WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
— Installation and service must be performed by a quali-
fied installer, service agency or the gas supplier.
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation
and operational procedures. For assistance or additional information consult a qualified installer, service
agency or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses
air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must
be provided. Refer to Air for Combustion and Ventilation
section on page 5 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where
not prohibited by local codes.
This appliance is only for use with the type of gas indi
cated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the
Commonwealth of Massachusetts.
Sellers of unvented propane or natural gas-fired supplemental room heaters shall provide to each
purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the Common
wealth of Massachusetts.
TABLE OF CONTENTS
Safety Information ............................................... 3
Local Codes ........................................................ 4
Parts Centrals .................................................... 31
Warranty Information ...........................
Back Cover
-
-
20
24
25
2
www.desatech.com
114683-01B
SAFETY INFORMATION
IMPORTANT: Read this owner’s
manual carefully and completely
be fore tr ying to assemb le,
operate or service this heater.
Improper use of this heater can
cause serious injury or death
from burns, fire, explosion,
electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of carbon
monoxide poisoning resemble the flu, with head
aches, dizziness or nausea. If you have these signs,
the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people
are more affected by carbon monoxide than others.
These include pregnant women, people with heart
or lung disease or anemia, those under the influence
of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and propane/
LP gases are fuel gases. Fuel gases are odorless. An
odor-making agent are added to fuel gases. The odor
helps you detect a fuel gas leak. However, the odor
added to fuel gas can fade. Fuel gas may be present
even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your
guide to safe and proper operation of this heater.
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not use a
blower insert, heat exchanger
insert or other accessory not approved for use with this heater.
Due to high temperatures, the
appliance should be located out
of traffic and away from furniture
and draperies.
Do not place clothing or other
flammable material on or near
the appliance. Never place any
objects on the heater.
Surface of heater becomes very
hot when running heater. Keep
children and adults away from
hot surface to avoid burns or
clothing ignition. Heater will
remain hot for a time after shutdown. Allow surface to cool
before touching.
Carefully supervise young chil-
-
dren when they are in the same
room with heater.
Make sure grill guard is in place
before running heater.
Keep the appliance area clear
and free from combustible ma
terials, gasoline and other flam
mable vapors and liquids.
1. This appliance is only for use with the type of
gas indicated on the rating plate. This appliance
is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) in
side any structure. Locate propane/LP supply
tank(s) outdoors.
3. This heater shall not be installed in a bedroom
or bathroom.
4. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use
any phone in your building
• immediately call your gas supplier from a
neighborʼs phone. Follow the gas supplierʼs
instructions
• if you cannot reach your gas supplier, call
the fire department
5. This heater needs fresh, outside air ventilation
to run properly. This heater has an Oxygen
Depletion Sensing (ODS) safety shutoff
system. The ODS shuts down the heater if
not enough fresh air is available. See Air for
Combustion and Ventilation,
page 5.
-
-
-
114683-01B3
www.desatech.com
SAFETY INFORMATION
Continued
6. Keep all air openings in front and bottom of
heater clear and free of debris. This will insure
enough air for proper combustion.
7. If heater shuts off, do not relight until you
provide fresh, outside air. If heater keeps
shutting off, have it serviced.
8. Do not run heater
• where flammable liquids or vapors are used
or stored
• under dusty conditions
9. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off. If
heated, the vapors from these products may
create a white powder residue within burner
box or on adjacent walls or furniture.
10. Do not use heater if any part has been under
water. Immediately call a qualified service
technician to inspect the room heater and to
replace any part of the control system and any
gas control which has been under water.
11. Turn off and let cool before servicing. Only
a qualified service person should service and
repair heater.
12. Operating heater above elevations of 4,500
feet could cause pilot outage.
13. To prevent performance problems, do not
use propane/LP fuel tank of less than 100
lbs. capacity.
14. Prov ide adequa te clearance s around air
openings.
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of local codes, use the
latest edition of National Fuel Gas Code, ANSI
Z223.1/NFPA 54
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
*.
