Desa Tech CSGF28NTA, VSGF28NTA Owner's Manual

4 (1)

DESA INTERNATIONAL

UNVENTED (VENT-FREE) NATURAL GAS FIREPLACE

This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes.

* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer

OWNER’S OPERATION AND INSTALLATION MANUAL

Variable

Manually-

Controlled

Models and

Thermostatically-

Controlled

“A” Models

with

Split Oak Logs

,,,,,,QQQQQQ¢¢¢¢¢¢

,,,,,,QQQQQQ¢¢¢¢¢¢

,,,,,,QQQQQQ¢¢¢¢¢¢

,,,,,,QQQQQQ¢¢¢¢¢¢

,,,,,,QQQQQQ¢¢¢¢¢¢

,,,,,,QQQQQQ¢¢¢¢¢¢

,Q¢,,,,,,QQQQQQ¢¢¢¢¢¢,,QQ¢¢

,,,,,,,,QQQQQQQQ¢¢¢¢¢¢¢¢,Q¢

®

Shown with optional cabinet mantel, hearth base, and trim accessories.

WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electrical switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

Installation and service must be performed by a qualified installer, service agency, or the gas supplier.

WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.

WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section in this manual.

Save this manual for future reference.

CONTENTS

SAFETY INFORMATION

2

SECTION

PAGE

Safety Information ...................................................................................

2

Product Identification ..............................................................................

4

Local Codes .............................................................................................

5

Unpacking ................................................................................................

5

Product Features ......................................................................................

5

Air for Combustion and Ventilation ........................................................

6

Installing ..................................................................................................

9

Check Gas Type ...............................................................................

9

Electrical Hookup .............................................................................

9

Assembling and Attaching Brass Trim ............................................

10

Installation Clearances .....................................................................

11

Conventional Fireplace Installation .................................................

11

Built-In Fireplace Installation ..........................................................

14

Installing Gas Piping to Fireplace Location .....................................

16

Connecting Fireplace to Gas Supply ................................................

17

Checking Gas Connections ..............................................................

18

Installing Logs ..................................................................................

20

Operating Fireplace (Thermostat-Controlled Models) ............................

22

Operating Fireplace (Manually-Controlled Models) ...............................

24

Inspecting Burners ...................................................................................

26

Cleaning and Maintenance ......................................................................

28

Troubleshooting .......................................................................................

28

Technical Service ....................................................................................

32

Service Hints ...........................................................................................

32

Replacement Parts ...................................................................................

32

Specifications ..........................................................................................

33

Wiring Diagram .......................................................................................

33

Accessories ..............................................................................................

34

Illustrated Parts Lists ...............................................................................

36-41

Warranty Information ..............................................................................

Back Cover

WARNINGS

IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, operate, or service this fireplace. Improper use of this fireplace can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.

DANGER

Carbon monoxide poisoning may lead to death!

Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the fireplace may not be working properly. Get fresh air at once! Have fireplace serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.

Natural Gas: Natural gas is odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.

Make certain you read and understand all Warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.

Safety Information continues on next page

103281

SAFETY

 

WARNING ICON G 001 WARNINGS Continued

 

WARNING: Any change to this fireplace or its controls can be dangerous.

 

INFORMATION

 

1.

This appliance is only for use with the type of gas indicated on the rating plate. This

 

Continued

 

appliance is not convertible for use with other gases.

 

2.

If you smell gas

 

 

 

 

 

• shut off gas supply

 

 

 

• do not try to light any appliance

 

 

 

• do not touch any electrical switch; do not use any phone in your building

 

 

 

• immediately call your gas supplier from a neighbor’s phone. Follow the gas

 

 

 

supplier’s instructions

 

 

 

• if you cannot reach your gas supplier, call the fire department

 

 

3.

This fireplace shall not be installed in a bedroom or bathroom.

 

 

4.

Never install the fireplace

 

 

 

• in a recreational vehicle

 

 

 

• where curtains, furniture, clothing, or other flammable objects are less than 36

 

 

 

inches from the front, top, or sides of the fireplace

 

 

 

• in high traffic areas

 

 

 

• in windy or drafty areas

 

 

5.

Do not use this fireplace as a wood-burning fireplace. Use only the logs provided with

 

 

 

the fireplace.

