Detcon 1010-N1 Rack User Manual

detcon inc.
Detcon Model 1010-N1 Rack
Panel Mount Control Enclosure
Operator’s Installation & Instruction Manual
July 15, 2004 • Document #2655 • Version 1.1
Table of Contents
1.0 Introduction
1.1 Description
1.3 Remote Reset
1.4 Installation
1.5 Start-Up
1.6 Maintenance and Repair
1.7 Spare Parts
1.8 Warranty
Detcon Model 1010-N1 Rack Panel Mount Control Enclosure PG.1
1.0 INTRODUCTION
Detcon Model 1010-N1 Rack consists of 3 major assemblies:
1. The NEMA 1 rack mount control enclosure.
2. The single channel digital control modules.
3. The remote mount gas sensor assemblies.
The NEMA 1 control enclosure is detailed in section 1.0 of the manual, the control modules in section
2.0, and applicable sensor assemblies in section 3.0.
1.1 DESCRIPTION
Detcon Model 1010-N1 along with Model 10B digital control modules is designed to serve as a host assem­bly for up to ten remote mount gas detection sensor assemblies. The control enclosure is rated NEMA 1 suitable for installation in non-hazardous locations. The single channel modular design supports applica­tion flexibility wherein multiple function gas detection systems can be configured in any combination up to ten channels. All control modules are plug-in front panel accessible for easy maintenance and repair.
The control enclosure houses a modular power supply (Model PS100-10B) which includes, as standard operating controls, a power on/off switch and a line power fuse.
Discreet output terminal strips located on the controller motherboard are provided for sensor terminations, Form C dry contact alarm outputs (normally open, normally closed and common) for two alarms plus fault, 4-20 mA outputs for remote recording devices, and RS-485 serial Modbus™. Additional terminations are provided for VAC power in, VDC power in, and remote alarm reset.
Form C relay outputs may be discreet, zoned or common by gold plated jumper tabs located on the con­troller mother board.
1.2 SPECIFICATIONS
Electrical Classification
NEMA 1
Dimensions
19"W, 5.25"H, 8"D
Capacity
10 Single Channels
Power Input
117VAC/24 VDC
Alarm Contacts
Discreet Fault, Low, High, per Channel 5 Amp @ 30VDC/5 Amp @ 125VAC Common, Normally Open and Normally Closed
Outputs
Discreet 4-20 mA DC Serial RS-485 Modbus™
Operating Temperature Range
-40°F to +175°F
Power Consumption
<5 Watts per Channel (includes gas sensor and control module)
Warranty
One Year
Detcon Model 1010-N1 Rack Panel Mount Control Enclosure PG.2
Loading...