Desa VT32EP-A, VT32EN-A User Manual

DIRECT-VENT FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
NATURAL GAS “TUDOR” MODELS (V)T32EN-A SERIES
PROPANE/LP GAS “TUDOR” MODELS (V)T32EP-A SERIES
WARNING: If the information in this manual is not fol-
lowed exactly, a re or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
— Installation and service must be performed by a quali-
ed installer, service agency or the gas supplier.
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, altera­tion, service or maintenance can cause injury or prop­erty damage. Refer to this manual for correct installation and operational procedures. For assistance or addi­tional information consult a qualied installer, service agency or the gas supplier.
This appliance may be installed in an aftermarket,* per­manently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas in­dicated on the rating plate. This appliance is not con­vertible for use with other gases, unless a certied kit is used.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
State of Massachusetts: The installation must be made by a licensed plumber or gas tter in the Commonwealth of Massachusetts.
TABLE OF CONTENTS
Safety Information ............................................... 2
Product Identication ........................................... 4
Local Codes......................................................... 4
Product Features ................................................. 4
Pre-Installation Preparation ................................. 5
Location of Termination Cap ................................ 7
Venting Installation Instructions ........................... 8
Fireplace Installation.......................................... 17
Wiring Diagram .................................................. 26
Operating Fireplace ........................................... 26
Cleaning and Maintenance ................................ 28
Inspecting Burners............................................. 28
Troubleshooting ................................................. 30
Replacement Parts ............................................ 32
Service Hints ..................................................... 32
Technical Service............................................... 32
Specications .................................................... 32
Accessories ....................................................... 33
illustrated Parts Breakdown and Parts List ........ 34
Warranty Information ........................... Back Cover

SAFETY INFORMATION

WARNING: This product con­tains and/or generates chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, op­erate or service this replace.
www.desatech.com
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, operate or service this replace. Inproper use of this replace can cause seri­ous injury or death from burns, re, explosions, electrical shock and carbon monoxide poisoning.
116647-01B2
SAFETY INFORMATION
Continued
DANGER: Carbon monoxide poisoning may lead to death!
This replace must be installed by a qualied (cer­tied or licensed) service person. It has a sealed gas combustion chamber that uses a coaxial pipe (pipe within a pipe and having the same center) venting system. It brings in fresh air for combus­tion through the outer pipe and combustion gases are exhausted through the inner pipe. If the glass door assembly and venting pipe are not properly seated, connected and sealed, carbon monoxide leakage (spillage) can occur.
Carbon Monoxide Poisoning: Early signs of carbon
monoxide poisoning resemble the u, with head­aches, dizziness or nausea. If you have these signs, the replace may not be working properly. Get fresh air at once! Have replace serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the inuence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and pro-
pane/LP gases are odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this replace.
WARNING: Any change to this replace or its controls can be dangerous.
WARNING: Do not use a blow­er insert, heat exchanger insert or other accessory not approved for use with this replace.
Do not use any solid fuels
(wood, coal, paper, cardboard, etc.) in this replace. Use only the gas type indicated on re­place name plate.
Carefully supervise young chil-
dren when they are in the room
with replace.
116647-01B 3
www.desatech.com
This fireplace reaches high temperatures. Keep children
and adults away from hot sur-
faces to avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
Do not operate replace with glass door removed, cracked or broken.
Keep the appliance area clear and free from combustible ma­terials, gasoline and other am­mable vapors and liquids.
Do not place clothing or other ammable material onor near replace. Never place any ob­jects on replace.
1. This appliance is only for use with the type of gas indicated on the rating plate. This ap­pliance is not convertible for use with other gases unless a certied kit is used.
2. For propane/LP replace, do not place propane/ LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity.
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use
any phone in your building
• immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions
• if you cannot reach your gas supplier, call
the re department
4. Never install the replace
• in a recreational vehicle
• in windy or drafty areas where curtains or other
combustible (ammable) objects can make contact with the replace front
• in high trafc areas
5. Do not modify this replace under any circum­stances. Any parts removed for servicing must be replaced prior to operating replace.
