Desa BDV34NA, BDV34PA User Manual

®
DIRECT-VENT FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
®
BDV34N(A) AND BDV34P(A)
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
FOR YOUR SAFETY WHAT TO DO IF YOU SMELL GAS
• Do not touch any electrical switch
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes. * Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
WARNING: Improper instal­lation, adjustment, altera­tion, service, or mainte­nance can cause injury or property damage. Refer to this manual for correct in­stallation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
— Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
Save this manual for future reference.
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
SAFETY INFORMATION
WARNINGS
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, oper­ate, or service this fireplace. Im­proper use of this fireplace can cause serious injury or death from burns, fire, explosions, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
This fireplace is a vented product. This fireplace will not produce any gas leakage into your home if properly installed. This fireplace must be properly installed by a qualified service person. The glass door must be properly seated and sealed. If this unit is not properly installed by a qualified service person with glass door properly seated and sealed, gas leakage can occur.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the fireplace may not have been installed properly. Get fresh air at once! Have fireplace inspected and ser­viced by a qualified service person. Some people are more affected by carbon monox­ide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Propane gas and natural gas are both odor­less. An odor-making agent is added to each of these gases. The odor helps you detect a gas leak. However, the odor added to these gases can fade. Gas may be present even though no odor exists.
Make certain you read and understand all Warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.
WARNING: Any change to this fireplace or its controls can be dangerous.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.
2. For propane fireplace, do not place pro­pane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors. To prevent perfor­mance problems, do not use propane fuel tank of less than 100 lbs. capacity .
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do
not use any phone in your building
• immediately call your gas supplier
from a neighbor’s phone. F ollow the gas supplier’s instructions
• if you cannot reach you gas supplier ,
call the fire department.
4. Never install the fireplace
• in a recreational vehicle
• where curtains, furniture, clothing, or
other flammable objects are less than 42" from the front, top, or sides of the fireplace
• in high traffic areas
• in windy or drafty areas
5. This fireplace reaches high tempera­tures. Keep children and adults away from hot surfaces to avoid b urns or cloth­ing ignition. Fireplace will remain hot for a time after shut-down. Allow sur­faces to cool before touching.
6. Carefully supervise young children when they are in the room with fireplace.
7. Do not modify this fireplace under any circumstances. Any parts removed for servicing must be replaced prior to op­erating fireplace.
8. Turn fireplace off and let cool before servicing, installing, or repairing. Only a qualified service person should in­stall, service, or repair this fireplace. Have fireplace inspected annually by a qualified service person.
9. You must keep control compartments, burners, and circulating air passages clean. More frequent cleaning may be needed due to excessive lint and dust from carpeting, bedding material, pet hair, etc. Turn off the gas valv e and pi­lot light before cleaning fireplace.
10. Have venting system inspected annu­ally by a qualified service person. If needed, have venting system cleaned or repaired. See Cleaning and Mainte- nance, page 26.
11. Keep the area around your fireplace clear of combustible materials, gaso­line, and other flammable vapor and liquids. Do not run fireplace where these are used or stored. Do not place items such as clothing or decorations on or around fireplace.
12. Do not use this fireplace to cook food or burn paper or other objects.
13. Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this fireplace. Use only the gas type indicated on fire­place nameplate.
14. This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electri-
cal Code, ANS/NFPA 70, or the Cana­dian Electrical Code, CSA C22.1.
15. Do not obstruct the flow of combus­tion and ventilation air in any way . Pro­vide adequate clearances around air openings into the combustion chamber along with adequate accessibility clear­ance for servicing and proper operation.
16. Do not install fireplace directly on car­peting, vinyl tile, or any combustible material other than wood. The fireplace must set on a metal or wood panel ex­tending the full width and depth of the fireplace.
17. Do not use fireplace if any part has been exposed to or under water . Immediately call a qualified service person to ar­range for replacement of the unit.
18. Do not operate fireplace if any log is broken.
19. Do not use a blower insert, heat ex­changer insert, or other accessory not approved for use with this fireplace.
20. Do not operate fireplace with glass door removed, cracked, or broken. Do not op­erate fireplace without screen in place.
2
105453
OWNER’S MANUAL
PRODUCT IDENTIFICATION
Top Louver Panel
Nailing Flange
Glass Door Assembly
Lower Louver Panel
Piezo Ignitor
Valve
Glowing Embers
Blower Adjustment (Optional Installation)
Figure 1 - Vanguard Direct-Vent Fireplace BDV Series
Vent Opening
Stand-off
Log Set Pilot Assembly
Burner
Grate Assembly
Lava Rock
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the absence to local codes, use the current National Fuel Gas Code ANS Z223.1, also known as NFPA 54* (USA) or the current CAN/CGA-B149[.1 or .2] Installation Codes (Canada).
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
PRODUCT FEATURES
OPERATION
This direct-vent fireplace is clean burning and vents easily through outside walls or vertically using outside air for combustion. Heat is generated by both realistic flames and glowing embers. When used without the blower accessory, the fireplace requires no electricity making it ideal for emergency backup heat.
PIEZO IGNITOR
This fireplace has a piezo ignitor. This sys­tem requires no matches, batteries, or other sources to light fireplace.
GLOSSARY OF TERMS
Chase - A box-like enclosure to protect venting from the elements when the venting run is on the outside of a structure.
Mastic - A pliable sealent for use around the vent terminal.
Snorkel Termination - A box that raises the horizontal termination above ground level clearances.
Vent Terminal - Mounted on an outside wall or roof to separate the inlet and outlet of the vent system and protect it from weather.
Vinyl Siding Standoff - A metal box that separates the vent cap from vinyl siding.
Wall Thimble/Firestop - A metal plate used to secure the vent pipe when it passes through a wall or ceiling.
105453
3
®
20"
34
3
/
4
"
5/8" for drywall facing
Must maintain a minimum 1" clearance to combustibles
D
RW
FW
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
PRE-INSTALLATION PREPARATION
LOCATION AND SPACE REQUIREMENTS
Determine the safest and most efficient loca­tion for your Vanguard direct-vent fireplace. Make sure that rafters and wall studs are not in the way of the venting system. Choose a location where the heat output is not affected by drafts, air conditioning ducts, windows or doors. Figure 2 shows some common loca­tions. Read all venting information in this manual. Be aware of all restrictions and precautions before deciding the exact loca­tion for your fireplace.
When deciding the location of your fire­place, follow these rules:
1. Do not connect this fireplace to a chim­ney flue serving a separate solid-fuel burning fireplace or appliance.
2. Due to high temperatures, do not lo­cate this fireplace in high traffic areas or near furniture or draperies.
3. Proper clearances must be maintained.
4. If your fireplace is to be installed di­rectly on carpeting, vinyl tile, or any combustible material other than wood, it must be installed on a metal or wood panel extending the full width and depth of the fireplace. See Figure 3.
CLEARANCES
Minimum clearances to combustibles for the fireplace are as follows:
Back, and sides 0"/mm Perpendicular walls 6" (152mm) Floor 0"/mm Ceiling to louver opening 42" (1067mm) Front 36" (914mm) Top of Standoffs 0"/mm
See General Venting on pages 5 and 6 for specific venting clearances.
FRAMING AND FINISHING
Figures 4 and 5 show typical framing of this fireplace. Figure 6 on page 5 shows framing for corner installation. All minimum clear­ances must be met. Do not install fireplace directly on carpeting, vinyl tile, or any com­bustible material other than wood. The fire­place must set on a metal or wood panel extending the full width and depth of the fireplace.
See Accessories on pages 32 and 33 for mantel kits available for this fireplace. If you are using a separate combustible mantel piece, refer to Figure 7 on page 5 for proper instal­lation height. You can install noncombustible mantels at any height above the fireplace.
Figure 5 - Framing Clearances for Typical Fireplace Installation
Through exterior wall enclosed in a chase
Figure 2 - Common Fireplace Locations
Fireplace size D x FW x RW
34" 18 1/2" 34" 14"
Figure 3 - Fireplace Bottom Dimensions
Flush with a wall
Corner installation
3
34
/4"
34 1/2"
20" Vertical Termination 19" Horizontal Termination
Figure 4 - Framing Clearances for Installation Against an Exterior Wall
4
105453
OWNER’S MANUAL
PRE-INSTALLA TION PREPARA TION
Continued
13"
29"
5
/8"
12
34
58"
Figure 6 - Framing Clearances for Corner Installation
A
B
C
1
9
/4"
1
/4"
3
/4"
34
D
E
F
G
GENERAL VENTING
These models are approved for use with Simpson Dura-Vent 6 5/8" direct-vent pipe components and terminations as well as both flex and rigid Vanguard vent components.
Your fireplace is approved to be vented either
41"
Nailing Tabs
1 2
3
4
5 6 7
Wall
through the side wall, or vertically using the following guidelines:
• Only use Vanguard or Simpson Dura­V ent GS venting components or kits spe­cifically approved for this fireplace.
• Minimum clearance between vent pipes and combustible materials is 1" (25 mm), except where stated otherwise.
• Combustible material may be flush with the top front of fireplace with a maxi­mum thickness of 3/4".
• Do not recess venting terminals into a wall or siding.
• Install horizontal venting with a 1/4" rise for every 12" of run to war d the termina­tion.
• You may paint the vent terminal with 450ºF (232ºC) heat-resistant paint to co­ordinate with the exterior finish.
• There must not be any obstruction such as bushes, garden sheds, fences, decks, or utility buildings within 24" from the front of the termination cap.
• Do not locate termination cap where ex­cessive snow or ice build up may occur. Be sure to clear vent termination area af­ter snow falls to prev ent accidental block­age of venting system. When using sno w blowers, do not direct snow to wards vent termination area.
Top of Louver Opening
Ref. Mantel Depth Ref. Mantel from Top
of Louver Opening 1 14" (356mm) A 16" (406mm) 2 12" (305mm) B 14" (356mm) 3 10" (254mm) C 12" (305mm) 4 8" (203mm) D 10" (254mm) 5 6" (152mm) E 8" (203mm) 6 4" (101mm) F 6" (152mm) 7 2" (51mm) G 4" (101mm)
Figure 7 - Clearances for Combustible Mantels
105453
LOCATION OF VENT TERMINATION
When locating vent termination, it is impor­tant to observe the minimum clearances shown in Figure 8, page 6. You will avoid extra framing by positioning your fireplace against an already existing framing mem­ber. The sides of the fireplace may be posi­tioned directly against combustible walls.
