1.0 Introduction
1.1 Description
1.2 Multiple Alarm Relay Circuit
1.3 Alarm Disable
1.5 Installation
1.6 Start-up
1.7 Power Supply
1.8 Warranty
1.9 Spare Parts
detcon inc.
Page 2
11..00 II
NNTTRROODDUUCCTTIIOONN
Detcon Model 610AFB gas detection system consists of 3 major assemblies:
1. The NEMA 4 fiberglass control enclosure.
2. The single channel digital control modules.
3. The remote mount gas sensor assemblies. The NEMA 4 fiberglass control enclosure is detailed in section 1.0 of the manual, the control modules in
section 2.0 and applicable sensor assemblies in section 3.0.
11..11 DD
EESSCCRRIIPPTTIIOONN
Detcon Model 610A-FB control enclosure is a NEMA 4X molded fiberglass case with hinged, gasketed door and is designed for surface mounting in both indoor and outdoor locations. An unbreakable glass view win­dow is gasket mounted in the door. The NEMA 4X rating is by definition raintight and therefore suitable for outdoor location in electrically non-hazardous environments.
The control enclosure houses the mainframe hardware compatible with Detcon Model Series 10A digital electronic controls. Model 610A-FB system capacity is up to 6 channels consisting of remote mounted area sensors and single channel electronic controls (Detcon Model 10A). The system is powered by AC line power and/or 24 VDC unless otherwise specified at time of order.
The control enclosure includes, as standard operating controls (see figure 1); a power on/off switch, an alarm disable switch and a line power fuse. Discreet output terminal strips located on the controller mother board are provided for sensor terminations, Form C dry contact alarm outputs, 4-20ma outputs for remote
Detcon Model 610A-FB Gas Detection System PG.2
MODEL 610A-FB
POWER 2 AMP ALARM
HOUSTON T EXAS
C
C
K
K
O
O
L
L
L
MODEL 10A
MODEL 10A
MODEL 10A
H2S MONITOR
H2S MONITOR
H2S MONITOR
ppm
ppm
HIGH
HIGH LOW
LOW FAULT
FAULT
ALARM
ALARM RESET
RESET
detcon inc.
detcon inc.
detcon inc.
HOUSTON, TEXAS
HOUSTON, TEXAS
HOUSTON, TEXAS
detcon inc.
C
C
K
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
C
K
ALARM RESET
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
K
O
ppm
HIGH LOW FAULT
DISABLE
C
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
C
K
K
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
Page 3
recording devices, AC power in, DC power in, remote reset as well as relay logic and power terminations for the multiple alarm relay circuit. Form C relay outputs may be discreet, zoned or common by gold plated jumper tabs located on the controller mother board. Form C dry contacts; common, normally open and nor­mally closed, are provided for 3 alarms; High, Low and Fault. Contacts are rated at .6 amp @125 VAC / 2 amp @ 30 VDC. When used in conjunction with the multiple alarm relay circuit (part #5026), contacts are rated 8 amp @ 117 VAC / 5 amp @ 30 VDC.
Detcon Model 610A-FB Gas Detection System PG.3
Figure 1 - Controller Terminals
MODEL 610A-FB
+
GND
+DC
COM
GND
L1 L2
L1 L2
DC IN
RESET
AC IN
ALARM POWER
POWER 2 AMP ALARM
HOUSTON TEXAS
C
O
K
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
C
O
K
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
detcon inc.
C
O
K
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
C
O
K
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
+
SENSOR
MANONCC
NO NCC
FAULT
NONCC
HIGH
LOW
+
4-20MA
ALARM
COIL
DC
POWER
+
4
3
2
1
COM
DISABLE
C
O
K
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
C
O
K
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
I/O
C
NC
4
NO
C
3
NC
NO
C
2
NC
NO
C
1
NC
NO
Page 4
11..22 MM
UULLTTIIPPLLEEAALLAARRMMRREELLAAYYCCIIRRCCUUIITT
A multiple alarm relay circuit (figure 2) mounted on the controller mother board is provided with each Detcon Model 610A-FB. The alarm circuit consists of 4 interposing relays (contacts are rated 8 amp @ 117 VAC / 5 amp @ 30 VDC) with 24VDC coils as standard. Other coil voltage ratings must be specified at time of order. The alarm circuit can be configured to output Form C dry contacts (common, normally open and normally closed), AC power or DC power. A 5 amp microfuse is provided for each relay and is configured in series with the common pole of its respective relay. This configuration is functional regardless of whether Form C dry contacts, AC power or DC power outputs are used.
