www.delta.com.tw/industrialautomation
ASIA
Delta Electronics, Inc.
Taoyuan1
31-1, Xingbang Road, Guishan Industrial Zone,
Taoyuan County 33370, Taiwan, R.O.C.
TEL: 886-3-362-6301 / FAX: 886-3-362-7267
Delta Electronics (Jiang Su) Ltd.
Wujiang Plant3
1688 Jiangxing East Road,
Wujiang Economy Development Zone,
Wujiang City, Jiang Su Province,
People's Republic of China (Post code: 215200)
TEL: 86-512-6340-3008 / FAX: 86-769-6340-7290
Delta Electronics (Japan), Inc.
Tokyo Office
Delta Shibadaimon Building, 2-1-14 Shibadaimon,
Minato-Ku, Tokyo, 105-0012, Japan
TEL: 81-3-5733-1111 / FAX: 81-3-5733-1211
Series
HMI Connection Manual
Series HMI Connection Manual
Delta Electronics (Korea), Inc.
Donghwa B/D 3F, 235-6, Nonhyun-dong,
Kangnam-gu, Seoul 135-010, Korea
TEL: 82-2-515-5303/5 / FAX: 82-2-515-5302
Delta Electronics (Singapore) Pte. Ltd.
8 Kaki Bukit Road 2, #04-18 Ruby Warehouse Complex,
Singapore 417841
TEL: 65-6747-5155 / FAX: 65-6744-9228
AMERICA
Delta Products Corporation (USA)
Raleigh Office
P.O. Box 12173,5101 Davis Drive,
Research Triangle Park, NC 27709, U.S.A.
TEL: 1-919-767-3813 / FAX: 1-919-767-3939
EUROPE
Deltronics (The Netherlands) B.V.
Eindhoven Office
De Witbogt 15, 5652 AG Eindhoven, The Netherlands
TEL: 31-40-2592850 / FAX: 31-40-2592851
*We reserve the right to change the information in this manual without prior notice
20080122
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
1.1 Pin Definition of Serial Communication
DOP-A Series
COM1
COM2
Pin1
PIN
1 N.C RXD- D-
PIN
1 N.C
2 RXD
3 TXD
4 N.C
5 GND
6 N.C
7 RTS
8 CTS
9 N.C
Mode 1 Mode 2 Mode 3
RS-232 RS-422 RS-485
Mode
RS-232
Pin1
2 RXD RXD+ D+
3 TXD TXD+ D+
4 N.C TXD- D-
5 GND GND GND
6 N.C RTS- N.C
7 RTS RTS+ N.C
8 CTS CTS+ N.C
9 N.C CTS- N.C
NOTE
1) Mode 3 is for RS-485. Pin 2 & 3 are D+ and pin 1 & 4 are D-.
2) Grounding is highly recommended if RS-485 & RS-422 are used for long transmission.
3) DO NOT connect Frame Ground (FGND) to GND. Please connect FGND to the outer covering of
connector.
4) Transmission speed is relevant to distance and baud rate.
Revision January, 2008, Doc. Name: 2007PDD23000007 1-1
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
DOP-AE Series
COM1
COM2/COM3
PIN
Pin1
Mode 1 Mode 2 Mode 3 Mode 4 Mode 5 Mode 6
RS-232 RS-422 RS-485
1 N.C RXD- D- N.C RXD- D-
PIN
1 N.C
2 RXD
3 TXD
4 N.C
5 GND
6 N.C
7 RTS
8 CTS
9 N.C
Mode
RS-232
RS-232x2 RS-422x2 RS-485x2
Pin1
COM2
COM3
2 RXD RXD+ D+ RXD RXD+ D+
3 TXD TXD+ D+ TXD TXD+ D+
4 N.C TXD- D- N.C TXD- D-
5 GND GND GND GND GND GND
6 N.C RTS- N.C N.C TXD- D-
7 RTS RTS+ N.C TXD TXD+ D+
8 CTS CTS+ N.C RXD RXD+ D+
9 N.C CTS- N.C N.C RXD- D-
1-2 Revision January, 2008, Doc. Name: 2007PDD23000007
DOP AS Series
COM1/COM3
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
COM2
Mode 1 Mode 2
PIN
RS-232
RS-232x2
1 N.C N.C
2 RXD RXD
COM 1
3 TXD TXD
4 N.C N.C
5 GND GND
6 N.C N.C
COM 3
7 RTS TXD
8 CTS RXD
9 N.C N.C
Mode 1 Mode 2
PIN
RS-422 RS-485
R- RXD- D-
R+ RXD+ D+
T- TXD- D-
T+ TXD+ D+
GND GND
Revision January, 2008, Doc. Name: 2007PDD23000007 1-3
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
1.2 Cable for Download
Download via COM Port
RS-232
DOP series HMI
9 pin D-SUB male (RS-232)
RXD (2) (3) TXD
TXD (3) (2) RXD
GND (5) (5) GND
RTS (7) (8) CTS
CTS (8) (7) RTS
PC
9 pin D-SUB female (RS-232)
Controller
上視圖
Pin1
Download via USB Flash Drive
USB Connection
1-4 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
1.3 Supported Controllers and Devices
Please refer to the following table for supported controllers and devices provided by DOP series HMI.
Brand Controller Name / Series Name
Delta Controller
For Servo/AC drive/Temperature Controller/PLC
Delta
(984 RTU mode / ASCII mode)
Delta DVP PLC
MicroLogix PLC
Allen Bradley
SLC5 PLC
Cimon Loader Protocol
Copley Servo (Stepnet Protocol)
Danfoss VLT 2800 (FC Protocol)
Emerson EC20 Series PLC
Facon FB Series PLC
Festo Festo PLC
GE Fanuc 90 Series SNP PLC
Hitachi EH Series
Hust Hust CNC Controller
Nano Series PLC
Jetter
JC Series PLC
Keyence KV/KZ Series
SU/DL Series
Koyo
K-Sequence
Lenze LECOM-A/B Protocol
Master-K120S/200S
Glofa GM6 CNET
LG
Master-K CNET
XGT CNET
LI YAN LYPLC EX
M2i Master
M2i
M2i Slave
Matsushita FP Series
Mirle FAMA SC
Revision January, 2008, Doc. Name: 2007PDD23000007 1-5
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Brand Controller Name / Series Name
FX / FX2N
FX3U
A Series/J71UC24
Mitsubishi A2A/A2AS/A2USH A1SH/A3N/A2ASH CPU Port
Mitsubishi
Q Series CPU Port
Q Series Computer Link
FX Series Computer Link
J2s Series
BY125
MKS
Modbus
Modicon
Moeller Moeller PLC
NIKKI DENSO NCS-FI/FS Series
CT150
MC700/720
Modbus (Master) --- 984 RTU / ASCII mode
Hexadecimal Address (Master) --- RTU / ASCII mode
nW (Master) --- RTU / ASCII mode
Modbus (Slave) --- RTU / ASCII mode
TSX Micro
TWIDO
C Series
Uni-Telway
Modbus RTU
Omron
Siemens
Taian TP02 PLC
Vigor M Series
VIPA VIPA PLC
Yokogawa ACE PLC
CJ1/CS1 Series
TPM1A
S7 200
S7-300 (with PC Adaptor)
S7-300 (without PC Adaptor)
1-6 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Delta (Servo/AC Drive/PLC/Temperature) Controller Back to Table
A. HMI factory setting
Baud rate: ASCII: 9600, 7, None, 2.
RTU: 9600, 8. None, 2.
Controller station number: 1.
Control area/status area: None.
NOTE
1) This driver can support all Delta products, i.e. AC drive, PLC, Servo, Temperature Controller and
Modbus standard connection. The users can easily set and communicate with these devices via using
this driver.
2) For people who are using Modbus standard connection:
Modbus / ASCII (Master), Modbus / 984 RTU (Master), Modbus / ASCII Hex Address (Master) and
Modbus / RTU Hex Address (Master) can be compatible with the new Delta controller ASCII and Delta
controller RTU. To change the driver settings, the user only needs to change the “Controller” Option
which is used to set the controller, then the new driver can be used immediately.
B. Definition of controller Read/Write address
Registers
Register Type Format
Servo communication
address
AC drive communication
address
TCntrl communication
address
WORD_DEVICE_X PLC_Xn n: 0 ~ 360(octal) N/A Word
WORD_DEVICE_Y PLC_Yn n: 0 ~ 360(octal) N/A Word
WORD_DEVICE_M PLC_Mn n: 0 ~ 1520, N/A Word
1536 ~ 4080 N/A Word
WORD_DEVICE_S PLC_Sn n: 0 ~ 1008 N/A Word
SERVO-n n: 0 ~ 0700h N/A Word
INVERTER-n n: 0 ~ 2299h N/A Word
TEMP_CTRL-n n: 0 ~ 6000h N/A Word
Read/Write Range
Data Length
Word No. Bit No.
