Desa VP1600E, VP2600E User Manual

Page 1
®
INFRARED VENT-FREE PROPANE/LP GAS HEATER
OWNER’S OPERATION AND INSTALLATION MANUAL
VP1600E VP2600E
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result caus­ing property damage, personal injury, or loss of life.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by
a qualified installer, service agency, or the gas supplier.
This appliance may be installed in an aftermarket*, permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
WARNING: Improper installa­tion, adjustment, alteration, ser­vice, or maintenance can cause injury or property damage. Re­fer to this manual for correct installation and operational pro­cedures. For assistance or ad­ditional information consult a qualified installer, service agency, or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxy­gen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to
Combustion and Ventilation
page 4 of this manual.
Air For
on
Save this manual for future reference.
Page 2
®
INFRARED PROPANE/LP GAS HEATER
SAFETY INFORMATION
WARNINGS
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, oper­ate, or service this heater. Im­proper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, persons with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Propane/LP Gas: Propane/LP gas is odor-
less. An odor-making agent is added to pro­pane/LP gas. The odor helps you detect a propane/LP gas leak. However, the odor added to propane/LP gas can fade. Propane/LP gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
WARNING: Any change to this heater or its controls can be dangerous.
WARNING: Do not use any accessory not approved for use with this heater.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Surface of heater becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will re­main hot for a time after shut­down. Allow surface to cool be­fore touching.
Carefully supervise young chil­dren when they are in the same room with heater.
Make sure grill guard is in place before running heater.
Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/ LP supply tank(s) outdoors.
3. This heater shall not be installed in a bedroom or bathroom.
4. If you smell gas
• Shut off gas supply
• Do not try to light any appliance
• Do not touch any electrical switch; do
not use any phone in your building
• Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instructions
• If you cannot reach your gas supplier,
call the fire department
5. Always run heater with plaque control knob at the 1, 2, 3, or 4 locked positions. Never set control knob between locked positions. Poor combustion and higher levels of carbon monoxide may result.
6. This heater needs fresh, outside air ven­tilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Air for Combustion and V entilation, pages 4 through 6.
7. If heater shuts off, do not relight until you provide fresh, outside air. If heater keeps shutting off, have it serviced.
8. Do not run heater
• where flammable liquids or vapors
are used or stored
• under dusty conditions
9. Do not use heater if any part has been under water. Immediately call a quali­fied service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.
10. Turn off and unplug heater and let cool before servicing. Only a quali­fied service person should service and repair heater.
11. Operating heater above elevations of 4,500 feet could cause pilot outage.
12. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity.
13. Before using furniture polish, wax, car­pet cleaner, or similar products, turn heater off. If heated, the vapors from these products may create a white pow­der residue within burner box or on adjacent walls or furniture.
2
103351
Page 3
OWNER’S MANUAL
PRODUCT IDENTIFICATION
Front Panel
Piezo Ignitor Control Knob
Grill Guard
Burners
Heater Cabinet
PRODUCT FEATURES
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater has a piezo ignitor. This system requires no matches, batteries, or other sources to light heater.
Figure 1 - Vent-Free Propane/LP Gas Heater (Model VP2600E Shown)
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of National Fuel Gas Code ANS Z223.1, also known as NFPA 54*.
*Available from: American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
UNPACKING
1. Remove heater from carton.
2. Remove all protective packaging ap­plied to heater for shipment.
3. Check heater for any shipping damage. If heater is damaged, promptly inform dealer where you bought heater.
103351
3
Page 4
®
INFRARED PROPANE/LP GAS HEATER
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ven­tilation air. Read the following in­structions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy effi­cient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper com­bustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide ad­equate fresh air for these appliances. This will insure proper venting of vented fuel­burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code. NFPA 54/ANS Z2233.1, Sec­tion 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 4 through 6 will
help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and win­dows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is de­fined as construction where:
a. walls and ceilings exposed to the
outside atmosphere have a con­tinuous water vapor retarder with a rating of one perm (6 x 10 per pa-sec-m2) or less with open­ings gasketed or sealed
b. weather stripping has been
added on openable windows and doors
c. caulking or sealants are applied
to areas such as joints around window and door frames, be­tween sole plates and floors, be­tween wall-ceiling joints, be­tween wall panels, at penetra­tions for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of the three criteria above, you must provide ad­ditional fresh air. See
From Outdoors
If your home does not meet all of the three criteria above, proceed to
and
, page 6
Ventilation Air
.
termining Fresh-Air Flow For Heater Location,
page 5.
and
-11
kg
De-
Confined and Unconfined Space
The National Fuel Gas Code ANS Z223.1
defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggre­gate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are con­sidered a part of the unconfined space.
This heater shall not be installed in a con­fined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air.
* Adjoining rooms are communicating only if there are doorless passageways or ventila­tion grills between them.
