Detcon 110A-FB User Manual

Detcon Model 110A-FB
Gas Detection System
Operator's Instruction Manual
May 21, 2002, Document #2473, Rev. 1.1
Table of Contents
1.0 Introduction
1.1 Description
1.2 Programming the 110A-FB
1.4 Latching/Non-latching Alarms
1.5 Alarm Firing Direction
1.6 Alarm Contacts
1.7 Alarm Reset
1.8 Remote Reset
1.9 Alarm Disable
1.10 Power Requirements
1.11 Fault Circuit Functions & Power Sense Bypass
1.12 Installation
1.13 Start-up
1.14 Specifications
1.15 Order Guide
1.16 Warranty
1.17 Maintenance
1.18 Trouble Shooting
1.19 Parts List
1.20 Recommended Spare Parts for 1 Year
detcon inc.
1.0 INTRODUCTION
The Detcon Model 110A-FB gas detection system consists of 2 major assemblies:
1. The NEMA 4 fiberglass control enclosure.
2. The remote mount gas sensor assemblies. The NEMA 4 fiberglass control enclosure is detailed in section 1.0 of the manual and any applicable sensor assemblies are detailed in section 3.0. Because the 110A-FB incorporates a non-modular control circuit, there is no section 2 in this manual.
Detcon Model 110A-FB Gas Detection System PG.2
HIGH
LOW
FAULT
MODEL 110A-FB
ppm / %
SPECIFIC
GAS
MONITOR
HIGH
ALARM
SET
LOW
ALARM
SET
HIGH
ALARM
LOW
ALARM
NL
NL
detcon inc.
TEXASHOUSTON
1.1 DESCRIPTION
Detcon Model 110A-FB is a single channel gas detection system, designed to supervise and display the sta­tus of remote sensor assemblies that monitor ambient air for a variety of toxic and combustible gases. The digital controls are compatible with a linear 4-20 madc input signal. The front panel features a direct read­ing 2 digit display of the concentration of gas and 3 alarm functions that are status displayed via light emit­ting diodes.
The assembly is enclosed in a NEMA 4X molded fiberglass case with a hinged, gasketed door and is designed for surface mounting in both indoor and outdoor locations. A Plexiglas view window is mounted in the door. The NEMA 4X rating is, by definition, raintight and therefore, suitable for outdoor location in electrically non-hazardous environments. The system is powered by AC line power and/or 24 VDC unless otherwise specified at time of order.
The control enclosure includes, as standard operating controls (see figure #1); a power on/off switch, an alarm reset switch, an alarm disable switch with LED indicator, AC line power fuse, DC power fuse, sen­sor power loop fuse, and alarm output fuses (5A) for Fault, Low and High alarm dry contacts. Discreet output terminal strips located on the controller mother board are provided for AC power in, DC power in, sensor terminations, 4-20 madc output for remote recording devices, remote reset and Form C dry contacts (Common, NO and NC). Contacts are provided for 3 alarms; High, Low and Fault and are rated 8 amp @ 117 VAC / 5 amp @ 30 VDC. Additional controls include latching / non-latching alarms, alarm firing direction, and alarm set dip switches.
Detcon Model 110A-FB Gas Detection System PG.3
Fig. #1
Operating
Controls & Terminals
1 Amp slow blow fuse is mounted on power supply.
DISPLAY ZERO
4-20 MA SPAN
4-20 MA ZERO
SPECIFIC
GAS
MONITOR
ppm / %
FACTORY SET
MODEL 110A-FB
HIGH
LOW
FAULT
detcon inc.
