Detcon 110A-FB-BBU User Manual

detcon inc.
Detcon Model 110A-FB-BBU
Operator's Instruction Manual
January 1, 1999, Document #2474, Revision 1.0
SPECIFIC
GAS
MONITOR
ppm / %
MODEL 110A-FB
HIGH
LOW
FAULT
detcon inc.
TEXASHOUSTON
ALARM NL L
HIGH
0
9
8
HIGH
ALARM
SET
1
2
3
4
5
6
7
LOW
ALARM
0
1
9
8
7
SET
0
1
2
2
3
3
4
4
5
5
9
6
6
8
7
LOW
ALARM
NL L
0
1
2
3
4
5
9
6
8
7
1.0 INTRODUCTION
Detcon Model 110A-FB-BBU gas detection system consists of 2 major assemblies:
1. The NEMA 4 fiberglass control enclosure.
2. The remote mount gas sensor assemblies. The NEMA 4 fiberglass control enclosure is detailed in section 1.0 of the manual and applicable sensor assemblies in section 3.0.
1.1 DESCRIPTION
Detcon Model 110A-FB-BB is a single channel gas detection system, designed to supervise and display the status of remote sensor assemblies that monitor ambient air for a variety of toxic and combustible gases. The digital controls are compatible with a linear 4-20 madc input signal. The front panel features a direct reading 2 digit display of the concentration of gas and 3 alarm functions that are status displayed via light emitting diodes. The assembly is enclosed in a NEMA 4X molded fiberglass case with a hinged, gasketed door and is designed for surface mounting in both indoor and outdoor locations. A plexiglas view window is mounted in the door. The NEMA 4X rating is by definition raintight and therefore suitable for outdoor location in electrically non-hazardous environments. The system is powered by AC line power and is backed up by batteries in the event of a power failure. The control enclosure includes, as standard operating controls (DWG #800.27A); a power on/off switch, an alarm reset switch, an alarm disable switch with LED indicator, AC line power fuse, DC power fuse, sensor power loop fuse, and alarm output fuses (5A) for Fault, Low and High alarm dry contacts. Discreet output terminal strips located on the controller mother board are provided for AC power in, DC power from batteries, sensor terminations, 4-20ma output for remote recording devices, remote reset and Form C dry contacts (Common, NO and NC). Contacts are provided for 3 alarms; High, Low and Fault and are rated 8 amp @ 117 VAC / 5 amp @ 30 VDC. Additional controls include latching / non-latching alarms, alarm firing direction, and alarm set dip switches.
1.2 PROGRAMMING THE 110A-FB
The 110A-FB-BBU controller board has several functions that may be changed or activated by the user. These include alarm set points, alarm firing direction (descending or ascending), latching alarms, alarm disable and other functions that will be fully discussed below.
1.3 ALARM LEVEL PROGRAMMING
The Low and High alarm levels are adjustable in single digit increments from 1 to 99% of scale. To program, refer to SW1, SW2, SW3 and SW4 (drawing #800.27A). SW1 corresponds to the Most Significant Digit (10's) on the high alarm. SW2 corresponds to the Least Significant Digit (1's) on the High alarm. SW3 corresponds to the Most Significant Digit (10's) on the Low alarm. SW4 corresponds to the Least Significant Digit (1's) on the Low alarm. While using a jeweler's screw driver, program the corresponding switches to the desired set point. For example,if the Low alarm set point is 10 ppm / %, set SW3 to 1 and SW4 to 0. If the High alarm set point is25, set SW1 to 2 and SW2 to 5.
1.4 LATCHING / NON-LATCHING ALARMS
The Low and High alarm relays may be programmed for latching or non-latching operation. To program, refer to JP4 - Low; and JP1 - High (drawing #800.27A). To program for non-latching operation, place the jumper tab on the upper 2 pins of the connector. To program for latching operation place the jumper tab on the lower 2 pins of the connector.
1.5 ALARM FIRING DIRECTION
The Low and High alarms may be programmed to fire during ascending gas conditions or descending gas condition (as in oxygen deficiency monitoring). To program, refer to JP3 - Low; and JP2 - High (drawing #800.27A). To program for an alarm to fire in ascending gas conditions, place the jumper tab on the upper 2 pins of the connector (>). To program for an alarm to fire in descending gas conditions, place the jumper tab on the lower 2 pins of the connector (<).
Detcon Model 110A-FB-BBU Gas Detection System PG.2
1.6 ALARM CONTACTS
Contacts are provided for 3 alarms; High, Low and Fault and are rated 8 amp @ 117 VAC / 5 amp @ 30 VDC. Alarm contacts are Form C dry contacts; common, normally open and normally closed. A 5 amp micro-fuse is provided in series with the common relay contact for each alarm.
1.7 ALARM RESET
The alarm reset switch located on the 110A-FB-BBU motherboard is a normally open momentary switch. The reset function is effective when the Low and/or High alarms have been programmed in the latching position and alarm conditions have passed.