 

 

6.

Do not add extra logs or ornaments such as pine cones, vermiculite, or rock wool.

 

 

 

Using these added items can cause sooting. Do not add lava rock around base. Rock

 

 

 

and debris could fall into the control area of fireplace.

 

 

7.

You must operate this fireplace with the fireplace screen in place. Make sure fireplace

 

 

 

screen is in place before running fireplace.

 

 

8.

This fireplace is designed to be smokeless. If logs ever appear to smoke, turn off

 

 

 

fireplace and call a qualified service person. Note: During initial operation, slight

 

 

 

smoking could occur due to log curing and fireplace burning manufacturing residues.

 

 

9.

Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner

 

 

 

flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered

 

 

 

burner patterns can cause sooting.

 

 

10.

Do not use a blower insert, heat exchanger insert or other accessory not approved for

 

 

 

use with this heater.

 

 

11.

This fireplace needs fresh air ventilation to run properly. This fireplace has an oxygen

 

 

 

depletion sensor (ODS) pilot light safety system. The ODS shuts down the fireplace if

 

 

 

not enough fresh air is available. See Air for Combustion and Ventilation, pages 6

 

 

 

through 8. If fireplace keeps shutting off, see Troubleshooting, pages 28 through 31.

 

 

12.

Do not run fireplace

 

 

 

• where flammable liquids or vapors are used or stored

 

 

 

• under dusty conditions

 

 

13.

Do not use this fireplace to cook food or burn paper or other objects.

 

 

14.

Never place any objects in the fireplace or on logs.

 

 

15.

Fireplace front and screen becomes very hot when running fireplace. Keep children

 

 

 

and adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will

 

 

 

remain hot for a time after shut-down. Allow surfaces to cool before touching.

 

 

16.

Carefully supervise young children when they are in the room with fireplace.

 

 

17.

Do not use fireplace if any part has been exposed to or under water. Immediately call a

 

 

 

qualified service technician to inspect the fireplace and to replace any part of the

 

 

 

control system and any gas control which has been under water.

 

 

18.

Do not operate fireplace if any log is broken. Do not operate fireplace if a log is

 

 

 

chipped (dime-sized or larger).

 

 

19.

Turn fireplace off and let cool before servicing. Only a qualified service person should

 

 

 

service and repair fireplace.

 

 

20.

Operating fireplace above elevations of 4,500 feet could cause pilot outage.

 

 

 

 

 

3

103281

Desa Tech CSGF28NTA, VSGF28NTA Owner's Manual

PRODUCT IDENTIFICATION

4

Crossover Log

Top Middle Log

Rear Log

 

Left

Front

Branch

 

 

Rear

 

 

Burner

Front

 

 

Burner

Right Front

Bottom

 

Middle

 

Branch

 

Log

 

Base Assembly

 

 

 

Figure 1 - Log Base Assembly, Split Oak Set

 

Top Louver

Assembly

Firebox

Hood

Firebox

Support

Screen

Assembly

Top Outer

Casing

Rear

Access

Door

Side

Access

Door

Bottom Louver

Assembly

Figure 2 - Fireplace

103281

LOCAL CODES

 

Install and use fireplace with care. Follow all local codes. In the absence of local

 

 

 

 

 

codes, use the latest edition of The National Fuel Gas Code ANSI Z223, also

 

 

 

known as NFPA 54*.

 

 

 

*Available from:

 

 

 

American National Standards Institute, Inc.

 

 

 

1430 Broadway

 

 

 

New York, NY 10018

 

 

 

National Fire Protection Association, Inc.

 

 

 

Batterymarch Park

 

 

 

Quincy, MA 02269

 

UNPACKING

 

1. Place the carton containing the fireplace unit on its back. Hold fireplace and

 

 

 

pull the carton and pallet away. Remove trim kit from front of fireplace.

 

 

 

2. Locate two screws above top corners of the fireplace screen. Remove and

 

 

 

discard these screws. Lift fireplace screen up and pull out to remove.

 

 

 

3. Remove protective packaging applied to logs, log base assembly, and fireplace.

 

 

 

4. Check all items for any shipping damage. If damaged, promptly inform dealer

 

 

 

where you bought fireplace.