An In/Out termination is provided for applying AC or DC power into any one of the interposing relays. A gold plated jumper tab is used to apply the in/out power option to its corresponding relay, thus the 4 relays may be used in a combination of Form C dry contacts and VDC outputs or Form C contacts and VAC out­puts.
The terminations labeled "Alarm Coil Power" located to the left of the alarm circuit are used only for coil power. The "+" termination may be used to provide for various relay logic through the Form C dry contacts of each individual Model 10A channel located on the controller mother board directly above the alarm cir­cuit card. The "-" termination should be wired into the common termination (shown by a common symbol) located on the left of the alarm circuit board.
The terminations labeled "Alarm Power" located to the far left of the unit are used for providing power to the In/Out termination on the alarm circuit card. As can be seen in the 610A-FB schematic / wiring diagram (figure 3), the alarm power terminations for AC come directly from the AC input terminals located above on the controller mother board. The same is true of the DC power terminations. Note: DC power used to drive alarms must be obtained through a remote DC power source. The remote DC power source should be termi­nated to the terminals labeled "DC IN" located on the controller mother board. The "DC IN" terminations function as both an alternative DC source used to power the 610A-FB as well as provide power for DC alarms. The 610A-FB power supply is not capable of providing power for alarm devices.
Detcon Model 610A-FB Gas Detection System PG.4
COIL #4 COIL #3 COIL #2 COIL #1
COMMON
Figure 2 - Multiple Alarm Relay Circuit
I/O JUMPERS
#4 #3 #2 #1
5 AMP MICRO FUSE
#4
#3
#2
#1
IN / OUT COM N.C. N.O. COM N.C. N.O. COM N.C. N.O. COM N.C. N.O.
#4
#3
#2
#1
Page 5
11..33 AA
LLAARRMMDDIISSAABBLLEE
The alarm disable switch, located on the front panel, operates by removing DC common from the "Alarm Coil Power" terminals. Disabling of alarms does not inhibit any function of the Model 10A digital control module. The digital display, alarm LED's and on board alarm relays remain active.
Detcon Model 610A-FB Gas Detection System PG.5
Figure 3 - Schematic/Wiring Diagram
+DC 16 GA. Red to TB2 Pin 5
–DC 16 GA. Black to TB2 Pin 4
POWER SUPPLY
BRACKET
L1
COMMON
+IN
+OUT
DISABLE
16 GA.-BLK
16 GA.-BLK
16 GA.-RED
16 GA.-RED
16 GA.-BLK
DC IN
+
PS+ PS-
TB2
5
4
3
2
1
TB1
DC+
DC–
L1
L2
GND
L1 - 16 GA.Black to TB1 Pin 3
3
L2 - 16 GA.White to TB1 Pin 2
2
GND - 16 GA.Green TB1 Pin 1
1
POWER
SUPPLY
SWITCH PCB
ALARM
POWER
COMMON BUS
RESET BUS + POWER BUS
16 GA.-BLK
2 AMP
DISABLE
TYP. MODEL 10A CONTROLLER TERMINALS
GND
L2
PS L1
RESET
AC IN
+
MANCNOCNONCCNONCC
SENSOR
FAULTHIGHLOW
L1
L2
GND
COIL
POWER
+DC
COM
+DC
COM
+
4-20MA
L1
L2
GND
ALARM
POWER
Page 6
11..44 RR
EEMMOOTTEERREESSEETT
A remote mounted normally open momentary switch may be used to reset all Model 10A controllers. The reset function is effective when the Model 10A's respective alarms have been programmed in the latching position and alarm conditions have passed. Each Model 10A controller has its own alarm reset switch which is discussed further in section 2.0.