1.8 REMOTE RESET
A remote mounted normally open momentary switch may be used to reset the Model 110A-FB-BBU controller. The reset function is effective when the alarms have been programmed in the latching position and alarm conditions have passed.
1.9 ALARM DISABLE
An alarm disable switch located on the motherboard will deactivate the Low and High alarm relays. An LED indicator located next to the switch will light when in the disable mode. CAUTION: The alarm disable function is a completely manual operation and care must be used to remember to put the switch back in the "Able" position after maintenance is completed.
1.10 POWER REQUIREMENTS
Model 110A-FB-BBU contains an internally mounted 24 vdc power supply that operates on 117 vac. Terminations are also provided on the motherboard for auxilary DC input (on model 110A-FB-BBU, these terminals are used for the battery backup). A 1/2 amp 3AG slow blow fuse mounted on the power supply protects against excessive line power (117 vac). To replace, remove the 110A-FB face plate and then the controller board directly above the power supply. Excessive DC current is protected by a 1 amp micro-fuse located on the mother board.
1.11 FAULT CIRCUIT FUNCTIONS
Model 110A-FB-BBU digital controls feature fail safe supervisory circuits designed to assure maximum reliability in system performance. The fault circuits supervise all field wiring between remote mounted sensor assemblies as well as supervise critical internal power supplies. Field wiring between sensors and control modules consists of + and – power loop and the 4-20 madc signal loop referenced to the – power loop. The fault relay is normally energized and will de-energize in the event of open power or signal loop between sensor and control module. Additionally the fault circuit will illuminate the front panel fault LED. The power loop to the remote sensor is fused (1/2 amp) on the motherboard to prevent circuit damage as a result of reverse polarity termination, induced transient spikes or shorted field wiring.
1.12 DISPLAY ZERO
The potentiometer (see drawing #800.27A) labled "Display Zero" is used to calibrate the digital display in accordance with the 4-20 madc signal input. This is factory set and should not require any user adjustment. Should fine tuning become neccessary the display should be calibrated to read "01" with a signal input of .16 madc.
Detcon Model 110A-FB-BBU Gas Detection System PG.3
1.13 ANALOG 4-20 MA OUTPUT CALIBRATION
The 110A-FB-BBU, 4-20 madc output is factory calibrated and tested prior to shipment and should not require field level adjustment. Should fine tuning become necessary, the digital to anlog converter is calibrated via the 4-20 MA Span and Zero potentiometer as shown on drawing #800.27A.
1.14 INTERNAL BATTERY BACKUP
The 110A-FB-BBU comes with a battery backup option not included with the 110A-FB. This option includes two batteries mounted under the motherboard that, in the event of a loss of VAC power, will power the unit for up to 18 hours. The batteries are automatically recharged when VAC power is re-established. Care should be taken to not allow the unit to run on battery power for more than 18 hours. The battery backup function is disabled when the power switch is turned to the off position.
1.15 INSTALLATION
Step 1. Securely mount the 110A-FB-BBU enclosure in accordance with detail drawing #801-BBU. Step 2. Connect 117 VAC input wiring to the lugless terminal strip (labled VAC IN) on the controller mother board as detailed in drawing #800.27A. Line power current load is maximum .5 amps. Step 3. Note that the 24 VDC standby batteries are prewired to the lugless terminal strip (labeled VDC IN) on the controller motherboard.. Caution: Observe correct polarity when terminating all input / output field wiring. Failure to do so may result in circuit damage on power up. Step 4. If applicable, connect a normally open momentary remote mounted switch to the lugless terminal strip (labled RESET) located on the cotroller mother board as detailed in drawing #800.27A Step 5. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in section
3.0. Terminate field wiring from sensors to Model 110A-FB-BBU lugless terminal strips located on the controller mother board as shown in drawing #800.27A. Note: Based on the application and use of relay contact outputs, complete all wiring terminations prior to application of power. Shut-in controls may be omitted until system test is complete.
1.16 START-UP
Upon completion of all field wiring: Turn the unit on via the power switch located on the motherboard. Note that the 110A-FB-BBU digital display illuminates. Varying readings may occur
1.17 SPECIFICATIONS
RANGE - 0-99 ppm ACCURACY / REPRODUCIBILITY - + or – 1% F.S. OPERATING TEMPERATURE - –40 deg. F to +175 deg. F INPUT POWER - 117 vac POWER CONSUMPTION - max 6 watts WARRANTY - one year OUTPUTS - 4-20 madc
Detcon Model 110A-FB-BBU Gas Detection System PG.4
1.18 ORDER GUIDE
MODEL NO.
HS - 110A-FB 02 - 110A-FB CO - 110A-FB SO - 110A-FB NO - 110A-FB NX - 110A-FB H2 - 110A-FB CH - 110A-FB HC - 110A-FB CL - 110A-FB HL - 110A-FB
PART NO.