4
103351
Page 5
OWNER’S MANUAL
AIR FOR COMBUSTION AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this worksheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length x width x height). Length x Width x Height = ________________________ cu. ft. (volume of space)
Example:
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
_____________________(volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)
Example:
3. Add the Btu/Hr of all fuel burning appliances in the space. Vent-free heater Btu/Hr Gas water heater* Btu/Hr Gas furnace Btu/Hr Vented gas heater Btu/Hr Gas fireplace logs Btu/Hr Other gas appliances* + __________________Btu/Hr T otal = __________________Btu/Hr * Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_________________ Btu/Hr (maximum the space can support) _________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-
ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6. C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)
Example:
Gas water heater 40,000 Btu/Hr Vent-free heater + 18,000 Btu/Hr T otal = 58,000 Btu/Hr
51,200 Btu/Hr (maximum the space can support) 58,000 Btu/Hr (actual amount of Btu/Hr used)
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the
103351
National Fuel Gas Code, ANS Z223.1, Section 5.3
5
or applicable local codes.
Continued
Page 6
®
Or
Remove
Door into
Adjoining
Room,
Option 3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills
into Adjoining
Room,
Option 1
INFRARED PROPANE/LP GAS HEATER
AIR FOR COMBUSTION AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro­vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see op­tion 3, Figure 2). Follow the National Fuel
Gas Code NFPA 54/ANS Z223.1, Section
5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
WARNING: Rework work­sheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two per­manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation
grills or ducts.
IMPORTANT:
inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
Do not provide openings for
Figure 2 - Ventilation Air from Inside Building
Outlet Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors
Outlet Air
Inlet Air
Ventilated Attic
To Attic
To
Crawl
Space
Ventilated
Crawl Space
6
103351
Page 7
OWNER’S MANUAL
36"
3"
FLOOR
CEILING
Minimum
Minimum Of Carpe Combust
8" Minimum From Sides Of Heater
Left Side
Right Side
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your pri­mary heating system. Do not in­stall this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circu­late the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualified ser­vice person must install heater. Follow all local codes.
CHECK GAS TYPE
Use only propane/LP gas. If your gas supply is not propane/LP, do not install heater. Call dealer where you bought heater for proper type heater.
INSTALLATION ITEMS
Before installing heater, make sure you have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• ground joint union
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench * A CSA/AGA design-certified equipment
shutoff valve with 1/8" NPT tap is an ac­ceptable alternative to test gauge connec­tion. Purchase the optional CSA/AGA de­sign-certified equipment shutoff valve from your dealer. See Accessories, page 22.
LOCATING HEATER
This heater is designed to be mounted on a wall.
WARNING: Maintain the mini-
mum clearances shown in Figure
4. If you can, provide greater clear­ances from floor, ceiling, and join­ing wall.
You can locate heater on floor, away from a wall. An optional floor mounting stand is needed. Purchase the floor mounting stand from your dealer. See Accessories, page 22.
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable objects are less than 36 inches from the front, top, or sides of the heater
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
CAUTION: If you install the
heater in a home garage
• heater pilot and burner must be at least 18 inches above floor
• locate heater where moving ve­hicle will not hit it
CAUTION: This heater cre­ates warm air currents. These currents move heat to wall sur­faces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as to­bacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls.
IMPORTANT:
Vent-free heaters add mois­ture to the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, pages 4 through 6.
For convenience and efficiency, install heater
• where there is easy access for operation,
inspection, and service
• in coldest part of room An optional fan kit is available from your
dealer. See Accessories, page 22. If plan­ning to use fan, locate heater near an electri­cal outlet.
Minimum To Top Surface Of Carpeting, Tile Or Other Combustible Material
Figure 4 - Mounting Clearances As Viewed From Front of Heater
103351
Continued
7
Page 8
®
INFRARED PROPANE/LP GAS HEATER
INSTALLATION
Continued
INSTALLING HEATER TO WALL
Mounting Bracket
Locate mounting bracket in heater car­ton. Remove mounting bracket from heater carton.
Mounting Bracket
Figure 5 - Mounting Bracket Location
Removing Front Panel Of Heater
1. Remove two screws near bottom cor­ners of front panel.
2. Lift straight up on grill guard until it stops. Grill guard will slide up about 1/4".
3. Pull bottom of front panel forward, then down.
Methods For Attaching Mounting Bracket To Wall
Only use last hole on each end of mounting bracket to attach bracket to wall. These two holes are 16 inches apart from their centers. Attach mounting bracket to wall in one of two ways.
1. Attaching to wall stud
2. Attaching to wall anchor
Attaching To Wall Stud: This method pro-
vides the strongest hold. Insert mounting screws through mounting bracket and into wall studs.
Attaching To Wall Anchor: This method
allows you to attach mounting bracket to hollow walls (wall areas between studs) or to solid walls (concrete or masonry).
Decide which method better suits your needs. Either method will provide a secure hold for the mounting bracket.
Marking Screw Locations
1. Tape mounting bracket to wall where heater will be located. Make sure mounting bracket is level.
13"
Min.
Only Insert Mounting Screws Through Last
Hole On Each End
Adjoining Wall
Model VP2600E
9 1/4"
Min.