WORD_DEVICE_T PLC_Tn n: 0 ~ 255 N/A Word
WORD_DEVICE_C PLC_Cn n: 0 ~ 199 N/A Word
WORD_DEVICE_D PLC_Dn n: 0 ~ 4095, N/A Word
4096 ~ 9999 N/A Word
WORD_DEVICE_HC PLC_HCn n: 200 ~ 255 N/A Double Word
PLC communication
address Module
Revision January, 2008, Doc. Name: 2007PDD23000007 1-7
PLC_Modulen n: 4000 ~ 4499h N/A Word
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Register Type Format
Output Registers RW-n n: 0 ~ FFFFh N/A Word
Input Registers R-n n: 0 ~ FFFFh N/A Word
Output Registers Wn n: 40001 ~ 50000 N/A Word
Input Registers Wn n: 30001 ~ 40000 N/A Word
NOTE
1) The above addresses of Servo, AC drive, Temperature controller and PLC Module are in hexadecimal
format. PLC Word Device X and Y are in octal format. Other PLC Word Device M, S, T, C, D and HC are
in decimal format.
2) WORD_DEVICE_ X / WORD_DEVICE_Y / WORD_DEVICE_M / WORD_DEVICE_S: Address must be
0 or the multiple of 16.
Contacts
Contact type Format
Read/Write Range
Data Length
Word No. Bit No.
Read/Write Range
Word No. Bit No.
Servo communication address SERVO-n.b n: 0 ~ 0700h b: 0 ~ f
AC drive communication address INVERTER-n.b n: 0 ~ 2299h b: 0 ~ f
TCntrl communication address TEMP_CTRL-n.b n: 0 ~ 6000h b: 0 ~ f
Servo Digital Input SERVO_DI-n N/A n: 1 ~ 8
Servo Digital Output SERVO_DO-n N/A n: 1 ~ 5
WORD_DEVICE_X PLC_Xn N/A n: 0 ~ 377(octal)
WORD_DEVICE_Y PLC_Yn N/A n: 0 ~ 377(octal)
WORD_DEVICE_M PLC_Mn N/A n: 0 ~ 1535
1536 ~ 4095
WORD_DEVICE_S PLC_Sn N/A n: 0 ~ 1023
WORD_DEVICE_T PLC_Tn N/A n: 0 ~ 255
WORD_DEVICE_C PLC_Cn N/A n: 0 ~ 255
TCntrl Bit communication address TEMP_CTRLB-n N/A n: 800 ~ 8FFh
Discrete Outputs RWB-n N/A n: 0 ~ FFFFh
Discrete Inputs RB-n N/A n: 0 ~ FFFFh
Discrete Outputs Bn N/A n: 1 ~ 10000
Discrete Inputs Bn N/A n: 10001 ~ 20000
NOTE
1) The above addresses of Servo, AC drive, Temperature controller and PLC Module are in hexadecimal
format.
1-8 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
2) PLC Word Device X and Y are in octal format. Other PLC Word Device M, S, T, C, D and HC are in
decimal format.
3) Servo Digital Input and Servo Digital Output are only for Servo.
Pay close attention to the following important notes:
4) For Delta AC drive:
Communication address for HMI read/write address uses hexadecimal format. For detailed information
about communication address of Delta AC drive, please refer to Delta AC drive “User Manual”.
Example 1: Parameter 9-01 of Delta VFD-S drive Transmission Speed needs to be set to INVERTER901
in HMI. (Decimal 9 is converted to 09 in hexadecimal and 01 is converted to 01 in hexadecimal.
Therefore, setting INVERTER901 to HMI will discard the first 0)
Decimal value
Hexadecimal value
The communication address of parameter 9-01 is 0901H.
Example 2: if setting of parameter 8-17 (Lower Bound of DC Braking Start-up Frequency) of Delta VFD-
S drive is desired, user needs to set INVERTER811 in HMI. (8 is converted to 08 in hexadecimal and 17
is converted to 11 in hexadecimal. Therefore, setting the INVERTER811 to HMI will discard the first 0)
Decimal value
Hexadecimal value
The communication address of parameter 8-17 is 0811H.
5) For Delta Servo drive:
01
(Hexadecimal value)
09
(Hexadecimal value)
11
(Hexadecimal value)
08
(Hexadecimal value)
y HMI Read/Write address setting needs to input the communication address listed in SERVO “User
Manual”.
y Servo Digital Input and Servo Digital Output are only for Servo.
6) For Delta Temperature Controller (DTA series):
HMI can be set up to connect to several Delta A series temperature controllers on standard Modbus
networks by using RTU transmission mode. However, the communication delay time may need to
increase. Therefore, 5ms or longer is highly recommended.
Revision January, 2008, Doc. Name: 2007PDD23000007 1-9
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
C. Connections (Connector Pinouts)
Delta Servo
RS-232
DOP Series
9 pin D-SUB male (RS-232)
RS-422
DOP Series
9 pin D-SUB male (RS-422)
RS-485
RXD (2)
TXD (3)
GND (5)
RXD+ (2)
RXD- (1)
TXD+ (3)
TXD- (4)
Controller
CN3 cable connector (RS-232)
TX
(4) RX
(1) GND
CN3 cable connector (RS-422)
Controller
(5) TX+
(6) TX-
(3) RX+
(4) RX-
Controller
CN3 cable connector
(RS-232)
CN3 cable connector
3 5
1
2
4 6
Top V ie w
Controller
(RS-422)
3 5
1
2
4 6
Top V ie w
DOP Series
9 pin D-SUB male (RS-485)
RXD+ (2)
TXD+ (3)
RXD- (1)
TXD- (4)
Controller
CN3 cable connector (RS-485)
(3) 485+
(5) 485+
(4) 485-
(6) 485-
Controller
CN3 cable connector
(RS-485)
3 5
1
2
4 6
Top V ie w
1-10 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta AC drive
RS-485
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
DOP Series
9 pin D-SUB male (RS-485)
RXD+ (2
TXD+ (3)
RXD- (1)
TXD- (4)
GND (5) (2) GND
NOTE
1) When connecting to a Delta VFD-M series AC drive, please connect Pin 5 (GND) of the Delta HMI and
Pin 2 (GND) of the Delta VFD-M AC drive.
Temperature Controller
RS-485
DOP Series
9 pin D-SUB male (RS-485)
RJ-11 cable connector (RS-485)
Controller
(4) SG+
(3) SG-
Controller
RJ-11 cable connector (RS-485)
2: GND
3: SG4: SG+
6
1
To p V ie w
DO NOT use Pin 1, 5 and 6 while
RS-485 cable connector
using RS-485 communication.
Controller
RXD+ (2)
D+
TXD+ (3)
RXD- (1)
TXD- (4)
D-
Revision January, 2008, Doc. Name: 2007PDD23000007 1-11
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Delta DVP PLC Back to Table
A. HMI factory settings
Baud rate: 9600, 7, Even, 1.
Controller station number: 1.
Control area/status area: D0 / D10.
B. Definition of controller Read/Write address
Registers
Register Type Format
X_Data Xn n: 0 ~ 360(octal) N/A
Y_Data Yn n: 0 ~ 360(octal) N/A
M_Data Mn n: 0 ~ 1520, 1536 ~ 4080 N/A
S_Data Sn n: 0 ~ 1008 N/A
T_Register Tn n: 0 ~ 255 N/A
C_Register Cn n: 0 ~ 199 N/A
D_Register Dn n: 0 ~ 4095, 4096 ~ 9999 N/A
HC_Register Cn n: 200 ~ 255 N/A
NOTE
1) (W) is “Word”.
2) (DW) is “Double Word”.
3) X_Data / Y_Data / M_Data / S_Data: Address must be 0 or the multiple of 16.
Word No. Bit No.
Read/Write Range
Contacts
Contact type Format
Word No. Bit No.
X_Data Xn N/A n: 0 ~ 377(octal)
Y_Data Yn N/A n: 0 ~ 377(octal)
M_Data Mn N/A n: 0 ~ 1520, 1536 ~ 4080
S_Data Sn N/A n: 0 ~ 1023
T_Coil Tn N/A n: 0 ~ 255
C_Coil Cn N/A n: 0 ~ 255
1-12 Revision January, 2008, Doc. Name: 2007PDD23000007
Read/Write Range
C. Connections (Connector Pinouts)
RS-232 Connection
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
DOP Series
9 pin D-SUB male (RS-232)
RS-485 Connection
9 pin D-SUB male (RS-485)
RXD (2)
TXD (3)
GND (5)
DOP Series
Controller
8 pin Mini DIN male (RS-232)
(5) TXD
(4) RXD
(8) GND
RXD+ (2
TXD+ (3)
RXD- (1)
TXD- (4)
8 pin Mini DIN male (RS-232)
Controller
RS-485 cable connector
D+
D-
Controller
1
5
4
8
Top View
Revision January, 2008, Doc. Name: 2007PDD23000007 1-13
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
AllenBradley MicroLogix PLC Back to Table
A. HMI factory setting
Baud rate: 19200, 8, None, 1.
PLC station number: 1.
Control area/status area: B3:0/B3:10.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format
Word No.
Low Byte
Output File O:n n: 0 ~ 3 N/A 0
Input File I:n n: 0 ~ 3 N/A 1
Status File S2:n n: 0 ~ 65 N/A 2
Bit File B3:n n: 0 ~ 255 N/A 3
Timer Flag T4:n n: 0 ~ 255 N/A 4
Timer Preset Value T4:n.PRE n: 0 ~ 255 N/A 4
Timer Accumulator Value T4:n.ACC n: 0 ~ 255 N/A 4
Counter Flag C5:n n: 0 ~ 255 N/A 5
Counter Preset Value C5:n.PRE n: 0 ~ 255 N/A 5
Counter Accumulator Value C5:n.ACC n: 0 ~ 255 N/A 5
Control File R6:n n: 0 ~ 255 N/A 6
Control Size of Bit Array R6:n.LEN n: 0 ~ 255 N/A 6
Control Reserved File R6:n.POS n: 0 ~ 255 N/A 6
Integer File N7:n n: 0 ~ 255 N/A 7
Bit No.