SAFETY INFORMATION
Continued
6. Turn replace off and let cool before servicing, installing or repairing. Only a qualied service person should install, service or repair this replace. Have replace inspected annually by a qualied service person.
7. You must keep control compartments, burn­ers and circulating air passages clean. More frequent cleaning may be needed due to ex­cessive lint and dust from carpeting, bedding material, etc. Turn off the gas valve and pilot light before cleaning replace.
8. Have venting system inspected annually by a qualied service person. If needed, have vent­ing system cleaned or repaired. See Cleaning and Maintenance, page 28.
9. Do not use this replace to cook food or burn paper or other objects.
10. This appliance, when installed, must be electri­cally grounded in accordance with local codes or, in the absence of local codes, with the
National Electrical Code, ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1.
11. Do not use replace if any part has been under water. Immediately call a qualied service per­son to arrange for replacement of the unit.
12. Do not operate replace if log is broken.
13.
Provide adequate clearances around air openings.
PRODUCT
IDENTIFICATION
Upper Louver Panel
Nailing Flange
Glowing Embers
Lower Louver Panel
Electronic Control Valve
Burner Assembly
Switch Bracket for Optional Remote and Blower
Figure 1 - Direct-Vent Fireplace with
Electronic Ignition
Glass Door Assembly
Flue Collar
Log Set
Lava Rock
www.desatech.com

LOCAL CODES

Install and use replace with care. Follow all local codes. In the absence to local codes, use the cur­rent National Fuel Gas Code ANSI Z223.1/NFPA
54* (USA) or the current CSA-B149.1 Installation Code (Canada).
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269

PRODUCT FEATURES

These are a few facts that can help you understand and enjoy your direct-vent replace:
• The venting system may be routed to the out­side of your home in several ways. It may vent through the roof (vertical) or it may vent to an outside/exterior wall (horizontal). The vent pipe installation is very important to allow for proper operation. You must follow the venting instructions very carefully for either vertical or horizontal applications.
• This replace may be installed in any room of your house provided all local codes and these installation instructions are followed.
• The blower requires electricity if installed. If you plan to install the blower at a later date, outlet must be wired at the bottom of the re­place when framing.
• The electronic ignition creates spark to ignite the pilot light. It does not require any matches, batteries or any other sources of ignition to light the pilot.
• Each time you turn on your replace, you may notice some amount of condensation on the in­side of the replace glass. This is normal and will disappear after 10-20 minutes of operation.
• Your direct-vent gas replace system (replace and venting) is a balanced and sealed gas op­erating unit. It requires approximately 10-20 minutes of operating time before the ame pattern stabilizes.
116647-01B4
D
RW
FW
PRE-INSTALLATION
PREPARATION
LOCATION AND SPACE
REqUIREMENTS
Determine the safest and most efcient location for your DESA direct-vent replace. Make sure that rafters and wall studs are not in the way of the venting system. Choose a location where the heat output is not affected by drafts, air conditioning ducts, windows or doors. Figure 2 shows some common locations. Be aware of all restrictions and precautions before deciding the exact location for your replace and termination cap.
When deciding the location of your replace, follow these rules:
• Do not connect this replace venting to a chim­ney ue serving a separate solid-fuel burning replace or appliance.
• Due to high temperatures, do not locate this replace in high trafc areas, windy or drafty areas or near furniture or draperies.
• Proper clearances must be maintained.
• If your replace is to be installed directly on carpeting, vinyl tile or any combustible mate­rial other than wood, it must be installed on a metal or wood panel extending the full width and depth of the replace. See Figure 3.
Flush with a wall
Through exterior wall enclosed in a chase
Corner installation
Figure 2 - Common Fireplace Locations
22 1/2"
16 5/8"
Figure 3 - Fireplace Bottom Dimensions
34 3/8"
• Your replace is designed to be used in zero clearance installations. Wall or framing material can be placed directly against any exterior sur­face on the back, sides or top of your replace, except where standoff spacers are integrally attached. If standoff spacers are attached to your replace, these spacers can be placed directly against wall or framing material. See framing details on page 6.