HIGH
ALARM
NON-LATCH
LATCH LATCH
JP1
JP2
AUX DC
Fuse
1 AMP
ON
SW1
Power
OFF
L1L2
117
VAC
IN
HIGH
ALARM
SET
SW1 SW2 SW3 SW4
0
0
1
1
2
2
3
3
4
4
5
5
9
9
6
6
8
8
7
7
LEAST SIGNIFICANT DIGIT
MOST SIGNIFICANT DIGIT
Micro Fuses
Sensor
FLT
Powe r
5 AMP
1/2 AMP
C
AUX 24
SENSOR
VDC IN
FAULTFAULT LOW HIGH 4-20
TEXASHOUSTON
ALARM
0
9
8
7
MSD LSD
LOW
5 AMP
C
NCNO
JP5 Power Sense Bypass Jumper
LOW
SET
0
1
1
2
2
3
3
4
4
5
5
9
6
6
8
7
HIGH
5 AMP
C
NCNO
NCNOMA
LOW
ALARM
NON-LATCH
JP3
JP4
ALARM FIRING DIRECTION ASCENDING >; DECENDING <
PUSH
ALARM
ABLE
ALARM RESET
ALARM
DISABLE
ALARM
RESET
OUT
DISABLE
INDICATOR
LED
1.2 PROGRAMMING THE 110A-FB
The 110A-FB controller board has several functions that may be changed or activated by the user. These include alarm set points, alarm firing direction (descending or ascending), latching alarms, alarm disable and other functions that will be fully discussed below.
1.3 ALARM LEVEL PROGRAMMING
The Low and High alarm levels are adjustable in single digit increments from 1 to 99% of scale. To pro­gram, refer to SW1, SW2, SW3 and SW4 (see figure #1). SW1 corresponds to the most significant digit (10's) on the high alarm. SW2 corresponds to the least significant digit (1's) on the High alarm. SW3 corresponds to the Most Significant Digit (10's) on the Low alarm. SW4 corresponds to the Least Significant Digit (1's) on the Low alarm.
While using a jeweler's screwdriver, program the corresponding switches to the desired set point. For example, if the Low alarm set point is 10 ppm/%, set SW3 to 1 and SW4 to 0. If the High alarm set point is 25, set SW1 to 2 and SW2 to 5.
1.4 LATCHING/NON-LATCHING ALARMS
The Low and High alarm relays may be programmed for latching or non-latching operation. To program, refer to JP4 - Low; and JP1 - High (see figure #1). To program for non-latching operation, place the jumper tab on the upper 2 pins of the connector. To program for latching operation, place the jumper tab on the lower 2 pins of the connector.
1.5 ALARM FIRING DIRECTION
The Low and High alarms may be programmed to fire during ascending gas conditions or descending gas conditions (as in oxygen deficiency monitoring). To program, refer to JP3 - Low; and JP2 - High (see figure #1). To program for an alarm to fire in ascending gas conditions, place the jumper tab on the upper 2 pins of the connector (>). To program for an alarm to fire in descending gas conditions, place the jumper tab on the lower 2 pins of the connector (<).
1.6 ALARM CONTACTS
Contacts are provided for 3 alarms; High, Low and Fault and are rated 8 amp @ 117 VAC/5 amp @ 30 VDC. Alarm contacts are Form C dry contacts; common, normally open and normally closed. A 5 amp micro-fuse is provided in series with the common relay contact for each alarm (see figures #1 and #2).
1.7 ALARM RESET
The alarm reset switch located on the 110A-FB motherboard is a normally open momentary switch. The reset function is effective when the Low and/or High alarms have been programmed in the latching posi­tion and alarm conditions have passed (see figures #1 and #2).
1.8 REMOTE RESET
A remote mounted normally open momentary switch may be used to reset the Model 110A-FB controller. The reset function is effective when the alarms have been programmed in the latching position and alarm conditions have passed (see figures #1 and #2).
1.9 ALARM DISABLE
An alarm disable switch located on the motherboard will deactivate the Low and High alarm relays. An LED indicator located next to the switch will light when in the disable mode (see figures #1 and #2).
CAUTION: The alarm disable function is a completely manual operation and care must be used to remem­ber to put the switch back in the “ABLE” position after maintenance is completed.
