Detcon 10C User Manual

m
Model 10C
Single Sensor Control Module
Operator’s Installation and Instruction Manual
Covers all Model 10C Control Modules
The Woodlands, Texas 77387
Ph.281.367.4100 / Fax 281.298.2868
January 29, 2009 • Document #3256 • Revision 0.B
3200 Research Forest Dr.,
www.detcon.co
Model 10C
Blank Page
Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 •
10C Control Module Instruction Manual ii
www.detcon.comsales@detcon.com
Model 10C
Table of Contents
1.0 Description................................................................................................................................................ 1
1.1 Display Function .................................................................................................................................. 2
1.2 Alarm Functions................................................................................................................................... 2
1.2.1 Latching or Non-latching Relays.................................................................................................. 2
1.2.2 Energized or De-energized Relay Coils ....................................................................................... 2
1.2.3 Ascending or Descending............................................................................................................. 3
1.2.4 Silenceable or Non-silenceable (Alarm Acknowledge) ................................................................ 3
1.2.5 Alarm Reset .................................................................................................................................. 3
1.3 Fault Circuit Functions......................................................................................................................... 4
1.4 RS-485 Modbus™................................................................................................................................ 5
1.5 Controller Models................................................................................................................................. 5
2.0 Operator Interface................................................................................................................................... 7
2.1 Normal Operation................................................................................................................................. 7
2.2 Program Mode...................................................................................................................................... 8
3.0 Normal Operation.................................................................................................................................. 10
3.1 Display Gas Concentration and Alarm Condition.............................................................................. 10
3.2 Displaying Gas Type and Units.......................................................................................................... 11
3.3 Program Status ................................................................................................................................... 11
4.0 Program Mode ....................................................................................................................................... 12
4.1 Set Gas Type ...................................................................................................................................... 12
4.2 Range Set............................................................................................................................................ 14
4.3 Set Units ............................................................................................................................................. 15
4.4 Alarm 1, 2, and Fault Set.................................................................................................................... 15
4.4.1 Set-Point ..................................................................................................................................... 15
4.4.2 Direction: Ascending / Descending............................................................................................ 16
4.4.3 Latching / Non-latching.............................................................................................................. 16
4.4.4 Energized / Non-energized ......................................................................................................... 16
4.4.5 Acknowledge: Silenceable / Non-silenceable............................................................................. 16
4.5 Modbus™ Set..................................................................................................................................... 17
4.6 Sensor-Cal Mode................................................................................................................................ 17
4.7 Test ..................................................................................................................................................... 18
5.0 Special Configuration (Technician Access) ......................................................................................... 19
5.1 Trim Input........................................................................................................................................... 19
5.2 Trim Output........................................................................................................................................ 20
5.3 Default Settings .................................................................................................................................. 21
6.0 Calibration.............................................................................................................................................. 22
7.0 Specifications.......................................................................................................................................... 23
8.0 Warranty and Service Policy................................................................................................................ 24
Table of Figures
Figure 1 System Application Diagrams............................................................................................................ iv
Figure 2 Front Panel of 10C Controller............................................................................................................ 1
Figure 3 Board Assembly Picture of 10C Controller ......................................................................................9
10C Control Module Instruction Manual iii
Model 10C
Master
Controller
Modbus
HOST
Modbus
HOST
4-20mA Current Output
M
O
C
S
U
B
D
O
M
5
8
4
S
R
10C
Controller
M
Facilities
Module
10C
Controller
4-20mA Current Input
4-20mA Current Input
Sensor
Fault
Alarm1
Alarm2
ZONE 1 OUTPUTS
Sensor
OUTPUT DEVI CES
10C
Controller
4-20mA Current Input
Sensor
10C
Controller
10C
Controller
10C
Controller
Relay
Outputs
4-20mA Current Input
4-20mA Current Input
4-20mA Current Input
Sensor
Sensor
Sensor
ZONE 2 OUTPUTS
Figure 1 System Application Diagrams
10C Control Module Instruction Manual iv
Model 10C
1.0 Description
The Detcon Model 10C single sensor control module (10C Controller) is designed to supervise and display gas concentration and the status of a remote gas sensor assembly. Mod 10C Controllers may be configured for a variety of toxic and combustible gases. The 10C Controller is designed to operate on a nominal input voltage range of 12 VDC to 24VDC and is compatible with a complete line of Detcon enclosures. The available enclosures include designs for stand-alone, rack, or panel mount indoor non-hazardous areas (NEMA 1 and
12), weatherproof indoor/outdoor locations in non-hazardous areas (NEMA 4 and 4X), and for indoor/outdoor location in areas classified as Class 1, Division 1, Groups B, C, and D hazardous (NEMA 7).
