual. Terminate field wiring from sensors on the 610-N4X-SA motherboard. Terminals are labeled “Sensor” (mA, + and –, Figure 2).
3. If applicable, terminate the discrete 4-20 mA outputs to external device(s). Terminals are labeled “4­20 Out” (+ and –, Figure 2).
4. If applicable, terminate the RS-485 serial output to external device(s). Terminals are labeled “RS­485” (A+, B–, and Shield, Figure 2). If applicable, terminate RS-485 Shield to Earth Ground via the jumper tab located to the left of the RS-485 terminals. Place the jumper on the bottom 2 contacts to tie RS-485 shield to Earth Ground or place the jumper tab on the top two terminals for storage.
5. There are three fused 5Amp 120VAC outputs for every Alarm Relay and the Fault Relay. These Fuse Block Terminals are located near the bottom center of the enclosure (Figure 3 and Figure 4). To the left of the Fuse Blocks are as many Thru-blocks tied to Neutral. Based on the application and use of relay contact outputs, all annunciators should be connected to these output terminals. All wiring
610-N4X-SA Instruction Manual Rev. 0.1 Page 3 of 8
Model 610-N4X-SA
terminations should be completed prior to application of power. Shut-in controls may be omitted until system test is complete.
PS VAC
RED +
BLK -
L1-BLK N-WHT GND-GRN
A(+)
B(-)
Alarm 2
Alarm 1
Fault
VDC-
+
-
L1
GND
Shld
+
VDCVAC
-
L1
GND
+
-
VDC
N
CH1
CH2-CH6 P12-P16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
+
-
mA
NC
NO
COM
NC
NO
COM
NO
NC
COM
+
Out
-
CH1 P11
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Typical
Jumpers
Typ. x 6
Sensor
N
ALM2
ALM1
FAULT
4-20mA
Figure 2 Motherboard Schematic Wiring Diagram
610-N4X-SA Instruction Manual Rev. 0.1 Page 4 of 8
Battery Backup
Model 610-N4X-SA
610 - Mother Board
BRKR
+
P1
-
+
P2
­PS DC
MODEL 10
ALM 2 ALM 1 FAULT
TEST
A1
PS VAC L1 N
P3
GND
MODEL 10
MODEL 10
MODEL 10
MODEL 10
MODEL 10
ALM 2
ALM 2
ALM 2
ALM 2
ALM 1
ALM 1
FAULT
FAULT
ALARM
ALARM
ALARM
RESET
RESET
RESET
TEST
TEST
ALM 2
ALM 1
ALM 1
ALM 1
FAULT
FAULT
FAULT
ALARM
ALARM
ALARM
RESET
RESET
RESET
TEST
TEST
TEST
TB3
Cut-Off
TB2
Low Voltage
123
4
TB1
AC INPUT ALARM OUTPUTS
123 4 567891011121314
ALM RESET
VDC IN
+
-
VAC IN L1 N
GND
RS-485
A(+) B(-) Shld
ALM POWER
+
-
L1 N
GND
ALM COIL
+
-
COMMON ALARMS ALM2 ALM1 FAULT VDC-
P4
P5
P7
P7
P8
P9
P10
CH1+CH2 CH3 CH5CH4 CH6
­mA
SENSORALM2
NC NO C NC NO C
ALM 1
NC NO C +
OUT
-
4-20 FAULT
27
K1 K2 K3
86543127865431
ALARM RELAYS K1 - K5
789101617181920
5
6
1112131415
21
23
22
24
2526272829
H2S LOW H2S HIGH FAULT LEL LOW LEL HIGH
Figure 3 Component Layout
TB1 - 3 Relay Unit
15 16 17 18 19 20 21 22 23
C
EN
S
27
27
27
S
T
PU
N
I
R
SO
A
m
2
0
-
4
:
-
6
1
H
K5K4
865431
30
865431
865431
32
333435
363738454647484950
3940414243
44
DRY CONTACTS
424344
4645484749
50
AC INPUT ALARM OUTPUTS
321
4
AC INPUT
Neutral
Rtn
8
657
Neutral
Rtn
19
131211109
1514181716
20
H2S LOW H2S HIGH FAULT
21
23
22
26
24
25
H2S LOW
ALARM OUTPUTS
FAULT
H2S LOW
H2S HIGH
DRY CONTACTS
30
29
27
28
333235
34
LEL LOWH2S HIGH FAULT
LEL HIGH
36
43
40
393837
FAULT
H2S LOW
H2S HIGH
50
444142
494748
45
46
LEL LOW
LEL HIGH
DRY CONTACTS
TB1 - 5 Relay Unit
Figure 4 Alarm Wiring
610-N4X-SA Instruction Manual Rev. 0.1 Page 5 of 8
Model 610-N4X-SA
6. Each alarm has an associated set of dry contacts from the Alarm/Fault relay’s (Figure 3 and Figure 5). These dry contact terminals consist of a Common relay connection through a terminal disconnect, and the NC and NO Contacts via through terminals (Figure 4).