*Check with local codes or with the current
CAN/CGA B149[.1 or .2] Installation Codes
for Canada or the USA Installations follow the current National Fuel Gas Code, ANS Z223.1, also known as NFPA 54.
5
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
GENERAL VENTING
D
E
V
B
L
V
A = clearance above grade, veranda, porch, deck, or balcony
[*12 inches (305mm) minimum]
B = clearance to window or door that may be opened
[12 inches (305mm) minimum]
C = clearance to permanently closed window [minimum 12 inches
(305mm) recommended to prevent condensation on window]
D = vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 24 inches (610mm) from the
center-line of the terminal [18 inches (457mm) minimum] E = clearance to unventilated soffit [12 inches (305mm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within
36 inches (914mm) horizontally from the center-line of the regulator
† vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings* ‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/SGA B149 (.1 or .2) Installation Codes (1991) for Canada or for U.S.A. installation follow
the current Note: Local codes or regulations may require different clearances
C
F
V
B
TERMINATION CAP
National Fuel Gas Code, ANS Z223.1
Continued
Fixed
Closed
Openable
V
Openable
B
AIR SUPPLY INLET
X
B
Fixed
Closed
J
V A
X
I = clearance to service regulator vent outlet [*72 inches (1829mm)
minimum]
J = clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other fireplace [*12 inches (305mm) minimum]
K = clearance to a mechanical air supply inlet [*72 inches (1829mm)
minimum]
L = † clearance above paved side-walk or a paved driveway located on
public property [*84 inches (2133mm) minimum] M = clearance under veranda, porch, deck [*12 inches (305mm) minimum ‡] N = clearance above a roof shall extend a minimum of 24 inches (610mm)
above the highest point when it passes through the roof surface and
any other obstruction within a horizontal distance of 18 inches (457mm)
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Inside Corner
Outside Corner Recessed Location
N
H
V
B
G
G
GAS METER RESTRICTED AREA
I
M
V
(TERMINATION PROHIBITED)
N
G
V
G
X
K
V
A
A
Balcony with No Side Wall
G = Combustible 24" (610mm)
Noncombustible 18" (457mm)
V
G V
A = 6" (152mm)
V
Balcony with Perpendicular Side Wall
H
Combustible & Noncombustible H = 24" (610mm) J = 20" (508mm)
Figure 8 - Minimum Clearances for Vent Terminations
B
V
J
B = 6" (152mm)
6
D
C
V
C = Maximum depth of 48" (1219mm) for
recessed location
D = Minimum width for back wall of
recessed location ­Combustible - 38" (965mm) Noncombustible - 24" (610mm)
E = Clearance from corner in
recessed location­Combustible - 6" (152mm) Noncombustible - 2" (51mm)
C
E
105453
OWNER’S MANUAL
VENTING INSTALLATION
WARNING: Read all instruc­tions completely and thoroughly before attempting installation. Failure to do so could result in serious injury, property damage or loss of life. Operation of im­properly installed and maintained venting system could result in serious injury, property damage or loss of life.
WARNING: Seal all of the con­nections with high temperature silicone (600°F/316° C) every time a vent connection is made. Be­fore joining elbows and pipes, apply a bead of high temperature silicone sealant (GE RTV 106/ Loctite RTV 81585) to the end of the elbow or pipe. High tempera­ture silicone must also be used to re-seal any connections after maintenance to venting system.
NOTICE: Failure to follow these instructions will void the warranty.
INSTALLATION PRECAUTIONS
Consult local building codes before beginning the installation. The installer must make sure to select the proper vent system for installa­tion. Before installing vent kit, the installer must read this fireplace manual and vent kit instructions.
Only a qualified service person should in­stall venting system. The installer must fol­low these safety rules:
• Wear gloves and safety glasses for protection
• Use extreme caution when using ladders or when on roof tops
• Be aware of electrical wiring locations in walls and ceilings
The following actions will void the war­ranty on your venting system:
• Installation of any damaged venting component
• Unauthorized modification of the vent­ing system
• Installation of any component part not manufactured or approved by DESA International
• Installation other than as instructed by these instructions
WARNING: This gas fireplace and vent assembly must be vented directly to the outside. The venting system must NEVER be attached to a chimney serving a separate solid fuel burning ap­pliance. Each gas appliance must use a separate vent system. Do not use common vent systems.
WARNING: Horizontal sec­tions of this vent system require a minimum clearance of 2" from the top of the pipe and 1" mini­mum to the sides and bottom. Vertical sections of this system require a minimum of 1" clear­ance to combustible materials on all sides of the pipe.
INSTALLATION PLANNING
There are two basic types of direct-vent installation:
• Horizontal T er mination
• Vertical Termination It is important to select the proper length of
vent pipe for the type of termination you choose. It is also important to note the wall thickness.
For Horizontal Termination: Select the amount of vertical rise desired. The horizon­tal run of venting must have 1/4" rise for every 12" of run towards the termination.
WARNING: Never run the vent downward as this may cause ex­cessive temperatures which could cause a fire.
You may use one or two 90° elbows in this vent configuration. See Horizontal Termina- tion Configurations on pages 10 and 11.
For Vertical Termination: Measure the distance from the fireplace flue outlet to the ceiling. Add the ceiling thickness, the verti­cal rise in an attic or second story, and allow for sufficient vent height above the roofline.
You may use one or two 90° elbows in this vent configuration. See Vertical Termination Configurations on pages 13 through 15.
Note:
You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when using 45° elbows.
For two-story applications, firestops are re­quired at each floor level. If an offset is needed in the attic, additional pipe and el­bows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house. See Installing Vent System in a Chase, below.
Your Vanguard direct-vent fireplace has been tested for a minimum 3' rise with a maximum 10" wall thickness. The maxi­mum horizontal run is 20' with 8' vertical rise (see Installation for Horizontal Termi- nation, page 8). The maximum vertical run is 30' (see Installation for Vertical Termina- tion, page 12).
It is very important that the venting system maintain its balance between the combus­tion air intake and the flue gas exhaust. Certain limitations apply to vent configura­tions and must be strictly followed.
Installing Vent System in a Chase
A chase is a vertical box-like structure built to enclose venting that runs along the out­side of a building. A chase is not required for such venting.
NOTICE: Treatment of firestops and construction of the chase may vary from building type to build­ing type. These instructions are not substitutes for the require­ments of local building codes. You must follow all local building codes.
Note:
When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially im­portant in cold climates. Minimum clear­ance between vent pipes and combustible materials such as insulation is 1".
After framing the chase (see Framing and Finishing on page 4) install the vent system by following the installation instructions.
Continued
105453
7
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
VENTING INSTALLATION
Continued
INSTALLATION FOR HORIZONTAL TERMINATION
1. Determine the route your horizontal venting will take. of the horizontal vent termination on the exterior wall must meet all local and national building codes and must not be easily blocked or obstructed.
WARNING: Do not recess vent
terminal into a wall or siding.
Snorkel terminations are available for terminations requiring a vertical rise on the exterior of the building (see Figures 9 and 10). Snorkel kit SVK is also avail­able (see page 15). Follow the same in­stallation procedures used for standard horizontal terminations. If installing the snorkel termination below grade (base­ment applications), you must provide proper drainage to prevent water from entering the snorkel termination (see Figure 10). Do not back fill around the snorkel termination.
2. Rigid vent pipes and fittings have spe­cial twist-lock connections. Assemble the desired combination of pipe and el­bows to the appliance adaptor with pipe seams oriented towards the wall or floor .
Twist-lock Procedure: The female ends of the pipes and fittings have four locking lugs (indentations). These lugs will slide straight into matching slots on the male ends of adjacent pipes and fit­tings. (All connections must be sealed with high temperature silicone sealant as specified in the second warning state­ment on page 7.) Push the pipe sections together and twist one section clockwise approximately one-quarter turn until the sections are fully locked. See Figure 11, page 9. must be supported every three feet. Use wall straps for this purpose.
Flexible vent pipe must be installed with spacer springs every 12". See Figure 11, page 9. All connections must be clamped tightly and sealed with high temperature silicone sealant as specified in the sec­ond warning statement on page 7.
Note:
Note:
The location
Horizontal runs of vent
Snorkel
12" Minimum To Ground Level
Figure 9 - Snorkel Termination
Snorkel
12" Minimum To Ground Level
Adequate drainage
Figure 10 - Snorkel Termination with Drainage Pipe
8
105453
OWNER’S MANUAL
VENTING INSTALLATION
Continued
3. Attach vent pipe assembly to the fire­place. Set fireplace in front of it’ s per­manent location to insure minimum clearances. Mark the wall for a 10" square hole (for noncombustible ma­terial such as masonry block or con­crete, a 7 1/2" diameter hole is accept­able). See Figure 12. The center of the hole should line up with the center­line of the horizontal rigid vent pipe. Cut a 10"x10" (254mm x 254mm) square hole through combustible ex­terior wall (7 1/2" [190mm] diameter hole if noncombustible). Frame as nec­essary (see Figure 12).
4" Clamp
Female Locking Lugs
Male Slots
7" Clamp
Spacer Spring
4" Flex Pipe
7" Flex Pipe
4. Apply a bead of non-hardening mastic around the outside edge of the vent cap. Position the vent cap in the center of the 7 1/2" or 10" hole on the exterior wall with the arrow on the vent cap pointing up. Insure proper clearance of 1" to combustibles is maintained. At­tach the vent cap with four wood screws supplied (see Figure 13).
Note
: Re­place the wood screws with appropri­ate fasteners for stucco, brick, concrete, or other types of siding.
WARNING: Do not recess vent termination in to any wall. This will cause a fire hazard.
For vinyl siding, stucco, or wood exte­rior use vinyl siding standoffs between vent cap and exterior wall. The vinyl sid­ing standoff prevents e xcessive heat from melting the vinyl siding material. Bolt the vent cap to the standoff. Apply non-hard­ening mastic around outside edge of the standoff instead of the vent cap assem­bly. Use w ood screws pro vided to attach the standoff. See Figure 14.
5. Slide the wall thimble over the vent pipe before connecting the horizontal run to the vent cap (see Figure 15).
6. Carefully move the fireplace with vent assembly attached toward the wall and insert the vent pipe into the horizontal termination. The pipe overlap should be a minimum of 1 1/4". Apply silicone to the connection. Fasten all vent con­nections with screws provided. Refer to Fir eplace Installation on page 16 for instructions on securing unit to fram­ing or floor.