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
PRODUCT
IDENTIFICATION
Heater
Cabinet
Front Panel
Ignitor Button
Figure 1 - Vent-Free Gas Heater
Control Knob
Grill Guard
Heat Shield
UNPACKING
1. Remove heater from carton.
2. Remove all protective packaging applied to
heater for shipment.
3. Check heater for any shipping damage. If
heater is damaged, promptly inform dealer
where you bought heater.
PRODUCT FEATURES
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free room
heaters. The ODS/pilot shuts off the heater if there
is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater has a piezo ignitor. This system requires no matches, batteries or other sources to
light heater.
THERMOSTATIC HEAT CONTROL
Thermostat models have a thermostat sensing
bulb and a control valve. This results in the great
est heater comfort. This can also result in lower
gas bills.
-
4
www.desatech.com
114683-01B
AIR FOR COMBUSTION
AND VENTILATION
WARNING: This heater shall
not be installed in a confined
space or unusually tight construction unless provisions are
provided for adequate combustion and ventilation air. Read the
following instructions to insure
proper fresh air for this and
other fuel-burning appliances
in your home.
Todayʼs homes are built more energy efficient
than ever. New materials, increased insulation and
new construction methods help reduce heat loss
in homes. Home owners weather strip and caulk
around windows and doors to keep the cold air out
and the warm air in. During heating months, home
owners want their homes as airtight as possible.
While it is good to make your home energy effi
cient, your home needs to breathe. Fresh air must
enter your home. All fuel-burning appliances need
fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers and fuel
burning appliances draw air from the house to
operate. You must provide adequate fresh air for
these appliances. This will insure proper venting
of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3,
Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol
lowing ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
The information on pages 5 through 7 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion and
ventilation. However, in buildings of unusually
tight construction, you must provide additional
fresh air.
Unusually tight construction is defined as
construction where:
a. walls and ceilings exposed to the out
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6x10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and floors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh
air. See Ventilation Air From Outdoors
page 7.
If your home does not meet all of the three
criteria above, proceed to Determining Fresh-
-
Air Flow For Heater Location, page 6.
Confined and Unconfined Space
The National Fuel G as Code, ANSI Z223. 1/
NFPA 54 defines a confined space as a space whose
volume is less than 50 cubic feet per 1,000 Btu
per hour (4.8 m
rating of all appliances installed in that space and
an unconfined space as a space whose volume is
not less than 50 cubic feet per 1,000 Btu per hour
3
(4.8 m
per kw) of the aggregate input rating of
all appliances installed in that space. Rooms com
municating directly with the space in which the
appliances are installed*, through openings not
furnished with doors, are considered a part of the
unconfined space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation grills
between them.
-11
kg per pa-sec-m2) or
3
per kw) of the aggregate input
-
,
-
114683-01B5
www.desatech.com
AIR FOR COMBUSTION
AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install
heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x
width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume
of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
_______ (volume of space) x 20 = (Maximum
Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in
the space.
Vent-free heater ______________
Gas water heater* ______________
Gas furnace ______________
Vented gas heater ______________
Gas fireplace logs ______________
Other gas appliances* + __________
Total = __________
* Do not include direct-vent gas appliances. Di
rect-vent draws combustion air from the outdoors
and vents to the outdoors.
Example: Gas water heater ______________
Vent-free heater + _____________
Total = _____________
40,000
30,000
70,000
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
4. Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
_______________Btu/Hr (maximum the space
can support)
_______________Btu/Hr (actual amount of
Btu/Hr used)
Example:51,200 Btu/Hr (maximum the space can support)
70,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space
because the actual Btu/Hr used is more than the maxi
mum Btu/Hr the space can support. You must provide
additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin
ing room. If the extra space provides an unconfined
space, remove door to adjoining room or add
ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.
B. Vent room directly to the outdoors. See Ventila
tion Air From Outdoors, page 7.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size
makes room unconfined.
If the actual Btu/Hr used is less than the maximum
Btu/Hr the space can support,
fined space. You will need no additional fresh air
ventilation.
the space is an uncon-
WARNING: If the area in
which the heater may be oper
ated is smaller than that defined
as an unconfined space or if the
building is of unusually tight
construction, provide adequate
combustion and ventilation air
by one of the methods described
in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section 5.3
or applicable local codes.
