Model 100 Duct Mount Kit
Model1 00
DETCON,INC.
DM-100
H2S
100PPM
CALP ORT
Operator’s Installation and Instruction Manual
Covers all versions of the 100 Series Sensor
4055 Technology Forest Blvd,
The Woodlands, Texas 77387
Ph.281.367.4100 / Fax 281.298.2868
November 19, 2012 • Document #3726 • Revision 0.1

100 Duct Mount
Table of Contents
1.0 Introduction.......................................................................................................................................1
1.1 Principal of Operation ..................................................................................................................... 1
2.0 Installation.........................................................................................................................................1
3.0 Calibration.........................................................................................................................................2
4.0 Maintenance.......................................................................................................................................3
5.0 Warranty............................................................................................................................................3
6.0 Revision Log.......................................................................................................................................4
Table of Figures
Figure 1 Sample flow ..................................................................................................................................... 1
Figure 2 Cut-out Template.............................................................................................................................. 2
Figure 3 Dimensional..................................................................................................................................... 2
Figure 4 Cal Port............................................................................................................................................ 3
Shipping Address: 4055 Technology Forest Blvd, The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 • www.detcon.com • sales@detcon.com
100 Series Duct Mount Kit ii

100 Duct Mount
1.0 Introduction
The Detcon Sensor Duct Mount Kit for Model 100 gas detection sensors allows a Detcon Model 100 gas
sensor assembly to be mounted so that the Sample Chamber is located inside of an air duct, while the Sensor
Assembly, located outside the duct, is still accessible for calibration and other adjustments. This method of
installation is much more economical than the typical sample draw type system that is normally used in such
applications. This instruction manual explains the installation, calibration, and maintenance procedures of the
duct mount con-figuration. Refer to the sensor instruction manual for information on the sensor assembly.
1.1 Principal of Operation
In operation, air flow through the duct enters the duct mount chamber through ports facing the on coming flow
of air. Once inside the chamber the sample passes by the sensor and then exits through similar ports that face
the opposite direction. If any target gas is present in the chamber, the sensor output signals will respond
accordingly as described in the sensor assembly instruction manual.
Sensor
Inside the DUCT
Flow
Sample Chamber
Flow
Figure 1 Sample flow
2.0 Installation
1 - Cut a clearance hole in duct as shown below. Mounting remains the same for square or round ducts.
Minimum suggested diameter for round duct is 10 inches to adapt with normal mounting techniques. Adapting
to an 8” diameter duct is possible with special mounting techniques. Below 8” diameter is not practical for
mounting.
2 - Mount the duct mount kit using four 1/4” sheet metal bolts or other appropriate hardware.
3 - If necessary mounting integrity can be enhanced by using the two holes on the upper portion of the duct
mount plate. Use standoffs and 1/4” sheet metal bolts or other appropriate hardware.
4 - Perform installation wiring as described in the sensor assembly instruction manual. If conduit is used, use
flexible conduit to allow for future maintenance.
A ¼” foam gasket is available for mounting the assembly on a round or curved ducts. Contact Detcon for
further information. Mounting remains the sane.
100 Series Duct Mount Kit Rev. 0.1 Page 1 of 4

100 Duct Mount
Model 100
DETCON,INC.
DM-100
100PPM
3.125"
4.25"
3"
Mounting Holes
5"
Figure 2 Cut-out Template
16.3"
H2S
Duct side
wall
Mounting Hardware
CALPORT
5"
7"
3"
5"6.15"
6.5"
Figure 3 Dimensional
3.0 Calibration
CAUTION: In high velocity air ducts, air flow may need to be shut down before calibration takes place.
1 - Verify that there is no air flow through the duct.
2 - Remove the cal port plug.
3 - Apply the target gas to the cal port at a flow rate of 500 milliliter per minute for combustible (FP series)
and solid state H2S (TP series) sensors. Apply a flow rate of 1000 ml/m for toxic gas (DM series) sensors.
Refer to the sensor manual for more information on the sensor calibration.
4 - Follow calibration instructions provided in the sensor instruction manual.
100 Series Duct Mount Kit Rev. 0.1 Page 2 of 4

5 - Remove the target gas and apply a zero air standard for clearing.
6 - If necessary, repeat items 3-5 as indicated in the sensor instruction manual.
7 - Replace the cal port plug. Calibration is complete.
Duct side
wall
Calibration tubing
Cal Port Plug
Gas Flow
Calibration Port
Figure 4 Cal Port
100 Duct Mount
4.0 Maintenance
To remove the sensor for replacement or maintenance, perform the following steps.
1 - Remove the two bolts that hold the sensor condulet to the duct mount plate.
2 - Pull the sensor out of the duct mount chamber and perform necessary maintenance.
3 - Reverse the procedure to replace the sensor. If necessary, lubricate the O-rings inside the duct mount
chamber so that the sensor rain shield will slide into the chamber easily.
5.0 Warranty
Detcon, Inc., as manufacturer, warrants each sensor duct mount kit for a period of one year under the
conditions described as follows: The warranty period begins on the date of shipment to the original purchaser
and ends one year thereafter. Should any part fail return the defective part to Detcon, Inc., for necessary
repairs or replacement.
100 Series Duct Mount Kit Rev. 0.1 Page 3 of 4

6.0 Revision Log
12Added notation regarding minimum round duct diameter.