24
COM - Common NC - Normally Closed NO - Normally Open
25 26
COM
NC
Disconnect Terminal Block
Through Terminal Block
NO
Figure 5 Typical Dry Contact Connections
7. If applicable, connect a 24VDC source or standby battery to the terminal strip labeled “VDC IN” (+ and –) on the Motherboard (Figure 2).
8. Connect 117VAC input to the Circuit Breaker labeled “VAC IN” in the lower left of the enclosure (Figure 3 and L1, N, EARTH in Figure 6). If applicable, connect 220VAC. The power supply will accept both voltages.
9. Connect Earth Ground to Terminal TB1-1, and Neutral to terminal TB1-5 (Figure 6).
20Amp
Brkr
78956
Neutral / N
Ground / Earth
123
4
ON
VAC Input / L1
Figure 6 Input Power Connections
2.1 Start Up
Upon completion of all field wiring: Apply power to the 610-N4X-SA by turning the 20Amp Circuit Breaker ON. Note that each Model 10 controller digital display illuminates. Note; varying readings may occur during sensor warm-up. A 10 second alarm delay will occur on power up. Refer to the applicable Sensor Instruction Manual for additional sensor start-up details.
3.0 Maintenance & Repair
The Detcon Model 610-N4X-SA’s modular design allows for minimum ‘down-time’ during maintenance and/or repair.
610-N4X-SA Instruction Manual Rev. 0.1 Page 6 of 8
Model 610-N4X-SA
Adding/Removing Control Modules
When adding or removing Control Modules it is imperative that the backplane jumpers are correctly removed or added to insure proper operation of the fault alarm circuitry (see Figure 7). When removing a Control Module, the jumpers for Fault (JPx-G, H, and I) directly to the left of the module being removed, must be installed to allow proper signal flow and fault operation. When a Control Module is being added to the configuration, the jumpers (JPx-G, H, and I) directly to the left of the module being installed, must be removed to insure that the signal does not bypass the new module. Incorrect placement of jumpers will cause the fault alarm circuit to operate incorrectly.
CH4CH3 CH5 CH6
Jumpers removed for
Control Modules 7 and 8.
A B C D E F
G
H
I
JP6
1 2 3 4 5 6 7 9 9 10 11 12 13 14
A B C D E F
G
H
I
JP7
1 2 3 4 5 6 7 9 9 10 11 12 13 14
A B C D E F
G
H
I
JP8
1 2 3 4 5 6 7 9 9 10 11 12 13 14
A B C D E F
G
H
I
JP9
1 2 3 4 5 6 7 9 9 10 11 12 13 14
Jumpers installed for Control Modules not installed in unit.
FAULT Output to Fault Relay
Fault Jumper positions G, H, and I.
Figure 7 Backplane Configuration Jumpers
Model 10 Control Modules
A Model 10 control module may be changed by simply loosening its mounting screw and sliding the module out of its card cage. See the Model 10 Instruction Manual for more information on the Model 10 controller.
Circuit Breaker/Power Switch
If the circuit breaker should trip due to a high current or over voltage, the circuit breaker can be reset by cycling the breaker ‘OFF’ and back ‘ON’. If the breaker trips again, a problem has occurred that will need to be alleviated before power can be restored.
Replacement of the circuit breaker is accomplished by disconnecting power from the unit, disconnecting the wires going to the breaker, and removing the breaker from the Din-Rail. Replace the breaker and reconnect the wires to the new breaker.
Power Supply
Replacement of the power supply is accomplished by, removing the 10 screws that secure the 610-N4X-SA face plate, disconnect the two power supply plugs from their respective headers, remove the three screws holding the power supply bracket to the Motherboard. Remove the four screws that hold the power supply bracket to the power supply; disconnect the wires from the power supply and reassembly with the new power supply. Reference Figure 6 for wiring details.
610-N4X-SA Instruction Manual Rev. 0.1 Page 7 of 8
Model 610-N4X-SA
4.0 Spare Parts List
Part # Description 363-752400-000 110 watt, 24 VDC switcher power supply 0224 Gold plated jumper tab 305-300410-000 Din-Rail Mounted Fused Terminal 0302 5Amp 3AG Slow-Blo Fuse 3309 DPDT 8 Pin Octal 10A Relay 330-901100-024 DPDT Hermetically Sealed 8 Pin Octal 10A Relay 330-794500-124 DPDT 8 Pin Octal Timer Relay 226-910120 20 Amp Circuit Breaker 500-505000-000 Low Voltage Cut-off PCB (If applicable) 3423-2 12V 2.9Ah Battery (If applicable)
5.0 Warranty
Detcon Inc., as manufacturer, warrants under intended normal use each new Model 610-N4X-SA NEMA 4X control enclosure to be free from defects in material and workmanship for a period of one year. The warranty period begins from the date of shipment to the original purchaser and ends one year thereafter. All warranties and service policies are FOB the Detcon Inc. facility located in The Woodlands, Texas.
610-N4X-SA Instruction Manual Rev. 0.1 Page 8 of 8
Loading...