Only Insert Mounting Screws Through Last
Hole On Each End
Adjoining Wall
Model VP1600E
Figure 7 - Mounting Bracket Clearances
Floor
16"
Floor
16"
18 3/4"
18 3/4"
Min.
Min.
Figure 6 - Removing Front Panel Of Heater
WARNING: Maintain mini-
WARNING ICON G 001
mum clearances shown in Figure
7. If you can, provide greater clear­ances from floor and joining wall.
2. Mark screw locations on wall (see Fig­ure 7).
Note:
Only mark last hole on each end of mounting bracket. Insert mounting screws through these holes only.
3. Remove tape and mounting bracket from wall.
8
103351
Page 9
OWNER’S MANUAL
INSTALLATION
Continued
Attaching Mounting Bracket To Wall
Note:
Wall anchors, mounting screws, and spacers are in hardware package. The hard­ware package is provided with heater.
Attaching To Wall Stud Method
For attaching mounting bracket to wall studs
1. Drill holes at marked locations using
9/64" drill bit.
2. Place mounting bracket onto wall. Line
up last hole on each end of bracket with holes drilled in wall.
3. Insert mounting screws through bracket
and into wall studs.
4. Tighten screws until mounting bracket
is firmly fastened to wall studs.
Attaching To Wall Anchor Method
For attaching mounting bracket to hollow walls (wall areas between studs) or solid walls (concrete or masonry)
1. Drill holes at marked locations using
5/16" drill bit. For solid walls (concrete or masonry), drill at least 1" deep.
2. Fold wall anchor as shown in Figure 8.
3. Insert wall anchor (wings first) into
hole. Tap anchor flush to wall.
4. For thin walls (1/2" or less), insert red
key into wall anchor. Push red key to “pop” open anchor wings.
IMPORTANT:
For thick walls (over 1/2" thick) or solid walls, do not pop open wings.
5. Place mounting bracket onto wall. Line
up last hole on each end of bracket with wall anchors.
6. Insert mounting screws through bracket
and into wall anchors.
7. Tighten screws until mounting bracket
is firmly fastened to wall.
Do not hammer key!
Figure 8 - Folding Anchor
Figure 9 - Popping Open Anchor Wings For Thin Walls
Placing Heater On Mounting Bracket
1. Locate two horizontal slots on back panel of heater.
2. Place heater onto mounting bracket. Slide horizontal slots onto stand-out tabs on mounting bracket.
Horizontal Slots
Stand-Out Tab
Figure 10 - Mounting Heater Onto Mounting Bracket
Mounting Bracket (attached to wall)
Installing Bottom Mounting Screws
1. Locate two bottom mounting holes. These holes are near bottom on back panel of heater (see Figure 11).
2. Mark screw locations on wall.
3. Remove heater from mounting bracket.
4. If installing bottom mounting screws into hollow or solid wall, install wall anchors. Follow steps 1 through 4 un­der Attaching To Wall Anchor Method. If installing bottom mounting screw into wall stud, drill holes at marked lo­cations using 9/64" drill bit.
5. Replace heater onto mounting bracket.
6. Place spacers between bottom mount­ing holes and wall anchor or drilled hole.
7. Hold spacer in place with one hand. With other hand, insert mounting screw through bottom mounting hole and spacer. Place tip of screw in opening of wall anchor or drilled hole.
8. Tighten both screws until heater is firmly secured to wall. Do not over tighten.
Note:
Do not replace front panel at this time. Replace front panel after making gas connections and checking for leaks (see pages 10 and 11).
Figure 11 - Installing Bottom Mounting Screws
103351
Continued
9
Page 10
®
INFRARED PROPANE/LP GAS HEATER
INSTALLATION
Continued
CONNECTING TO GAS SUPPLY
WARNING: This appliance re­quires a 3/8" NPT (National Pipe Thread) inlet connection to the pressure regulator.
WARNING: A qualified service person must connect heater to gas supply. Follow all local codes.
CAUTION: Never connect heater directly to the propane/ LP supply. This heater requires an external regulator (not sup­plied). Install the external regu­lator between the heater and pro­pane/LP supply.
The installer must supply an external regu­lator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incom­ing gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure
12. Pointing the vent down protects it from freezing rain or sleet.
Propane/LP Supply Tank
External Regulator
Vent Pointing Down
Figure 12 - External Regulator With Vent Pointing Down
CAUTION: Use only new, black iron or steel pipe. Inter­nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of large enough diameter to allow proper gas volume to heater. If pipe is too small, undue loss of pres­sure will occur.
Typical Inlet Pipe Diameters
VP1600E 3/8" or greater VP2600E 1/2" or greater
Installation must include equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 13).
IMPORTANT:
Install an equipment shutoff valve in an accessible location. The equip­ment shutoff valve is for turning on or shutting off the gas to the appliance.
Pressure Regulator
Regulator Bracket
Heater Cabinet
Tee Joint
Test Gauge Connection *
Sediment Trap
Reducer Bushing to 1/8" NPT
1/8" NPT Plug Tap
Tee Joint Pipe Nipple Cap
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
CAUTION: Use pipe joint seal­ant that is resistant to liquid pe­troleum (LP) gas.