11..55 II
NNSSTTAALLLLAATTIIOONN
Step 1. Securely mount the 610A-FB enclosure (see figure 4).
Step 2. Connect 117 VAC input wiring to the lugless terminal strip (labeled AC IN) on the controller mother board as detailed in figure 1. Line power current load is maximum 2 amps.
Step 3. Connect the 24 VDC standby battery to the lugless terminal strip (labeled DC IN) on the controller mother board as detailed in figure 1. The DC current load is a maximum 3 amps.
Caution: Observe correct polarity when terminating all input / output field wiring. Failure to do so may result in circuit damage on power up.
Step 4. If applicable, connect a normally open momentary remote mounted switch to the lugless terminal strip (labeled RESET) located on the controller mother board as detailed in figure 1.
Detcon Model 610A-FB Gas Detection System PG.6
Figure 4 - Dimensions/Mounting Detail
.31" DIA. MOUNTING HOLE .56" DIA. COUNTERBORE
17.25
14.75"
PADLOCKING LATCH
DIMENSIONS WITH MOUNTING FOOT: WIDTH - SAME AS STANDARD; HEIGHT - 18.75" MOUNTING HOLE DIMENSIONS (CENTER TO CENTER): VERTICLE - 17.25 HOROZONTAL - 10.5
10"
13.25"
9.65
Page 7
Step 5. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in section 3.0. Terminate field wiring from sensors to Model 610A-FB lugless terminal strips located on the controller moth­er board as shown in figure 1.
Note: Based on the application and use of relay contact outputs, complete all wiring terminations prior to application of power. Shut-in controls may be omitted until system test is complete.
11..66 SS
TTAARRTT
--UU
PP
Upon completion of all field wiring: Depress the power switch on the controller assembly front panel. Note that each Model 10A controller digital display illuminates. Varying readings may occur during sensor warm­up. A 10 second alarm delay will occur on power up. Refer to section 3.0 for additional sensor start-up detail.
11..77 PP
OOWWEERR
SS
UUPPPPLLYY
The 610A-FB is modularly designed so as to avoid unnecessary down time in the event of component failure. In the event of a power supply failure, the power supply may be removed without disconnecting field wiring. To remove and replace the power supply, follow the instructions below.
Note: Reference figure 3 for wiring locations and colors.
1. Remove the Model 10A control modules.
2. Remove the 4 screws from the front panel and expose the power supply.
3. Disconnect the 5 pin plug on the left of the power supply.
4. Disconnect the 2 pin plug on the right of the power supply.
5. Remove the 4 screws from the bracket that holds the power supply to the controller mother board.
6. Lift the power supply and front panel assembly out of the enclosure.
7. Remove the two screws that hold the power supply to the power supply bracket.
8. Use a screwdriver to remove the five wires that terminate to the power supply.
9. Reverse the above procedure with the new power supply (Detcon part number 3655-24
).
Note: Be sure to re-connect the wires properly (see figure 3). Failure to do so may result in damage during power up.
11..88 WW
AARRRRAANNTTYY
Detcon inc., as manufacturer, warrants under intended normal use each new Model 610A-FB control enclo­sure to be free from defects in material and workmanship for a period of one year from the date of shipment to the original purchaser. All warranties and service policies are FOB the Detcon Inc. facility located in the Woodlands, Texas.
11..99 SS
PPAARREEPPAARRTTSS
PART # DESCRIPTION 5026 Multiple alarm relay circuit 3655-24 3 amp, 24 vdc switcher power supply 0224 Gold plated jumper tab 2812 28 vdc lamp for power and disable switch 0295 5 amp micro fuse 0298 2 amp 3AG fuse 3218 Power switch 3218 Disable switch 2806 Green switch cap 2807 Red switch cap 3280 Fuse holder
Detcon Model 610A-FB Gas Detection System PG.7