7. Slide the wall thimble against the inte­rior wall surface and attach with screws provided (see Figure 15).
Cut Vinyl Siding Away to Fit Standoff
Wood Screw
Standoff
UP
Nut
Apply Mastic to All Four Sides
Figure 14 - Installing Vinyl Siding Standoff
Vent Cap
Bolt
Rigid Vent Pipe Flexible Vent Pipe
Figure 11 - Vent Pipe Connections
Vent Opening
Combustible Wall
10"
(254mm)
10"
(254mm)
(Framing
Vent Opening
Noncombustible Wall
7 1/2"
(190mm)
Figure 12 - Vent Opening Requirements
105453
Detail)
Apply Mastic to All Four Sides
UP
Wood Screw
Vent Cap
Figure 13 - Installing Horizontal Vent Cap
9
Interior Wall Surface
Wall Thimble
Vent Cap (Horizontal Termination)
Figure 15 - Connecting Vent Cap with Horizontal Vent Pipe
Screw
Horizontal Vent Pipe
Continued
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
VENTING INSTALLATION
Continued
Horizontal Termination Configurations
Figures 16 through 20 show different con­figurations for venting with horizontal ter­mination. Each figure includes a chart with vertical minimum/maximum and horizon­tal maximum dimensions which must be met. All connections must be sealed with high temperature silicone sealant as speci­fied in the second warning statement on page 7. All horizontal terminations require 1/4" rise per 12" of horizontal run.
(30° and 90° only, no vertical pipe)
(30° elbow, 1' vertical pipe, 90° elbow)
Note:
corner installation.
Figure 17 - Horizontal Termination Configuration for Rigid Venting Using One
°
90
Horizontal Venting
Vertical (V) Horizontal (H)
44" min. 29" max.
55" min. 41" max.
67" min. 60" max. 79" min. 84" max. 96" min. 20' max.
This configuration for use with
Elbow
UP
BVK Vent Kit Shown
UP
GFVK Vent Kit Shown (recommended for use with cabinet mantels)
Horizontal Venting
Vertical (V) Horizontal (H)
37" min. 10" max.
Figure 16 - Horizontal Termination Configuration for Rigid Venting
Horizontal Venting
See information in Figures 17 and 18 for Vertical(V) and Horizontal(H) maxi-
UP
mums and minimums. The same amounts apply for flexible venting.
Figure 18 - Horizontal Termination Using Flexible Venting
BFGFVK and FGFVK Vent Kits Shown
10
105453
VENTING INSTALLATION
Continued
Venting with Two 90° Elbows
Vertical (V) Horizontal (H1) Horizontal (H1) +
Horizontal (H2)
5' min. 2' max. 6' max. 6' min. 4' max. 12' max. 7' min. 6' max. 18' max. 8' min. 8' min. 20' max.
20' max. 8' max. 20' max.
OWNER’S MANUAL
UP
Figure 19 - Horizontal Termination Configuration for Rigid Venting Using Two 90° Elbows
Venting with Two 90° Elbows
Vertical (V) Horizontal (H1) +
Horizontal (H2)
5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max.
20' max. 20' max.
Figure 20 - Horizontal Termination Configuration for Rigid Venting Using Two 90
°
Elbows with Termination at 90° with Fireplace
105453
Continued
11
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
VENTING INSTALLATION
Continued
INSTALLATION FOR VERTICAL TERMINATION
1. Determine the route your vertical vent­ing will take. If ceiling joists, roof rafters, or other framing will obstruct the vent­ing system, consider an offset (see Fig­ure 21) to avoid cutting loadbearing members. these installation instructions for re­quired clearances (air space) to combus­tibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of the venting system and any maximum hori­zontal offset limitations. Offsets must fall within the parameters shown in Figure 8 on page 6.
2. Set the fireplace in desired location. Drop a plumb line down from the ceil­ing to the position of the fireplace exit flue. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole at this point.
Drop a plumb line from the inside of the roof to the locating hole in the ceil­ing. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.
Wall Strap
Note:
Pay special attention to
Roof Flashing
Flat Ceiling Installation
1. Cut a 10" square hole in the ceiling us­ing the locating hole as a center point. The opening should be framed to 10"x10" (254mm x 254mm) inside di­mensions, as shown in Figure 12 on page 9 using framing lumber the same size as the ceiling joists. If the area above the ceiling is an insulated ceil­ing or a room, nail firestop from the top side. This prevents loose insulation from falling into the required clearance space. Otherwise, install firestop below the framed hole. The firestop should be installed with no less than three nails per side (see Figure 22).
2. Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop. All connections must be sealed with high temperature silicone sealant as specified in the second warning state­ment on page 7. Be sure all pipe and elbow connections are fully twist­locked (see Figure 11, page 9).
3. Cut a hole in the roof using the locating hole as a center point. (Cover any ex­posed open vent pipes before cutting hole in roof.) The 10"x10" hole must be measured on the horizontal; actual length may be larger depending on the pitch of the roof. There must be a 1" clearance from the vent pipe to combus­tible materials. Frame the opening as shown in Figure 12 on page 9.
If area above is a room, install firestop above framed hole.
4. Connect a section of pipe and extend up through the hole.
Note:
If an offset is needed to avoid obstructions, you must support the vent pipe every 3 feet. Use wall straps for this purpose (see Figure 21). Whenev er possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less re­striction to the flow of the flue gases and intake air.
5. Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and framing with roofing nails. Be sure roofing material overlaps the top edge of the flashing as shown in Figure
21. There must be a 1" clearance from the vent pipe to combustible materials.
6. Continue to add pipe sections until the height of the vent cap meets the mini­mum building code requirements de­scribed in Figure 8 on page 6. must increase vent height for steep roof pitches. Nearby trees, adjoining rooflines, steep pitched roofs, and other similar fac­tors may cause poor draft or down-draft­ing in high winds. Increasing the vent height may solve this problem.
7. Twist-lock the vent cap onto the last section of vent pipe and seal with high temperature silicone sealant as speci­fied in the second warning statement on page 7.
Note:
If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclo­sure with standard construction material. Make sure and meet the minimum allowable clear­ances to combustibles. Do not fill any of the required air spaces with insulation.
Note
: Y ou
45° Elbow
Ceiling Firestop
Figure 21 - Offset with Wall Strap and 45 Elbows
If area above is not a room, install firestop below framed hole.
°
Figure 22 - Installing Firestop
12
Cathedral Ceiling Installation
1. Remove shingles or other roof cover-
ing as necessary to cut the rectangular hole for the support box. Mark the out­line of the cathedral ceiling support box on the roof sheathing using the locat­ing hole as a center point.
2. Cut the hole 1/8" larger than the sup-
port box outline (see Figure 23, page 13).
105453
OWNER’S MANUAL
VENTING INSTALLATION
Continued
3. Lower the support box through the hole in the roof until the bottom of the box extends at least 2" below the ceiling (see Figure 23). Align the support box vertically and horizontally using a level. Temporarily tack the support box in place through the inside walls and into the roof sheathing.
4. Using tin snips, cut the support box from the top corners down to the roofline and fold the resulting flaps over the roof sheathing (see Figure 24). Apply a bead of non-hardening mastic around the top edges of the support box to make a seal between the box and the roof. Nail in place with roofing nails. Remove any combustible material that might be in­side of the support box.
5. Complete the cathedral ceiling instal­lation by following the same proce­dures outlined in steps 2 through 7 for Flat Ceiling Installation, page 12
.
Vertical Termination Configurations
Figures 25 through 28 show four different configurations for vertical termination. All connections must be sealed with high temperature silicone sealant as specified in the second warning statement on page 7.
Venting with Two 90° Elbows
Vertical (V) Horizontal (H1) +
Horizontal (H2)
5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max.
20' max. 8' max.
Note:
Install restrictor into 4" collar of stove as shown.
Level
Cathedral ceiling support box
2" minimum below
finished ceiling
Cut hole 1/8" larger than support box when projected onto roofline
Figure 23 - Cathedral Ceiling Support Box Installation
Non-hardening Mastic under all edges of support box before nailing
Figure 24 - Installed Cathedral Ceiling Support Box
Figure 25 - Vertical Rigid Venting Configuration Using Two 90° Elbows with Two Horizontal Runs
Note:
Install restrictor into 4" collar of stove as shown.
Venting with One 90° Elbow
Vertical (V) Horizontal (H)
5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max.
20' max. 8' max.
Figure 26 - Vertical Rigid Venting Configuration Using One 90° Elbow
Continued
105453
13
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
VENTING INSTALLATION
Continued
Note:
restrictor into 4" collar of stove as shown.
Venting with Two 90° Elbows
Vertical (V1) Horizontal (H)
5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max.
Note:
Vertical (V1) +
Vertical (V2) = 20' max.
Figure 27 - Vertical Rigid Venting Configuration Using Two 90° Elbows
Install
RVF Kit Shown
Vertical V enting
V = 30' max.
Figure 28 - Vertical Rigid Venting Configuration With No Horizontal Run
14
105453
OWNER’S MANUAL
VENTING INSTALLATION
Continued
HIGH ALTITUDE INSTALLATION
Your Vanguard direct-vent fireplace has been AGA tested and approved for eleva­tions from 0-2000 feet and CGA certified for elevations from 0-4500 feet.
When installing this fireplace at an elevation above 2000 feet (in the USA), you may need to decrease the input rating by changing the existing burner orifice to a smaller size. Re­duce input 4% for each 1000 feet above sea level. Check with your local gas company for proper orifice size identification.
When installing this fireplace at an eleva­tion above 4500 feet (in Canada), check with local authorities.
Consult your local gas company to help de­termine the proper orifice for your location.
For assistance with any high altitude instal­lation contact DESA International’s Tech­nical Service Department at 1-800-DESA­LOG (1-800-337-2564).
PARTS LISTS FOR VENTING KITS AND COMPONENTS
Vanguard Rigid Venting
Number Description
BGFVK Basic Ground Floor Rigid Vent Kit
Includes: 7" x 60° Elbow, Extended Adjustable Horizontal Termination, Wall Thimble and 14 Screws
GFVK Ground Floor Rigid Vent Kit
Includes: 7" x 60° Elbow, 7" Adjust­able Galvanized Coaxial Pipe (7-12"), Wall Thimble, Horizontal Termina­tion, RTV Silicone and 16 Screws
BVK Basement Rigid Vent Kit
Includes: 7" x 30° Elbow, 7" x 4' Galvanized Pipe, 7" x 90° Elbow, 7" Adjustable Galvanized Pipe (7-12"), Wall Thimble, Horizontal Termina­tion, RTV Silicone and 20 Screws
CVK Corner Vent Kit
Includes: 7" x 30° Elbow, 7" x 90° Elbow, 7" Adjustable Galvanized Pipe (7-12"), 6" Pipe, Wall Thimble, Horizontal Termination, RTV Sili­cone and 20 Screws
Vanguard Rigid Venting
(Cont.)