Install sediment trap in supply line as shown in Figure 13. Locate sediment trap where it is within reach for cleaning. Locate sedi­ment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.
IMPORTANT:
Hold pressure regulator with wrench when connecting it to gas pip­ing and/or fittings.
3/8" NPT Pipe Nipple
Ground Joint Union
Equipment Shutoff Valve *
Inlet Pipe From External Regulator (11" W.C. to 14" W.C. Pressure)
3" Minimum
Figure 13 - Gas Connection
* A CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA/AGA design-certified equipment shutoff valve from your dealer. See Accessories, page 22.
10
103351
Page 11
OWNER’S MANUAL
I
O S
INSTALLATION
Continued
CHECKING GAS CONNECTIONS
WARNING: Test all gas pip­ing and connections for leaks after installing or servicing. Cor­rect all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.
CAUTION: Make sure exter­nal regulator has been installed between propane/LP supply and heater. See guidelines under
necting to Gas Supply
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect appliance with its appliance main gas valve (control valve) and equip­ment shutoff valve from gas supply pip­ing system. Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was con­nected.
3. Pressurize supply piping system by ei­ther using compressed air or opening propane/LP supply tank valve.
4. Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form­ing show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve to gas supply. Check re­connected fittings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig­ure 14).
Con-
, page 10.
2. Pressurize supply piping system by ei­ther using compressed air or opening propane/LP supply tank valve.
3. Check all joints from propane/LP sup­ply tank to equipment shutoff valve (see Figure 15). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
4. Correct all leaks at once.
Pressure Testing Heater Gas Connections
1. Open equipment shutoff valve (see Fig­ure 14).
2. Open propane/LP supply tank valve.
3. Make sure control knob of heater is in the OFF position.
4. Check all joints from equipment shutoff valve to control valve (see Figure 15). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operating Heater Pages 11 through 13). Check the rest of the internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to Appliance, page 13).
8. Replace front panel.
ON
Open
Equipment Shutoff Valve
Figure 14 - Equipment Shutoff Valve
Control Valve Location
Propane/LP Supply Tank
Figure 15 - Checking Gas Joints
POSIT
PO
Closed
Equipment Shutoff Valve
OPERATING HEATER
FOR YOUR SAFETY
READ BEFORE
LIGHTING
WARNING: If you do not fol­low these instructions exactly, a fire or explosion may result caus­ing property damage, personal injury or loss of life.
A. This appliance has a pilot which must
be lighted by hand. When lighting the pilot, follow these instructions exactly .
B. BEFORE LIGHTING smell all
around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHA T TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas sup­plier, call the fire department.
C. Use only your hand to push in or turn
the gas control knob. Nev er use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician or gas supplier. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part
has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been un­der water.
Continued
103351
11
Page 12
®
INFRARED PROPANE/LP GAS HEATER
OPERATING HEATER
Continued
LIGHTING
INSTRUCTIONS
1. STOP! Read the safety information on page 11, column 3.
2. Make sure equipment shutoff valve is fully open.
3. Turn control knob clockwise
to the OFF position.
Clockwise
Ignitor Button
PILOT
IGN
IGNITOR
LOW
Figure 16 - Control Knob In The OFF Position
4. Wait five minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety in­formation page 11, column 3. If you don’t smell gas, go to the next step.
5. Turn control knob to PILOT/IGN and press in.
Note:
You may be running this heater for the first time after hook­ing up to gas supply. If so, you may need to press in control knob for 30 seconds. This will allow air to bleed from the gas system.
• If control knob does not pop up
when released, contact a quali­fied service person or gas sup­plier for repairs.
6. With control knob pressed in, push down and release ignitor button. This will light pilot. The pilot is at­tached to the front of burner. If needed, keep pressing ignitor but­ton until pilot lights.
If pilot does not light
• turn control knob clockwise
to the OFF position
Clockwise
• repeat steps 5 and 6
OFF
MED
Control Knob
HIGH
If pilot does not stay lit after sev­eral tries
• refer to Troubleshooting, pages 14 through 16
• contact a qualified service person or gas supplier for repairs
Until repairs are made, light pilot with match. To light pilot with match, see Manual Lighting Procedure, page 13 .
7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob.
Note:
If pilot goes out, repeat steps
3 through 7.
Ignitor Electrode
Thermocouple
Pilot Burner
Figure 17 - Pilot
Control
Knob VP1600E VP2600E
OFF
PILOT
IGN
LOW
OFF
PILOT
IGN
MED
OFF
PILOT
IGN
HIGH
OFF
Figure 18 - Burner Patterns
TO SELECT
HEATING LEVEL
WARNING: When running heater, set control knob at LOW, MEDIUM, or HIGH locked posi­tions. Never set control knob be­tween locked positions. Poor combustion and higher levels of carbon monoxide may result.
CAUTION: Do not try to adjust heating levels by using the equip­ment shutoff valve.