10C controllers accept 4-20mA current-loop analog input, and feature a four-character display, RS-485 Modbus™ serial communications, 4-20mA analog signal output, and three alarm relays (Alarm 1, Alarm 2, and Fault). Alarm status is displayed via light emitting diodes (LEDs) located on the front panel. Multiple 10C Controllers, each configured individually and installed in a 10-Series Detcon Enclosure, provide the monitoring of a variety of gases from several field sensors in one system.
The , exemplifies how 10C Controllers can be utilized and connected
Figure 1 System Application Diagrams
in an overall Model 10C System.
The overall 10C system design includes Facilities Modules and Relay Modules to be applied with a collection of 10C Controllers. These additional modules are optional and are the same form-factor as the 10C Controller. The Facilities Module communicates with 10C Controllers to gather data to associate the controllers in assigned zones, to optionally log data, to report multiple controllers as one Modbus™ ID, and to logically process and output conditions to the Relay Modules. The scope of this document is restricted to the 10C controller and does not include any further description of the Facilities and Relay modules.
Pushbuttons located on the Front Panel provide access to retrieve and set information within the controller and to provide the “Alarm Reset” and “Alarm Silence” functions. The pushbuttons allow the user to navigate through an interactive menu to access programming of the 10C Controller’s configuration.
RESET ALARM. The “UP” pushbutton doubles as the Reset Alarm function.
SILENCE ALARM. The “DOWN” pushbutton doubles as the Silence Alarm function.
Figure 2 Front Panel (faceplate) of 10C Controller
10C Control Module Instruction Manual Rev. 0.B Page 1 of 25
Four character display shows numeric values and text. Scrolls text for improved interactive function.
Alarm 1 and Alarm 2 LED indicators.
Fault Alarm LED indicator.
Four pushbuttons provided for interactive user interface to configure and view values and settings in Controller. Keys are: ESCAPE,
ENTER,
×UP and ØDOWN.
Model 10C
1.1 Display Function
The main purpose of the 10C Controller’s 4-character display is to show the gas concentration reading at all times. The reading is given in numeric form and with the desired units, as converted from the current input signal of the attached gas sensor. Upon operation of the pushbuttons, the display also allows viewing gas type and units very simply, and with further manipulation allows viewing of any configurable setting.
1.2 Alarm Functions
The alarm configuration, programmed into the controller, determines how the 10C Controller responds to the 4-20mA current-loop analog input. In response to the analog input relative to alarm configuration, the Controller outputs to its relays and panel LEDs. Alarm configurations for the alarm output relays and LEDs can be programmed as latching or non-latching, ascending or descending, energized or de-energized, and silenceable or non-silenceable operation. Any combination of these settings can be programmed to provide setups for almost any contingency. Some planning may be needed to determine the best configuration for the application.
1.2.1 Latching or Non-latching Relays
All alarms, Alarm 1, Alarm 2, and Fault, can be programmed as Latching or Non-latching. If an alarm is programmed to Latch, its corresponding relay and LED Indicator, once activated, will stay activated until reset, even if the analog input “clears”.
NOTE: The term “Clear” refers to when the alarm condition of the sensor signal returns to normal, which means that the input current changes to the non-alarm side of the Set-Point threshold.
If an alarm is programmed as Non-latching, the alarm will not remain activated if the analog input clears.
There is a reset pushbutton on the 10C front panel and there is also a signal input to the 10C controller via the backplane where an external switch can be connected. When the “Reset” pushbutton on the front panel or the external switch is momentarily activated, the 10C accepts the signal as an alarm reset function. If resettable alarms are latched, and in response to the front panel reset switch, the 10C front panel display will scroll the text: “Reset Alarms?” In response to this query, the “ENT” pushbutton should be pressed to acknowledge the reset. In response to an front panel reset button acknowledgement , the front panel display scrolls the text: “Reset DONE”.