• If you plan on installing a television or enter­tainment center recessed above your replace, it is recommended that you maintain a minimum 18" above top of louver opening.
• When locating termination cap, it is important to observe the minimum clearances shown in Figure 7, page 7.
• If recessing into a wall, you can avoid extra framing by positioning your replace against an already existing framing member.
• Do not recess termination cap into a wall or siding.
• You may paint the termination cap with 450º F heat-resistant paint to coordinate with the exterior nish.
• There must not be any obstruction such as bushes, garden sheds, fences, decks or util­ity buildings within 24" from the front of the termination cap.
• Do not locate termination cap where excessive snow or ice build up may occur. Be sure to clear vent termination area after snow falls to prevent accidental blockage of venting system. When using snow blowers, do not direct snow towards vent termination area.
CLEARANCES
Minimum clearances to combustibles for the replace are as follows:
*Back and sides 0"
Perpendicular walls 6"
Floor 0"
Ceiling to louver opening 42"
Front 36"
Top 0"
Vent (S ee ve nti ng ins tru cti ons fo r specic venting clearances.)
Combustible material with a maximum thick­ness of 5/8" may be ush with the top front of replace.
* For back and sides of replace, do not pack with insulation or other materials. Zero inch clearance to combustible materials are for framing purpose only.
116647-01B 5
www.desatech.com
PRE-INSTALLATION
A
B
E
F
G
H
D
C
Nailing Tabs
C
B
A
D
E
F
G
Top of Louver Opening
3
2
1
4
5
6
7
Wall
PREPARATION
Continued
NOTICE: This replace is in­tended for use as supplemental heat. Use this replace along with your primary heating sys­tem. Do not install this replace as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using replace. This will help circulate the heat throughout the house. In the event of a power outage, you can use this replace as a heat source.
FRAMING AND FINISHING
Figure 4 shows typical framing of this replace. Figure 5 shows framing for corner installation. All minimum clearances must be met.
For available accessories for this replace, see Accessories on page 33. If you are using a separate combustible mantel piece, refer to Figure 6 for proper installation height. You can install noncom­bustible mantels at any height above the replace. Note: Noncombustible mantels may discolor!
13 5/8"
10 3/8"
39 3/8"
28 1/2"
97/8"
343/8"
345/8"
541/8"
Nailing Tabs
Figure 5 - Framing Clearances for Corner
Installation
323/8"
345/8"
Figure 4 - Framing Clearances for
Installation Against an Exterior Wall
17" (Horiz. Vent) 20" (Vert. Vent)
www.desatech.com
Ref.
Mantel
Depth Ref.