Slightly press in control knob and turn coun­terclockwise to the LOW, ME­DIUM, or HIGH positions (see Figure 18).
IMPORTANT:
sure while turning control knob. Control knob will lock at the desired position.
Release downward pres-
LOW
MED
HIGH
OFF
12
103351
Page 13
OWNER’S MANUAL
OPERATING HEATER
Continued
TO TURN OFF GAS TO
APPLIANCE
Shutting Off Heater
1. T urn control knob clockwise to the OFF position.
2. Turn off all electric power to the ap­pliance if service is to be performed.
Clockwise
Shutting Off Burner Only (pilot stays lit)
Turn control knob clockwise the PILOT position.
Clockwise
to
MANUAL LIGHTING
PROCEDURE
1. Follow steps 1 through 5 under Light­ing Instructions, page 12.
2. With control knob pressed in, strike match. Hold match to pilot until pi­lot lights.
3. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob.
INSPECTING BURNER
Check pilot flame pattern and burner flame pattern often.
PILOT FLAME PATTERN
Figure 19 shows a correct pilot flame pattern. Figure 20 shows an incorrect pilot flame pattern. The incorrect pilot flame is not touch­ing the thermocouple. This will cause the thermocouple to cool. When the thermo­couple cools, the heater will shut down.
If pilot flame pattern is incorrect, as shown in Figure 20
• turn heater off (see To Turn Off Gas to
Appliance)
• see Troubleshooting, pages 14 through 16
BURNER FLAME PATTERN
Pilot Burner
Thermocouple
GRH/OV 007GOOD PILOT/LP
Figure 19 - Correct Pilot Flame Pattern
Pilot Burner
Thermocouple
GRH/OV 008BAD PILOT/LP
Figure 20 - Incorrect Pilot Flame Pattern
Figure 21 shows a correct burner flame pattern. Figure 22 shows an incorrect burner flame pattern.
If burner flame pattern is incorrect, as shown in Figure 22
• turn heater off (see To Turn Off Gas to Appliance)
• see Troubleshooting, pages 14 through 16
Figure 21 - Correct Burner Flame Pattern
Figure 22 - Incorrect Burner Flame Pattern
CLEANING AND MAINTENANCE
WARNING: Turn off heater
and let cool before cleaning.
CAUTION: You must keep con­trol areas, burner, and circulating air passageways of heater clean. Inspect these areas of heater be­fore each use. Have heater in­spected yearly by a qualified ser­vice person. Heater may need more frequent cleaning due to ex­cessive lint from carpeting, bed­ding material, pet hair, etc.
ODS/PILOT AND BURNER ORIFICE
• Use a vacuum cleaner, pressurized air, or small, soft bristled brush to clean.
CLEANING BURNER PILOT AIR INLET HOLE
We recommend that you clean the unit every 2,500 hours of operation or every three months.
We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these parts we recom­mend using compressed air no greater than 30 PSI. Your local computer store, hard­ware store, or home center may carry com­pressed air in a can. You can use a vacuum cleaner in the blow position. If using com­pressed air in a can, please follow the direc­tions on the can. If you don't follow direc­tions on the can, you could damage the pilot assembly.
1. Shut off the unit, including the pilot.
Allow the unit to cool for at least thirty minutes.
2. Inspect burner, pilot for dust and dirt.
3. Blow air through the ports/slots and
holes in the burner.
Clean the pilot assembly also. A yellow tip on the pilot flame indicates dust and dirt in the pilot assembly. There is a small pilot air inlet hole about two inches from where the pilot flame comes out of the pilot assembly (see Figure 23). With the unit off, lightly blow air through the air inlet hole. You may blow through a drinking straw if compressed air is not available.
CABINET
Air Passageways
• Use a vacuum cleaner or pressurized air to clean.
Exterior
• Use a soft cloth dampened with a mild soap and water mixture. Wipe the cabi­net to remove dust.
Pilot Air Inlet Hole
Pilot Assembly
Figure 23- Pilot Inlet Air Hole
103351
13
Page 14
®
INFRARED PROPANE/LP GAS HEATER
TROUBLESHOOTING
Note:
For additional help, visit DESA
International’s technical service web site at www.desatech.com.
Note:
All troubleshooting items are listed in
order of operation.
OBSERVED PROBLEM
When ignitor button is pressed in, there is no spark at ODS/pilot
When ignitor button is pressed in, there is a spark at ODS/Pilot but no ignition
WARNING: Turn off and un­plug heater and let cool before servicing. Only a qualified ser­vice person should service and repair heater.
POSSIBLE CAUSE
1. Ignitor electrode positioned wrong
2. Ignitor electrode broken
3. Ignitor electrode not connected to igni­tor cable
4. Ignitor cable pinched or wet
5. Broken ignitor cable
6. Bad piezo ignitor
7. Piezo ignitor nut is loose
1. Gas supply turned off or equipment shutoff valve closed
2. Control knob not fully pressed in while pressing ignitor button (non-thermostat models only) Thermostat control knob not fully pressed in while pressing ignitor button (thermostat models only)
3. Air in gas lines when installed
4. Depleted gas supply
5. ODS/pilot is clogged
6. Gas regulator setting is not correct
7. Thermostat control knob is not in pilot position (thermostat models only)
CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/ pilot unit.
