Delta Electronics DPM-C530A User Manual

www.deltaww.com
Multi-functional Power Meter DPM-C530A User Manual
1
Table of Contents
2.1 Safety Notes ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧3
2.2 Installation Environment ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧4
3.1 Operating Interface ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧5
3.2 Product Name Tag ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧5
3.3 Exterior and Dimensions ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧5
4.1 Installation Method ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧7
4.2 Basic Checks ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧9
5.1 Wiring on the Back ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧10
5.2 Descriptions of Wiring ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧11
6. Panel Display and Settings ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧ 13
6.1 Panel Display ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧13
6.2 General Operations ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧15
6.3 Setup Operations ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧16
7.1 Overview of Parameters ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧22
9.1 Specications ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧74
9.2 Communication Specications ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧76
9.3 Modbus Communication ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧77
Appendix 1: Selecting Accessories ‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧‧82
2
Preface
Thank you for choosing this product. This manual offers information related to installation of the
DPM-C530A power meter. Before using the meter, please read this manual carefully to ensure
proper use of this meter. Also, please place the manual at an easy-to-find location for reference at
any time. Before you finish reading this manual, please observe the following notes:
■No water vapor, corrosive and flammable gas shall be present in the installation environment.
■Follow the instructions on the diagram for wiring the device.
■Grounding must be performed correctly and properly according to provisions from related regulations on electric work currently effective in the country.
■Do not disassemble the meter or alter its wiring with power connected.
■With power on, do not touch the power-connecting area to avoid electric shock.
If you still experience issues in the use, please contact your distributor or our customer service center.
As the product gets updated and improved, modifications on the specifications will be addressed in
the newest version of manual obtainable by contacting your distributor or downloading from the Delta Electronics website
http://www.delta.com.tw/ia/.
DANGER
DANGER
STOP
STOP
3
2.1 Safety Notes
Always be aware of the following safety notes when installing, wiring, operating, maintaining, and
checking the device.
◆ Notes on Installation
»
Install the power meter according to instructions on the manual. Otherwise, damage on the device might result.
»
It is forbidden to expose and use this product in a place present with matters, such as water vapor,
corrosive and flammable gas. Otherwise, electric shock, re, or explosion might result.
»
Do not install the meter in an environment with a temperature that exceeds range on the specication.
Otherwise, inability of the meter to operate normally or damage on the meter might result.
»
Do not use the meter on an alarm console that might cause personnel injury or death, damage on the device, or system shutdown.
◆ Note on Wiring
»
Keep a good grounding on the grounded terminals, as improper grounding might cause
abnormal communication, electric shock, or re.
◆ Notes on Operation
»
Do not alter wiring with power turned on. Otherwise, electric shock or personnel injury might result.
»
Do not touch the panel with a sharp item. Otherwise, indentation on the panel might result, which causes the meter to not function normally.
◆ Maintenance and Check
»
Do not get to inside of the meter. Otherwise, electric shock might result.
»
Do not take the meter panel apart when the power is on. Otherwise, electric shock might result.
»
Do not touch the wiring terminals within 10 minutes after turning off power, as the remaining voltage
might cause electric shock.
»
Do not block ventilation ducts when operating the meter. Otherwise, the meter will breakdown
because of inadequate heat dissipation.
◆ Methods of Wiring
»
Do not use voltage that exceeds range specied for the meter. Otherwise, electric shock or re might result.
»
When wiring, take apart the quick connector from the main meter body.
»
Connect only one cord on one plug on the quick connector.
»
For wrongfully forced unplug, recheck the connecting cord and restart.
◆ Wiring for Communication Circuits
»
Follow the standard specication on use of wires for communication wiring.
»
Length of communication wires should be within the specied standard.
»
Use correct grounding loop to avoid communication issues.
»
To avoid stronger noise interference that causes the meter to not operate normally, use an independent
wiring slot to separate the communication cable for the meter from all power cords and motor power cords.
Notes
4
2.2 Installation Environment
Before installation, this product must be placed in its packaging box. If not used for a while, be
sure to watch for the following when storing the meter, so that the product could be kept under
the company's warranty coverage for future maintenance.
■Place the device in a dry location free of dust.
■Ambient temperature for the storage location must be within the range of -20° C to +70
° C (-4° F
to 158° F).
■Relative humidity for the storage location must be within the range of 5% to 95%, with no condensation.
■Avoid storing at an environment present with corrosive gas and liquid.