 

PRODUCT

 

Operation

 

 

This vent-free fireplace is clean burning. It requires no outside venting. There is no

 

FEATURES

 

heat loss out a vent or up a chimney. Heat is generated by both realistic flames and

 

 

glowing embers. When used without the blower, the fireplace requires no electricity

 

 

 

 

 

 

making it ideal for emergency back-up heat.

 

 

 

Safety Device

 

 

 

This fireplace has a pilot with an Oxygen Depletion Sensor Shutoff System

 

 

 

(ODS). The ODS/pilot is a required feature for vent-free room heaters. The ODS

 

 

 

system shuts off the fireplace if there is not enough fresh air.

 

 

 

Piezo Ignition System

 

 

 

This fireplace has a piezo ignitor. This system requires no matches, batteries, or

 

 

 

other sources to light fireplace.

 

 

 

Blower Assembly

 

 

 

This fireplace has a blower assembly. The blower operates thermostatically or

 

 

 

manually. The blower circulates heated air from the fireplace into the room. Use of

 

 

 

blower is optional.

 

 

 

Thermostat Control Models (VSGF28NTA/CSGF28NTA)

 

 

 

These fireplaces have a thermostat sensing bulb and a control valve. The thermo-

 

 

 

stat controls the heat output and flame height. This maintains a consistent room

 

 

 

temperature. Even the lowest setting provides realistic flames and glowing embers

 

 

 

from two burners. Selecting higher comfort settings allows fireplace to run longer,

 

 

 

producing greater heat output. At lower comfort settings, the fireplace will run

 

 

 

less. This results in increased heating comfort. This can also result in lower

 

 

 

gas bills.

 

 

 

Variable Manual Control (VSGF28NV/CSGF28NV)

 

 

 

These fireplaces have a variable manual control valve which allows the user to

 

 

 

choose the heat setting that best suits his needs. Any setting between low and high

 

 

 

may be selected by simply turning the control knob.

 

 

 

 

 

 

 

 

 

 

5

 

 

 

103281

AIR FOR COMBUSTION AND VENTILATION

6

WARNING

This heater shall not be installed in a confined space unless provisions are provided for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.

Today’s homes are built more energy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.

While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.

PROVIDING ADEQUATE VENTILATION

The following is exerpts from National Fuel Gas Code. NFPA 54/ANSI Z223.1,

Section 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three following ventilation classifications: 1. Unusually Tight Contruction; 2. Unconfined Space; 3. Confined Space.

The information on pages 6 through 8 will help you classify your space and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where:

a.walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm or less with openings gasketed or sealed and

b.weather stripping has been added on openable windows and doors and

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 8.

If your home does not meet all of the three criteria above, proceed to page 7.

Unconfined Space

The National Fuel Gas Code, ANSIZ223.1, 1992, Section 5.3 defines unconfined space as having a minimum air volume of 50 cubic feet (127 cubic cm) for each 1000 Btu/Hr input rating of all appliances in the space (cubic feet equals length x width x height of space). Include adjoining rooms only if there are doorless passageways or ventilation grills between the rooms.

Confined Space

The National Fuel Gas Code, ANSIZ223.1, 1992, Section 5.3 defines confined space as having an air volume of less than 50 cubic feet (127 cubic cm) for each 1000 Btu/Hr input rating of all appliances in the space (cubic feet equals length x width x height of space). Include adjoining rooms only if there are doorless passageways or ventilation grills between the rooms.

103281

AIR FOR COMBUSTION AND VENTILATION

Continued

DETERMINING AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1. Determine the volume of the space (length x width x height).

Length x Width x Height = ___________________ cu. ft. (volume of space) Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) =

3168 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

____________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 3168 cu. ft. (volume of space) ÷ 50 cu. ft. = 63.3 or 63,300 (maximum Btu/Hr the space can support)

3. Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

 

___________________ Btu/Hr

Gas water heater*

 

___________________ Btu/Hr

Gas furnace

 

___________________ Btu/Hr

Vented gas heater

 

___________________ Btu/Hr

Gas fireplace logs

 

___________________ Btu/Hr

Other gas appliances*

+ ___________________ Btu/Hr

Total

= ___________________ Btu/Hr

Example: Gas water heater

 

40,000

Btu/Hr

Vent-free fireplace

+

28,000

Btu/Hr

Total

=

 

 

Btu/Hr

68,000

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________

Btu/Hr (maximum the space can support)

_________________

Btu/Hr (actual amount of Btu/Hr used)

Example: 63,300

Btu/Hr (maximum the space can support)

68,000

Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework work sheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air from Inside Building, page 8.