1.10 POWER REQUIREMENTS
Model 110A-FB contains an internally mounted 24 VDC power supply that operates on 117 VAC. Terminations are also provided on the motherboard for auxiliary DC input 20-28 VDC. A 1/2 amp 3AG
Detcon Model 110A-FB Gas Detection System PG.4
slow blow fuse mounted on the power supply protects against excessive line power (117 VAC). Excessive DC current is protected by a 1 amp micro-fuse located on the motherboard (see figures #1 and #2).
1.11 FAULT CIRCUIT FUNCTIONS
Model 110A-FB digital controls feature fail-safe supervisory circuits designed to assure maximum reliabili­ty in system performance. The fault circuits supervise all field wiring between remote mounted sensor assemblies as well as supervise critical internal power supplies. Field wiring between sensors and control
Detcon Model 110A-FB Gas Detection System PG.5
Fig. #2
Motherboard Schematic Diagram
POWER SUPPLY
1
L1 IN
R1 1K
RED CR1
3
2
Transformer
4
+DC OUT
+DC
3
4
L2 IN
COM
1A F6
D5
4001
D6
SA30CA
PLUG
COM
1
2
1 AMP SLOW BLOW
+ OUT +S - OUT -S
ALARM
DISABLE
SW2
D4
F1 JUMP
SW1
POWER
4001
F2 1/2A
Sensor Power
5 7 9
D1
K1
4
5
1
F3
F3 5A
5A
Fault
5
2
1
3
F4 5A
D2
K2
Low
D3
K3
4
2
3
4
5
2
1
3
High
F5 5A
61211
8
RESET
SW3
ORANGE CONNECTOR
C
MA
NCCNO
NO
FAULT LOW HIGH
NCCNO
NC
4-20MA
REMOTE
RESET
RIBBON CONNECTOR
L1 L2
VAC
IN
VDC
IN
SENSOR
modules consists of “+” and “–” power loop and the 4-20 madc signal loop referenced to the “–” power loop. The fault relay is normally energized and will de-energize in the event of open power or signal loop between sensor and control module. Additionally, the fault circuit will illuminate the front panel fault LED. The power loop to the remote sensor is fused (1/2 amp) on the motherboard to prevent circuit dam­age as a result of reverse polarity termination, induced transient spikes or shorted field wiring (see figures #1 & #2).
Power Sense Bypass
When a sensor from the Detcon DM series or IR series is used with the Model 110A-FB controller, the power sense bypass jumper must be installed on JP5 to prevent a false fault alarm. This jupers purpose is to bypass the heater/bridge fault detection circuitry which is not needed when used with Detcon oxygen, toxic or infrared gas sensors
. To install the jumper, remove the 4 screws that secure the face plate to the circuit
board, lift off the face plate, place the jumper on JP5 and then reinstall the face plate (reference fig. #1).
1.12 INSTALLATION
01. Securely mount the 110A-FB enclosure (see figure #3).
02. Connect 117 VAC input wiring to the lugless terminal strip (labeled VAC IN) on the controller mother
board (see figure #4). Line power current load is maximum 1/5 amp.
Detcon Model 110A-FB Gas Detection System PG.6
Fig. #3
Dimensions/Mounting Detail
.312" DIA. MOUNTING HOLE
11.625"
10.75"
6"
4.25"
9.75"
03. If applicable, connect the 24 VDC standby battery to the lugless terminal strip (labeled VDC IN) on the
controller motherboard (see figure #4). The DC current load is a maximum 1 amp.
Caution: Observe correct polarity when terminating all input/output field wiring. Failure to do so may result in circuit damage on power up.
04. If applicable, connect a normally open momentary remote mounted switch to the lugless terminal strip
(labeled RESET) located on the controller motherboard (see figure #4).
05. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in section 3.0.
Terminate field wiring from sensors to Model 110A-FB lugless terminal strips located on the controller motherboard (see figure #4).
Note: Based on the application and use of relay contact outputs, complete all wiring terminations prior to application of power. Shut-in controls may be omitted until system test is complete.
1.13 START-UP
Upon completion of all field wiring, turn the unit on via the power switch located on the motherboard (see figure #1). Note that the 110A-FB digital display illuminates. Varying readings may occur during sensor warm-up. A 10 second alarm delay will occur on power up.