Mantel from Top of
Louver Opening
1 14" A 16" 2 12" B 14" 3 10" C 12" 4 8" D 10" 5 6" E 8" 6 4" F 6" 7 2" G 4"
Figure 6 - Clearances for Combustible
Mantels
116647-01B6
Fixed
Closed
Openable
Fixed
Closed
Openable
V
V
V
V
V
V
V
V
X
X
V
X
G
G
J
F
B
B
K
N
H
I
A
N
E
L
D
B
M
A
C
B
V
V
A
G
G
B
TERMINATION CAP
AIR SUPPLY INLET
GAS METER RESTRICTED AREA
(TERMINATION PROHIBITED) A = clearance above grade, veranda, porch, deck, or balcony [*12 inches (30.5mc) minimum] B = clearance to window or door that may be opened [12 inches (30.5cm) minimum] C = clearance to permanently closed window [minimum 12 inches (30.5cm) recommended to prevent condensation on window] D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24 inches (61cm) from the center-line of the terminal [18 inches (45.7cm) minimum] E = clearance to unventilated soffit [12 inches (30.5cm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within 36 inches (91.4cm) horizontally from the center-line of the regulator
I = clearance to service regulator vent outlet [*72 inches (182.9cm) minimum] J = clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other fireplace [*12 inches (30.5cm) minimum] K = clearance to a mechanical air supply inlet [*72 inches (182.9cm) minimum] L = † clearance above paved side-walk or a paved driveway located on public property [*84 inches (213.3cm) minimum] M = clearance under veranda, porch, deck [*12 inches (30.5cm) minimum ‡] N = clearance above a roof shall extend a minimum of 24 inches (61cm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18 inches (45.7cm)
† vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings* ‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A. Note: Local codes or regulations may require different clearances
A = 6" (15.2cm)
Inside Corner
V
B
E
V
B = 6" (15.2cm)
C = Maximum depth of 48" (121.9cm) for recessed location D = Minimum width for back wall of recessed location ­ Combustible - 38" (965mm) Noncombustible - 24" (61cm) E = Clearance from corner in recessed location­ Combustible - 6" (15.2cm) Noncombustible - 2" (5.1cm)
Outside Corner Recessed Location
G
H
G = 12" (30.5cm) minimum clearance
Balcony with No Side Wall
V
J
Combustible & Noncombustible H = 24" (61cm) J = 20" (50.8cm)
Balcony with Perpendicular Side Wall
C
D
C
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors

LOCATION OF TERMINATION CAP

Figure 7 - Minimum Clearances for Termination Cap
116647-01B 7
www.desatech.com
VENTING INSTALLATION
INSTRUCTIONS
NOTICE: Read these instruc­tions completely before at­tempting installation.
These models are tested and approved for use with DESA (direct-vent) pipe components and terminations.
The venting system must terminate on the outside of the structure and can not be attached to a chimney or ue system serving a separate solid fuel or gas burning appliance. A direct-vent appliance must have its own venting system. DO NOT common vent this appliance.
These models are approved to be vented either horizontally through an outside wall or vertically through a roof or chase enclosure using the fol­lowing guidelines:
• When venting system terminates horizontally on an outside wall, you may install a standoff if the termination cap is to be installed directly on a combustible nish such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may cause excessive temperatures which could cause a re.
• Vent pipe air space clearances to combustibles are 1" on all sides except on the horizontal sections, which requires 2" clearance from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
• Snorkel terminations are required when minimum clearance to grade cannot be met (see Figure 16 on page 12).
• Have replace and selected vent components on hand to help determine the exact measurements when elbowing or offsetting. Always use wall restops when penetrating walls and restops when penetrating ceilings or attic spaces.
• Install horizontal venting with a 1/4" rise for every 12" of run toward the termination.
WARNING: Read all instruc-
tions completely and thoroughly before attempting installation.
Failure to do so could result in
serious injury, property damage or loss of life.
NOTICE: Failure to follow these in­structions will void the warranty.
IMPORTANT: Do not seal vent cap to pipe. Cap must be removable for service.
INSTALLATION PRECAUTIONS
• Wear gloves and safety glasses for protection
• Use extreme caution when using ladders or when on roof tops
• Be aware of electrical wiring locations in walls and ceilings
The following actions will void the warranty on your venting system:
In s t all a t ion of any da m a ged ven t i ng component
• Unauthorizedmodicationoftheventingsys­tem (Do not cut or alter vent components)
• Instal lation of any component part not manufactured or approved by DESA
• Installation other than as instructed by these instructions
WARNING: This gas replace and vent assembly must be vented directly to the outside. The venting system must NEVER be attached to a chimney serv­ing a separate solid fuel burning appliance. Each direct-vent gas appliance must use a separate vent system. Do not use com­mon vent systems.