■Package properly and store on a rack or counter.
■Suitable installation environment for this product includes: place with no device that generates high amount of heat; place with no water drop, vapor, dust, and oily dust; place with no corrosive
and flammable gas; place with no floating dust and metal particles; place with no shaking and
interference from electromagnetic noise.
5
3.1 Operating Interface
DPM-C530A uses a LCD display that exhibits four pieces of measurement information on each
page. Diagram below is an illustration of the interface.
3.2 Product Name Tag
3.3 Exterior and Dimensions
Descriptions of Parts
A. Title
B. Area of display
C. Pulse light
D. Fault light
E. Menu key
F. Up key
G. Down key
H. Enter key
Descriptions:
MODEL : XXXXXXXXX REV. : XX.XX Input : 80~265VAC, 50/60Hz 100~300VDC MAX 4.6W
XXXXXXXXXXXXXXXX
MADE IN XXXXXX
Model
Version
Certification
Serial Number
Country
SPEC LABEL
94.1
90
72.0 22.1
96
90
96
6
◆ Front
◆ Back
FUNCTION PIN VOLTAGE CURRENT
MEASURED VOTAGE
V1
20V L-N ~ 400V L-N
35V L-L ~ 690V L-L
-
V2
V3
Vn
CONTROL POWER
L1/+
80 ~ 265 VAC
100 ~ 300 VDC
400mA MAX.
L2/-
MEASURED CURRENT
I1+
- 1A ~ 5A
I1-
I2+
I2-
I3+
I3-
RS-485
D+
-7 ~ +12 VDC -
D-
PULSE
MENU UP DOWN ENTER
FAULT
198*160 DOTS LCD DISPLAY
I3-
V1 V2 V3 Vn L1/+ L2/-
D+ D-
I1+ I1- I2+ I2- I3+
INPUT / OUTPUT CONNECTOR PIN ASSIGNMENT
7
4.1 Installation Method
Note
■The installation method should be based on instructions. Otherwise, breakdown would result.
■For better effectiveness of cooling cycles, sufcient space must be kept between adjacent objects and walls during the installation. Otherwise, imperfect cooling would result.
■Maximal thickness for the panel installed should not exceed 5 mm.
Illustration of Installation
Step 1:
Open the square hole on the metal plate and then
install the power meter.
Step 2:
Install the fixing mount into the sliding slot and
then push the meter in to touch the metal plate.
Step 3:
During the installation, reserve a 50 mm-wide space behind the power meter for dissipating heat
50
單位:mm
Installation
8
Dimensions of Panel Hole
9
4.2 Basic Checks
Items Checked Contents of Checks
General Check
■Regularly check for losing of the xing mount at the location where the power
meter and device are connected.
■Guard against entrance of foreign objects, such as oil, water, or metal powder at
the heat dissipating holes. Guard against entrance of drill cut powders into the
power meter.
■Should the power meter be installed at a place present with harmful gas or dust,
guard against entrance of those matters into the meter.
Pre-operation
Check
(not supplied with
control power)
■Insulate the connecting spot of the wiring terminals.
■Communications wiring should be done properly, or abnormal operations might
result.
■Check for presence of conducive and flammable objects, such as screws or metal
pieces, in the power meter.
■Should electronic devices used near the power meter experience electromagnetic
interference, tune with instruments to reduce electromagnetic interference.
■Check for correct voltage level for the power supplied to the power meter.
Pre-running Check
(supplied with
control power)
■Check whether power indicator light is lit.
■Check whether communication between every device is normal.
■If there is any abnormal response from the power meter, contact your distributor
or our customer service center.
10
5.1 Wiring on the Back
This chapter illustrates how the wiring on the back is done.
Note:
■To avoid electric shock, do not alter wiring when the power is on.
■As there is no power switch on the power meter, be sure to install a breaker switch on the power cord for the meter.
Recommended wiring materials are shown below:
Connecting Terminals Wire Diameters Screw Turning Torque
Functional Power AWG 10~24 7.14 kgf-cm (0.7 N*m)
Measured Voltage AWG 10~26 7.14 kgf-cm (0.7 N*m)
Measured Current AWG 14~22 8.0 kgf-cm (0.79 N*m)
RS-485 AWG 14~28 2.04 kgf-cm (0.2 N*m)
RTwisted pair cables must be used in cabling for RS485 communication. When connecting multiple
devices in series, the wiring method is displayed in the diagram below.