Detcon Model 110A-FB Gas Detection System PG.7
Fig. #4
Wiring Detail
117
VAC IN
L1L2
AUX 24 VDC IN
SENSOR
External Alarm Reset Switch Normally Open Momentary
ALARM CONTACTS
Common, Normally Open
and Normally Closed
FAULT LOW HIGH
C
C
NCNO
NCNO
MA
– +
C
NCNOMA
4-20MA
24VDC
4-20 madc OUT
RESET
Typical Sensor
Refer to section 3.0 for additional sensor start-up detail.
1.14 SPECIFICATIONS
Range: 0-99 ppm/% (see section 3.0 for specific gas range) Accuracy/Reproducibility: ± 1% F.S. Operating Temperature: –40° F to +175° F Input Power: 117 VAC/ 24 VDC Power Consumption: max 6 watts Warranty: one year Outputs: 4-20 madc
1.15 ORDER GUIDE
Part # Model # Range Gas Type
954-520050-099 CG-110FB 0-99 % LEL combustible gas 954-010050-099 HS-110FB 0-99 PPM Hydrogen Sulfide 954-340050-025 O2-110FB 0-25 % Oxygen Deficiency 954-EA0050-099 C2H30-110FB 0-99 PPM Acetyldehyde 954-EG0050-099 C2H2-110FB 0-99 PPM Acetylene 954-EM0050-099 C3H3N-110FB 0-99 PPM Acrylonitrile 954-000050-099 NH3-110FB 0-99 PPM Ammonia 954-190050-1X0 AsH3-110FB 0-1 PPM Arsine 954-750050-5X0 Br2-110FB 0-5 PPM Bromine 954-EB0050-099 C4H6-110FB 0-99 PPM Butadiene 954-400050-1X0 C02-110FB 0-1 % Carbon Dioxide 954-EH0050-099 CS2-110FB 0-99 PPM Carbon Disulfide 954-EN0050-099 COS-110FB 0-99 PPM Carbonyl Sulfide 954-440050-099 CO-110FB 0-99 PPM Carbon Monoxide 954-740050-9X9 CL2-110FB 0-9.9 PPM Chlorine 954-760050-1X0 CLO2-110FB 0-1 PPM Chlorine Dioxide 954-210050-5X0 B2H6-110FB 0-5 PPM Diborane 954-EC0050-099 C2H6S-110FB 0-99 PPM Dimethyl Sulfide 954-EI0050-099 C3H5OCL-110FB 0-99 PPM Epichlorohydrin 954-EZ0050-099 C2H5SH-110FB 0-99 PPM Ethyl Mercaptan 954-EO0050-099 C2H5OH-110FB 0-99 PPM Ethanol 954-ED0050-099 C2H4-110FB 0-99 PPM Ethylene 954-EJ0050-099 C2H4O-110FB 0-99 PPM Ethylene Oxide 954-270050-1X0 F2-110FB 0-1 PPM Fluorine 954-EP0050-099 CH20-110FB 0-99 PPM Formaldehyde 954-250050-2X0 GeH4-110FB 0-2 PPM Germane 954-260050-1X0 N2H4-110FB 0-1 PPM Hydrazine 954-840050-099 H2-110FB 0-99 PPM Hydrogen 954-050050-099 H2-110FB 0-99 % LEL Hydrogen 954-080050-030 HBr-110FB 0-30 PPM Hydrogen Bromide 954-140050-030 HCL-110FB 0-30 PPM Hydrogen Chloride 954-040050-030 HCN-110FB 0-30 PPM Hydrogen Cyanide 954-330050-9X9 HF-110FB 0-9.9 PPM Hydrogen Fluoride 954-010050-099 H2S-110FB 0-99 PPM Hydrogen Sulfide 954-EE0050-099 CH30H-110FB 0-99 PPM Methanol 954-EK0050-099 CH3SH-110FB 0-99 PPM Methyl Mercaptan 954-940050-099 NO-110FB 0-99 PPM Nitric Oxide 954-640050-5X0 NO2-110FB 0-5 PPM Nitrogen Dioxide 954-390050-1X0 O3-110FB 0-1 PPM Ozone 954-410050-1X0 COCL2-110FB 0-1 PPM Phosgene 954-200050-5X0 PH3-110FB 0-5 PPM Phosphine
Detcon Model 110A-FB Gas Detection System PG.8
Part # Model # Range Gas Type
954-230050-050 SiH4-110FB 0-50 PPM Silane 954-540050-020 SO2-110FB 0-20 PPM Sulfur Dioxide 954-430050-099 C4H8S-110FB 0-99 PPM Tetrahydrothiophene 954-EQ0050-099 C4H4S-110FB 0-99 PPM Thiophane 954-ER0050-099 C6H5CH3-110FB 0-99 PPM Toluene 954-EF0050-099 C4H6O2-110FB 0-99 PPM Vinyl Acetate 954-EL0050-099 C2H3CL-110FB 0-99 PPM Vinyl Chloride
1.16 WARRANTY