WARNING: Vent pipe air space clearances to combustibles are 1" on all sides except on the horizontal sections, which require 2" clearances from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
www.desatech.com
116647-01B8
VENTING INSTALLATION
(Framing
Detail)
10 3/4"
10 3/4" Inside Framing
10 3/4"
8 1/2"
Vent Opening
Combustible Wall
Vent Opening
Noncombustible Wall
INSTALLATION PLANNING
There are two basic types of direct-vent instal­lation:
• Horizontal Termination
• Vertical Termination
Horizontal Termination Installation
IMPORTANT: Horizontal square terminations require only inner portion of wall restop. Hori­zontal installations using round termination require exterior portion of wall restop (see Figure 14, page 11).
1. Set the replace in its desired location and determine the route your horizontal venting will take. Do not secure the replace until all venting has been installed. Some installa­tions require sliding the replace in and out of position to make nal venting connections. Figures 14 through 18 on pages 11 through 13 show different congurations for venting with horizontal termination that will help you decide which application best suits your installation. Check to see if wall studs or roof rafters are in the path of your desired venting route. If they are, you may want to adjust the location of the replace.
2. Direct vent pipe sections and components are designed with special twist-lock connections.
Twist-Lock Procedure: The female ends of
the pipes have locking lugs (indentations). These lugs will slide straight into matching slots on the male ends of adjacent pipes. Push pipe sections together and twist one section clockwise approximately one-quar­ter turn until the sections are fully locked (see Figure 8). Note: Horizontal runs of vent must be supported every three feet. Use wall straps for this purpose.
3. Use a 45° elbow to connect venting system to replace ue collar. The elbow is designed to be twist-locked onto the flue collar as described in step 2. IMPORTANT: Do not attempt to alter the conguration of the elbow by cutting, twisting, bending, etc.
4. Assemble the desired combination of pipe and elbows to the replace ue collar. If there are long portions of venting run, pre-assembled pipe sections may be installed as subassem­blies for convenience.
116647-01B 9
INSTRUCTIONS
Continued
5. Carefully determine the location where the vent pipe assembly will penetrate the outside wall. The center of the hole should line up with the center-line of the horizontal vent pipe. Mark the wall for a 10 3/4" x 10 3/4" square hole. Cut and frame the square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of noncombustible material, such as masonry block or concrete, a 8 1/2" hole with zero clearance is acceptable (see Figure 9).
WARNING: Do not recess
vent termination into any wall. This will cause a re hazard.
Male Slots
Female Locking Lugs
Figure 8 - Vent Pipe Connections
Center of Hole
Figure 9 - Vent Opening Requirements
www.desatech.com
VENTING INSTALLATION
INSTRUCTIONS
Continued
6. Noncombustible Exterior Wall: Position the horizontal vent cap in the center of the 8 1/2" round hole and attach to the exterior wall with four screws. No te: The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete or other types of sidings. Before attaching the vent cap to exterior wall, run a bead of non-hardening mastic (pliable sealant) around the outside edges to make a seal between it and the outside wall.
Combustible Exterior Wall: For vinyl siding,
stucco or wood exteriors, a siding standoff may be installed between the vent cap and exterior wall. The siding standoff prevents excessive heat from damaging the siding mate rials. Siding material must be cut to accommodate standoff. Bolt the vent cap to the standoff. Ap­ply non-hardening mastic around outside edge of standoff. Position the standoff/cap assembly in the center of the 10 3/4" square hole and attach to exterior wall with wood screws provided (see Figure 11). The siding standoff must sit ush against the exterior fascia material.
7. Combustible Exterior Wall Only: Slide the wall restop over the vent pipe before connecting horizontal run to vent cap (see Figure 12).
8. Carefully move replace, with vent assembly attached, toward wall and insert vent pipe into horizontal termination. The pipe overlap should be a minimum of 11/4" (see Figure 13, page 11).
9. Combustible Exterior Wall Only: Slide wall restop against interior wall surface and attach with screws provided (see Figure 12). See Figure 13, page 11 for horizontal termination details.
Vent Cap
Wood Screw
10. Place replace into position and shim with noncombustible material if needed. Nail or screw side anges to framing to secure unit in place. IMPORTANT: Make sure replace is level before securing. If replace is not level it will not work properly.