The external reset does not have an acknowledge feature and when the 10C Controller senses that the external reset signal is momentarily activated, the 10C scrolls a text message on its front panel display: “Ext Alm Rst”.
1.2.2 Energized or De-energized Relay Coils
All alarm relays (Alarm 1, Alarm 2, and Fault) can be programmed as normally Energized or normally De­energized. The standard setting for alarms is De-energized, however, a relay can be programmed as Energized to provide application specific features. For De-energized relays, the coil will energize in an alarm state. For Energized relays, the coil is normally Energized and will de-energize in an alarm state. It should be noted that with a normally Energized relay the N.O. (Normally Open) contact and the COM (Common) contact are CLOSED, and the N.C. (Normally Closed) contact and the COM contact are OPEN, while in the non-alarm state.
10C Control Module Instruction Manual Rev.0.B Page 2 of 25
Model 10C
A typical application of an Energized relay could be the use of the Fault Relay in a Fail-Safe Fault Circuit. The loss of functionality of the Controller would cause the coil to De-Energize, thus creating a Fault output to the receiving equipment, for instance: if power is lost to the 10C Controller, or if the 10C module is unplugged from the live chassis.
1.2.3 Ascending or Descending
Alarm 1, and Alarm 2 can be programmed for whether the alarm condition is triggered by an increasing concentration (Ascending) or a decreasing concentration (Descending) through a set-point. The descending feature, although mainly used for oxygen deficiency, can be useful for setting the trigger of alarms when there is lack of gas concentration. When set for ascending, the associated alarms will trigger when the gas concentration goes above the preset set-point. When set for descending, the associated alarms will trigger when the gas concentration falls below the preset set-point.
1.2.4 Silenceable or Non-silenceable (Alarm Acknowledge)
The terminology “to acknowledge alarms” is synonymous with the terminology “to silence an alarm”. All Alarms (Alarm 1, Alarm 2, and Fault) can be programmed as Silenceable or Non-silenceable. When an alarm is programmed as Silenceable, the setting allows the alarm(s) to be silenced even during an alarm state. To silence an alarm the 10C controller’s alarm must be programmed as Silenceable. When an alarm occurs, the Silenceable alarm can be silenced by pressing the “SLNC” pushbutton, followed by acknowledging the “Silence Alarms?” scrolling display by pressing the “ENT” pushbutton. An instance where this feature might be used is a Strobe device connected to Alarm 1 and a Horn device connected to Alarm 2. In the event of an alarm, where both the Strobe and Horn were activated, the Horn could be silenced while the Strobe would remain activated. The silenced state is reset when and if the alarm condition clears and then exceeds alarm set­point again. The Horn would be reactivated upon the return of the alarm condition.
The “Remote Reset” signal that resets latched alarms also functions as a signal to silence active Silenceable Alarms.
NOTE: There is a minimum alarm time before acknowledge. When a silenceable alarm triggers, a minimum-time timer starts. Whenever a silenceable alarm is attempted to be silenced, the alarm will not silence unless/until the minimum-time timer has timed out. This guarantees that the alarm has a minimum activity time.
1.2.5 Alarm Reset
An alarm “RESET” pushbutton key-switch is located on the front panel of the 10C Controller. This switch is used to reset alarms that have been programmed as latching. Once alarm conditions clear, alarms that have been set as latching can be reset by use of this switch. If cleared latched alarms are pending, pressing the “RESET” pushbutton will cause the display to scroll the text: “Reset Alarms?” Pressing the “ENT” pushbutton will reset the alarms which is apparent with the displayed text: “Reset DONE”. The “Remote Reset” signal, activated from an optional external switch, can be momentarily operated to reset the latched relays.
The “Remote Reset” signal needs to be operated only once and without an acknowledge sequence, to reset all pending latched alarms. The text “Ext Alm Rst” scrolls across the 10C Controller front panel display when the “Remote Reset” signal is sensed.
10C Control Module Instruction Manual Rev. 0.B Page 3 of 25
Model 10C
1.3 Fault Circuit Functions
How the 10C Controller responds to a fault condition is determined by the configuration programmed into the controller. Faults can be programmed as latching or non-latching, energized or de-energized, and silenceable or non-silenceable operation. Any combination of these settings, and the set-point threshold at which a fault will trigger, can be programmed to provide setups for almost any contingency. Some system level planning should be exercised to determine the best configuration for the application.