High Byte
File No.
Bit No
¾
¾
¾
¾
1) After last communication data has been memorized by PLC (PLC will send 0x10 0x05 consecutively),
1-14 Revision January, 2008, Doc. Name: 2007PDD23000007
: Low byte is not used, so the value is 0. High byte stores file number.
Data Size
T4, C5 and R6 only read 1 Word once.
If reading multiple Words once, the communication speed of PLC will be slow.
communication may fail. At this time, power off and power up HMI or power off and power up PLC once.
: Word.
NOTE
Contacts
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Read/Write Range
Contact Type Format
Bit No.
Word No.
Low Byte High Byte
Bits File No.
Output O:n/b n: 0 ~ 3 b: 0 ~ 15 0
Input I:n/b n: 0 ~ 3 b: 0 ~ 15 1
Status S2:n/b n: 0 ~ 65 b: 0 ~ 15 2
Bit B3:n/b n: 0 ~ 255 b: 0 ~ 15 3
Timer T4:n/b n: 0 ~ 255 b: 0 ~ 15
4
T4:n/EN n: 0 ~ 255 15
T4:n/TT n: 0 ~ 255 14
T4:n/DN n: 0 ~ 255 13
Timer Preset Value T4:n.PRE/b n: 0 ~ 255 b: 0 ~ 15 4
Timer Accumulator Value T4:n.ACC/b n: 0 ~ 255 b: 0 ~ 15 4
Counter flag C5:n/b n: 0 ~ 255 b: 0 ~ 15
5
C5:n/CU n: 0 ~ 255 15
C5:n/CD n: 0 ~ 255 14
C5:n/DN n: 0 ~ 255 13
C5:n/OV n: 0 ~ 255 12
C5:n/UN n: 0 ~ 255 11
C5:n/UA n: 0 ~ 255 10
Counter Preset Value C5:n.PRE/b n: 0 ~ 255 b: 0 ~ 15 5
Counter Accumulator Value C5:n.ACC/b n: 0 ~ 255 b: 0 ~ 15 5
Control R6:n/b n: 0 ~ 255 b: 0 ~ 15
R6:n/EN n: 0 ~ 255 15
R6:n/DN n: 0 ~ 255 13
R6:n/ER n: 0 ~ 255 11
R6:n/UL n: 0 ~ 255 10
R6:n/IN n: 0 ~ 255 9
R6:n/FD n: 0 ~ 255 8
Control Size of Bit Array R6:n.LEN/b n: 0 ~ 255 b: 0 ~ 15 6
Control Reserved R6:n.POS/b n: 0 ~ 255 b: 0 ~ 15 6
Integer N7:n/b n: 0 ~ 255 b: 0 ~ 15 7
Bit No
¾
: Low byte stores Bit address. High byte stores file number.
6
Revision January, 2008, Doc. Name: 2007PDD23000007 1-15
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
C. Connections (Connector Pinouts)
RS-232 Connection
DOP Series
9 pin D-SUB male (RS-232)
RXD (2)
TXD (3)
GND (5)
Controller
8 pin Mini DIN male (RS-232)
(7) TXD
(4) RXD
(2) GND
(3) RTS
(6) CTS
Controller
8 pin Mini DIN male
(RS-232)
2
1
3
4
6
7
Top View
1-16 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
AllenBradley SLC5 PLC Back to Table
A. HMI factory setting
Baud rate: 19200, 8, None, 1.
PLC station number: 1.
Control area/status area: B3:0/B3:10.
NOTE
1) Error Check uses CRC (Cyclical Redundancy Check).
B. Definition of controller Read/Write address
Registers
Register Type Format
Read/Write Range
Word No. Bit No.
Low Byte High Byte
Element No.
Slot or File No.
Output File O:n
O:s.n
Input File I:n
I:s.n
Status File S2:n n: 0 ~ 255 N/A File No. = 2
Bit File Bf:n n: 0 ~ 255 N/A f: 10 ~ 255
Timer Flag Tf:n n: 0 ~ 255 N/A f: 10 ~ 255
Timer Preset Value Tf:n.PRE n: 0 ~ 255 N/A f: 10 ~ 255
Timer Accumulator Value Tf:n.ACC n: 0 ~ 255 N/A f: 10 ~ 255
Counter Flag Cf:n n: 0 ~ 255 N/A f: 10 ~ 255
n: 0 ~ 30 N/A Slot No. s = 0
s: 0 ~ 255
File No. = 0
n: 0 ~ 30 N/A Slot No. s = 0
s: 0 ~ 255
File No. = 1
If f is ignored, file no. will be
default setting 3.
If f is ignored, file no. will be
default setting 4.
If f is ignored, file no. will be
default setting 4.
If f is ignored, file no. will be
default setting 4.
If f is ignored, file no. will be
default setting 5.
Counter Preset Value Cf:n.PRE n: 0 ~ 255 N/A f: 10 ~ 255
If f is ignored, file no. will be
default setting 5.
Revision January, 2008, Doc. Name: 2007PDD23000007 1-17
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Read/Write Range
Register Type Format
Word No. Bit No.
Low Byte High Byte
Element No.
Slot or File No.
Counter Accumulator Value Cf:n.ACC n: 0 ~ 255 N/A f: 10 ~ 255
If f is ignored, file no. will be
default setting 5.
Control File Rf:n n: 0 ~ 255 N/A f: 10 ~ 255
If f is ignored, file no. will be
default setting 6.
Control Size of Bit Array Rf:n.LEN n: 0 ~ 255 N/A f: 10 ~ 255
If f is ignored, file no. will be
default setting 6.
Control Reserved File Rf:n.POS n: 0 ~ 255 N/A f: 10 ~ 255
If f is ignored, file no. will be
default setting 6.
Integer File Nf:n n: 0 ~ 255 N/A f: 10 ~ 255
If f is ignored, file no. will be
default setting 7.
Bit No
¾
: Low byte is not used, so the value is 0. High byte stores file number.
Contacts
Read/Write Range
Word No. Bit No.
Contact Type Format
Low Byte High Byte
Element No.
Bits Slot or File No.
Output O:n/b
O:s.n/b
n: 0 ~ 30 b: 0 ~ 15 Slot No. s = 0
s: 0 ~ 255
File No. = 0
Input I:n/b
I:s.n/b
n: 0 ~ 30 b: 0 ~ 15 Slot No.
s = 0
s: 0 ~ 255
File No. = 1
Status S2:n/b n: 0 ~ 31 b: 0 ~ 15 2
Bit Bf:n/b n: 0 ~ 255 b: 0 ~ 15 f: 10 ~ 255
If f is ignored, file no. will be
default setting 3.
Timer Tf:n/b n: 0 ~ 255 b: 0 ~ 15
Tf:n/EN n: 0 ~ 255 15
f: 10 ~ 255
If f is ignored, file no. will be
default setting 4.
Tf:n/TT n: 0 ~ 255 14
Tf:n/DN n: 0 ~ 255 13
Timer Preset Value Tf:n.PRE/b n: 0 ~ 255 b: 0 ~ 15 f: 10 ~ 255
If f is ignored, file no. will be
default setting 4.
1-18 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Read/Write Range
Contact Type Format
Timer Accumulator Value Tf:n.ACC/b n: 0 ~ 255 b: 0 ~ 15 f: 10 ~ 255
Counter Flag Cf:n/b n: 0 ~ 255 b: 0 ~ 15
Cf:n/CU n: 0 ~ 255 15
Cf:n/CD n: 0 ~ 255 14
Cf:n/DN n: 0 ~ 255 13
Cf:n/OV n: 0 ~ 255 12
Cf:n/UN n: 0 ~ 255 11
Cf:n/UA n: 0 ~ 255 10
Counter Preset Value Cf:n.PRE/b n: 0 ~ 255 b: 0 ~ 15 f: 10 ~ 255
Counter Accumulator Value Cf:n.ACC/b n: 0 ~ 255 b: 0 ~ 15 f: 10 ~ 255
Word No. Bit No.
Low Byte High Byte
Element No.
Bits Slot or File No.
If f is ignored, file no. will be
default setting 4.
f: 10 ~ 255
If f is ignored, file no. will be
default setting 5.
If f is ignored, file no. will be
default setting 5.
If f is ignored, file no. will be
default setting 5.
Control Rf:n/b n: 0 ~ 255 b: 0 ~ 15
Rf:n/EN n: 0 ~ 255 15
Rf:n/DN n: 0 ~ 255 13
Rf:n/ER n: 0 ~ 255 11
Rf:n/UL n: 0 ~ 255 10
Rf:n/IN n: 0 ~ 255 9
Rf:n/FD n: 0 ~ 255 8
Control Size of Bit Array Rf:n.LEN/b n: 0 ~ 255 b: 0 ~ 15 f: 10 ~ 255
Control Reserved Rf:n.POS/b n: 0 ~ 255 b: 0 ~ 15 f: 10 ~ 255
Integer Nf:n/b n: 0 ~ 255 b: 0 ~ 15 f: 10 ~ 255
Bit No
¾
: Low byte stores Bit address. High byte stores file number.