Number Description
SVK Snorkel Rigid Vent Kit
Includes: 7" x 30° Elbow, 7" x 4' Galvanized Pipe, 7" x 90° Elbow, 7" Adjustable Galvanized Pipe (7-12"), Wall Thimble, 36" Snorkel Termi­nation, RTV Silicone and 28 Screws
RVF Roof Rigid Vent Kit
Includes: Flue Restrictor, Storm Collar, 7" x 30° Elbow, 7" x 4' Galvanized Pipe, 7" x 2' Galva­nized Pipe, 7" Adjustable Galva­nized Pipe (7-12"), Firestop Sup­port, Roof Flashing, RTV Silicone, Vertical Termination, and 26 screws
D1000 7" x 12" Galvanized Coaxial
Pipe(6 pcs.)
D1010 7" x 24" Galvanized Coaxial
Pipe(6 pcs.)
D1020 7" x 48" Galvanized Coaxial
Pipe(6 pcs.)
D1030 7" Adjustable (7-12")
Galvanized Coaxial Pipe (6 pcs.)
D1050 7" x 6" Galvanized Coaxial Pipe
(6 pcs.) D2000 7" x 90° Elbow (6 pcs.) D2010 7" x 45° Elbow (6 pcs.) D2020 7" x 30° Elbow (6 pcs.) D2030 7" x 60° Elbow (6 pcs.) D3000 Wall Strap/Offset Support
(6 pcs.) D3010 Storm Collar (6 pcs.) D3020 Wall Thimble (6 pcs.) D3040 Vertical Vent Termination Cap D3050 Vertical Restrictor (6 pcs.) D3060 Ceiling Firestop/Support (6 pcs.) D3070 Rectangular Horizontal Rigid
Vent Termination Cap D3090 Cathedral Ceiling Support Box D4000 Roof Flashing 6/12-9/12 D4010 Roof Flashing 9/12-12/12 D5000 Vinyl Siding Standoff (6 pcs.)
Vanguard Flexible Venting
Number Description
BFGFVK Basic Flex Ground Floor Vent Kit
Includes: Flex Adapter, 7" x 2' Flex-
ible Pipe, 4" x 2' Flexible Pipe, Wall
Thimble, Horizontal
Termination, (2) Spacer Springs,
(2) 4" Hose Clamps, (2) 7" Hose
Clamps, and 10 Screws
Vanguard Flexible Venting
(Cont.)
Number Description
FGFVK Flex Ground Floor Vent Kit
Includes: Flex Adapter, 7" x 4' Flex­ible Pipe, 4" x 4' Flexible Pipe, Wall Thimble, Horizontal Termination, (4) Spacer Springs, (2) 4" Hose Clamps, (2) 7" Hose Clamps, RTV Silicone, and 10 Screws
D1040 7" x 25' Coaxial Flex Pipe
with Spacer Springs
D3080 Rectangular Horizontal Flex
Termination Cap D4020 Flex Connector (6 pcs.) D4030 Flex Wall Thimble (6 pcs.) D4040 4" Hose Clamp (6 pcs.) D4050 7" Hose Clamp (6 pcs.)
SIMPSON DURA-VENT GS 4" x 6 5/8 "
Number Description Available from DESA International:
SD2040 Simpson Dura-Vent GS
30° Elbow (6 pcs.) SD2050 Simpson Dura-Vent GS
60° Elbow (6 pcs.)
Available from Simpson Dura-Vent Only:
902 7" x 48" Pipe 903 7" x 36" Pipe 904 7" x 24" Pipe 906 7" x 12" Pipe 907 7" x 9" Pipe 908 7" x 6" Pipe 911 7" Adjustable (11"-14 940 Wall Thimble 941 Cathedral Ceiling Support Box 943 Roof Flashing 0/12-6/12 943S Roof Flashing 7/12-12/12 945 7" x 45° Elbow 950 Vinyl Siding Standoff 953 Storm Collar 963 Ceiling Firestop 981 36" Snorkel Termination 984 Horizontal Termination Vent Cap 988 Wall Strap 990 7" x 90° Elbow 991 Vertical High Wind Termination
5
/8") Pipe
105453
15
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
FIREPLACE INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your pri­mary heating system. Do not in­stall this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circu­late the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
NOTICE: A qualified service per­son must install fireplace. Follow all local codes.
CAUTION: This fireplace cre­ates warm air currents. These cur­rents move heat to wall surfaces next to fireplace. Installing fire­place next to vinyl or cloth wall coverings or operating fireplace where impurities (such as to­bacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls.
Note:
Your fireplace is designed to be used in zero clearance installations. Wall or fram­ing material can be placed directly against any exterior surface on the rear, sides, or top of your fireplace, except where stand-off spacers are integrally attached. If stand-off spacers are attached to your fireplace, these spacers can be placed directly against wall or framing material. See framing details on page 4.
Place the fireplace into position and shim with noncombustible material if needed. Nail the side flanges to the framing to secure the unit in place. There are two floor brack­ets included with each unit. Use these as an alternative method of securing the fireplace.
IMPORTANT:
before securing. If fireplace is not level it will not work properly.
Make sure fireplace is level
CHECK GAS TYPE
Use proper gas type for the fireplace unit you are installing. If you have conflicting gas types, do not install fireplace. See dealer where you purchased the fireplace for proper fireplace according to your gas type.
INSTALLING OPTIONAL BLOWER ACCESSORY
NOTICE: If installing blower in an existing fireplace with gas con­nections, shut off gas supply and disconnect heater from gas sup­ply. Contact a qualified service person to do this.
Attaching Thermal Switch to DA3610T Thermostatically Controlled Blower
When installing the DA3610T thermostati­cally controlled blower accessory, you must first secure the thermal switch to the blower.
1. Remove the two hex head screws on the blower assembly as shown in Figure 29.
2. Place the green wire between the bot­tom hole on the thermal switch bracket and the bottom hole on the blower as­sembly. Insert one of the hex screws into all three pieces and tighten.
3. Insert the top screw through the ther­mal switch bracket and into the blower assembly. Tighten screw.
4. Connect the blue wire on the blower assembly to the right side of the ther­mal switch.
5. Connect the black wire to the left side of the thermal switch.
Thermal Switch with Bracket
Black Wire
Hex Head Screws
Figure 29 - Attaching Thermal Switch to DA3610T Thermostatically Controlled Blower Accessory
White Wire
Green Wire
Blue Wire
Installing GA3700/DA3610T Blowers
IMPORTANT
bly and grate/burner assembly are not shown in Figures 30 through 33, page 17. They will, however, be in your fireplace when you are installing the blower. Also for clarity the firebox is shown with dotted lines.
1. Open lower louver panel or remove f or easier access.
2. Place the blower against the lower rear wall of firebox outer wrapper with the exhaust port directed upward. Align the holes in the top mounting tabs of blower with holes in wall of wrapper (see Fig­ure 30, page 17). Using the two screws provided, mount blower and tighten screws securely.
Note:
thermal switch is comfortably under the back of the firebox as shown in Figure 31, page 17.
3. Be sure to securely attach all wire ter­minals to terminals on blower motor (and thermal switch where applicable) and that the screw retaining the green ground wire is tight.
4. Remove screws securing the plate con­taining the ON/OFF switch to the bot­tom of the firebox and set aside.
5. Place speed control against back of this plate and push the plastic control shaft through opening (see Figure 32, page 17).
6. While supporting speed control, secure control shaft with lock nut by pushing and turning lock nut with pliers clockwise until tight against the plate. Place control knob provided onto shaft (see Figure 32, page 17).
7. Replace plate containing switches and tighten screws securely.
: For clarity, gas valve assem-
For DA3610T, make sure the
Blower Assembly
16
105453
OWNER’S MANUAL
FIREPLACE INSTALLATION
Continued
8. Plug in blower power cord.
a. If your fir eplace system is installed
as a freestanding unit with an ac­cessory mantel, determine whether
the power cord will exit the left side or the right side of the firebox. In­stall one plastic bushing provided into the 1 1/2" hole in the outer cas­ing through which the power cord will exit. Install the second plastic bushing provided into the floor sup­port bracket if exiting through the right side (see Figure 33). Route power cord through (both) plastic bushing(s) and plug the power cord into a properly grounded 3-prong wall receptacle near the firebox.
b. If your fireplace system installation
is recessed and/or pre-wired, a qualified installer must make all elec­trical connections for the outlet kit included with the fireplace.
9. Check to make sure that the power cord is completely clear of the blower wheel and that there are no other foreign ob­jects in blower wheel. Turn blower on and check for operation. Turn blower off by rotating knob fully counterclock­wise before continuing.
WARNING: Never touch the
blower wheel while in operation.
10. Peel off the backing paper and stick the supplied wiring diagram decal on the firebox bottom approximately 3" to the right of the blower speed control bracket (see Figure 33).
WARNING: Failure to position the parts in accordance with sup­plied diagrams or failure to use only parts specifically approved with this heater may result in dam­age or personal injury.
11. Connect or reconnect gas supply to fire­place per Connecting Fir eplace to Gas Supply on page 19 of this manual.
NOTICE: A qualified service per­son must connect fireplace to gas supply. Follow all local codes.
Firebox Bottom
Thermal Switch
Firebox Back
Firebox Flange
Blower
Lower Rear Wall of Firebox Wrapper
Screws
Blower
Lower Louver Panel
Exhaust Port
Top Mounting Tab
Thermal Switch
Figure 31 - Locating Thermal Switch Against Back of Firebox
Speed Control
Control Knob
Locknut
Figure 32 - Attaching Speed Control to Firebox
Wiring Diagram
Control Shaft
Plastic Bushing
Side View
Figure 30 - Mounting Blower to Firebox
105453
Blower Speed Control Bracket
Figure 33 - Installing Plastic Bushing and Wiring Diagram Sticker
17
Continued
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
FIREPLACE INSTALLATION
Continued
INSTALLING GAS PIPING TO FIREPLACE LOCATION
NOTICE: A qualified service per­son must connect fireplace to gas supply. Follow all local codes.