B.Vent room directly to the outdoors. See Ventilation Air from Outdoors, page 8.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

Continued 7

103281

AIR FOR

WARNING

COMBUSTION

 

If the area in which the heater may be operated is smaller than

AND

that defined as an unconfined space, provide adequate combus-

tion and ventilation air by one of the methods described in the

VENTILATION

National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3.

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

WARNING

Rework worksheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

 

 

12"

Ventilation

 

Ventilation Grills

Grills

 

Into Adjoining

Or

Into Adjoining Room,

Room,

Option 2

Remove

Option 1

 

Door into

 

 

 

 

Adjoining

 

 

Room,

 

 

Option

,,QQ¢¢

 

3

 

 

 

12"

,,QQ¢¢

 

 

,,,QQQ¢¢¢

Figure 3 - Ventilation Air from Inside Building

Ventilation Air From Outdoors

 

Provide extra fresh air by using ventilation grills or ducts. You must provide two perma-

 

nent openings: one within 12" of the ceiling and one within 12" of the floor. Connect

 

these items directly to the outdoors or spaces open to the outdoors. These spaces include

 

attics and crawl spaces.

 

 

 

 

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a

 

thermostat-controlled power vent. Heated air entering the attic will activate the power

 

vent.

 

 

 

 

 

Outlet

Ventilated

 

 

 

Attic

 

 

 

Air

 

 

 

 

 

 

Outlet

 

 

 

 

Air

 

 

To Attic

 

 

 

 

 

 

 

¢¢¢¢QQQQ,,,,

To

 

 

 

¢¢¢¢QQQQ,,,,

Crawl

 

Inlet

 

¢¢¢¢QQQQ,,,,

Space

 

 

¢¢¢¢QQQQ,,,,

 

 

Air

 

¢¢¢¢QQQQ,,,,

 

 

 

Inlet Air

Ventilated

 

 

 

Crawl Space

 

 

 

8

Figure 4 - Ventilation Air from Outdoors

103281

INSTALLING

NOTICE

 

A qualified service person must install fireplace. Follow all local

 

codes.

 

 

 

 

 

WARNING

 

Never install the fireplace

 

• in a bedroom or bathroom

 

• in a recreational vehicle

 

• where curtains, furniture, clothing, or other flammable

 

objects are less than 36 inches from the front, top, or sides

 

of the fireplace

 

• in high traffic areas

 

• in windy or drafty areas

 

 

 

 

 

WARNING

 

This fireplace has a three-prong, grounded electrical plug. This

 

plug helps protect you against electrical shock. Only connect

 

plug to a properly grounded, three-prong receptacle. Do not cut

 

or remove the grounding prong from this plug.

 

 

 

 

 

WARNING ICON G 001 CAUTION

 

 

 

This fireplace creates warm air currents. These currents move heat

 

to wall surfaces next to fireplace. Installing fireplace next to vinyl or

 

cloth wall coverings or operating fireplace where impurities in the

 

air (such as tobacco smoke) exist, may discolor walls.

 

 

 

IMPORTANT: Vent-free heaters add moisture to the air. Although this is beneficial,

 

installing fireplace in rooms without enough ventilation air may cause mildew to

 

form from too much moisture. See Air for Combustion and Ventilation, pages 6

 

through 8.

 

IMPORTANT: Make sure the fireplace is level. If fireplace is not level, log set will

 

not work properly.

 

CHECK GAS TYPE

 

Use only natural gas. If your gas supply is not natural gas, do not install fireplace.

 

Call dealer where you bought fireplace for proper type fireplace.

 

ELECTRICAL HOOKUP

 

This fireplace has a blower assembly with an electrical cord. The electrical cord is

 

five feet in length. You must locate fireplace within reach of a 120 volt grounded

 

electrical outlet. If not, you must install an electrical outlet within reach of fire-

 

place power cord.