The D+ communication terminal for all devices should be connected on the same twisted pair cable. The
D- terminals should be connected on the other twisted pair cable. The insulation net is grounded. The
device on the end terminal needs to have terminal resistor installed on it.
Wiring Diagrams
Terminal Resistor
11
5.2 Descriptions of Wiring
This chapter illustrates how wiring is done for this panel.
■Measured Voltage:
When measured voltage is higher than the rated specication (refer to Electrical Specication) for the
device, use of an external potential transformer should be considered.
■Measured Current:
When measured current is higher than the rated specication (refer to Electrical Specication) for the
device, use of an external current transformer should be considered.
■Supported Methods of Wiring:
A N
I1+
I1
-
I2+
I2
-
I3+
I3
-
V1 V2 V3 Vn
I1+
I1-
I2+
I2-
I3+
I3-
V1 V2 V3 Vn
A NB
Diagram 5-1: One-phase two-wire, 1 CT Diagram 5-2: One-phase three-wire, 2 CT
I1+
I1-
I2+
I2-
I3+
I3
-
V1 V2 V3 Vn
A NB C
I1+
I1-
I2+
I2-
I3+
I3-
V1 V2 V3 Vn
A NB C
Diagram 5-3: Three-phase three-wire,
Δ Delta-connection, 3 CT, No PT
Diagram 5-4: Three-phase three-wire,
Δ Delta-connection, 2 CT, No PT
12
I1+
I1-
I2+
I2-
I3+
I3-
V1 V2 V3 Vn
A NB C
I1+
I1-
I2+
I2
-
I3+
I3
-
V1 V2 V3 Vn
A NB C
Diagram 5-5: Three-phase three-wire,
Δ Delta-connection, 3 CT, 2 PT
Diagram 5-6: Three-phase four-wire,
Y-connection, 3 CT, No PT
I1+
I1-
I2+
I2
-
I3+
I3
-
V1 V2 V3 Vn
A N
B C
I1+
I1-
I2+
I2
-
I3+
I3
-
V1 V2 V3 Vn
A NBC
Diagram 5-7: Three-phase four-wire,
Y-connection, 3 CT, 3 PT
Diagram 5-8: Three-phase four-wire,
Y-connection, 2 CT, 3 PT
■The following symbols are used in the diagram:
Symbol
Description Grounding
Current
transformer
Terminal resistor
Potential
or voltage
transformer
Fuse
13
6.1 Panel Display
6.1.1 Area of Display
DPM-C530A uses LCD display that exhibits four pieces of measurement information on each page.
Diagram below is an illustration of the display panel:
Descriptions:
A
Title
B
Area of display
C
Pulse light
D
Fault light
E
Menu key
F
Up key
G
Down key
H
Enter key
6.1.3 Descriptions of the Keys
Name of Key General Mode Conguration Mode
Menu key
Enter into Menu or return to previous page
Return without saving current settings
Up key Move up to select an item or page Increase numbers
Down key Move down to select an item or page Decrease numbers
Enter key Enter into the selected item
Enter into the setting and move to the next location of setting
Panel Display and Settings
Current THD
1. Time, date
Phase voltage Line voltage
Unbalanced phase voltage %
Unbalanced line voltage %
0. Setting
1. Voltage Measure
1. Current
1. Current
1. Area
History
2. Current measure
2. Voltage
2. Voltage
2. Auto mation
3. PF/Hz
3. Power
3. Power
3. Data Log
4. Power measure
4. Power factor
4. Power factor
5. Energy measure
5. Frequency
5. Frequency
6.Harmonics
6. Harmonics
6. Harmonics
7. Demanics
8.Maximum
9. Minimum
10.Alarm
11. Advanced
2. Meter information
Current
Unbalanced current %
3. Communication parameter
Power factor Displacement PF Frequency
4.CT, PT proportion
Total power Active power Reactive power Apparent power
Apparent power demand
5. System parameter
Active energy Reactive energy Apparent energy
Automatic energy 1
Automatic energy 2
6. Alarm
Total harminics
Phase voltage THD
7. Demand
Current demand
Active power demand
Reactive power demand
8. Reset
14
6.1.3 Menu Tree
Default
MENU
15
6.2 General Operations
6.2.1 Observing Measured Data
■Voltage Measurement: Parameter of voltage measured by the power meter, including phase voltage, line voltage, rate of phase voltage imbalance, rate of line voltage imbalance, etc
■Current Measurement: Parameter of currents measured by the meter, including phase/line voltage, rate of current imbalance, etc.