CAUTION: For propane units, never connect heater directly to the propane supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and propane supply.
Installation Items Needed
Before installing fireplace, make sure you have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• manual shutoff v alve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved flexible gas line with g as con­nector (if allowed by local codes) (not provided)
* An A.G.A. design-certified manual shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Pur­chase the A.G.A. design-certified manual shutoff valve from your dealer.
For propane connections only, the installer must supply an external regulator. The ex­ternal regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 34. Pointing the vent down protects it from freezing rain or sleet.
CAUTION: Use only new, black iron or steel pipe. Inter­nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to fireplace. If
requirements for locating manual shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.
pipe is too small, undue loss of pressure will occur.
CAUTION: Use pipe joint seal-
Check your building codes for any special
Installation must include a manual shutoff valve, union, and plugged 1/8" NPT tap.
ant that is resistant to liquid pe­troleum (LP) gas.
Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 35).
Propane Supply
Tank External Regulator
Install sediment trap/drip leg in supply line as shown in Figure 35. Locate sediment trap/drip leg where it is within reach for cleaning. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and con­taminants. This keeps them from going into fireplace gas controls. If sediment trap/drip leg is not installed or is installed wrong, fireplace may not run properly.
Vent Pointing Down
Figure 34 - External Regulator with Vent Pointing Down (Propane Only)
A.G.A. Design-Certified Manual Shutoff Valve with 1/8" NPT Tap*
Approved Flexible Gas Line
3" Minimum
Cap Pipe Nipple Tee Joint
Sediment Trap/Drip Leg
Figure 35 - Gas Connection
Natural - From Gas Meter (5" W.C. to 10.5" W.C. Pressure )
LP - From External Regulator (11" W.C. to 14" W.C. Pressure)
* The A.G.A. design-certified manual shutoff valve may be supplied with the appliance or you can purchase it from your dealer.
18
105453
OWNER’S MANUAL
FIREPLACE INSTALLATION
Continued
CONNECTING FIREPLACE TO GAS SUPPLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not provided)
1. Open lower louver door panel by gen-
tly pulling forward.
2. Route flexible gas line (provided by
installer) from manual shutoff valv e to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace.
3. Attach flexible gas line from gas sup-
ply to control valve (see Figure 36).
4. Check all gas connections for leaks. See
Checking Gas Connections.
To Gas Supply (Natural)
Manual Shutoff Valve
CHECKING GAS CONNECTIONS
WARNING: Test all gas pip­ing and connections for leaks after installing or servicing. Cor­rect all leaks at once.
WARNING: Never use an open
flame to check for a leak. Apply commercial leak test solution to all gas joints. Bubbles forming show a leak. Correct all leaks at once.
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1.
Disconnect fireplace and its individual manual shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator .
2. Cap off open end of gas pipe where manual shutoff valve was connected.
3. Pressurize supply piping system by ei­ther opening propane supply tank valve for propane gas fireplace or main gas valve located on or near gas meter for natural gas fireplace, compressed air.
4. Check all joints of gas supply piping system. Apply commercial leak test solution to all gas joints. Bubbles form­ing show a leak. Correct all leaks at once.
5. Reconnect fireplace and manual shutoff valve to gas supply . Check reconnected fittings for leaks.
opening
or using
To External Regulator (Propane)
Control Valve
Flexible Gas Line from Manual Shutoff Valve Provided by Installer
Figure 36 - Attaching Flexible Gas Lines To The Control Valve
Continued
105453
19
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
FIREPLACE INSTALLATION
Continued
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close manual shutoff valve (see Fig­ure 37).
2. Pressurize supply piping system by ei­ther opening propane supply tank valve for propane gas fireplace or main gas valve located on or near gas meter for natural gas fireplace, compressed air.
3. Check all joints from propane supply tank or gas meter to manual shutoff valve (see Figure 38 for propane or Fig­ure 39 for natural). Apply commercial leak test solution to all gas joints. Bubbles forming show a leak. Correct all leaks at once.
Pressure Testing Fireplace Gas Connections
1. Open manual shutoff valve (see Figure
37).
2. Open propane supply tank valve for propane fireplace or main gas valv e lo­cated on or near gas meter for natural gas fireplace.
3. Make sure control knob of fireplace is in the OFF position.
4. Check all joints from manual shutoff valve to thermostat gas valve (see Fig­ure 38 for propane or Figure 39 for natu­ral). Apply commercial leak test solu­tion to all gas joints. Bubbles forming show a leak. Correct all leaks at once.
5. Light fireplace (see Operating Fire- place, pages 24 and 25). Check all other internal joints for leaks.
6. Turn off f ireplace (see To Turn Off Gas to Appliance, page 24).
opening
or using
INSTALLING OPTIONAL WALL MOUNT SWITCH GWMS2
1. Connect one terminal of 25 ft. wire for the wall switch to the TPTH terminal on the valve. Connect remaining wire terminal to the TH terminal on the valve. Make sure that the wire termi­nals are in the positions on the unit as
2. Route the 25 ft. wire through openings provided on the sides of the fireplace to a convenient location to mount your switch.
3. Connect one bare wire end to each of the terminals of the GWMS2 Wall Switch.
4. Install the wall switch and cover in the wall.
pictured in Figure 41, page 21. If wires are not connected as shown the switch will not work.
Propane Supply Tank
Manual Shutoff Valve
Gas Valve
Figure 38 - Checking Gas Joints for Propane/LP Gas Fireplace
Manual
Gas Meter
Shutoff Valve
ON
Open
Manual Shutoff Valve
Figure 37 - Manual Shutoff Valve
POSITION
POSITION
Closed
OFF
Gas Valve
Figure 39 - Checking Gas Joints for Natural Gas Fireplace
20
105453
OWNER’S MANUAL
FIREPLACE INSTALLATION
Continued
INSTALLING OPTIONAL WIRELESS HAND-HELD REMOTE CONTROL ACCESSORY - GHRC
Installing Remote Receiver
1. Open bottom louver and locate the switch bracket on the left.
2. Unscrew the switch bracket. Lean bracket forward so you are able to ac­cess the back of the remote receiver.
3. Locate the battery clip mounted on the back of the receiver. Slide a 9-volt bat­tery (not included) through the clip.
4. Attach the terminal wires to the battery.
5. Remove the wire that runs from TH to TPTH from the valve (see Figure 40).
6. Connect wires from reciever to TH and TPTH on the valve (see Figure 41).
7. Replace the switch bracket.
Receiver
Terminal Wires
Battery Clip
9-Volt Battery
Figure 42 - Attaching Battery to Receiver
Installing 9-Volt Battery in Hand­Held Remote Control Unit
1. Remove battery cover on back of re­mote control unit.
2. Attach terminal wires to a 9-volt bat­tery (not included). Place battery into the battery housing.
3. Replace battery cover onto remote con­trol unit.
Battery
Terminal Wires
9-Volt Battery
Cover
Remote Control Unit
3. Grasp door by both sides and ease it upward off of the lower bracket (see Figure 45).
4. T o replace glass door, follow the above instructions in reverse.
Top Louver Panel
Figure 44 - Removing Top Louver Panel
Figure 40 - Disconnecting TH to TPTH Wire
To Wall Optional Remote Accessory
Figure 41 - Control Valve Terminals
Battery Housing
Figure 43 - Installing Battery in Hand­Held Remote Control Unit
REMOVING/REPLACING GLASS DOOR
You must remove glass door to install op­tional brick liners, logs, lava rock, and em­ber material.
CAUTION: Do not operate this fireplace with a broken glass door panel or without the glass door panel securely in place. For re­placement part information see
Replacement Parts
1. Remove the upper louver panel by lift­ing upward and out (see Figure 44).
2. Remove the screws from the three tabs at the top of the glass door while hold­ing door securely keeping it from fall­ing forward.
, page 30.
Screw
Glass Door Assembly
Lower Bracket for Glass Door Assembly
Figure 45 - Removing/Replacing Glass Door
Continued
105453
21
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
FIREPLACE INSTALLATION
Continued
INSTALLING OPTIONAL BRICK LINER D8037
WARNING: If fireplace has been running, turn off and un­plug fireplace. Let cool before installing brick liner.
This brick liner kit is optional. You may purchase brick liner from your local dealer or see Accessories, page 32.
CAUTION: Always handle brick panels with two hands. Do not force brick panels into place. Excessive force will break brick panels.
Left Side Brick Panel
Figure 46 - Installing Left Side Brick Panel
1. Remove glass door . See Removing/Re­placing Glass Door, page 21.
2. If installing brick liner in new fireplace, go to step 3. If installing brick liner in an existing fireplace, carefully remov e logs, lava rock, and ember material.
3. Install left side brick panel first by slid­ing it between the grate and the side of the firebox (see Figure 46).
4. Slide the left retainer bracket against the left side brick panel. Loosely se­cure the bracket screw . This secures the left side brick panel.
5. Install the right brick panel using the same method described in step 3.
6. Slide the right retainer bracket against the right side brick panel. Loosely se­cure the bracket screw . This secures the right side brick panel.
7. Install rear brick panel. Rest bottom edge of panel on back edge of grate (see Figure 47).
8. Loosely secure retainer brackets to grate. Brackets are adjustable left to right to allow proper placement of panel. These will hold rear panel in place.
9. Tighten all bracket screws.
10. Follow instructions on page 23 to install logs, lava rock, and ember material.
11. Replace glass door (see page 21).
Rear Brick Panel
Retaining Brackets
Figure 47 - Installing Rear Brick Panel and Retainer Brackets
22
105453
OWNER’S MANUAL
4
FIREPLACE INSTALLATION
Continued
INSTALLING LOGS, LAVA ROCK AND GLOWING EMBERS
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this heater may result in property damage or personal injury.
Each log is marked with a number. These numbers will help you identify the log when installing. It is very important to install these logs exactly as instructed. Do not modify logs. Only use logs supplied with fireplace.
Remove glass door. See Removing/Replacing Glass Door, page 21. Install logs according to instructions for fireplace model numbers.
6. Pull ember material apart into pieces no larger than a dime. Place these pieces loosely and sparingly directly onto the exposed section of the front burner and along the space between the burner and grate prongs (see Figure 52). This will create the glowing ember ap­pearance as the flame touches the em­ber material. Do not block air slots by using too much ember material in one area. It is not necessary to use all of the ember material provided.