Continued 9

103281

INSTALLING

Continued

10

ASSEMBLING AND ATTACHING BRASS TRIM

IMPORTANT: If you are recessing the firebox in a wall, do not attach brass trim at this time. See page 13.

Note: The instructions below show assembling and attaching brass trim to fireplace.

1.Remove packaging from three pieces of brass trim.

2.Locate four brass screws, two adjusting plates with set screws, and two shims in the hardware packet.

3.Align shim under adjusting plate as shown in Figure 5.

4.Slide one end of adjusting plate/shim in slot on mitered edge of top brass trim (see Figure 5).

5.Slide other end of adjusting plate/shim in slot on mitered edge of side brass trim (see Figure 5).

6.While firmly holding edges of brass trim together, tighten both set screws on the adjusting plate with slotted screwdriver.

7.Repeat steps 1 through 6 for other side.

Top Brass Trim

Side Brass Trim

Set Screws

Adjusting

Plate

Shim

Slot

Mitered Edge

Slot

Figure 5 - Assembling Brass Trim

8.Tighten trim hanging screws (#10 x 6.25 shoulder) into holes in cabinets. Place the assembled trim onto fireplace cabinet. Align hanging notches on trim with hanging screws on side of fireplace (see Figure 6). Push trim firmly into place, sliding hanging notches over hanging screws.

Trim Hanging

Screws

Assembled

Brass Trim

Hanging

Notches on

Trim

Figure 6 - Attaching Brass Trim to Fireplace

103281

INSTALLING

INSTALLATION CLEARANCES

Continued

WARNING

Maintain the minimum clearances. If you can, provide greater clearances from floor, ceiling, and adjoining wall.

Carefully follow the instructions below. This will ensure safe installation.

Minimum Wall and Ceiling Clearances (see Figure 7)

A.Clearances from the side of the fireplace opening to any combustible wall should not be less than 16 inches for a cabinet mantel or 12 inches for a corner installation.

B.Clearances from the top of the fireplace opening to the ceiling should not be less than 42 inches.

 

 

MINIMUM CLEARANCE

Note: Clearances

42"

Side Wall - 16 " Cabinet and

are the same if

Face Mantel

 

using optional

 

Ceiling - 42" Corner Mantel

cabinet mantel or

 

Floor - 0"

built-in installation.

 

 

16"

,,,QQQ¢¢¢

Face or

,,,QQQ¢¢¢

Cabinet

Mantel

,,,QQQ¢¢¢

12"

,,,QQQ¢¢¢

Corner

 

 

Mantel

 

 

Figure 7 - Minimum Clearance to Wall and Ceiling

CONVENTIONAL FIREPLACE INSTALLATION

Conventional installation of this fireplace involves installing fireplace along with the corner, face, or cabinet mantel with hearth base accessories against a wall in your home. Follow the instructions below to install the fireplace in this manner.

WARNING

WARNING ICON

G 001

For conventional installation, it is recommended you use the cabinet mantel, corner mantel, face mantel, or hearth bases specified in this manual. Surface clearances may not be sufficient with other cabinet mantels and hearth bases. This may create a fire hazard. See Accessories, pages 34 and 35 for correct mantels and hearth bases.

Note: The instructions below show installation using the cabinet mantel and the G3000F/G3001U hearth base accessories. The hearth base accessory shown is optional for this installation. You can install fireplace and cabinet mantel directly on the floor. The corner mantel and face mantel accessories cannot be installed with the G3000F/G3001U hearth base. You must install corner and face mantel directly on the floor. If mounting fireplace and cabinet mantel to the floor or using face mantel or corner mantel, an optional G3005 Slim Base kit may be installed.

1.Assemble cabinet mantel, hearth base, and trim accessories. Assembly instructions are included with each accessory.

Continued

11

103281

INSTALLING

Continued

12

2.Install a properly grounded, 120 volt three-prong electrical outlet at fireplace location if an outlet is not there. If possible, locate outlet so cabinet mantel will cover it when installed (see Figure 8).