Detcon, Inc., as manufacturer, warrants under intended normal use, each new Model 110A-FB control enclosure to be free from defects in material and workmanship for a period of one year from the date of shipment to the original purchaser. All warranties and service policies are FOB the Detcon, Inc. facility located in The Woodlands, Texas.
1.17 MAINTENANCE (No special tools or test equipment required.)
TOOLS REQUIRED
01. Jeweler‘s screwdriver
02. Medium size phillips screwdriver
03. Medium size standard head screwdriver
04. Digital volt/ohm meter
DISPLAY ZERO
The potentiometer labeled "Display Zero" is used to calibrate the digital display in accordance with the 4-20 madc signal input (see figure #1). This is factory set and should not require any user adjustment. Should fine tuning become necessary, the display should be calibrated to read "01" with a signal input of 4.16 madc.
ANALOG 4-20 MA OUTPUT CALIBRATION
The 110A-FB, 4-20 madc output is factory calibrated and tested prior to shipment and should not require field level adjustment (see figure #1). Should fine tuning become necessary, the digital to analog converter
is calibrated via the 4-20 MA Span and Zero potentiometer. A zero signal input of 4 milliamps should be matched at the signal output via the ZERO potentiometer. A span signal input of 20 milliamps should be matched at the signal output via the SPAN potentiometer.
1.18 TROUBLE SHOOTING
FAULT INDICATOR LIGHT IS ON
01. Verify power is going out to the sensor. Using the volt/ohm meter measure 24 VDC across "+" and "–"
SENSOR terminals on the controller motherboard (see figure #4). If there is not 24 VDC, remove and check sensor fuse (F2) for continuity (see figures #1 & #2). If open, replace with 1/2 amp micro fuse (see parts list).
02. Verify that the 3 conductor cable from the controller to the sensor is not broken or shorted.
03. Verify that the controller is receiving a 4-20 madc signal from the sensor by placing the volt/ohm meter
in series with the signal wire "MA" and measuring a signal greater than 3.5 madc but less than 20 madc. If out of this range, the sensor may be bad. Check sensor trouble shooting procedure in section 3.0.
DISPLAY DOES NOT LIGHT UP
01. Verify that the controller motherboard is receiving 117 VAC across terminals L1 and L2.
02. Verify that the power switch is "ON".
03. Verify that the power supply fuse is not open. First turn off the power switch. Next, remove the front
plate, the control circuit and the ribbon cable (see figure #5). Remove the power supply fuse (see figure #6) and measure for continuity. If open, replace with 1/2 amp 3AG slow blow fuse (see parts list).
04. Verify that the power supply is outputting 24 VDC. First turn off the power switch. Next, remove the
Detcon Model 110A-FB Gas Detection System PG.9
front plate, the control circuit and the ribbon cable (see figure #5). Turn the power switch back on and measure the VDC output on the power supply on the terminals labeled "+ OUT" and "– OUT" (see fig­ure #6). If you do not measure between 22 VDC and 28 VDC, replace the power supply as shown in the breakaway drawing figure #5.