NOTE
f: 10 ~ 255
If f is ignored, file no. will be
default setting 6.
If f is ignored, file no. will be
default setting 6.
If f is ignored, file no. will be
default setting 6.
If f is ignored, file no. will be
default setting 7.
1) Device O and I need to assign Slot No. (s). If not assign Slot No., it will use default setting 0.
Revision January, 2008, Doc. Name: 2007PDD23000007 1-19
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
C. Connections (Connector Pinouts)
RS-232
DOP series
9 pin D-SUB male (RS-232)
RXD (2)
TXD (3)
GND (5)
9 pin D-SUB female (RS-232)
(3) TXD
(2) RXD
(5) SG
Controller
(7) RTS
(8) CTS
Controller
9 pin D-SUB female
(RS-232)
Pin1
Top View
1-20 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Cimon PLC (Loader Protocol) Back to Table
A. HMI factory setting
Baud rate: 38400, 8, None, 1, RS-232.
PLC station number: 1.
Control area/status area: D00000 / D00010.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format
Data Length
Word No. Bit No.
Input Xn n: 000-512 N/A Word
Output Yn n: 000-512 N/A Word
General Purpose Relay Mn n: 000-999 N/A Word
General Purpose Relay Ln n: 000-999 N/A Word
Latch Relay Kn n: 000-999 N/A Word
Flags Fn n: 000-127 N/A Word
Timer (Set) TSn n: 0000-4095 N/A Word
Timer (Current) TCn n: 0000-4095 N/A Word
Counter (Set) CSn n: 0000-4095 N/A Word
Counter (Current) CCn n: 0000-4095 N/A Word
General Purpose Word Data Dn n:00000-31999 N/A Word
Step Controller Sn n: 0-99 N/A Byte
Contacts
Read/Write Range
Contact Type Format
Word No. Bit No.
Input Xnb n: 000-512 b: 0-F
Output Ynb n: 000-512 b: 0-F
General Purpose Relay Mnb n: 000-999 b: 0-F
General Purpose Relay Lnb n: 000-999 b: 0-F
Latch Relay Knb n: 000-999 b: 0-F
Flags Fnb n: 000-127 b: 0-F
Timer Status Tb N/A b: 0-4095
Counter Status Cb N/A b: 0-4095
Revision January, 2008, Doc. Name: 2007PDD23000007 1-21
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
C. Connections (Connector Pinouts)
RS-232
DOP series
9 pin D-SUB male (RS-232)
RXD (2 )
Controller
6 pin RJ11
2
Controller
9 pin D-SUB female
(RS-232)
TXD (3)
GND (5)
NOTE
1) Device S
The unit of PLC internal memory is byte and Device S is read by the unit of byte. Therefore, we
recommend the user do not use two consecutive devices S as the read addresses or the interference will
occur. For example, when choosing two numeric input device, please use S24 and S26, do not use S24
and S25.
3
5
1 ~ 6
Top View
1-22 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Copley Servo (Stepnet Protocol) Back to Table
A. HMI factory setting
Baud rate: 9600, 8, None, 1.
PLC station number: 0.
Control area/status area: None.
B. Definition of controller Read/Write address
Registers
Register Type Format
RAM memory Rn n: 00-FF (Hex) N/A DWord
Flash memory Fn n: 00-FF (Hex) N/A DWord
Internal Register IRn n: 0-31 N/A Word
Contacts
Read/Write Range
Data Length
Word No. Bit No.
Contact Type Format
BIT_DEVICE_RB RBn.b n: 00-FF (Hex) b: 0-31
BIT_DEVICE_FB FBn.b n: 00-FF (Hex) b: 0-31
BIT_DEVICE_T0 T0n N/A n: 0
BIT_DEVICE_T1 T1n N/A n: 0
BIT_DEVICE_T2 T2n N/A n: 0
BIT_DEVICE_RST RSTn N/A n: 0
BIT_DEVICE_CPR CPRn n: 00-FF (Hex) N/A
BIT_DEVICE_CPF CPFn n: 00-FF (Hex) N/A
NOTE
1) RB and FB are the bit access of Ram/Flash memory. Therefore, RB0x21.14 indicates bit 14 of Ram
memory 0x21.
2) T0, T1 and T2 is virtual device for simulating Trajectory Generator Command. The number of 0, 1 and 2
indicates the subcommand of that command, so only bit 0 is acceptable.
Read/Write Range
Word No. Bit No.
3) RST is for simulating Reset Command, so only bit 0 is acceptable.
4) CPR and CPF are for simulating Copy Command of Ram and Flash individually. The address (n) after
CPR and CPF is just the copy address for Ram/Flash memory. For example, CPRCA indicates that the
content of Ram memory 0xCA will be copied into Flash memory 0xCA and CPFA6 indicates that the
content of Flash memory 0xA6 will be copied into Ram memory 0xA6.
5) T0, T1, T2, RST, CPR, CPF are all write-only and they can not be used on Reset button.
Revision January, 2008, Doc. Name: 2007PDD23000007 1-23
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
C. Connections (Connector Pinouts)
RS-232
DOP series
9 pin D-SUB male (RS-232)
RXD (2 )
TXD (3)
GND (5)
9 pin D-SUB female (RS-232)
RS-232 Tx
RS-232 RxD
Signal Ground
Controller
1-24 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Danfoss VLT 2800 (FC Protocol) Back to Table
A. HMI factory setting
Baud rate: 9600, 8, Even, 1, RS-485.
PLC station number: 1.
Control area/status area: None / None.
NOTE
1) Delta HMI can be connected to for VLT-2800, 5000, 6000, 7000 controllers.
2) Each data length format of Danfoss AC drive parameter is not fixed, therefore, “Multiple Duplicate”
function is not provided.
3) Max. supported alarm number is 16. If the alarm number is over 16, a fault will occur.
4) Does not support “optimum read/write” characteristic.
5) If the selected element is a string, the minimum data length should be more than 2.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format
Parameter Pn:I n: 0 ~ 999 0 I: 0 ~ 31
Control Word CTRWD 0 N/A N/A
Status Word STAWD 0 N/A N/A
Index No : If the index No. is not used, its default setting will be 0. The default setting of index No. for
¾
parameter P606 ~ P617 is 1.
Please notice that it is necessary to input the index No. when using some parameters of Danfoss
¾
controllers. At this time, please pay close attention on the setting range of index number. If the setting
range is not started from 0, the parameter read & write failure will occur. For example, the index No.
setting range of the parameter P615 is from 1 to 20, if the users do not input the index No., the system
Word No.
Low Byte High Byte
Index No.
Bit No.
will assume the index number is 0 (default setting) and the a fault will occur when the users read or write
the parameter.
CTRWD: Write-only. (Can not be used on the devices which can display the value or input value. It is
¾
recommended to be used on the setting value/setting constant (button), or marco function.)
STAWD: Read-only.
¾
Control & Status Word: Please refer to the explanation on the next page.
¾
Revision January, 2008, Doc. Name: 2007PDD23000007 1-25
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Contacts
Read/Write Range
Contact Type Format
Word No. Bit No.
Low Byte High Byte
Element No.
Bits Index No.
Parameter Pn:I.b n: 0 ~ 999 b: 0 ~ 31 I: 0 ~ 31
Bit No
¾
: Low byte stores Bit address. High byte stores index number.
C. Connections (Connector Pinouts)
RS-485
DOP Series
9 pin D-SUB male (RS-485)
RXD+ (2
TXD+ (3)
RXD- (1)
TXD- (4)
Shell Shell
RS-485 cable connector
68 TXD/RXD+
69 TXD/RXD-
Controller
Explanation of Control Word & Status Word
Control Word
Bit Bit = 0 Bit = 1
15 No Function Reversing
14 Choice of Setup 2 (msb)
13 Choice of Setup 1 (lsb)
12 No Function Relay 04 activated
11 No Function Relay 01 activated
10 Data Not Vaild Vaild
9 Ramp 1 Ramp2
8 Jog 1 OFF ON
7 No Function Reset
6 Ramp Stop Start
5 Hold Ramp Enable
4 Quick-Stop Ramp
3 Coasting Enable
2 DC Brake Ramp
1 Preset reference choice msb
0 Preset reference choice msb
When Bit 10 = 1 (Data Valid), the Control Word is valid.
¾
1-26 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Status Word
Bit Bit = 0 Bit = 1
15 Timer OK Above limit
14 Torque OK Above limit
13 Voltage OK Above limit
12 Temperature OK Over-Temp, auto-start pending
11 Not Running Running
10 Out of Range Frequency OK
9 Local Control Bus Control
8
Speed ≠ reference Speed = reference
7 No Warning Warning
6 Reserved
5 Reserved
4 Reserved
3 No Fault Trip
2 Coasting Enabled
1 VLT not ready Ready
0 Control not ready Ready
Revision January, 2008, Doc. Name: 2007PDD23000007 1-27
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Emerson EC20 Series PLC Back to Table
A. HMI factory setting
Baud rate: 19200, 8, Even, 1 (RS-232).
PLC station number: 0.