10C Controllers can be set up in a Fail-Safe Fault supervisory circuit. A Fail-Safe Fault can be created by setting the Fault Relay as Energized, and connecting the fault circuits of several 10C Controllers in electrical series. If a fault occurs anywhere in the series circuit, the de-energized fault relay will ‘break’ the circuit, causing a system fault. The logical “OR” of all faults in the series circuit is simply constructed with such a method. Mainly, with this set-up, loss of power to any unit will break the circuit because of the normally­energized coils, thus creating a “Fault Condition” due to the loss of power.
The 10C Controller is designed to detect a sensor as being “In Calibration Mode” when the 4-20mA input is nominally 2mA. The Display will show “CAL” to signify this sensor Calibration Mode. When the 10C Controller 4-20mA falls below 2mA, the display will change to “SENS” to signify that there is a sensor related problem. The Fault Set-Point can be set to any point below 4mA (in steps of .05mA) so that the input of the sensor can trigger a fault at any point below 4mA.
For 3-wire sensors, the Set-Point can be adjusted to 1.8mA so that when the sensor is in Calibration, a Fault is not generated. If the input current falls below 1.8mA, a fault will be generated. Since most sensors reduce their output current for internally detected faults, this set-point is a good setting.
For 2-wire sensors, the sensor uses the loop current for power and so the set-point ordinarily must be set higher. The fault Set-Point for 2-wire sensors is suggested to be 3.5mA.
10C Control Module Instruction Manual Rev.0.B Page 4 of 25
Model 10C
1.4 RS-485 Modbus™
The 10C Controllers feature Modbus™ compatible communications protocol and are addressable via the programming menu for multi-point communications. Communication is two wire, half-duplex, with the Model 10C controller set up as a slave device. A master controller can address a maximum of 255 different 10C Controllers. The actual limit of how many 10C Controllers can be connected to one RS485 Multi-drop line depends upon desired maximum response time, noisy conditions, cable quality, and length. If a multi­point system is utilized, each 10C Controller must be set with a unique Modbus™ address. Address settings are given in hexadecimal, such as: 01, 02, 03, 04, 05, 06, 07, 08, 09, 0A, 0B, 0C, 0D, 0E, 0F, 10, 11, etc. (See Section 4.5 to set the Modbus™ address.)
The following register list describes the parameters available from 10C controller:
Register # High Byte Low Byte 40000 Range 40001 Reading 40002 Alarm 1 Set Point 40003 Alarm 2 Set Point 40004 Not Used 40005 Status Bits
40005 Status Bits High Byte: Bit 15 – Reserved Bit 14 – Reserved Bit 13 – Reserved Bit 12 – Test mode status Bit 11 – Reserved Bit 10 – Reserved Bit 9 – Reserved Bit 8 – Reserved
40005 Status Bits Low Byte: Bit 7 – Alarm 2 / 0 – Ascending, 1 – Descending Bit 6 – Alarm 2 / 0 – Non-latching, 1 – Latching Bit 5 – Alarm 2 alarm status / 0 – no alarm, 1 – alarm Bit 4 – Alarm 1 / 0 – Ascending, 1 – Descending Bit 3 – Alarm 1 / 0 – Non-latching, 1 – Latching Bit 2 – Alarm 1 alarm status / 0 – no alarm, 1 – alarm Bit 1 – Fault / 0 – Non-latching, 1 – Latching Bit 0 – Fault status / 0 – no fault, 1 - fault
1.5 Controller Models
Table 1 provides a list of the available 10C Controller Models, the target gas, the standard Range and Units for that gas, and the gas formula. Most 10C Controllers can be programmed for a Range other than the standard Range if needed. (For more information on setting Range, see Section 4.2 Range Set.)
The label on the Model 10 faceplate follows a standard color scheme for identifying the gas type: Yellow = Solid State H2S, Orange = Combustible Gas, Green = Oxygen and Blue = Electrochemical Toxic (various). The gas identifier label on the face plate also shows the gas formula and Units: ppm, ppb, or %.
10C Control Module Instruction Manual Rev. 0.B Page 5 of 25
Loading...
+ 20 hidden pages