7. Replace the glass door. See Removing/ Replacing Glass Door, page 21.
WARNING: The glass door must be securely in place before running this fireplace. Do not run this fireplace if glass is missing or broken.
1
3
Figure 50 - Installing Log No. 3
Fireplace Models BDV34N(A) and BDV34P(A)
1. Place log #1 (back log) on top of grate. Make sure the notches in the bottom of the log fit over the grate (see Figure 48).
2. Rest log #2 (large front log) on the pins on the front part of the grate (see Figure 49).
3. Place log #3 (crossover log) onto the rear and front logs. Make sure it is seated properly into the notch on the front log and over the raised triangular portion of the rear log as shown in Figure 50.
4. Place log #4 (small log) onto the front left part of the grate making sure the notches fit over the prong of the grate. See Figure 51.
5. Place lava rock along sides and front of firebox bottom in areas that are vis­ible only. It is not necessary to use all of the lava rock provided.
NOTICE: Do not put lava rock on burner or under burner. Placing lava rock on burner could cause performance problems.
Figure 51 - Installing Log No. 4
Figure 48 - Installing Log No. 1
Ember Material
2
Figure 52 - Placing Ember Material on Burner
105453
Figure 49 - Installing Log No. 2
23
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
OPERATING FIREPLACE
FOR YOUR SAFETY
READ BEFORE
LIGHTING
WARNING: If you do not fol­low these instructions exactly, a fire or explosion may result caus­ing property damage, personal injury or loss of life.
A. This appliance has a pilot which must
be lighted by hand. When lighting the pilot, follow these instructions exactly .
B. BEFORE LIGHTING smell all
around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHA T TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
C. Use only your hand to push in or turn
the gas control knob. Ne ver use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. For ce or attempted repair may result in a f ire or explosion.
D. Do not use this appliance if any part
has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been un­der water.
LIGHTING
INSTRUCTIONS
1. STOP! Read the safety information in column 1.
2. Open lower louver panel.
3. Disconnect the wire that runs from TH to TPTH from the valve.
4. Turn off all electric power to the fireplace.
5. Push in gas control knob slightly and turn clockwise to “OFF”.
6. Wait f ive (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety in­formation in column one. If you don't smell gas, go to the next step.
7. The pilot is located by the main burner and should not require ac­cessing for lighting.
8. Turn knob on gas control counter­clockwise to “PILOT”.
9. Push in control knob all the way and hold. Immediately light the pilot by repeatedly depressing the piezo spark ignitor until a flame appears. Continue to hold for about one (1) minute after the pilot is lit. Release knob and it will pop back. Pilot should remain lit. If it goes out, re­peat steps 5 through 8.
If knob does not pop up when re­leased, stop and immediately call your service technician or gas supplier.
• If the pilot will not stay lit after sev-
eral tries, turn the gas control knob to “OFF” and call your service technician or gas supplier.
10. Reconnect the wire that runs from TH to TPTH from the valve.
Gas Control Knob Piezo
Ignitor
Variable Control Knob
I
T
O
L
I
O
P
N
F
F
O
H
L
O
11. Turn on all electric power to the fireplace.
12. Turn gas control counterclockwise
to “ON”.
13. This valve is equipped with a HI/LO feature. Set fir eplace input as desired.
14. Close lower louver panel.
TO TURN OFF GAS
TO APPLIANCE
1. Open lower louver panel.
2a. If using optional ON/OFF switch,
turn ON/OFF switch to “OFF”.
2b. If Using Optional Hand-Held Re-
mote: Set selector switch in the OFF position to prevent draining battery.
3. Turn off all electrical power to the appliance if service is to be performed.
4. Push in gas control knob slightly and turn clockwise to “OFF”.
5. Close lower louver panel.
Shutting Off Burners Only (pilot stays lit)
You may shut off the burners and keep the pilot lit by doing one of the following:
1. Turn control knob clockwise to the PILOT position.
2. Set selector switch in the OFF position.
MANUAL LIGHTING
PROCEDURE
1. Remove glass door (see Removing/ Replacing Glass Door, page 21).
2. Follow steps 1 through 8 under Light­ing Instructions.
3. Depress control knob and light pilot with match.
4. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Now follow steps 10 through 14, column 2.
5. Replace glass door (see Removing/ Replacing Glass Door, page 21).
Figure 53 - Control Valve
24
105453
OWNER’S MANUAL
OPERATING FIREPLACE
Continued
OPTIONAL REMOTE
OPERATION
Note:
The GHRC receiver and hand­held remote control accessory must be purchased separately (See Accessories on page 33). Follow instructions included with the remote control.
NOTICE: You must light the pilot before using the hand-held re­mote control unit. See
Instructions,
page 24.
1. After lighting, let pilot flame burn for
about one minute. Turn control knob on the control valve to ON position. Turn flame adjustment knob any­where between HI and LO. Turn the knob to the REMOTE setting. The burner may light if hand-held re­mote ON button was on when selector switch was last turned off. Y ou can now turn the burners on and off with the hand-held remote control unit.
IMPORTANT:
Do not leave the se­lector switch in the REMOTE posi­tion when the pilot is not lit. This will drain the battery.
IMPORTANT:
Be sure to press the ON/OFF button on the hand-held re­mote control unit for up to 3 seconds to assure proper operation.
2. Press the ON/OFF button to turn the burners on and off. When turning burners off, the pilot will remain lit.
IMPORTANT:
To turn the pilot off, manually turn the control knob on the heater to the OFF position.
Lighting
Note
OPERATING
OPTIONAL BLOWER
ACCESSORY
Locate the blower controls by opening the lower louver panel on the fireplace. Blower controls are located on the left side of the switch bracket to the left just inside the louver panel.
Both the GA3700 manual blower and the DA3610T thermostatically controlled blower have an ON setting and an OFF setting. The blower will only run when the switch is in the ON position. In the OFF position, the blower will not operate.
Note for DA3610T Only:
and blower will not turn on and off at the same time. The fireplace may run for sev­eral minutes before the blower turns on. After the heater modulates to the pilot position, the blower will continue to run. The blower will shut off after the firebox temperature decreases.
:
The blower helps distribute heated air from the fireplace. Periodically check the louvers of the firebox and remove any dust, dirt, or other obstructions that will hinder the flow of air.
Blower Control Knob (Optional Accessory)
OFF
ON
REMOTE OFF ON
Remote Control Knob in Remote Position (Optional Remote Control)
Figure 54 - Setting the Remote Control Knob, Valve Control Knob, and Flame Adjustment Knob for Remote Operation
Your fireplace
Flame Adjustment Knob
N
O
T
O
L
I
P
Control Knob in On Position
INSPECTING BURNERS
Check pilot flame pattern and burner flame patterns often.
PILOT ASSEMBLY
The pilot assembly is factory preset for the proper flame height. Alterations may have occurred during shipping and handling. Call a qualified service person to readjust the pilot if necessary.
The height of the thermopile must be 3/8" to 1/2" above the pilot flame as shown in Figure
55. The thermocouple must be at a height of about 1/8" above the pilot flame. The flame from the pilot burner must extend beyond both the thermocouple and thermopile.
If your pilot assembly does not meet these requirements:
• turn fireplace off (see To Turn Of f Gas to Appliance, page 24)
• see Troubleshooting, pages 27 through 29
Thermopile
3/8" to 1/2"
Pilot Burner
1/8"
L
O
O
F
F
I
H
Piezo Ignitor
Figure 55 - Pilot Assembly
Thermocouple
105453
Continued
25
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
INSPECTING BURNERS
Continued
BURNER FLAME PATTERN
Burner flames will be steady; not lifting or floating. Flame patterns will be different from unit to unit and will vary depending on installation type and weather conditions.
If the vent configuration is installed incor­rectly, the flames will lift or "ghost". This can be dangerous. Inspect the flames after installation to ensure proper installation and performance.
Figure 56 shows a typical flame pattern for models BDV34N(A) and BDV34P(A).
If burner flame pattern differs from that described:
• turn fireplace off (see To Turn Off Gas to Appliance, page 24)
• see Troubleshooting, pages 27 through 29
GLASS DOOR
WARNING: Handle glass door panel with care. Do not strike, slam or otherwise abuse glass. Do not operate fireplace with the glass door removed, cracked, or broken.
WARNING: Do not use abra­sive cleaners as this may damage glass. Use a nonabrasive house­hold glass cleaner to clean glass. Do not clean glass when hot.
Glass must be cleaned periodically. During start-up it is normal for condensation to form on the inside of the glass causing lint, dust, and other airborne particles to cling to the glass surface. During initial start-up a slight film may form on the glass due to paint curing. The glass should be cleaned several times with a non-ammonia, non­abrasive household cleaner and warm water after the first two weeks of operation. There­after, clean the glass two or three times during each heating season, depending on the usage and circumstances present. Refer to Removing/Replacing Glass Door on page 21 of this manual when removing glass door for cleaning.
Use only the glass door replacement in­tended for this fireplace (see Replacement Parts, page 30 for detail on ordering). No substitutions may be made. See Removing/ Replacing Glass Door, page 21 for instruc­tions for replacing glass door.
WARNING: Do not operate fireplace with the glass door re­moved, cracked, or broken.
PILOT AND BURNERS
• Remove ember material before cleaning burners and replace when cleaning is complete.
• Burner and controls should be cleaned with compressed air to remove dust, dirt, or lint.
• Use a vacuum cleaner or small, soft bristled brush to remove excess dust, dirt, or lint.
LOGS
• If you remove logs for cleaning, refer to
Installing Logs, Lava Rock, and Glowing Embers, page 23, to properly replace logs.
• Use a vacuum cleaner to remove an y car­bon build up on logs.
• Replace log(s) if broken. See Replace- ment Parts on page 30.
• Replace ember material periodically as needed. See Replacement P arts on page 30.
Figure 56 - Typical Flame Pattern for BDV34N(A) and BDV34P(A)
CLEANING AND MAINTENANCE
WARNING: Turn off fireplace
and let cool before cleaning.
CAUTION: You must keep con­trol areas, burners, and circulat­ing air passageways of fireplace clean. Inspect these areas of fire­place before each use. Have fire­place inspected yearly by a quali­fied service person. Fireplace may need more frequent cleaning due to excessive lint from carpeting, bedding material, pet hair, etc.