Control area/status area: D0 / D10.
B. Definition of controller Read/Write address
Registers
Register Type Format
Data Word Dn n: 0-7999 N/A Word
Special Data Word SDn n: 0-255 N/A Word
Data Word Zn n: 0-15 N/A Word
Timer Tn n: 0-255 N/A Word
Counter Cn n: 0-199 N/A Word
DoubleWord Counter CDWn n: 200-255 N/A DWord
DoubleWord Data Word DDWn n: 0-7998 N/A DWord
Contacts
Contact Type Format
External Output Relay Yb N/A b: 0-377(Octal)
External Input Relay Xb N/A b: 0-377(Octal)
Internal Relay Mb N/A b: 0-1999
Special Internal Relay SMb N/A b: 0-255
Read/Write Range
Data Length
Word No. Bit No.
Read/Write Range
Word No. Bit No.
Status Relay Sb N/A b: 0-991
Timer Tb N/A b: 0-255
Counter Cb N/A b: 0-255
NOTE
PLC Communication Settings:
1) Emerson EC20 series PLC has two communication ports, COM0 and COM1. They are provided for the
communication protocol for connecting to PC, Modbus communication protocol and user-defined
protocol. The default setting is COM0 to be enabled only, so the user needs to set the communication
mode as Modbus RTU via PC software before using it.
2) COM1 supports RS-232 and RS-485.
1-28 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
3) Please note that not all of the addresses can be written when reading SM and SD device. We
recommend the user not to set all of the addresses as write address except when setting parameters.
C. Connections (Connector Pinouts)
RS-232
RS-485
DOP series
9 pin D-SUB male (RS-232)
RXD (2 )
TXD (3)
GND (5)
DOP series
9 pin D-SUB male (RS-232)
D- (1
D- (4)
D+ (2)
D+ (3)
G ND (5)
Controller
TX
RXD
GND
Controller
(3) RS485+
(4) RS485-
GND
COM1
COM1
Revision January, 2008, Doc. Name: 2007PDD23000007 1-29
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Facon FB Series PLC Back to Table
A. HMI factory settings
Baud rate: 9600, 7, Even, 1.
Controller Station number: 1.
Control area/status area: R0 / R10.
B. Definition of controller Read/Write address
Registers
Register Type Format
Data length
Word No. Bit No.
Input Relay WXn n: 0 ~ 9992 N/A Byte
Output Relay WYn n: 0 ~ 9992 N/A Byte
Internal Relay WMn n: 0 ~ 9992 N/A Byte
Step Relay WSn n: 0 ~ 9992 N/A Byte
Data Register Rn n: 0 ~ 65534 N/A Word
Data Register Dn n: 0 ~ 65534 N/A Word
Timer Present Value RTn n: 0 ~ 9999 N/A Word
Counter Present Value RCn n: 0 ~ 9999 N/A Word
Data Register DRCn n: 200 ~ 255 N/A Double Word
Read/Write range
Input Relay / Output Relay / Internal Relay / Special Relay: Address must be the multiple of 8.
¾
Contacts
Read/Write range
Contact type Format
Word No. Bit No.
Input Relay Xn N/A n: 0 ~ 9999
Output Relay Yn N/A n: 0 ~ 9999
Internal Relay Mn N/A n: 0 ~ 9999
Step Relay Sn N/A n: 0 ~ 9999
Timer Flag Tn N/A n: 0 ~ 9999
Counter Flag Cn N/A n: 0 ~ 9999
1-30 Revision January, 2008, Doc. Name: 2007PDD23000007
C. Connections (Connector Pinouts)
RS-232
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
DOP Series
9 pin D-SUB male (RS-232)
RXD (2)
TXD (3)
GND (5)
(2) TXD
(1) RXD
(6) SG
Controller
15 pin male (RS-232)
(3) RTS
(4) CTS
RS-232
Connecting to CB (Communication Board) or CM (Communication Module)
FBs Series Port 1
9 pin D-SUB male (RS-232)
DOP Series
9 pin D-SUB male (RS-232)
Controller
RXD (2) (2) TXD
TXD (3)
(3) RXD
Controller
15 pin male (RS-232)
Pin1
9 pin D-SUB male (RS-232)
Top View
Controller
Pin1
RS-232
FBs Series Port 0
DOP Series
9 pin D-SUB male (RS-232)
GND (5)
(5) GND
(8) RTS
(7) CTS
4 pin Mini DIN male (RS-232)
RXD (2) (4) TXD
TXD (3)
GND (5)
(2) RXD
(1) GND
(3) +5V
Controller
Controller
4 pin Mini DIN male
(RS-232)
2
1
3
4
Revision January, 2008, Doc. Name: 2007PDD23000007 1-31
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Festo PLC Back to Table
A. HMI factory settings
Baud rate: 9600, 8, None, 1.
Controller Station number: 0. (no PLC station number in protocol)
Control area/status area: R0 / R10.
NOTE
1) Connectable PLC: FEC-FC Model
B. Definition of controller Read/Write address
Registers
WORD_DEVICE_IW Iwn n: 0 ~ 255 N/A Word
WORD_DEVICE_OW Own n: 0 ~ 255 N/A Word
WORD_DEVICE_FW FWn n: 0 ~ 9999 N/A Word
WORD_DEVICE_TW TWn n: 0 ~ 255 N/A Word
WORD_DEVICE_CW CWn n: 0 ~ 255 N/A Word
WORD_DEVICE_R Rn n: 0 ~ 255 N/A Word
WORD_DEVICE_TP TPn n: 0 ~ 255 N/A Word
WORD_DEVICE_CP CPn n: 0 ~ 255 N/A Word
Contacts
Register Type Format Word No. Bit No. Data Size
Register Type Format Word No. Bit No.
BIT_DEVICE_I In.b n: 0 ~ 255 b: 0 ~ 15
BIT_DEVICE_O On.b n: 0 ~ 255 b: 0 ~ 15
BIT_DEVICE_F Fn.b n: 0 ~ 9999 b: 0 ~ 15
BIT_DEVICE_T Tn N/A n: 0 ~ 255
BIT_DEVICE_C Cn N/A n: 0 ~ 255
BIT_DEVICE_TON TONn N/A n: 0 ~ 255
BIT_DEVICE_TOFF TOFFn N/A n: 0 ~ 255
BIT_DEVICE_T / BIT_DEVICE_C / BIT_DEVICE_TON / BIT_DEVICE_TOFF: Only 1 Bit can be
¾
transferred for each communication.
Only 1 Bit or 1 Word can be transferred for each write command.
¾
1-32 Revision January, 2008, Doc. Name: 2007PDD23000007
C. Connections
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
NOTE
1) Communication port of PLC: COM port
2) It needs to use the dedicated cable for FESTO controllers Æ Cable for transferring TTL to RS-232 and it
is 6 pin RJ-12 connector at PLC side.
Revision January, 2008, Doc. Name: 2007PDD23000007 1-33
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
GE Fanuc 90 Series SNP PLC Back to Table
A. HMI factory settings
Baud rate: 19200, 8, ODD, 1.
Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)
Control area/status area: %R1 / %R10.
NOTE
1) Please notice that no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication
is allowed.
2) If the PLC enabled “Check Password” function, the user needs to set the password by clicking Option >
Configuration > Communication. The user can find Controller Settings and set PLC password on
Communication Tab in the Configuration dialog box. Please enter a 4-digit password (If entering a
password that exceeds 4-digit number, only the first 4-digit number is valid).
B. Definition of controller Read/Write address
Registers
Register Type Format
Discrete Inputs %In n: 1 ~ 12288 N/A Word (the multiple of 16 + 1)
Discrete Outputs %Qn n: 1 ~ 12288 N/A Word (the multiple of 16 + 1)
Discrete Temporaries %Tn n: 1 ~ 256 N/A Word (the multiple of 16 + 1)
Read/Write range
Data length
Word No. Bit No.
Discrete Internals %Mn n: 1 ~ 12288 N/A Word (the multiple of 16 + 1)
%SA Discretes %SAn n: 1 ~ 128 N/A Word (the multiple of 16 + 1)
%SB Discretes %SBn n: 1 ~ 128 N/A Word (the multiple of 16 + 1)
%SC Discretes %SCn n: 1 ~ 128 N/A Word (the multiple of 16 + 1)
%S Discretes %S-n n: 1 ~ 128 N/A Word (the multiple of 16 + 1)
Genius Global Data %Gn n: 1 ~ 7680 N/A Word (the multiple of 16 + 1)
Registers %Rn n: 1 ~ 16384 N/A Word
Analog Inputs %AIn n: 1 ~ 8192 N/A Word
Analog Outputs %AQn n: 1 ~ 8192 N/A Word
1-34 Revision January, 2008, Doc. Name: 2007PDD23000007
Contacts
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Contact Type Format
Discrete Inputs %In N/A n: 1 ~ 12288
Discrete Outputs %Qn N/A n: 1 ~ 12288
Discrete Temporaries %Tn N/A n: 1 ~ 256
Discrete Internals %Mn N/A n: 1 ~ 12288
%SA Discretes %SAn N/A n: 1 ~ 128
%SB Discretes %SBn N/A n: 1 ~ 128
%SC Discretes %SCn N/A n: 1 ~ 128
%S Discretes %-Sn N/A n: 1 ~ 128
Genius Global Data %Gn N/A n: 1 ~ 7680
C. Connections (Connector Pinouts)
RS-232
DOP
9 pin D-SUB male
(RS-232)
Word No. Bit No.