Cut Siding Away to Fit Standoff
Standoff
Wood Screw
Vent Cap
Screws
Apply Mastic to All Four Sides
Figure 11 - Installing Siding Standoff
(Combustible Exterior)
Interior Wall Surface
Wall Firestop
Vent Cap (Horizontal Termination)
Figure 12 - Connecting Vent Cap with
Screw
Horizontal Vent Pipe
Horizontal Vent Pipe
Figure 10 - Installing Horizontal Vent Cap
(Noncombustible Exterior)
www.desatech.com
116647-01B10
VENTING INSTALLATION
INSTRUCTIONS
Continued
Siding Standoff
GROUND FLOOR INSTALLATION
Recommended Applications:
• Installation using cabinet surrounds
• Through the wall using round or square termi-
nation (up to 12" horizontal pipe)
• NOT FOR CORNER INSTALLATION
Minimum Pipe Overlap 11/4"
Wall Firestop
Direct Vent Pipe
Maintain 1" Minimum Air Space Around Outer Pipe When Penetrating a Wall
Figure 13 - Typical Horizontal
Termination Cap Mounting with
Additional Siding Standoff Installed
Horizontal Termination Congurations
Figures 14 through 18 show different congura­tions and alternatives for venting with horizontal termination. Each gure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: Remember that a horizontal run of venting must have a 1/4" rise for every 12" of run toward the termination.
10 3/4" x 10 3/4" Framed Opening
Screws
High Wind Termination
Apply Mastic to Outside Edge of Standoff
Exterior Wall with Vinyl Siding
Horizontal High Wind Square Termination
45° Elbow
Figure 14 - Horizontal Termination
Conguration for Square or Round
45° Elbow
Adjustable Pipe 12" Max.
Wall Firestop
Square Termination
Vertical (V) Horizontal (H)
29 3/4" 17" max.
Exterior
Wall Firestop
Termination
Portion of Wall Firestop (Round Termination Only)
Horizontal Round Termination
WARNING: Never run vent
downward as this may cause
excessive temperatures which could cause a re. Operation of improperly installed and main­tained venting system could result in serious injury, property damage or loss of life.
116647-01B 11
www.desatech.com
VENTING INSTALLATION INSTRUCTIONS
Continued
CORNER INSTALLATION
Recommended Applications:
• Corner ground oor installation
• Ground oor installation where pipe vents horizontally through wall (over 12" horizontal pipe)
• Basement installation where one foot clearance from ground to termination is possible
Not to Exceed
Square Termination
Wall Firestop
Figure 15 - Horizontal Termination Conguration for Corner Installation Using One
SNORKEL TERMINATION INSTALLATION
Recommended Applications:
• Installations requiring a vertical rise on building exterior
• Any installation using snorkel termination to achieve one foot above ground
(H) Limits
45° Elbow
Vertical (V) Required
Vertical (V) Vertical Pipe Horizontal (H)
*43 3/4" min. None 30" max. 53 3/4" min. 1 ft. 48" max. 65 3/4" min. 2 ft. 60" max. 77 3/4" min. 3 ft. 84" max.
89 3/4" min. 4 ft. 20' max.
* Ground Floor Corner Venting
Snorkel Termination
90° Elbow
As Required for (V), See Chart for Pipe Section Required
90° Elbow
Not to Exceed (H) Limits
90° Elbow
Wall Firestop
45° Elbow
Snorkel terminations are available for installations requiring a vertical rise on the exterior of the build­ing. If installing snorkel termination below grade, you must provide proper drainage to prevent water from entering snorkel termination (see Figure 16). Do not back ll around snorkel termination.
Snorkel
Termination
90° Elbow
12" Min.
Wall
Firestop
Square Termination
12" Min.
Snorkel
Termination
12" Min.
12" Min.
Adequate
Drainage
Figure 16 - Snorkel Termination Congurations for Below Ground Installation
www.desatech.com
116647-01B12
Loading...
+ 28 hidden pages