WARNING: Only parts sup­plied by the manufacturer should be used when replacing broken or damaged glass door panel (see
Replacement Parts
glass door panel is a complete unit. No substitute materials may be used.
CAUTION: Wear gloves and safety glasses while handling or removing broken glass. Do not remove if glass is hot. Keep chil­dren and pets away from glass.
If glass has been broken, carefully remove glass door (see Removing/Replacing Glass Door, page 21). Vacuum all glass pieces with a shop vac.
CAUTION: Do not vacuum if pieces are hot.
, page 30). This
26
VENTING SYSTEM
Conduct annual inspection of the venting system following these guidelines:
1. Check areas of venting system that are exposed to the weather for corrosion (rust spots or streaks and, in extreme cases, holes). Have these items replaced imme­diately by a qualified service person.
2. Remove the vent cap and shine a flash­light into the vent. Remove any foreign material.
3. Check for evidence of excessive con­densation. Continuous condensation can cause corrosion of caps, pipes, and fittings and can be caused by having excessive lateral runs, too man y elbows, or exterior portions of the system be­ing exposed to cold weather.
4. Inspect joints to verify that no pipe sec­tion or fitting has been disturbed and loosened. Check mechanical supports such as wall straps for rigidity.
105453
OWNER’S MANUAL
TROUBLESHOOTING
Note:
For additional help, visit DESA
International’s Technical Service web site at www.desatech.com.
Note:
All troubleshooting items are listed in
order of operation.
OBSERVED PROBLEM
When ignitor button is pressed, there is no spark at pilot
When ignitor button is pressed, there is spark at pilot but no ignition
WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.
POSSIBLE CAUSE
1. Ignitor electrode not connected to igni­tor cable
2. Ignitor cable pinched or wet
3. Piezo ignitor nut is loose
4. Broken ignitor cable
5. Bad piezo ignitor
6. Ignitor electrode broken
7. Ignitor electrode positioned wrong
1. Gas supply turned off or manual shutoff valve closed
2. Control knob not in PILOT position
3. Control knob not pressed in while in PILOT position
4. Air in gas lines when installed
5. Depleted gas supply (propane models only)
6. Pilot is clogged
7. Gas regulator setting is not correct
CAUTION: Never use a wire, needle, or similar object to clean pilot. This can damage pilot unit.
REMEDY
1. Reconnect ignitor cable
2. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry
3. Tighten nut holding piezo ignitor. Nut is located behind the mounting bracket.
4. Replace ignitor cable
5. Replace piezo ignitor
6. Replace pilot assembly
7. Replace pilot assembly
1. Turn on gas supply or open manual shutoff valve
2. Turn control knob to PILOT position
3. Press in control knob while in PILOT position
4. Continue holding down control knob. Repeat igniting operation until air is removed
5. Contact local propane gas company
6. Clean pilot (see Cleaning and Maintenance, page 26) or replace pilot assembly
7. Replace gas control
Pilot lights but flame goes out when control knob is released
105453
1. Control knob not fully pressed in
2. Control knob not pressed in long enough
3. Manual shutoff valve not fully open
4. Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This prob­lem could be caused by one or both of the following: A) Low gas pressure B) Dirty or partially clogged pilot
5. Thermocouple connection loose at con­trol valve
6. Thermocouple damaged
7. Control valve damaged
www.desatech.com
27
1. Press in control knob fully
2. After pilot lights, keep control knob pressed in 30 seconds
3. Fully open manual shutoff valve
4. A) Contact local gas company
B) Clean pilot (see Cleaning and Maintenance, page 26) or replace pilot assembly
5. Hand tighten until snug, then tighten 1/4 turn more
6. Replace thermocouple
7. Replace control valve
Continued
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
TROUBLESHOOTING
Continued
OBSERVED PROBLEM
Burner does not light after pilot is lit
Delayed ignition burner
Burner backfiring during combustion
Slight smoke or odor during initial operation
Heater produces a whistling noise when burner is lit
POSSIBLE CAUSE
1. Burner orifice clogged
2. Inlet gas pressure is too low
3. Thermopile leads disconnected or im­properly connected
4. Thermopile is defective
1. Manifold pressure is too low
2. Burner porting or orifice clogged
1. Burner orifice is clogged or damaged
2. Damaged burner
3. Gas regulator defective
1. Residues from manufacturing processes and logs curing
1. Turning control knob to HI position when burner is cold
2. Air in gas line
3. Dirty or partially clogged burner orifice
REMEDY
1. Clean burner (see Cleaning and Maintenance, page 26) or replace burner
orifice
2. Contact local propane or natural gas company
3. Reconnect leads (see Wiring Diagram, page 30)
4. Replace thermopile
1. Contact local propane or natural gas company
2. Clean burner (see Cleaning and Main- tenance, page 26) or replace burner orifice
1. Clean burner (see Cleaning and Maintenance, page 26) or replace burner orifice
2. Replace damaged burner
3. Replace gas control
1. Problem will stop after a few hours of operation
1. Turn control knob to LO position and let warm up for a minute
2. Operate burner until air is removed from line. Have gas line checked by local pro­pane gas company
3. Clean burner (see Cleaning and Maintenance, page 26) or replace burner orifice
Glass soots
Fireplace produces a clicking/ticking noise just after burners are lit or shut off
1. Flame impingement on logs
2. Debris around burner air mixer
1. Metal expanding while heating or con­tracting while cooling
www.desatech.com
28
1. Adjust the log set so that the flame does not excessively impinge on it
2. Inspect the opening at the base of the burner to see that it is NOT packed with any type of material
1. This is common. If noise is excessive, contact qualified service person
105453
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
OWNER’S MANUAL
IMPORTANT:
paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air and create odors. These odors will disappear over time.
OBSERVED PROBLEM
Fireplace produces unwanted odors
Fireplace shuts off in use
Operating fireplace where impurities in air exist may create odors. Cleaning supplies,
POSSIBLE CAUSE
1. Gas leak. See Warning statement above
1. High or gusting winds
2. Low line pressure
3. Pilot is partially clogged
4. Inner vent pipe leaking exhaust gasses into system.
5. Horizontal vent improperly pitched
6. Glass too loose and air tight gasket leaks in corners after usage
7. Bad thermopile or thermocouple
8. Improper vent cap installation
REMEDY
1. Locate and correct all leaks (see Check­ing Gas Connections, page 19)
1. Fireplace has been tested for up to 40mph winds. However, extreme con­ditions may occur. See Lighting Instruc- tions on page 24.
2. Contact local propane or natural gas company
3. Clean pilot (see Cleaning and Mainte- nance, page 26)
4. Locate and correct all leaks (see Check- ing Gas Connections, page 19)
5. Horizontal vent termination should slope down only enough to prev ent an y water from entering the unit. The maximum downward slope of the vent termination is 1/4" for any horizontal run.
6. Tighten glass
7. Replace faulty component
8. Check for proper installation and free­dom from debris or blockage
Gas odor even when control knob is in OFF position
Gas odor during combustion
Dark residue on logs or inside of fireplace
105453
1. Gas leak. See Warning statement above
2. Control valve defective
1. Gas leak. See Warning statement
above
1. Improper log placement
2. Air holes at burner inlet blocked
3. Burner flame holes blocked
www.desatech.com
29
1. Locate and correct all leaks (see Check­ing Gas Connections, page 19)
2. Replace control valve
1. Locate and correct all leaks (see Check- ing Gas Connections, page 19)
1. Properly locate logs (see Installing Logs, Lava Rock, and Glowing Embers, page 23)
2. Clean out air holes at burner inlets. Pe­riodically repeat as needed
3. Remove blockage or replace burner
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
REPLACEMENT PARTS
Note:
Use only original replacement parts.
This will protect your warranty coverage for parts replaced under warranty.
PARTS UNDER WARRANTY
Contact authorized dealers of this product. If they can not supply original replacement part(s), call DESA International’s Techni­cal Service Department at 1-800-DESA LOG (1-800-337-2564).
When calling DESA International, have ready
• your name
• your address
• model number of your fireplace
• how fireplace was malfunctioning
• type of gas used (propane/LP or natural gas)
• purchase date
Usually, we will ask you to return the defec­tive part to the factory.
PARTS NOT UNDER WARRANTY
Contact authorized dealers of this product. If they can not supply original replacement part(s), call DESA International’s Parts De­partment at 1-800-972-7879 for referral in­formation.
When calling DESA International, have ready
• model number of your fireplace
• the replacement part number
TECHNICAL SERVICE
You may have further questions about in­stallation, operation, or troubleshooting. If so, contact DESA International’s Technical Service Department at 1-800-DESA LOG (1-800-337-2564).
You can also visit DESA International’s Technical Service web site at www.desatech.com.
WIRING DIAGRAM
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous opera­tion. Verify proper operation af­ter servicing.
Variable
Fan Switch
1
Off
110/115
V.A.C.
Figure 57 - Blower Wiring Diagram for Thermostat-Controlled Models
Black
White
Green
2
On
Fan Switch
(N.O.)
Red
Black
Red
Black
SERVICE HINTS
When Gas Pressure Is Too Low:
• pilot will not stay lit
• burners will have delayed ignition
• fireplace will not produce specified heat
• propane/LP gas supply might be low (propane units only)
When Gas Quality Is Bad:
• pilot will not stay lit
• burners will produce flames and soot
• fireplace will backfire when lit
If you feel your gas pressure is too low or gas quality is bad, contact your local natural or propane/LP gas supplier.
Blower
Motor
30
105453
OWNER’S MANUAL
SPECIFICATIONS
BDV34N(A) BDV34P(A)
15,000/21,000 Btu/hr 16,000/20,000 Btu/hr Gas Type Natural Propane Ignition Piezo Piezo Manifold Pressure 3.5" w.c. 10.0" w.c. Minimum Inlet Supply Pressure 4.5" w.c. 11.0" w.c. Dimension, Inches/mm (HxWxD)
Fireplace 33" x 34" x 18 1/2" 33" x 34" x 18 1/2"
838 x 940 x 470mm 838 x 940 x 470mm
Carton 37" x 40" x 21" 37" x 40" x 21"
940 x 1016 x 533mm 940 x 1016 x 533mm Weight, lbs/kg
Fireplace 132 lbs/60 kg 132 lbs/60 kg Shipping 135 lbs/61 kg 135 lbs/61 kg
105453
31
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
ACCESSORIES
Purchase these fireplace accessories from your local dealer. If they can not supply these accessories, call DESA International’s Sales Department at 1-800-432-2382 for information. You can also write to the ad­dress listed on the back page of this manual.