REMEDY
1. Replace ignitor
2. Replace ignitor
3. Reconnect ignitor cable
4. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry
5. Replace ignitor cable
6. Replace control valve (piezo is part of control valve)
7. Tighten nut holding piezo ignitor. Nut is located inside heater cabinet at top
1. Turn on gas supply or open equipment shutoff valve
2. Turn to PILOT/IGN position. Fully press in cotrol knob while pressing ignitor button (non-thermostat models only) Fully press in thermostat control knob while pressing ignitor button (thermo­stat models only)
3. Continue holding down control knob. Re­peat igniting operation until air is removed
4. Contact local propane/LP gas company
5. Clean ODS/pilot (see Cleaning and Maintenance, page 13) or replace ODS/ pilot assembly
6. Replace gas regulator
7. Turn thermostat control knob to pilot position
www.desatech.com
14
103351
Page 15
TROUBLESHOOTING
Continued
OWNER’S MANUAL
OBSERVED PROBLEM
ODS/pilot lights but flame goes out when control knob is released
Burner(s) does not light after ODS/pilot is lit
POSSIBLE CAUSE
1. Control knob not fully pressed in
2. Control knob not pressed in long enough
3. Equipment shutoff valve not fully open
4. Thermocouple connection loose at con­trol valve
5. Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This prob­lem could be caused by one or both of the following: A) Low gas pressure B) Dirty or partially clogged ODS/pilot
6. Thermocouple damaged
7. Control valve damaged
8. Safety interlock system has been trig­gered (thermostat models only)
1. Burner orifice(s) is clogged
2. Burner orifice(s) diameter is too small
3. Inlet gas pressure is too low
REMEDY
1. Press in control knob fully
2. After ODS/pilot lights, keep control knob pressed in 30 seconds
3. Fully open equipment shutoff valve
4. Hand tighten until snug, then tighten 1/4 turn more
5. A) Contact local propane/LP gas company B) Clean ODS/pilot (see Cleaning and Maintenance, page 13) or replace ODS/ pilot assembly
6. Replace thermocouple
7. Replace control valve
8. Wait one minute for safety interlock sys­tem to reset. Repeat ignition operation
1. Clean burner orifice(s) (see Cleaning and Maintenance, page 13) or replace burner orifice(s)
2. Replace burner orifice(s)
3. Contact local propane/LP gas company
Delayed ignition of burner(s)
Burner backfiring during combustion
Burner plaque(s) does not glow
Slight smoke or odor during initial operation
Heater produces a clicking/ticking noise just after burner is lit or shut off
White powder residue forming within burner box or on adjacent walls or furniture
103351
1. Manifold pressure is too low
2. Burner orifice(s) is clogged
1. Burner orifice(s) is clogged or damaged
2. Burner damaged
3. Gas regulator defective
1. Plaque damaged
2. Inlet gas pressure is too low
3. Control knob set between locked posi­tions
1. Residues from manufacturing processes
1. Metal expanding while heating or con­tracting while cooling
1. When heated, vapors from furniture pol­ish, wax, carpet cleaner, etc., turn into white powder residue
www.desatech.com
15
1. Contact local propane/LP gas company
2. Clean burner orifice(s) (see Cleaning and Maintenance, page 13) or replace burner orifice(s)
1. Clean burner orifice(s) (see Cleaning and Maintenance, page 13) or replace burner orifice(s)
2. Replace burner
3. Replace gas regulator
1. Replace burner
2. Contact local propane/LP gas company
3. Turn control knob until it locks at de­sired setting
1. Problem will stop after a few hours of operation
1. This is common with most heaters. If noise is excessive, contact qualified ser­vice person
1. Turn heater off when using furniture polish, wax, carpet cleaners, or simi­lar products
Continued
Page 16
®
INFRARED PROPANE/LP GAS HEATER
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
IMPORTANT:
supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air and create odors.