Controller
RJ-45 cable connector
(RS-232)
Read/Write range
RJ-45 cable connector
Controller
(RS-232)
RS-422
RXD (2) (5) TXD
TXD (3)
GND (5)
DOP Series
9 pin D-SUB male (RS-232)
RXD- (1
RXD+ (2)
TXD+ (3)
TXD- (4)
(1 2 ) SD ( A')
(13) SD( B')
(11) RD(B)
(10 ) RD(A)
(9 ) RD ( *)
(6 ) RT S(A)
(15 ) CTS(A')
(8 ) CT S(B)
(6) RXD
(4) GND
15 pin male (RS-232)
Controller
(NOTE 1 )
8
1
Top V iew
Controller
15 pin male (RS-232)
Pin1
Top View
(14 ) RTS(B')
NOTE
1) (9) RD(*) should be connected to 10(RD)(A) in serial. But if connecting PLC model is Series 90-70 PLC
IC697CPU731 and IC697CPU771, (9) RD(*) needs to be connected to 11(RD)(B).
Revision January, 2008, Doc. Name: 2007PDD23000007 1-35
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Hitachi EH Series PLC Back to Table
A. HMI factory settings
Baud rate: 19200, 7, EVEN, 1.
Controller station number: 0.
Control area/status area: WR0 / WR10.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format
Data Length
Word No. Bit No.
External Input WX WXrusn Word
s: 0-A n: 0-7
External Output WY WYrusn
r: 0-4
u: 0-4
N/A
Word
Internal Output WR WRn n: 0-C3FF N/A Word
Special Internal Output WR WRn n: F000-F1FF N/A Word
Shared Internal Output WM WMn n: 0-3FF N/A Word
CPU Link Area 1 WL WLn n: 0-3FF N/A Word
CPU Link Area 2 WL WLn n: 1000-13FF N/A Word
Timer/Counter TC TCn n: 0-511 N/A Word
Contacts
Read/Write Range
Register Type Format
Word No. Bit No.
External Input X Xrusb
s: 0-A N/A
External Output Y Yrusb
r: 0-4
u: 0-4
b: 0-95
Internal Output R Rb N/A b: 0-7FF
Shared Internal Output M Mnb n: 0-3FF b: 0-F
CPU Link Area 1 L Lnb n: 0-3FF b: 0-F
CPU Link Area 2 L Lnb n: 1000-13FF b: 0-F
On Delay Timer TD TDb N/A b: 0-255
Single-shot Timer SS SSb N/A b: 0-255
Up Counter CU CUb N/A b: 0-511
Up-down Counter up input CTU CTUb N/A b: 0-511
Up-down Counter down input CTD CTDb N/A b: 0-511
Up-down Counter down output CT CTb N/A b: 0-511
Progress Value Clear CL CLb N/A b: 0-511
Rising Edge Detection DIF DIFb N/A b: 0-511
Falling Edge Detection DFN DFNb N/A b: 0-511
1-36 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
NOTE
1) Communication Settings:
y In Hitachi EH series PLC, only port 1 can be used for communication through procedure 2. The
user can select procedure type via DIP switch and specific Special Internal Input (WR).
y In Hitachi EH-150 series PLC, only EH-CPU***A/448/516/548 can use procedure 2.
y It needs to set the external I/O (WX, WY, X, Y) of EH series PLC first or HMI cannot read and write
their addresses.
y Hitachi EH series PLC and PC can be connected only by procedure 1 (@19200bps)
2) CPU Relevant Notice:
EH-150
y DIP5 should be set to ON.
y If DIP5 is set to ON, PLC will determine the proper procedure (1 or 2) by the value of WRf037.
When setting the address, the highest bit of write value must be 1 and then PLC can write the value
into other seven bits. The data will not lost even when the power of PLC is cut off. Therefore,
i) Write the value 0x8000 into the address. After restart PLC, the address value will become
0x0000 and perform communication by procedure 1.
ii) Write the value 0xC000 into the address. After restart PLC, the address value will become
0x4000 and perform communication by procedure 2.
y Use DIP3 and DIP4 to set the communication speed of port 1.
i) When DIP3 is ON and DIP4 is OFF, the communication speed is 19200bps.
y Use DIP6, PHL to set the communication speed of port 2.
i) When DIP6 is ON and PHL is OFF, the communication speed is 19200bps.
ii) The EH-150 PLC is a “Base Unit” which has a built-in CPU module. This unit allows easy
connection of extension module, such as “External I/O”.
MicroEH
y DIP5 is used to set communication speed.
i) When SW1 is ON, the communication speed is 19200bps.
y MicroEH PLC will determine the proper procedure (1 or 2) by the value of WRf01a. Different than
EH-150, when setting the address, the highest bit of write value does not need to be 1. But the data
will lost even the power of PLC is cut off. However, if set the value of R7f6 to 1, the data of WRf01a
will be saved into Flash memory.
i) 0x0000 for procedure 1.
ii) 0x8000 for procedure 2.
iii) If the PLC uses procedure 2 and saves the data into Flash memory, it cannot connect to
the peripheral devices and programs (Ladder Editor) that only support procedure 1.
iv) Standard External I/O built in MicroEH PLC are listed as below:
Digital Type
Revision January, 2008, Doc. Name: 2007PDD23000007 1-37
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
slot 0: X48
slot 1: Y32
slot 2: empty16
Analog Type
slot 3: X4W
slot 4: Y4W
3) Communication Protocol:
External I/O (X, Y, WX, WY)
y Address rules:[r][u][s][n/b].
i) Word no/Bit no [n/b]
ii) Slot number [s]
iii) Unit number [u]
iv) Remote number [r]
Only support EH-150
v) ex1: WX103 represents unit 1, word 3 of slot 0
vi) ex2: X103 represents bit 3 of slot 1
vii) ex3: X113 represents bit 13 of slot 1
viii) ex4: Y2004 represents unit 2, bit 4 of slot 0
ix) ex5: Y2104 represents unit 2, bit 4 of slot 1
y External I/O (X, Y, WX, WY) cannot read and write several addresses one time so they do not
support “optimum read/write” characteristic.
Internal Output
y Shared Internal Output (M, WM) read and write the same address. For example,
i) M3ab and WM3a: the read and write address of M3ab is the bit b of WM3a.
y CPU Link Area (L, WL) are the same as Shared Internal Output (M, WM). CPU Link Area (L, WL)
also read and write the same address.
i) Only support EH-150.
C. Connections (Connector Pinouts)
RS-232
DOP Series
9 pin D-SUB male (RS-232)
RX D (2
TXD (3)
GND (5)
RTS (7) (7) DR1
CT S (8) (8 ) RS1
9 pin D-SUB male (RS-232)
(5) SD1
(6) R D1
(1) SG1
Controller
Controller
9 pin D-SUB male (RS-232)
Pin1
Top View
1-38 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
HUST CNC Controller Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 2.
Controller station number: 0.
Control area/status area: W0 / W10.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format
Word No. Bit No.
Word Register Wn n: 0 ~ 13500 N/A Word
Double Word Register Dn n: 0 ~ 13500 N/A Double Word
NOTE
Data Length
1) The unit for Hust CNC controller is D Word and Wn is the low word of Dn.
Contacts
Contact Type Format
BIT_DEVICE_B Bm.n m: 0 ~ 13500 n: 0 ~ 31
BIT_DEVICE_I In N/A n: 0 ~ 255 (8 DW)
BIT_DEVICE_O On N/A n: 0 ~ 255 (8 DW)
BIT_DEVICE_C Cn N/A n: 0 ~ 255 (8 DW)
BIT_DEVICE_S Sn N/A n: 0 ~ 255 (8 DW)
BIT_DEVICE_A An N/A n: 0 ~ 1023 (32 DW)
C. Connections (Connector Pinouts)
RS-232
DOP Series
9 pin D-SUB male (RS-232)
RXD (2)
TXD (3)
GND (5)
9 pin D-SUB male (RS-232)
(2) TXD
(3) RXD
(5) SG
Word No. Bit No.
Controller
(8) RTS
Read/Write range
9 pin D-SUB male
Controller
(RS-232)
Pin1
(7) CTS
Revision January, 2008, Doc. Name: 2007PDD23000007 1-39
Top View
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Jetter Nano Series PLC Back to Table
A. HMI factory settings
Baud rate: 9600, 8, EVEN, 1 (RS-232).
Controller station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)
Control area/status area: WR0 / WR10.
NOTE
1) Please notice that no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication
is allowed.
2) Only 1 Bit or 1 Word can be transferred for each communication.
3) In general, each register occupies max. 24 Bits. However, some registers occupies 8 Bits only.
4) Because the initial time of this controller is longer, it is recommended to set HMI startup delay time
(Recommended time is 10 seconds).
5) When the register R is used for Double Word device, please set its format as signed format. (The default
format in Screen Editor is signed format)
B. Definition of controller Read/Write address
Registers
Register Type Format
Read/Write Range
Word No. Bit No.
Data
Length
16 Bits Register WRn n: 0 ~ 32767 N/A 16 Bits
32 Bits Register Rn n: 0 ~ 32767 N/A 24 Bits
Only the first 16 bits are used for WRn registers.