CABINET MANTEL
GM100F Series - Walnut Finished
GM101U Series - Unfinished GM106F Series - Oak Finished
with Medium Stain GM107U Series - Unfinished GM102W Series - Off White Paint
Shown with optional base and laminate hearth and mantel trim accessories.
Dimensions (WxHxD): 56 3/4" x 48 3/4" x 22 7/8"
HEARTH BASE TRIM KIT (Not Shown)
G3003J Series - Jade Marble Laminate
G3003S Series - Sandstone Marble Laminate
G3003B Series - Black Onyx Marble Laminate
HARDWOOD HEARTH BASE
G3000F Series- Walnut Finished G3001U Series - Unfinished G3006F Series - Oak Finished
with Medium Stain G3007U Series - Unfinished Oak G3004W Series- Off White Paint
The hearth base creates a handsome riser for the fireplace (cannot be used with corner mantel).
Dimensions (WxHxD): 58" x 6 1/2" x 28 9/16"
SLIM HEARTH BASE
(Not Shown) G3005J Series - Jade Marble
Laminate G3005S Series - Sandstone
Marble Laminate G3005B Series - Black Onyx
Marble Laminate
The slim hearth base allows you to further customize your fireplace.
Dimensions (WxHxD): 41 7/8" x 5/8" x 10"
MANTEL TRIM (Not Shown)
G3002J Series - Jade Marble Laminate
G3002S Series - Sandstone Marble Laminate
G3002B Series - Black Onyx Marble Laminate
MANUAL BLOWER KIT GA3700
Manual-variable control blower accessory for the BDV Series fireplaces.
THERMOSTATICALLY­CONTROLLED BLOWER KIT DA3610T
Provides better heat distribution. Blower turns off and on automatically, as needed. Complete installation and operation instruc­tions included in this manual.
CORNER MANTEL
GM200F Series - Walnut Finished GM201U Series - Unfinished
Shown with optional laminate mantel trim accessory.
Dimensions (WxHxD): 60 7/8" x 48 3/4" x 34 5/8"
BRICK LINER
D8037 (Not Shown)
This brick liner adds a touch of style to your direct-vent fireplace and comes with easy to follow instructions for installation.
32
105453
ACCESSORIES
Continued
DUPLEX OUTLET KIT GA3555 (NOT SHOWN)
For built-in installation when accessory blowers are used.
BRASS PERIMETER TRIM KIT - GA6090 (Not Shown)
Optional three sided brass trim kit covers unfinished edges around fireplace. Provides a finished appearance with the class of brass.
BRASS LOUVER KIT
D6034 (Not Shown)
These louvers will give your fireplace an elegant look and allows you to customize your fireplace. They easily replace the stan­dard black louvers by screwing into place.
DECORATIVE 2-PIECE BRASS ACCENT TRIM D7034 (Not Shown)
OWNER’S MANUAL
RECEIVER AND HAND-HELD REMOTE CONTROL KIT GHRC SERIES
For all models. Allows the heater to be turned on and off conveniently.
ON/OFF WALL MOUNT SWITCH - GWMS2
For all models. Allows the heater to be manually turned on and off.
These strips have a magnetic backing which makes installation and removal quick and easy. They are designed to go at the top and bottom of the glass door on BDV units.
Note:
Remove the plastic film covering on
strips before installing on fireplace.
FIREPLACE SCREEN
DS34
For all models. This fireplace screen easily attaches to the front glass panel with in­cluded clips.
105453
33
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
ILLUSTRATED PARTS BREAKDOWN
BDV34N(A)
37
33
7
2
11 (Included in Hardware Pack)
1
38
31-4
31-2
31-3
31-1
29
44
6
25
43
42
26
27
40
39
32
9
17
28
34
6
10
35
46
5
4
13
14
15
5
12
8
5
18
6
20
32
7
41
32
19
30
24
36
21
16
28
22
23
45
3
34
105453
OWNER’S MANUAL
PARTS LIST
This list contains replaceable parts used in your fireplace. When ordering parts, follow the instructions listed under Replacement Parts on page 30 of this manual.
DIRECT-VENT FIREPLACE BDV34N(A)
KEY NO. PART NUMBER DESCRIPTION QTY.
1 104445-01 Top Outer Casing 1 2 105278-01 Outer Casing 1 3 105297-01 Bottom Outer Casing 1 4 104479-10BR Firebox Assembly 1 5 M11084-26 Screw, Hex 50 6 M11084-46 Screw, Hex 8 7 105394-01 Louver, Extruded 2 8 104443-01 Firebox Support, Right 1 9 104486-01 Firebox Support, Left 1 10 104482-01 Switch Bracket 1 11 104483-01 Floor Mounting Bracket 2 12 104491-01 Relief Cover 1 13 104518-01 Relief Cover Gasket 1 14 104527-01 Relief Spring 2 15 104528-01 Relief Washer 2 16 104537-01 Valve Bracket 1 17 104496-01 SIT Valve, Natural 1 18 104497-01 SIT Pilot, Natural 1 19 104498-01 Thermocouple 1 20 104499-01 Thermopile 1 21 104500-01 Ignitor 1 22 104501-01 Ignitor Bracket 1 23 104502-01 Ignitor Screw 1 24 104503-01 Ignitor Wire 1 25 104504-01 Burner 1 26 104506-01 Orifice 1 27 104507-01 Brass Elbow 1
KEY NO. PART NUMBER DESCRIPTION QTY.
28 104508-01 Brass Fitting 2 29 104509-01 Aluminum Tubing Assy 1 30 104510-01 Pilot Tubing Assy 1 31 104516-01 Log Set 31-1 104876-02 Rear Log 1 31-2 104877-02 Front Log 1 31-3 104878-02 Crossover Log 1 31-4 104879-02 Log Piece 1 32 M10908-2 Screw 6 33 M12461-73 Screw 3 34 H5C4-20B Bolt 2 35 M12461-26 Screw 4 36 104555-02CJ Grate Assembly 1 37 104940-09 Glass Door Assy 1 38 104615-02 Insulation 1 39 105450-01 Front Assembly 1 40 104313-01 Hinge, Pin 1 41 104313-02 Hinge, Pin 1 42 104954-01 Screw 3 43 104963-01 Washer 3 44 104955-01 Nut 3 45 105575-01 Wire Harness 1 46 NTC-4C Locknut 2
PARTS AVAILABLE - NOT SHOWN
GA6060 Lava Rock 1 104529-01 Ember Material 1
105453
35
®
DIRECT-VENT FIREPLACE (NATURAL/PROPANE)
ILLUSTRATED PARTS BREAKDOWN
BDV34P(A)
37
33
7
2
11 (Included in Hardware Pack)
1
38
31-4
31-2
31-3
31-1
29
44
6
25
43
42
26
27
40
39
32
9
17
28
34
6
10
35
46
5
4
13
14
15
5
12
8
5
18
6
20
32
7
41
32
19
30
24
36
21
16
28
22
23
45
3
36
105453
OWNER’S MANUAL
PARTS LIST
This list contains replaceable parts used in your fireplace. When ordering parts, follow the instructions listed under Replacement Parts on page 30 of this manual.
DIRECT-VENT FIREPLACE BDV34P(A)
KEY NO. PART NUMBER DESCRIPTION QTY.
1 104445-01 Top Outer Casing 1 2 105278-01 Outer Casing 1 3 105297-01 Bottom Outer Casing 1 4 104479-10BR Firebox Assembly 1 5 M11084-26 Screw, Hex 50 6 M11084-46 Screw, Hex 8 7 105394-01 Louver, Extruded 2 8 104443-01 Firebox Support, Right 1 9 104486-01 Firebox Support, Left 1 10 104482-01 Switch Bracket 1 11 104483-01 Floor Mounting Bracket 2 12 104491-01 Relief Cover 1 13 104518-01 Relief Cover Gasket 1 14 104527-01 Relief Spring 2 15 104528-01 Relief Washer 2 16 104537-01 Valve Bracket 1 17 104496-02 SIT Valve, Natural 1 18 104497-02 SIT Pilot, Natural 1 19 104498-01 Thermocouple 1 20 104499-01 Thermopile 1 21 104500-01 Ignitor 1 22 104501-01 Ignitor Bracket 1 23 104502-01 Ignitor Screw 1 24 104503-01 Ignitor Wire 1 25 104504-02 Burner 1 26 104506-02 Orifice 1 27 104507-01 Brass Elbow 1
KEY NO. PART NUMBER DESCRIPTION QTY.
28 104508-01 Brass Fitting 2 29 104509-01 Aluminum Tubing Assy 1 30 104510-01 Pilot Tubing Assy 1 31 104516-01 Log Set 31-1 104876-02 Rear Log 1 31-2 104877-02 Front Log 1 31-3 104878-02 Crossover Log 1 31-4 104879-02 Log Piece 1 32 M10908-2 Screw 6 33 M12461-73 Screw 3 34 H5C4-20B Bolt 2 35 M12461-26 Screw 4 36 104555-02CJ Grate Assembly 1 37 104940-09 Glass Door Assy 1 38 104615-02 Insulation 1 39 105450-01 Front Assembly 1 40 104313-01 Hinge, Pin 1 41 104313-02 Hinge, Pin 1 42 104954-01 Screw 3 43 104963-01 Washer 3 44 104955-01 Nut 3 45 105575-01 Wire Harness 1 46 NTC-4C Locknut 2
PARTS AVAILABLE - NOT SHOWN
GA6060 Lava Rock 1 104529-01 Ember Material 1
105453
37
WARRANTY INFORMATION
KEEP THIS WARRANTY
Model Serial No. Date Purchased
Always specify model and serial numbers when communicating with the factory. We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written
warranty. We make no other warranty, expressed or implied.
LIMITED WARRANTY
DIRECT-VENT FIREPLACE
DESA International warrants this product to be free from defects in materials and components for four (4) years from the date of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this heater to proper operating condition and an allowance for labor when provided by a DESA Authorized Service Center. Warranty part(s) MUST be obtained through authorized dealers of this product and/or DESA International who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURA­TION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO FOUR (4) YEARS ON ALL COMPONENTS FROM THE DATE OF FIRST PURCHASE; AND DESA INTERNATIONAL’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND DESA INTERNATIONAL SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state. For information about this warranty write:
INTERNATIONAL
2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004
www.desatech.com
105453 01