-
-
-
-
-
6
www.desatech.com
114683-01B
Or
Remove
Door into
Adjoining
Room,
Option 3
Ventilation Grills
Into Adjoining Room,
Option
2
12"
12"
Ventilation
Grills
into Adjoining
Room,
Option 1
Outlet
Air
Ve
ntilated
Attic
Outlet
A
ir
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
AIR FOR COMBUSTION
AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un
confined space. When ventilating to an adjoining
unconfined space, you must provide two permanent openings: one within 12” of the ceiling and
one within 12” of the floor on the wall connecting
the two spaces (see options 1 and 2, Figure 2). You
can also remove door into adjoining room (see
option 3, Figure 2). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for
Combustion and Ventilation for required size of
ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or
ducts. You must provide two permanent openings:
one within 12” of the ceiling and one within 12”
of the floor. Connect these items directly to the
outdoors or spaces open to the outdoors. These
spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
Section 5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet
or outlet air into attic if attic has a thermostatcontrolled power vent. Heated air entering the attic
will activate the power vent.
-
Figure 3 - Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your pri
mary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualified service person must install heater.
Follow all local codes.
-
CHECK GAS TYPE
Use only the correct type of gas (natural or propane/LP). If your gas supply is not the correct gas
type, do not install heater. Call dealer where you
bought heater for proper type heater.
WARNING: This appliance
is equipped for (natural or pro
pane/LP) gas. Field conversion
Figure 2 - Ventilation Air from Inside
114683-01B7
Building
www.desatech.com
is not permitted.
-
INSTALLATION
Minimum
From
Sides Of
Heater
36"
14"
FLOOR
CEILING
Minimum
Minimum To
To
p Surface
Of Carpeting,
Ti
le Or Other
Combustible
Material
Left
Side
Right
Side
6"
Continued
INSTALLATION ITEMS
Before installing heater, make sure you have the
items listed below.
• for propane/LP gas, external regulator (supplied
by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• ground joint union
• sediment trap
• tee joint
• pipe wrench
• for natural gas, test gauge connection*
* A CSA design-certified equipment shutoff valve
with 1/8" NPT tap is an acceptable alternative to
test gauge connection. The optional CSA designcertified equipment shutoff valve can be purchased
from your dealer. See
LOCATING HEATER
This heater is designed to be mounted on a wall.
WARNING: Maintain the
minimum clearances shown
in Figure 4. If you can, provide
greater clearances from floor,
ceiling and joining wall.
You can locate heater on floor, away from a wall.
An optional floor mounting stand is needed. Pur
chase the floor mounting stand from your dealer.
See Accessories, page 30.
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture,
clothing or other flammable
objects are less than 36 inches
from the front, top or sides of
the heater
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
8
Accessories, page 30.
CAUTION: This heater creates warm air currents. These
currents move heat to wall surfaces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as, but
not limited to, tobacco smoke,
aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
IMPORTANT: Vent-free heaters add moisture to
the air. Although this is beneficial, installing heater
in rooms without enough ventilation air may cause
mildew to form from too much moisture. See Air for Combustion and Ventilation, page 5. If high hu
midity is experienced, a dehumidifier may be used
to help lower the water vapor content in the air.
CAUTION: When installing
heater in a home garage
• heater pilot and burner must be
at least 18 inches above floor
• locate heater where moving
vehicle will not hit it
For convenience and efficiency, install heater
• where there is easy access for operation, inspec
tion and service
-
• in coldest part of room
An optional fan kit is available from your dealer.
See Accessories, page 30. If planning to use fan,
locate heater near an electrical outlet.
Figure 4 - Mounting Clearances As
Viewed From Front of Heater
www.desatech.com
-
-
114683-01B
INSTALLATION
Continued
THERMOSTAT SENSING BULB
(Thermostat Models Only)
The thermostat sensing bulb has been placed
below the heater.
