Detcon 10C Facilities User Manual

Model 10C
MODEL 10 FACILITIES MODULE (FM)
Operator’s Installation and Instruction Manual
The Woodlands, Texas 77387
Ph.281.367.4100 / Fax 281.298.2868
3200 Research Forest Dr.,
www.detcon.com
May 15, 2010 • Document #3584 • Revision 0.0
This page left intentionally blank
Model 10C
10C Control Module Instruction Manual ii
Model 10C
Table of Contents
1.0 Description................................................................................................................................................ 2
1.1 Display Function .................................................................................................................................. 2
1.2 Alarm Functions................................................................................................................................... 2
1.2.1
Latching or Non-Latching Relays ................................................................................................ 3
1.2.2
Energized or Non-Energized Relay Coils..................................................................................... 3
1.2.3
Silenceable or Non-Silenceable.................................................................................................... 3
1.2.4
Alarm Reset .................................................................................................................................. 4
1.3 Fault Circuit Functions......................................................................................................................... 4
1.4 RS-485 Modbus to SSC Slaves............................................................................................................ 4
1.5 RS-485 Modbus to Host....................................................................................................................... 5
2.0 Operator Interface................................................................................................................................... 7
2.1 Normal Operation................................................................................................................................. 8
2.2 Program Mode...................................................................................................................................... 8
3.0 Normal Operation.................................................................................................................................... 8
3.1 Display Modbus Address ..................................................................................................................... 8
3.2 Display Slave Addresses in Fault......................................................................................................... 8
3.3 Display Program Status Summary ....................................................................................................... 8
4.0 Program Mode ......................................................................................................................................... 9
4.1 Set Number of SSC Slaves................................................................................................................... 9
4.2 Alarm 1, 2 and Fault Set....................................................................................................................... 9
4.2.1
Latching...................................................................................................................................... 10
4.2.2
Energized.................................................................................................................................... 10
4.2.3
Silenceable.................................................................................................................................. 10
4.3 Modbus Address Set........................................................................................................................... 10
5.0 Default Settings ...................................................................................................................................... 10
6.0 Specifications.......................................................................................................................................... 11
7.0 MODEL 10C Backplane Pinout ........................................................................................................... 12
8.0 MODEL 10 FACILITIES MODULE Backplane Pinout................................................................... 13
Appendix C ....................................................................................................................................................... 14
Revision History............................................................................................................................................. 14
Table of Figures
Figure 1 System Application Diagrams............................................................................................................ 1
10C Control Module Instruction Manual iii
Model 10C
This page left intentionally blank
Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 •
10C Control Module Instruction Manual iv
www.detcon.com
sales@detcon.com
Model 10C
Master
Controller
Modbus
HOST
Modbus
HOST
4-20mA Current Output
M
O
C
S
U
B
D
O
M
5
8
4
S
R
10C
Controller
M
Facilities
Module
10C
Controller
10C
Controller
4-20mA Current Input
4-20mA Current Input
4-20mA Current Input
Sensor
Fault
Alarm1
Alarm2
ZONE 1 OUTPUTS
Sensor
Sensor
OUTPUT DEVICES
10C
Controller
10C
Controller
10C
Controller
Relay
Outputs
4-20mA Current Input
4-20mA Current Input
4-20mA Current Input
Sensor
Sensor
Sensor
ZONE 2 OUTPUTS
Figure 1 System Application Diagrams
10C Control Module Instruction Manual Rev. 0.0 Page 1 of 14
Model 10C
1.0 Description
Physically, the Detcon Model 10 Facilities Module (FM) is a Model 10C board assembly with some slight variation in board component population1 and with different firmware, compared to the Mod 10C Single Sensor Controller (SSC) board.
The Detcon Model 10 Facilities Module is designed to be used primarily for gathering data from multiple Mod10 Single Sensor Control modules. With the data from a group of sensors being available in the Facilities Module, the Modbus Master only needs to talk to the FM in order to get the data from the group of sensors. Another important function of the FM is to provide a final output for alarms, to represent the alarms for the whole group. These alarms are provided as output through the relays on the FM module.
The Figure 1 System Application Diagram exemplifies how the FM is used to connect to a multitude of SSC modules. The FM communicates with the SSC modules through the Modbus RS485 signal bus that runs through the mother board backplane. The FM is limited to polling 32 Modbus Slave devices and so a maximum installation might appear as: the FM board seated in the first slot of one card rack with the rest of the slots occupied by 15 SSC boards, and with the Modbus jumpered to a second card rack filled with 16 SSC boards. The FM has a second RS485 port for the purpose of interfacing to the Modbus Master Host. Since analog inputs and outputs are not needed and are not used on the FM, the analog signal terminations on the backplane for the FM slot are utilized for RS485 to the Host. The backplane board marks the terminal “SENSOR MA” for the RS485+ signal (or “A” signal) and marks the terminal “4-20 OUT +” for the RS485­signal (or “B” signal), these being the two signal wires for RS485 to the Modbus Master Host for the system.
The Operator Interface, or “Human Machine Interface” (HMI) is provided on the FM Front Panel Bracket. A pushbutton switch located on the Front Panel provides access to retrieve and set information within the Facilities Module, and to provide the “Alarm Reset” and “Alarm Silence” functions. The pushbuttons allow the user to navigate through an interactive menu to access programming of the FM’s configuration. The pushbutton layout, the display, and the navigation methods are modeled after the Mod 10C SSC. Given familiarity with the SSC, the FM user interface is one that should be quickly mastered. The pushbuttons are labeled: Upper left button: “RESET” and [up-arrow symbol] Lower left button: “SLNC” and [down-arrow symbol] Upper right button: “ESC” Lower right button: “ENT”
The single LED annunciators on the Front Panel Bracket are labeled ALM2, ALM1 and FAULT.
1.1 Display Function
The 4-character display on the front panel is provided the user to monitor and modify the configuration settings of the FM and to see the status of communications between the FM and SSC modules. While idle, this display shows the Modbus Address or ID of the FM module. The user can quickly see if a prevailing Fault alarm is due to communications faults with any one or more SSC modules through this display. The FM’s display does not allow the user to see individual SSC data; for that, the user should go to the SSC module and access such data from the individual module.
1.2 Alarm Functions
The alarm configuration for each SSC can be individually set through the front panel of the individual SSC module. Instructions for settings of the Mod10C are in the Instruction Manual for the Mod10C.
1
Components F1 and F4 are removed from the Mod10C assembly to make an FM assembly.
10C Control Module Instruction Manual Rev.0.0 Page 2 of 14