Only the first 24 bits are used for Rn registers, the highest 8 bits (Bit 24 ~ 31) are set to 0 by default setting.
(24-bit Integer : If in decimal format, the range is -8388608 ~ +8388607. If in hexadecimal format, the range
is 0x000000 ~ 0xFFFFFF.)
NOTE
1) The difference between WRn and Rn:
y When using devices that the data length is in Word, only Bit 0 ~ 15 are valid for both of WRn and
Rn registers.
y When using devices that the data length is in Double Word,
if the read/write address format is set to WRn, the Bit 0 ~ 15 of WRn register is the low word of a
read/write value, the Bit 0 ~ 15 of WRn+1 register is the high word of a read/write value.
1-40 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
if the read/write address format is set to Rn, only Bit 0 ~ 23 are valid for Rn registers.
(Notice: As the Jetter controller is a 24-bit format controller, the valid setting range is 24 Bits.
If exceeds this range, HMI will stop read/write operation and show “… ..Value is Incorrect”
on the screen. So, please do not set any bit on Bit24 ~ Bit31 (Bit24 ~ Bit31 cannot be written).
y When using devices that the data length is in m Words,
if the read/write address format is set to WRn, the Bit 0 ~ 15 of WRn register is the lowest word of a
read/write value and the Bit 0 ~ 15 of WRn+m-1 register is the highest word of a read/write value.
if the read/write address format is set to Rn, the Bit 0 ~ 23 of Rn register is the lowest word of a
read/write value and the Bit 0 ~ 23 of Rn+1 register is the highest word of a read/write value.
Each register is regards as a “Double Word”. The value of Bit24 ~ Bit31 is 0.
Contacts
Contact type Format
Input Relay Inbb n: 1 ~ 32 bb: 01 ~ 08
Output Relay Onbb n: 1 ~ 32 bb: 01 ~ 08
Flag Relay Fn N/A n: 0 ~ 32767
C. Connections (Connector Pinouts)
RS-232
DOP Series
9 pin D-SUB male (RS-232)
Word No. Bit No.
Controller
9 pin D-SUB male (RS-232)
Read/Write Range
RXD (2) (2) TXD
TXD (3)
GND (5)
(3) RXD
(7) GND
Controller
9 pin D-SUB male
(RS-232)
Pin1
Top View
The pin definition of the cable of Jetter controller is different than the general RS-232 cable. Please pay
¾
close attention.
Revision January, 2008, Doc. Name: 2007PDD23000007 1-41
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Jetter JC Series PLC Back to Table
A. HMI factory settings
Baud rate: 9600, 8, EVEN, 1 (RS-232).
Controller station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)
Control area/status area: WR0 / WR10.
NOTE
1) Please notice that no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication
is allowed.
2) Only 1 Bit or 1 Word / 2 Words can be transferred for each read and write command.
B. Definition of controller Read/Write address
Registers
Register Type Format
16 Bits Register WRn n: 0 ~ 32767 N/A 16 Bits
32 Bits Register Rn n: 0 ~ 32767 N/A 24 Bits
The characteristics of WRn and Rn of JC series are the same as the Nano series. Please refer to the section
that introduces Jetter Nano Series PLC
Contacts
Read/Write Range
Word No. Bit No.
.
Data
Length
Contact type Format
Word No. Bit No.
Input Relay Inbb n: 1 ~ 32 bb: 01 ~ 16
Output Relay Onbb n: 1 ~ 32 bb: 01 ~ 16
Flag Relay Fn N/A n: 0 ~ 32767
Read/Write Range
1-42 Revision January, 2008, Doc. Name: 2007PDD23000007
C. Connections (Connector Pinouts)
RS-232
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
DOP Series
9 pin D-SUB male (RS-232)
RXD (2) (8) TXD
TXD (3)
GND (5)
Controller
8 pin Mini DIN male (RS-232)
(4) RXD
(2) GND
Controller
8 pin Mini DIN male (RS-232)
2
4
8
Top View
Revision January, 2008, Doc. Name: 2007PDD23000007 1-43
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Keyence KV/KZ Series Back to Table
A. HMI factory settings
Baud rate: 9600, 8, EVEN, 1 (RS-232).
Controller station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)
Control area/status area: DM-0 / DM-10.
NOTE
1) Please notice that no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication
is allowed.
2) Only 1 Bit or 1 Word can be transferred for each communication. (Communication speed is slow.)
B. Definition of controller Read/Write address
Registers
Register Type Format
Timer T-nnn nnn: 0 ~ 199 N/A Word
Counter C-nnn nnn: 0 ~ 199 N/A Word
High-speed Counter CTH-n n: 0 ~ 1 N/A Word
High-speed Counter
Comparator
Data Memory DM-nnnn nnnn: 0 ~ 1999 N/A Word
Temporary Data Memory TM-nn nn: 0 ~ 31 N/A Word
Read/Write Range
Data Length
Word No. Bit No.
CTC-n n: 0 ~ 3 N/A Word
Timer Preset Value PT-nnn nnn: 0 ~ 199 N/A Word
Counter Preset Value PC-nnn nnn: 0 ~ 199 N/A Word
CTC Preset Value PCTC-n n: 0 ~ 3 N/A Word
Contacts
Contact type
Relay R-nnnbb nnn: 0 ~ 69 bb: 00 ~ 15
Timer T-nnn N/A nnn: 0 ~ 199
Counter C-nnn N/A nnn: 0 ~ 199
High-speed counter
comparator
1-44 Revision January, 2008, Doc. Name: 2007PDD23000007
Format
Word No. Bit No.
CTC-n N/A n: 0 ~ 3
Read/Write Range
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
NOTE
When using the protocol format of KV series and connecting to KZ-80T PLC, some errors occur. Please refer
to the following description:
1) Readable Timer address is not continuous. For example, T-0 ~ T-9 can be read, T10 cannot be read,
T11 ~ T20 can be read, T21 ~ T50 cannot be read, …etc.
2) Counter cannot be read. For example,
Registers: C- (Counter), CTH- (High-speed counter), CTC- (High-speed counter comparator),
PC- (Counter preset value), PCTC- (CTC preset value) they all cannot be read.
Contacts: C- (Counter), CTC- (High-speed counter comparator) they all cannot be read also.
C. Connections (Connector Pinouts)
RS-232
KV Series
9 pin D-SUB male (RS-232)
DOP
RJ-11 cable connector (RS-232)
Controller
Controller
RJ-11 cable connector (RS-232)
RXD (2) (3) SD
TXD (3)
GND (5)
KZ Series
DOP
9 pin D-SUB male (RS-232)
RXD (2) (5) SD
(5) RD
(4) SG
RJ-11 cable connector (RS-232)
Controller
6 - 1
Top V iew
PLC side (Comm. Port)
Controller
RJ-11 cable connector (RS-232)
6 - 1
Top V iew
TXD (3)
GND (5)
(3) RD
(4) SG
PLC side (Comm. Port)
Revision January, 2008, Doc. Name: 2007PDD23000007 1-45
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
NOTE
1) Communication Cable: The pins of SD and RD of KZ-80T and KV Series are reverse.
1-46 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Koyo SU/DL Series Back to Table
A. HMI factory settings
Baud rate: 9600, 8, ODD, 1 (RS-232).
Controller station number: 1.
Control area/status area: V1400 / V1410.
B. Definition of controller Read/Write address
Registers
Register Type Format
Read/Write Range
Word No. Bit No.
Data
Length
Timer Accumulated Vn n: 0 ~ 177 (octal) N/A Word
Counter Accumulated Vn n: 1000 ~ 1177 (octal) N/A Word
V Memory Vn n: 1400 ~ 7777 (octal) N/A Word
Linker Relays Vn n: 40000 ~ 40037 (octal) N/A Word
Input Status Vn n: 40400 ~ 40423 (octal) N/A Word
Output Status Vn n: 40500 ~ 40523 (octal) N/A Word
Control Relays Vn n: 40600 ~ 40635 (octal) N/A Word
Stage Vn n: 41000 ~ 41027 (octal) N/A Word
Timer Status Vn n: 41100 ~ 41107 (octal) N/A Word
Counter Status Vn n: 41140 ~ 41147 (octal) N/A Word
Spec. Relay 1 Vn n: 41200 ~ 41205 (octal) N/A Word
Spec. Relay 2 Vn n: 41216 ~ 41230 (octal) N/A Word
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
Linker Relays GXn N/A n: 0 ~ 777 (octal)
Input Status Xn N/A n: 0 ~ 477 (octal)
Output Status Yn N/A n: 0 ~ 477 (octal)
Control Relays Cn N/A n: 0 ~ 737 (octal)
Stage Sn N/A n: 0 ~ 577 (octal)
Timer Status Tn N/A n: 0 ~ 177 (octal)
Counter Status CTn N/A n: 0 ~ 177 (octal)
Spec. Relay 1 SPn N/A n: 0 ~ 137 (octal)
Spec. Relay 2 SPn N/A n: 320 ~ 617 (octal)
Revision January, 2008, Doc. Name: 2007PDD23000007 1-47
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
C. Connections (Connector Pinouts)
RS-232
DOP
9 pin D-SUB male (RS-232)
RXD(2)
TXD(3)
GND(5)
Controller
RJ-11 cable connector (RS-232)
(4)TXD
(3)RXD
(1)GND
(6)GND
Controller
RJ-11 cable connector
(RS-232)
1 - 6
Top V iew
1-48 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Koyo K-Sequence Back to Table
A. HMI factory settings
Baud rate: 9600, 8, ODD, 1 (RS-232).