05. If operating by auxiliary DC power, verify that the AUX DC fuse is not open (see figure #1) by remov-
ing it and measuring for continuity. If open, replace with 1 amp micro fuse (see parts list).
ALARMS ARE NOT ACTIVATING
01. If external alarm devices are not working properly, verify that their corresponding fuses are not open
by removing them from the motherboard (see figure #1) and checking for continuity. Fault, Low and High alarms all use 5 amp micro fuses (see parts list).
MISCELLANEOUS
01. If other problems exist, return the 110A-FB for repair or replacement as discussed in section 1.16 of this
manual or replace damaged components according to the breakaway drawing figure #5. Refer to parts list for part numbers.
Detcon Model 110A-FB Gas Detection System PG.10
Fig. #5
Breakaway Detail
6-32 x 5/16
Screw Typ.
110A-FB Front Plate PN8108
6-32 x 5/16 Screw Typ.
110A-FB Control Circuit Assembly PN5405
110A-FB Power
Supply Assembly
PN3605
6-32 x 5/16 Screw Typ.
Orange Connector
Ribbon Connector PN9874
110A-FB Motherboard Assembly PN5406 - Includes Power Supply
1.19 PARTS LIST
VEND # DESCRIPTION QTY RQD ORIG. MFG ORIG. MFG # STD QTY LEAD PRICE
0224 gold plated jumper tab 4 Samtec SNT-100-BKG 1 3 weeks 0290 1/2 amp micro fuse 1 Little Fuse 273.500 5 3 weeks 0292 1 amp micro fuse 1 Little Fuse 273001 5 3 weeks 0295 5 amp micro fuse 3 Little Fuse 273005 5 3 weeks 0297 1 amp 3AG slow blow fuse 1 Little Fuse 313001 5 3 weeks 3597 110A-FB power supply assy. 1 Detcon Inc. 3597 1 3 weeks 5406 110A-FB motherboard assy. 1 Detcon Inc. 5406 1 3 weeks 5405 110A-FB control circuit assy. 1 Detcon Inc. 5405 1 3 weeks 8108 110A-FB front plate 1 Detcon Inc. 8108 1 3 weeks
All prices are subject to change without notice.
Maximum allowable operating time - not applicable Contract turnaround time for overhaul - not applicable Failure rate data - not applicable
Detcon Model 110A-FB Gas Detection System PG.11
1/2 Amp Slow Blow Fuse
Fig. #6
Power Supply
PN0297
24 VDC Output Terminals
+ OUT
– OUT
110A-FB Power Supply PN3506
AUX DC
Fuse
1 AMP
PN0292
L1L2
117
VAC IN
AUX 24 VDC IN
Sensor
Powe r 1/2 AMP PN0290
Micro Fuses
FLT
LOW
5 AMP
5 AMP
PN0295
PN0295
C
C
SENSOR
NCNO
FAULTFAULT LOW HIGH 4-20
HIGH
5 AMP
PN0295
NCNO
C
RESET
NCNOMA
OUT
Detcon Model 110A-FB Gas Detection System PG.12
Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands, Texas 7381
Mailing Address: P.O. Box 8067, The Woodlands, Texas 77387-8067
phone 888-367-4286, 281-367-4100 • fax 281-292-2860 • www.detcon.com • sales@detcon.com
1.20 RECOMMENDED SPARE PARTS FOR 1 YEAR
VEND # DESCRIPTION QTY RQD ORIG. MFG ORIG. MFG # STD QTY LEAD PRICE
0290 1/2 amp micro fuse 5 Little Fuse 273.500 5 3 weeks 0292 1 amp micro fuse 5 Little Fuse 273001 5 3 weeks 0295 5 amp micro fuse 5 Little Fuse 273005 5 3 weeks 0297 1 amp 3AG slow blow fuse 5 Little Fuse 313001 5 3 weeks
Detcon Model 110A-FB Gas Detection System PG.13
Loading...