■Power Factor, Frequency (PFHz): Power factor and parameter of frequency measured by the meter, including power factor, displacement power factor, frequency, etc.
■Power Measurement: Parameter of power measured by the meter, including active, reactive, and apparent power for every and combined phase.
■Energy Measurement: Parameter of electrical energy by the meter, including active, reactive, and apparent electrical energy on positive and opposite phases.
■Harmonic: Parameter of harmonic measured by the meter, including total harmonic for voltage and current, harmonic for voltage on every phase, harmonic for current on every phase.
■Demand: Parameter of demand measured by the meter, including demand for previous, current, forecast and peak current; active power; and reactive power.
■Maximum: Maximum parameter measured by the meter, including maximum value of voltage, current, power factor, frequency, power, harmonic, and demand.
■Minimum: Minimum parameter measured by the meter, including minimum value of voltage, current, power factor, frequency, power, harmonic, and demand.
■Alarm: Parameter of alarms for the meter.
(1) Press the Menu key until the menu appears.
(2) Select an item from 1~7 that you want to take a look at.
(3) Press the Up or Down key to switch between pages for every item of parameter.
(4) Press the Menu key to return to the menu page.
Example:
Assume having entered into the page of item 1. Measurement of Voltage, you will a page for phase
voltage. Press the Down key to switch to the page for line voltage. Press the Down key again to switch
to the page for the rate of phase voltage imbalance. Press the Down key again to switch to the page
for the rate of line voltage imbalance. Press the Down key again to return to the phase voltage page.
Otherwise, press the Up key to reverse the cycling order mentioned above.
16
6.3 Setup Operations
6.3.1 Time and Date Settings
■Time:Current time on the meter, including hour, Minute, second.
■Date: Current date on the meter, including last two digits of the year, Month, Day, and day of week.
■Steps to set up are as follows:
(1) Press Menu key until the menu appears.
(2) Select 0. Setup and press Enter key to enter into the setup menu.
(3) Select 1. Date/Time and press the Enter key to enter into options.
(4) Select Time or Date and press the Enter key to start setting up.
(5) When the option is highlighted, start setting up by using the Up and Down keys to select the
numbers needed for the time and date.
(6) Press the Enter key to nish setting up for a number and move on to set up for the next number.
(7) Repeat steps (5)~(6) until nishing setup for the last number and press the Enter key. When the
highlight disappears, setup is complete. If there is a need to cancel the setup in the middle, press the Menu key to return without saving the numbers that were just set.
(8) After completing or cancelling the setup, press the Menu key again to return to the setup menu.
6.3.2 Communication Settings
■Address: Range of address for the device is 1~254, with the broadcast address of 255 and factory default of 1.
■Protocol: Mode of communication transmission, with a selection from RTU (factory default) and ASCII.
■Baud Rate: Speed of communication transmission, with the factory default of 9600 kbps.
■Data Bit: Length of packet data, with a selectable range of 7 and 8 bits; however, only 8 bits (factory default) is selectable under RTU mode.
■Parity: Odd and even checking bit for communication, with a selection from None (factory default), Even, and Odd.
■Stop Bit: Signal for completion of packet transmission, with a selection from 1 and 2 bit(s) (factory default: 1 bit).
■Steps to set up are as follows:
(1) Press Menu key until the menu appears.
(2) Select 0. Setup and press Enter key to enter into the setup menu.
17
(3) Select 3. Communication and press the Enter key to enter into options.
(4) Select Address and press the Enter key to start setting up for the address.
(5) When the option is highlighted, start setting up by using the Up and Down keys to select the
numbers needed.
(6) Press the Enter key to nish setting up for a number and move on to set up for the next number.
(7) Repeat steps (5)~(6) until nishing setup for the last number and press the Enter key. When the
highlight disappears, setup is complete. If there is a need to cancel the setup in the middle, press the Menu key to return without saving the numbers that were just set.
(8) Select Protocol and press the Enter key to start setting up for communication mode.
(9) When the option is highlighted, start setting up by using the Up and Down keys to select the mode
needed, such as RTU or ASCII.
(10) Press the Enter key to complete. When the highlight disappears, setup is complete. If there is a
need to cancel the setup in the middle, press the Menu key to return without saving the mode that was just selected.