Operating heater where impurities in air exist may create odors. Cleaning
OBSERVED PROBLEM
Heater produces unwanted odors
Heater shuts off in use (ODS operates)
Gas odor even when control knob is in OFF position
Gas odor during combustion
POSSIBLE CAUSE
1. Heater burning vapors from paint, hair spray, glues, etc. See statement above
2. Low fuel supply
3. Gas leak. See W arning statement at
top of page
1. Not enough fresh air is available
2. Low line pressure
3. ODS/pilot is partially clogged
1. Gas leak. See W arning statement at
top of page
2. Control valve defective
1. Foreign matter between control valve and burner
2. Gas leak. See W arning statement at
top of page
IMPORTANT
REMEDY
1. Ventilate room. Stop using odor caus­ing products while heater is running
2. Refill supply tank
3. Locate and correct all leaks (see Check- ing Gas Connections, page 11)
1. Open window and/or door for ventilation
2. Contact local propane/LP gas company
3. Clean ODS/pilot (see Cleaning and Maintenance, page 13)
1. Locate and correct all leaks (see Check- ing Gas Connections, page 11)
2. Replace control valve
1. Take apart gas tubing and remove for­eign matter
2. Locate and correct all leaks (see Check- ing Gas Connections, page 11)
Moisture/condensation noticed on windows
1. Not enough combustion/ventilation air
www.desatech.com
16
1. Refer to Fresh Air for Combustion and Ventilation requirements (page 4)
103351
Page 17
OWNER’S MANUAL
SPECIFICATIONS
VP1600E VP2600E
Btu (Variable) 6,000/11,000/16,000 6,000/16,000/26,000 Type Gas Propane/LP Only Propane/LP Only Ignition Piezo Piezo Pressure Regulator Setting 8" W.C. 8" W.C. Inlet Gas Pressure* (in. of water)
Maximum 14" 14" Minimum 11" 11"
Dimensions, Inches (H x W x D)
Heater 23.5 x 18.5 x 8 23.5 x 25.9 x 8 Carton 25.8 x 21.3 x 10.1 25.8 x 28.7 x 10.1
Weight (pounds)
Heater 22 30 Shipping 27 36
Note
: Dimensions listed are outer most points on the heater (includes control knobs
and grill).
* For purposes of input adjustment.
SERVICE HINTSSERVICE
PUBLICATIONS
You can purchase a service manual from the address listed on the back page of this manual. Send a check for $5.00 payable to DESA International.
TECHNICAL SERVICE
You may have further questions about in­stallation, operation, or troubleshooting. If so, contact DESA International’s Technical Service Department at 1-800-323-5190.
You can also visit DESA International’s technical service web site at
www.desatech.com.
When Gas Pressure Is Too Low
• pilot will not stay lit
• burner(s) will have delayed ignition
• heater will not produce specified heat
• propane/LP gas supply may be low
When Gas Quality Is Bad
• pilot will not stay lit
• burner(s) will produce flames and soot
• heater will backfire when lit You may feel your gas pressure is too low or
gas quality is bad. If so, contact your local propane/LP gas supplier.
REPLACEMENT PARTS
Note:
Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty.
PARTS UNDER WARRANTY
Contact authorized dealer from whom you purchased this product. If they are unable to supply original replacement part(s), call DESA International’s Technical Service De­partment at 1-800-323-5190 for information.
When contacting your dealer or DESA In­ternational, have ready:
• your name
• your address
• model and serial numbers of your heater
• how heater was malfunctioning
• type of gas used (propane/LP or natural
gas)
• purchase date Usually, we will ask you to return the defec-
tive part to the factory.
PARTS NOT UNDER WARRANTY
Contact authorized dealers of this product. If they can’t supply original replacement part(s), call DESA International’s Parts Department at 1-800-972-7879 for referral information. When calling DESA Interna­tional, have ready:
• model number of your heater
• the replacement part number
103351
17
Page 18
®
INFRARED PROPANE/LP GAS HEATER
ILLUSTRATED PARTS BREAKDOWN
VP1600E
3
11
17
18
12
14
6
10
4
8
13
5
6
15
9
7
16
2
1
13-6
13-10
13-13
13-14
13-11
13-12
13-7
13-5
13-1
13-2
13-3
13-4
13-8
13-9
ODS/PILOT
BURNER ASSEMBLY
18
103351
Page 19
OWNER’S MANUAL
PARTS LIST
VP1600E
This list contains replaceable parts used in your heater. When ordering parts, follow the instructions listed under Replacement Parts on page 17 of this manual.
KEY PART NO. NUMBER DESCRIPTION QTY.
1 098304-01 Screw, #10 x 3/8" 2 2 098742-13 Front Panel 1 3 098238-06 Grill Guard 1 4 101108-01 Clip-Grill Guard 2 5 103843-02 Apron 1 6 M11084-26 Screw, #10 x 3/8" 9 7 098462-01 Control Rod Assembly 1 8 098457-01 Reflector Assembly 1 9 099415-09 Regulator with Pressure Tap 1 10 098303-02 Screw, #6 x 3/8" 2 11 098455-12 Cabinet Assembly 1 12 098324-01 Control Knob 1 13 See Detail Burner Assembly 1 13-1 099218-06 Burner 1 13-2 098508-01 Valve Retainer Nut 1 13-3 099056-01 Injector-Plaque A 1 13-4 103352-01 Tubing-Valve to Plaque A 1 13-5 103352-02 Tubing-Valve to Plaque B 1 13-6 099056-25 Injector-Plaque B 1 13-7 M11084-37 Screw, #8 x 1/4" 2 13-8 103844-01 Control Valve 1 13-9 102911-01 Pilot Tubing-Valve to Pilot 1 13-10 099051-01 Inlet Tubing 1 13-11 103594-02 ODS/Pilot 1 13-12 M11084-26 Screw, #10 x 3/8" 2 13-13 098593-01 Thermocouple 1 13-14 106842-01 Ignitor Electrode 1 14 099066-01 Mounting Bracket 1 15 100537-02 Regulator Bracket 1 16 098325-01 Roll Pin 1 17 097159-04 Piezo Ignitor, Snap-in 1 18 098271-03 Ignitor Cable 1
103351
PARTS AVAILABLE - NOT SHOWN
100822-01 Control Position Label 1 100642-01 Hardware Assembly 1
19
Page 20
®
13-1
13-2
13-6
13-3
13-9
13-4
13-5
13-6
13-7
13-8
13-10
13-10
13-12
13-13
13-11
INFRARED PROPANE/LP GAS HEATER
ILLUSTRATED PARTS BREAKDOWN
VP2600E
3
11
17
17
12
14
6
10
4
13
5
8
6
15
9
7
16
2
1
13-14 13-15
ODS/PILOT BURNER ASSEMBLY
20
103351
Page 21
OWNER’S MANUAL
PARTS LIST
VP2600E
This list contains replaceable parts used in your heater. When ordering parts, follow the instructions listed under Replacement Parts on page 17 of this manual.