3.Install gas piping to fireplace location. This installation includes an approved flexible gas line (if allowed by local codes) after the manual shutoff valve. The flexible gas line must be the last item installed on the gas piping. See Installing Gas Piping to Fireplace Location, page 16.

4.Place hearth base accessory against wall at installation location. Cut an access hole in hearth top to run flexible gas line to fireplace (see Figure 8). Make sure to locate access hole so cabinet mantel will cover it when installed. Note: You can secure base to floor using wood screws. Countersink screw heads and

putty over.

Flexible Gas Line

Electrical Outlet

Hearth Base

Gas Line Access

,,,,,QQQQQ¢¢¢¢¢ Hole

,,,,,QQQQQ¢¢¢¢¢

Figure 8 - Placing Hearth Base Accessory Against Wall

5.Route flexible gas line through access hole in hearth base.

6.Center cabinet mantel on hearth base (see Figure 9). Make sure mantel is flush against wall.

¢¢¢QQQ,,,

Cabinet Mantel

¢¢¢QQQ,,,

¢¢¢QQQ,,,

¢¢¢QQQ,,,

,,,,,QQQQQ¢¢¢¢¢

,,,,,QQQQQ¢¢¢¢¢

Figure 9 - Installing Cabinet Mantel

103281

INSTALLING

7. Break off nailing flanges (see Figure 10) with hammer or pliers.

 

Continued

Nailing Flanges

Figure 10 - Location of Nailing Flanges

8.Place cardboard or other protective material on top of hearth base. Carefully set fireplace on protective material, with back of fireplace inside mantel opening.

9.Attach flexible gas line to fireplace gas regulator. See Connecting Fireplace to

Gas Supply, page 17.

10.Route blower electrical cord through side or rear access door of fireplace. Plug electrical cord into electrical outlet.

11.Carefully insert fireplace into cabinet mantel. Be careful not to scratch or damage hearth base, cabinet mantel, or any laminate trim on hearth base. Remove protective material from top of hearth base and from front of fireplace (if any). Note: You can secure fireplace to hearth or floor. Open lower louver. Locate screw holes in bottom of base. Tighten wood screws through these holes and into hearth or floor.

12.Check all gas connections for leaks. See Checking Gas Connections, page 18.

,,,QQQ¢¢¢

,,,QQQ¢¢¢

,,,QQQ¢¢¢

,Q¢,,,QQQ¢¢¢,Q¢

,,,,,QQQQQ¢¢¢¢¢

Figure 11 - Inserting Fireplace Into Cabinet Mantel

Continued 13

103281

INSTALLING

Continued

14

BUILT-IN FIREPLACE INSTALLATION

Built-in installation of this fireplace involves installing fireplace into a framed-in enclosure. This makes the front of fireplace flush with wall. If installing a mantel above the fireplace, but you must follow the clearances shown in Figure 15, page 15. Follow the instructions below to install the fireplace in this manner.

Height

Front Width

Depth

 

 

 

 

 

 

Actual

Framing

Actual

Framing

Actual

Framing

 

 

 

 

 

 

32 3/8"

33"

34 5/16"

35 1/2"

16 11/16"

17 3/4"

1.Frame in rough opening. Use dimensions shown in Figure 12 for the rough opening.

17 3/4"

33"

35 1/2"

Figure 12 - Rough Opening for Installing in Wall

If installing in a corner, use dimensions shown in Figure 13 for the rough opening. The height is 33" which is the same as the wall opening above.

39 3/8"

27 7/8"

35 1/2" 55 5/8"

Figure 13 - Rough Opening for Installing in Corner

2.Install a properly grounded, three-prong 120 volt electrical outlet at fireplace location. Locate outlet inside the framed enclosure.

3.Install gas piping to fireplace location. This installation includes an approved flexible gas line (if allowed by local codes) after the manual shutoff valve. The flexible gas line must be the last item installed on the gas piping. See Installing

Gas Piping to Fireplace Location, page 16.

4.Carefully set fireplace in front of rough opening with back of fireplace inside wall opening.

5.Attach flexible gas line to fireplace gas regulator. See Connecting Fireplace to Gas Supply, page 17.

6.Route blower electrical cord through side or rear access door of fireplace. Plug electrical cord into electrical outlet.

7.Carefully insert fireplace into rough opening.

103281