(11) Setup for Baud rate, data bit, parity, and stop bit all follow the steps mentioned above.
(12) After completing or cancelling the setup, press the Menu key again to return to the setup menu.
6.3.3 Settings for Potential and Current Transformers
■Primary-side current transformer (CT1): Ampere for the primary-side current transformer, with a selectable range of 1~9999 A (factory default: 1 A).
■Secondary-side current transformer (CT2): Ampere for the secondary-side current transformer, with a selection of 1 and 5 A (factory default: 1 A).
■Primary-side potential transformer (PT1): Voltage for the primary-side potential transformer, with a selectable range of 1~9999 V (factory default: 1 V).
■Secondary-side potential transformer (PT2): Voltage for the secondary-side potential transformer, with a selectable range of 1~9999 V (factory default: 1 V).
■Steps to set up are as follows:
(1) Press Menu key until the menu appears.
(2) Select 0. Setup and press Enter key to enter into the setup menu.
(3) Select 4. Transformer Ratio and press the Enter key to enter into options.
(4) Select CT1 and press the Enter key to start setting up for current transformer on the primary side.
(5) When the option is highlighted, start setting up by using the Up and Down keys to select the
numbers needed.
(6) Press the Enter key to nish setting up for a number and move on to set up for the next number.
(7) Repeat steps (5)~(6) until nishing setup for the last number and press the Enter key. When the
highlight disappears, setup is complete. If there is a need to cancel the setup in the middle, press the Menu key to return without saving the numbers that were just set.
18
(8) When the setup is nished, other parameters could be set. The steps start from step 5 mentioned
above.
(9) After completing or cancelling the setup, press the Menu key again to return to the setup menu.
6.3.4 Settings for System Parameters
■Language: Language displayed on the operating interface of the meter. Selectable languages are English (factory
default) and Simplied Chinese.
■Backlight: Brightness of LCD backlight on the meter, with a selection of 100% (factory default), 50%, and 25%.
■Timeout: Time to maintain brightness of LCD backlight on the meter. With 100% selected, the backlight always remains bright. With 50% and 25% selected, power saving mode is on with a time set for the backlight (factory default is 30 seconds). Once the time is up, the backlight is turned off. Touching the keys turns on the backlight with a brightness based on the percentage selected.
■Power System: Selection of wiring method for the system, with a selection of one-phase two-wire, one-phase three­wire, three-phase three-wire, three-phase four-wire (factory default).
■Phase: For the phase A wire connected to phase C, reversing to phase C wire connected to phase A does not require re-wiring. Conversion is done by directly selecting this parameter. Selectable modes are ABC (factory default) and CBA.
■Number of CTs: Numbers of current transformers on the system. 0, 1, 2, 3 current transformers are selectable. The default setting of current transformers is 3.
■Number of PTs: Numbers of potential transformers on the system. 0, 2, 3 potential transformers are selectable. The default setting of potential transformers is 3.
■Steps to set up are as follows:
(1) Press Menu key until the menu appears.
(2) Select 0. Setup and press Enter key to enter into the setup menu.
(3) Select 5. System and press the Enter key to enter into options.
(4) Select Language and press the Enter key to start setting up for language.
(5) When the option is highlighted, start setting up by using the Up and Down keys to select the mode
needed.
(6) Press the Enter key to complete. When the highlight disappears, setup is complete. If there is a
need to cancel the setup in the middle, press the Menu key to return without saving the mode that was just selected.
19
(7) Setup for backlight brightness, method of wiringCT 數、PT and phase sequence reversal all
follow the steps mentioned above.
(8) Select Timeout and press the Enter key to start setting up for timeout.
(9) When the option is highlighted, start setting up by using the Up and Down keys to select the
numbers needed.
(10) Press the Enter key to nish setting up for a number and move on to set up for the next number.
(11) Repeat steps (9)~(10) until nishing setup for the last number and press the Enter key. When the
highlight disappears, setup is complete. If there is a need to cancel the setup in the middle, press the Menu key to return without saving the numbers that were just set.
(12) After completing or cancelling the setup, press the Menu key again to return to the setup menu
6.3.5 Alarm Settings
■Alarm: Whether this alarm is enabled or disabled (factory default).
■Upper: When the threshold set on the meter is exceeded, an alarm will be generated. The factory default is 0.
■Timeout: When the threshold set on the meter is exceeded and the time delay set is overdue, an alarm will be generated. The factory default is 0.