KEY PART NO. NUMBER DESCRIPTION QTY.
1 098304-01 Screw, #10 x 3/8" 2 2 098742-14 Front Panel 1 3 098238-07 Grill Guard 1 4 101108-01 Clip-Grill Guard 2 5 098198-04 Apron 1 6 M11084-26 Screw, #10 x 3/8" 9 7 098462-01 Control Rod Assembly 1 8 098457-02 Reflector Assembly 1 9 099415-09 Regulator 1 10 098303-02 Screw, #6 x 3/8" 2 11 098456-06 Cabinet Assembly 1 12 098324-01 Control Knob 1 13 See Detail Burner Assembly 1 13-1 099218-07 Burner 1 13-2 098508-01 Valve Retainer Nut 1 13-3 099056-01 Injector-Plaque B 1 13-4 103353-01 Tubing-Valve to Plaque A 1 13-5 103353-02 Tubing-Valve to Plaque B 1 13-6 099056-25 Injectors-Plaques A and C 2 13-7 103353-03 Tubing-Valve to Plaque C 1 13-8 100747-01 Control Valve 1 13-9 099051-02 Inlet Tubing 1 13-10 099044-01 Pilot Tubing-Valve to Pilot 1 13-11 103594-02 ODS/Pilot 1 13-12 M11084-37 Screw, #8 x 1/4" 5 13-13 M11084-26 Screw, #10 x 3/8" 2 13-14 098593-01 Thermocouple 1 13-15 106842-01 Ignitor Electrode 1 14 099066-01 Mounting Bracket 1 15 100537-02 Regulator Bracket 1 16 098325-01 Roll Pin 1 17 097159-04 Piezo Ignitor, Snap-in 1 18 098271-03 Ignitor Cable 1
103351
PARTS AVAILABLE - NOT SHOWN
100822-01 Control Position Label 1 100642-01 Hardware Assembly
21
Page 22
®
INFRARED PROPANE/LP GAS HEATER
ACCESSORIES
Purchase these heater accessories from your local dealer. If they can not supply these accessories, call DESA International’s Parts Department at 1-800-972-7879 or write to the address listed on the back page of this manual for referral information.
FAN KITS - GA3100(A,B) AND GA3200T(A,B)
FLOOR MOUNTING STAND
Models VP1600E - GA4000B Models VP2600E - GA4010B
For locating heater on the floor, away from a wall. Complete installation instructions provided with floor mounting stand.
EQUIPMENT SHUTOFF VALVE GA5010
For all models. Equipment shutoff valve with 1/8" NPT tap.
For all models. Provides better heat distribu­tion. Makes heater more efficient. Complete installation and operating instructions included.
Manually-controlled - GA3100(A,B). In­cludes ON/OFF switch.
Thermostatically-controlled - GA3200T(A,B). Includes three settings: ON/OFF/AUTO.
22
103351
Page 23
OWNER’S MANUAL
NOTES
_______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________
103351
23
Page 24
WARRANTY INFORMATION
KEEP THIS WARRANTY
Model Serial No. Date Purchased
Always specify model and serial numbers when communicating with the factory. We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written warranty.
We make no other warranty, expressed or implied.
LIMITED WARRANTY
VANGUARD VENT-FREE PROPANE/LP GAS HEATERS
DESA International warrants this product to be free from defects in materials and components for four (4) years from the date of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this heater to proper operating condition and an allowance for labor when provided by a DESA Authorized Service Center. Warranty part(s) MUST be obtained through authorized dealers of this product and/or DESA International who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO FOUR (4) YEARS ON ALL COMPONENTS FROM THE DATE OF FIRST PURCHASE; AND DESA INTERNATIONAL’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND DESA INTERNA­TIONAL SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state. For information about this warranty write:
INTERNATIONAL
2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004
www.desatech.com
Patent Pending
103351 01
NOT A UPC
103351-01 REV. D
02/00
Loading...