9180 9181 9182 9183 9184 9185 9186 9187 9188 9189 9190
GAS
Hydrogen Sulfide Oxygen Deficiency Carbon Monoxide Sulfur Dioxide Nitrogen Dioxide Nitric Oxide Hydrogen Combustible Hydrocarbons Hydrogen Cyanide Chlorine Hydrogen Chloride
RANGE
0 - 99 ppm 0 - 25 % 0 - 99 ppm 0 - 99 ppm 0 - 99 ppm 0 - 99 ppm 0 - 99 ppm 0 - 99 % LEL 0 - 99 ppm 0 - 99 ppm 0 - 99 ppm
1.19 WARRANTY
Detcon Inc., as manufacturer, warrants under intended normal use each new Model 110A-FB-BBU control enclosure to be free from defects in material and workmanship for a period of one year from the date of shipment to the original purchaser. All warranties and service policies are FOB the Detcon Inc. facility located in the Woodlands, Texas.
1.20 SPARE PARTS
PART # DESCRIPTION
0224 Gold plated jumper tab 0290 .5 amp micro fuse - box of 5 0292 1 amp micro fuse - box of 5 0295 5 amp micro fuse - box of 5 0297 1 amp 3AG slow blow fuse - box of 5 3604 110A-FB power supply assembly 3423 12VDC, 2.6 amp/hour battery (two required)
Mailing address: P.O. Box 8067, The Woodlands, Texas 77387-8067 Phone: (281) 367-4100 Fax: (281) 292-2860
Shipping address: 3200 A-1 Research Forest Dr., The Woodlands, Texas 77381
HEIGHT = 3.5"
7.25
1 Amp slow blow is mounted on power supply.
9.25
DISPLAY ZERO
4-20 MA SPAN
4-20 MA ZERO
NON-LATCH
LATCH
SW1
L1L2 VAC IN
FACTORY SET
HIGH
ALARM
JP1
JP2
POWER
ON
OFF
VDC IN
SPECIFIC
GAS
MONITOR
ppm / %
MODEL 110A-FB
HIGH
LOW
FAULT
detcon inc.
HIGH
ALARM
SET
SW1 SW2 SW3 SW4
0
0
1
1
2
2
3
3
4
4
5
9
8
7
MOST SIGNIFICANT DIGIT
5
9
6
6
8
7
LEAST SIGNIFICANT DIGIT
SENSOR
1/2 AMP
FLT
5 AMP
C
SENSOR
FAULTFAULT LOW HIGH 4-20
TEXASHOUSTON
LOW
ALARM
SET
0
1
2
3
4
5
9
6
8
7
MSD LSD
LOW
5 AMP
C
NCNO
0
9
8
HIGH
5 AMP
NCNO
1
6
7
C
LOW
ALARM
NON-LATCH
2
3
4
5
LATCH
JP3
JP4
ALARM FIRING DIRECTION ASCENDING >; DECENDING <
PUSH
ALARM
AB LE
ALARM RESET
NCNOMA
RESET
ALARM
DISAB LE
ALARM
DISAB LE
INDICATOR
LED
OUT
detcon inc.
MATERIAL
TITLE
110A-FB CONTROLS/CONTROLLER TERMINALS 800.27A
DRN BY
FINISH
TED S.
SCALE
SHEET OF
APPROVED BY
STOCK #
DRAWING NUMBER
DATE
STATUS
REV #
02-19-91
ORANGE CONNECTOR
RIBBON CONNECTOR
L1 IN
L2 IN
COM
PLUG
POWER SUPPLY
1
1 AMP SLOW BLOW
3
2
+DC OUT
+DC
3
4
1A F6
D5
4001
D6
SA30CA
F1 JUMP
D4 JUMP
SW1
POWER
COM
1
2
4
+ OUT +S - OUT -S
RED CR1
R1 1K
5 7 9
D2
K2
4
5
2
1
3
F4 5A
SW2
F2 1/2A
ALARM
DISABLE
5
1
F3 5A
D1
K1
D3
K3
4
2
3
4
5
2
1
3
F5 5A
61211
8
RESET
SW3
BATTERY
12V 2.6 A/H
detcon inc.
MATERIAL
BATTERY
12V 2.6 A/H
TITLE
DRN BY
FINISH
L1 L2
VAC
IN
VDC
IN
SENSOR
C
MA
NO
FAULT LOW HIGH
110A-FB-BBU SCHEMATIC / WIRING DIAGRAM
TED S.
SCALE
SHEET OF
APPROVED BY
STOCK #
NCCNO
DRAWING NUMBER
DATE
STATUS
NCCNO
4-1-92
NC
4-20MA
1090A
REV #
REMOTE
RESET
0
7"
0
REV #
801-BBU
2-19-91
PADLOCKING
LATCH
6"
10"
DRAWING NUMBER
110A-FB-BBU DIMENSIONS / MOUNTING DETAIL
TITLE
STATUS
DATE
STOCK #
APPROVED BY
SCALE
SHEET OF
TED S.
DRN BY
FINISH
.31" DIA. MOUNTING HOLE
.56" DIA. COUNTERBORE
13"
10.75"
detcon inc.
MATERIAL
Loading...