■Lower: When the threshold set on the meter falls short, the alarm will be cancelled. The factory default is 0.
■Timeout: When the threshold set on the meter falls short and the time delay set is overdue, the alarm will be cancelled. The factory default is 0.
■Steps to set up are as follows:
(1) Press Menu key until the menu appears.
(2) Select 0. Setup and press Enter key to enter into the setup menu.
(3) Select 6. Alarm and press the Enter key to enter into options.
(4) Select the setup item needed and press the Enter key to enter into the option.
(5) Select Alarm and press the Enter key to start setting up.
(6) When the option is highlighted, start setting up by using the Up and Down keys to select the mode
needed.
(7) Press the Enter key to complete. When the highlight disappears, setup is complete. If there is a
need to cancel the setup in the middle, press the Menu key to return without saving the mode that was just selected.
(8) Select Upper and press the Enter key to start setting up for timeout.
(9) When the option is highlighted, start setting up by using the Up and Down keys to select the
numbers needed.
20
(10) Press the Enter key to nish setting up for a number and move on to set up for the next number.
(11) Repeat steps (9)~(10) until nishing setup for the last number and press the Enter key. When the
highlight disappears, setup is complete. If there is a need to cancel the setup in the middle, press the Menu key to return without saving the numbers that were just set.
(12) Select Timeout and press the Enter key to start setting up for timeout.
(13) When the option is highlighted, start setting up by using the Up and Down keys to select the
numbers needed.
(14) Press the Enter key to nish setting up for a number and move on to set up for the next number.
(15) Repeat steps (13)~(14) until nishing setup for the last number and press the Enter key. When the
highlight disappears, setup is complete. If there is a need to cancel the setup in the middle, press the Menu key to return without saving the numbers that were just set.
(16) For Lower and Timeout below, the steps to set up for them are the same as those from (8)~(15).
(17) For other alarm options, the steps to set up for them are the same as those from (4)~(16).
(18) After completing or cancelling the setup, press the Menu key twice to return to the setup menu.
6.3.6 Settings for Demands
■Method: There is only one mode to calculate xed interval on the meter.
■Interval: Time interval to calculate for the demand, with a selectable range of 1~99 min (factory default is 1 min).
■Steps to set up are as follows:
(1) Press Menu key until the menu appears.
(2) Select 0. Setup and press Enter key to enter into the setup menu.
(3) Select 7. Demand and press the Enter key to enter into options.
(4) Select the setup item needed and press the Enter key to enter into the option.
(5) Select Interval and press the Enter key to start setting up.
(6) When the option is highlighted, start setting up by using the Up and Down keys to select the
numbers needed.
(7) Press the Enter key to nish setting up for a number and move on to set up for the next number.
(8) Repeat steps (6)~(7) until nishing setup for the last number and press the Enter key. When the
highlight disappears, setup is complete. If there is a need to cancel the setup in the middle, press the Menu key to return without saving the numbers that were just set.
(9) After completing or cancelling the setup, press the Menu key again to return to the setup menu.
21
6.3.7 Restore Settings
■Default: Restores settings on the meter to factory default.
■Energy: Resets to zero for the value of electrical energy accumulated on the meter and that calculated without a meter-checking personnel.
■Demand: Resets to zero for the currents calculated by the meter, value of power demand, and logged time and date.
■Alarm: Clears away all alarm logs detected on the meter.
■MaxMin: Clears away all records of maximum and minimum values logged on the meter.
■Data Log: Clears away all historical data logs that are stored in the memory on the meter.
■Clear All: Restores all settings on the meter to factory default and clears away all historical data logs.
■Steps to set up are as follows:
(1) Press Menu key until the menu appears.
(2) Select 0. Setup and press Enter key to enter into the setup menu.
(3) Select 8. Reset and press the Enter key to enter into options.
(4) Select the setup item needed and press the Enter key to enter into the option.
(5) Press the Enter key to start setting up.
(6) When the option is highlighted, start setting up by using the Up and Down keys to select the mode
needed.
(7) Press the Enter key to complete. When the highlight disappears, setup is complete. If there is a
need to cancel the setup in the middle, press the Menu key to return without saving the mode that was just selected.
(8) Repeat steps (6)~(7) until nishing setup for the last number and press the Enter key. When the
highlight disappears, setup is complete. If there is a need to cancel the setup in the middle, press the Menu key to return without saving the numbers that were just set.
(9) After completing or cancelling the setup, press the Menu key again to return to the setup menu.