1. Place clamp on thermostat sensing bulb as
shown in Figure 5. Clamp is provided in
hardware package.
2. Snap clamp into upper mounting hole as shown
in Figure 5. Mounting hole is located on lower
left edge on back of heater. Make sure the
thermostat sensing bulb is pointing up.
Clamp
Thermostat
Sensing Bulb
Figure 5 - Attaching Thermostat Sensing
Bulb
INSTALLING HEATER TO WALL
Mounting Bracket
Locate mounting bracket in heater carton. Remove
mounting bracket from heater carton.
Figure 7 - Removing Front Panel Of
Heater
Methods For Attaching Mounting Bracket
To Wall
Only use last hole on each end of mounting bracket
to attach bracket to wall. These two holes are 14
inches apart from their centers. Attach mounting
bracket to wall in one of two ways:
1. Attaching to wall stud
2. Attaching to wall anchor
Attaching to Wall Stud: This method provides the
strongest hold. Insert mounting screws through
mounting bracket and into wall studs.
Attaching to Wall Anchor: This method allows you
to attach mounting bracket to hollow walls (wall
areas between studs) or to solid walls (concrete
or masonry).
Decide which method better suits your needs.
Either method will provide a secure hold for the
mounting bracket.
Marking Screw Locations
1. Tape mounting bracket to wall where heater
will be located. Make sure mounting bracket
is level.
Figure 6 - Mounting Bracket
WARNING: Maintain mini-
mum clearances shown in Figure
Removing Front Panel Of Heater
1. Remove the four painted screws, two on each
side of front panel.
2. Pull bottom of front panel forward, then out.
3. Remove any remaining packaging materials.
114683-01B9
www.desatech.com
8, page 10. If you can, provide
greater clearances from floor
and joining wall.
INSTALLATION
32"
Min.
12"
Min.
14"
Ad j o inin g Wa l l
Only Insert Mounting
Screws Through Last
Hole On Each End
Floor
Continued
2. Mark screw locations on wall (see Figure 8).
Note: Only mark last hole on each end of
mounting bracket. Insert mounting screws
through these holes only.
3. Remove tape and mounting bracket from
Figure 8 - Mounting Bracket Clearances
Attaching Mounting Bracket To Wall
Note: Wall anchors, mounting screws and spacers
are in hardware package. The hardware package
is provided with heater.
Attaching To Wall Stud Method
For attaching mounting bracket to wall studs
1. Drill holes at marked locations using 9/64"
drill bit.
2. Place mounting bracket onto wall. Line up last
hole on each end of bracket with holes drilled
in wall.
3. Insert mounting screws through bracket and
into wall studs.
4. Tighten screws until mounting bracket is
firmly fastened to wall studs.
Attaching To Wall Anchor Method
For attaching mounting bracket to hollow walls
(wall areas between studs) or solid walls (concrete
or masonry)
1. Drill holes at marked locations using 5/16"
drill bit. For solid walls (concrete or masonry),
drill at least 1" deep.
2. Fold wall anchor as shown in Figure 9.
3. Insert wall anchor (wings first) into hole. Tap
anchor flush to wall.
4. For thin walls (1/2" or less), insert red key
into wall anchor. Push red key to “pop” open
anchor wings. IMPORTANT: Do not hammer
key! For thick walls (over 1/2" thick) or solid
walls, do not pop open wings.
5. Place mounting bracket onto wall. Line up
last hole on each end of bracket with wall
anchors.
6. Insert mounting screws through bracket and
into wall anchors.
7. Tighten screws until mounting bracket is
firmly fastened to wall.
Figure 9 - Folding
Anchor
Figure 10 - Popping
Open Anchor Wings
For Thin Walls
Placing Heater On Mounting Bracket
1. Locate two horizontal slots on back panel of
heater.
2. Place heater onto mounting bracket. Slide
horizontal slots onto stand-out tabs on mount
ing bracket.
Horizontal Slots
-
StandOut Tab
Mounting Bracket
(attached to wall)
10
www.desatech.com
Figure 11 - Mounting Heater Onto
Mounting Bracket
114683-01B