22
7.1 Overview of Parameters
Modbus Address
Item Communicated Range Data Type Unit
Data Size
(Byte)
Read (R) /
Write (W)
0. System Parameter: 0001 ~ 00FF
1
Current date on meter
year: 00~99 month: 1~12
byte year, month 2 R / W
2
day: 1~31, week: Sun. – Sat.
byte day, week 2 R / W
3
Current time on meter
hour: 00~24 minute: 00~60
byte
hour and
minute
2 R / W
4 second: 00~60 byte second 1 R / W
5 Meter constant 3200 Uint P/kWh 2 R
6 Meter model
0: None 1: DPM-C530A
byte 1 R
7
Total time on power
day: 0~65535 byte day 2 R
8
hour: 00~24 minute: 00~60
byte
hour and
minute
1 R
9 Firmware version number 0.0000 ~ 9.9999 Uint 2 R
A
Last write-in date on rmware
year: 00~99 month : 1~12
byte year, month 2 R
B day: 1~31 byte day 1 R
C
Positive and opposite phase sequence
0: ABC 1: CBA
byte 1 R / W
D
Method of wiring for electric system
0: 3φ4W 1: 3φ3W 2: 1φ2W 3: 1φ3W
byte 1 R / W
E
Value of current on primary-side current transformer (A)
1 ~ 9999 Uint 2 R / W
F
Value of current on secondary­side current transformer (A)
0: 1A 1: 5A 2: 2.5A
byte 1 R / W
10
Multiplier on primary-side potential transformer
1 ~ 9999 Uint 2 R / W
11
Multiplier on secondary-side potential transformer
1 ~ 9999 Uint 2 R / W
12 Quantity of Transformer
0:3CT3PT 1:3CT2PT 2:3CT0PT 3:2CT3PT 4:2CT2PT 5:2CT0PT 6:1CT3PT 7:1CT2PT 8:1CT0PT 9:0CT3PT 10:0CT2PT 11:0CT0PT
byte 1 R / W
13 Language
0: English 1: Traditional Chinese 2: Simplify Chinese
byte 1 R / W
14 Power-saving mode (second) 0~99 byte sec 1 R / W
Parameters and Functions
23
15 Screen brightness
0: 100% 1: 50% 2: 25%
byte 1 R / W
16 Baud Rate
0: 9600, 1: 19200, 2: 38400
byte bps 1 R / W
17 Communication mode
0: ASCII 1: RTU
byte 1 R / W
18 Data bit
0: 8 1: 7
byte 1 R / W
19 Parity
0: None 1: Even 2: Odd
byte 1 R / W
1A Stop bit
0: 1 1: 2
byte 1 R / W
1B Meter address 0 ~ 255 byte 1 R / W
1C Reset parameters on meter
0: None 1: Reset factory default 2: Reset value of energy 3: Reset value of demand 4: Clear alarm logs and times 5: Reset maximum and minimum values 6: Clear saved logs 7: Clear all values
byte 1 W
1D Demand (method of calculation) 0: block byte 1 R
1E Time interval for demand (min) 0 ~ 60 byte minute 1 R / W
Alarm - Over Current
1F Alarm Enable
0: Disable 1: Enable
byte 1 R / W
20
Pickup setpoint (currents exceeding this value(A), alarm generated)
0.000~99999.999 Float
A 4 R / W
21
22
Pickup time delay (triggering delayed)
0~99 byte s 2 R / W
23
Dropout setpoint (currents lower than this value (A), alarm cleared)
0.000~99999.999 Float A 4 R / W
24
25
Dropout time delay (restoration delayed)
0~99 byte s 2 R / W
Alarm - Under Current
26 Alarm Enable
0: Disable 1: Enable
byte 1 R / W
27
Pickup setpoint (currents lower than this value (A), alarm generated)
0.000~99999.999 Float A 4 R / W
28
29
pickup time delay (triggering delayed)
0~99 byte s 2 R / W
2A
Dropout setpoint (currents exceeding this value (A), alarm cleared)
0.000~99999.999 Float A 4 R / W
2B
2C
Dropout time delay (restoration delayed)
0~99 byte s 2 R / W
Alarm - Over Neutral Current
2D Alarm Enable
0: Disable 1: Enable
byte 1 R / W
24
2E
Pickup setpoint (currents exceeding this value(A), alarm generated
0.000~99999.999 Float A 4 R / W
2F
30
pickup time delay (triggering delayed)
0~99 byte s 2 R / W
31
Dropout setpoint (currents lower than this value (A), alarm cleared)
0.000~99999.999 Float A 4 R / W
32
33
Dropout time delay (restoration delayed)
0~99 byte s 2 R / W
Alarm - Over Line Voltage
34 Alarm Enable
0: Disable 1: Enable
byte 1 R / W
35
pickup setpoint (voltage exceeding this value (V), alarm generated)
0.000~99999.999 Float V 4 R / W
36
37
pickup time delay (triggering delayed)
0~99 byte s 2 R / W
38
dropout setpoint (voltage lower than this value (V), alarm cleared)
0.000~99999.999 Float V 4 R / W
39
3A
dropout time delay (restoration delayed)
0~99 byte s 2 R / W
Alarm - Under Line Voltage
3B Alarm Enable
0: Disable 1: Enable
byte 1 R / W
3C
pickup setpoint (voltage lower than this value (V), alarm generated)
0.000~99999.999 Float V 4 R / W
3D
3E
pickup time delay (triggering delayed)
0~99 byte s 2 R / W
3F
dropout setpoint (voltage exceeding this value (V), alarm cleared)
0.000~99999.999 Float V 4 R / W
40
41
dropout time delay (restoration delayed)
0~99 byte s 2
R / W
Alarm - Over Phase Voltage
42 Alarm Enable
0: Disable 1: Enable
byte 1 R / W
43
pickup setpoint (voltage exceeding this value (V), alarm generated)
0.000~99999.999 Float V 4 R / W
44
45
pickup time delay (triggering delayed)
0~99 byte s 2 R / W
46
dropout setpoint (voltage lower than this value (V), alarm cleared)
0.000~99999.999 Float V 4 R / W
47
48
dropout time delay (restoration delayed)
0~99 byte s 2 R / W
Alarm - Under Phase Voltage
49 Alarm Enable
0: Disable 1: Enable
byte 1 R / W
4A
pickup setpoint (voltage lower than this value (V), alarm generated)
0.000~99999.999 Float V 4 R / W
4B
25
4C
pickup time delay (triggering delayed)
0~99 byte s 2 R / W
4D
dropout setpoint (voltage exceeding this value (V), alarm cleared)
0.000~99999.999 Float V 4 R / W
4E
4F
dropout time delay (restoration delayed)
0~99 byte s 2 R / W
Alarm - Over Voltage Unbalance
50 Alarm Enable
0: Disable 1: Enable
byte 1 R / W
51
pickup setpoint (voltage unbalance exceeding this value (V), alarm generated)
0.000~99999.999 Float % 4 R / W
52
53
pickup time delay (triggering delayed)
0~99 byte s 2 R / W
54
dropout setpoint (voltage unbalance lower than this value (V), alarm cleared)
0.000~99999.999 Float % 4 R / W
55
56
dropout time delay (restoration delayed)
0~99 byte s 2 R / W
Alarm - Over Current Unbalance
57 Alarm Enable
0: Disable 1: Enable
byte 1 R / W
58
pickup setpoint (current unbalance exceeding this value (A), alarm generated)
0.000~99999.999 Float % 4 R / W
59
5A
pickup time delay (triggering delayed)
0~99 byte s 2 R / W
5B
dropout setpoint (current unbalance lower than this value (A), alarm cleared)
0.000~99999.999 Float % 4 R / W
5C
5D
dropout time delay (restoration delayed)
0~99 byte s 2 R / W
Alarm - Over Active Power
5E Alarm Enable
0: Disable 1: Enable
byte 1 R / W
5F
pickup setpoint (active power exceeding this value (kW), alarm generated)
0.000~99999.999 Float kW 4 R / W
60
61
pickup time delay (triggering delayed)
0~99 byte s 2 R / W
62
dropout setpoint (active power lower than this value (kW), alarm cleared)
0.000~99999.999 Float kW 4 R / W
63
64
dropout time delay (restoration delayed)
0~99 byte s 2 R / W
Alarm - Over Reactive Power
65 Alarm Enable
0: Disable 1: Enable
byte 1 R / W
66
pickup setpoint (reactive power exceeding this value (kVAR), alarm generated)
0.000~99999.999 Float kVAR 4 R / W
67
68
pickup time delay (triggering delayed)
0~99 byte s 2 R / W
Loading...
+ 58 hidden pages