Controller station number: 1.
Control area/status area: R1400 / R1420.
NOTE
1) If read / write address exceeds the valid range, HMI will stop read/write operation and show “….Error
6….. Command Can Not be Executed….” on the screen.
B. Definition of controller Read/Write address
Registers
Register Type Format
Read/Write Range
Word No. Bit No.
Data
Length
Input Status Xnnnn nnnn: 0 ~ 1760 (octal) N/A Word
Output Status Ynnnn nnnn: 0 ~ 1760 (octal) N/A Word
Link Relays GXnnnn nnnn: 0 ~ 3760 (octal) N/A Word
Relays GQnnnn nnnn: 0 ~ 3760 (octal) N/A Word
Relays Mnnnn nnnn: 0 ~ 3760 (octal) N/A Word
Stage Snnnn nnnn: 0 ~ 1760 (octal) N/A Word
Timer Status Tnnn nnn: 0 ~ 360 (octal) N/A Word
Control Relays Cnnn nnn: 0 ~ 360 (octal) N/A Word
Special Relay 1 SPnnn nnn: 0 ~ 760 (octal) N/A Word
Register Rnnnnn nnnnn: 0 ~ 41237 (octal) N/A Word
Register Pnnnnn nnnnn: 0 ~ 37777 (octal) N/A Word
nnnn: Is in octal format and must be the multiple of 16 except for R and P.
¾
Contacts
Contact type Format
Word No. Bit No.
Input Status Xnnnn N/A nnnn: 0 ~ 1777 (octal)
Read/Write Range
Output Status Ynnnn N/A nnnn: 0 ~ 1777 (octal)
Linker Relays GXnnnn N/A nnnn: 0 ~ 3777 (octal)
Relays GQnnnn N/A nnnn: 0 ~ 3777 (octal)
Control Relays Mnnnn N/A nnnn: 0 ~ 3777 (octal)
Stage Snnnn N/A nnnn: 0 ~ 1777 (octal)
Timer Status Tnnn N/A nnn: 0 ~ 377 (octal)
Revision January, 2008, Doc. Name: 2007PDD23000007 1-49
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Contact type Format
Counter Status Cnnn N/A nnn: 0 ~ 377 (octal)
Spec. Relay 1 SPnnn N/A nnn: 0 ~ 777 (octal)
C. Connections (Connector Pinouts)
RS-232
Port 0 Communication Cable
DOP
9 pin D-SUB male (RS-232)
RXD(2)
TXD(3)
GND(5)
RJ-11 cable connector (RS-232)
Word No. Bit No.
Controller
(4)TXD
(3)RXD
(1)GND
(6)GND
(Note 1)
Read/Write Range
Controller
RJ-11 cable connector
(RS-232)
1 - 6
Top V iew
If pin 6 is not grounded, a communication error may occur when connecting to a CKD SM 24R controller.
¾
Ensure that pin 6 is well grounded. This will not cause any problems when connecting to SN32DRA
controller.
DOP Series
9 pin D-SUB male (RS-232)
RXD (2)
TXD (3)
GND (5)
RS-485
Port 1 Communication Cable
DOP
9 pin D-SUB male (RS-485)
9 pin D-SUB male (RS-232)
D- (1)
Controller
(3) TXD
(2) RXD
(5) SG
Controller
9 pin D-SUB male (RS-232)
Pin1
DOP
9 pin D-SUB male (RS-485)
Top View
D-
D- (4)
D+ (2)
D+ (3)
1-50 Revision January, 2008, Doc. Name: 2007PDD23000007
D+
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
The corresponding registers of CCM2 and K-Sequence
Address Corresponding Relationship:
CCM2 K sequence SN32DRA
V R R
X X I
Y Y Q
C M M
S S S
T T T
CT C C
SP SP SP
Revision January, 2008, Doc. Name: 2007PDD23000007 1-51
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Lenze LECOM-A/B Protocol Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1 (Baudrate: 1200/2400/4800/9600/19200).
Controller station number: 1 (1~99).
Control area/status area: None / None.
NOTE
1) Please pay close attention to each pin definition of cable connectors.
2) Ensure not to use the general RS-232 5-pin cable. This is because if pin 2, 3, 5, 7, 8 are all connected to
the drive, the drive can not recognize the communication signal and can not identify what kind of
communication it is.
3) For more detailed information of pin definition of cable connectors, please refer to the C. Connections
(Connector Pinouts) of Lenze LECOM-A/B Protocol controller.
4) Ensure the HMI communication data format (The communication data written into the drive) is correct.
The Word “m” in the following table is used to specify the HMI communication data format.
5) Ensure the HMI display data format (Property table/Setting value...etc.) is correct.
6) When using broadcast function, please check if device is available. This is because the broadcast
function can be activated only when the user chooses “write only” device for broadcast station number
(only choose setting value/setting constant (button) and then the broadcast function can be used). If
choosing other devices, the system will ask you to read back the drive setting value, so please ensure to
choose the correct device. If choosing the incorrect devices, a “Controller Station Number Error…” fault
message will display on HMI screen.
7) Support 82XX frequency inverters and 93XX servo inverters.
B. Definition of controller Read/Write address
Registers (n, m, y are in decimal)
Read/Write Range
Register Type Format
CWn n: 1 ~ 10000 N/A N/A Word Parameter without subcode
CWn.m n: 1 ~ 10000 m: 0 ~ 23 N/A Word
Parameter with subcode CWn/y n: 1 ~ 10000 N/A y:1 ~ 255 Word
CWn/y.m n: 1 ~ 10000 m: 0 ~ 23 y:1 ~ 255 Word
Word No. Bit No.
Data Length
LowByte HighByte
subcode
1-52 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Read/Write Range
Register Type Format
Parameter without subcode
Parameter with subcode CDn/y n: 1 ~ 10000 N/A y:1 ~ 255 DoubleWord
CDn/y.m n: 1 ~ 10000 m: 0 ~ 23 y:1 ~ 255 DoubleWord
NOTE
1) m : HMI communication data format
2) The value of m represents the different communication data format:
CDn n: 1 ~ 10000 N/A N/A DoubleWord
CDn.m n: 1 ~ 10000 m: 0 ~ 23 N/A DoubleWord
Word No. Bit No.
Data Length
LowByte HighByte
subcode
y If m value is undefined: ASCII hexadecimal format (VH). (4 or 8 numbers.)
y m >= 23 : ASCII hexadecimal format (VH). (4 or 8 numbers.)
y m = 0 ~10 : unsigned, ASCII decimal format (VD).
m represents decimal place, For example:
m=0 Æ no decimal place
m=1 Æ one decimal place (tenth)
m=2 Æ two decimal place (hundredth)
y m = 11 ~20 : signed, ASCII decimal format (VD).
m represents decimal place, For example:
m=11 Æ one decimal place (tenth)
m=12 Æ two decimal place (hundredth)
y m = 21 : signed, ASCII decimal format (VD).
without decimal place
y m = 22 : ASCII hexadecimal format (VH). 2 numbers.
when using this format, the write value will be limited within the range of 0~0xFF
(low byte).
For example: when entering 0x1234 during communication, the actual write value
is 0x34, not 0x1234.
Contacts (n, b, y are in decimal)
Read/Write Range
Register Type Format
Parameter without subcode CBn.b n: 1 ~ 10000 b: 0 ~ 31 N/A
Parameter with subcode CBn/y.b n: 1 ~ 10000 b: 0 ~ 31 1 ~ 255
Revision January, 2008, Doc. Name: 2007PDD23000007 1-53
Word No. Bit No.
LowByte HighByte
subcode
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Only VH type parameter can provide Bit read/write function (it is convenient for the user to read/write Bit No.
of parameters).
CBn.b, CWn (CWn.m), CDn (CDn.m): read/write address is the same (address n).
NOTE
1) Since the data format of this controller is complicated (a. VS (String format), b. VO (Octet string format
data blocks), c. VH (ASCII hexadecimal format)(1, 2, 4 bytes), d. VD (ASCII decimal format)(positive,
negative, decimal,..)) and the communication format is not compatible, therefore, it is needed to ensure
the HMI communication data format is correct, or an error may occur.
2) Registers: only can read/write the data of ASCII hexadecimal format (VH), ASCII decimal format (VD)
(i.e. Either VH or VD data format can be set via communication.)
Contacts: only can read/write the data of ASCII hexadecimal format (VH)
HMI display data format (Property table/Setting value...etc.) should also be correct.
Explanation:
y Registers: only can read/write the data of VH, VD. HMI needs to set communication data format
(please refer to 4), 5) and 6)). String format (VS), and Octet string format for data blocks (VO) can
not be used. If the controller returns the data in VS or VO format, HMI will show “……Value Is
Incorrect” on the screen.
y Contacts: only can read/write the data of ASCII hexadecimal format (VH). Only VH type parameter
can provide Bit read/write function. If the controller returns the data in other format, HMI will show
“……Value Is Incorrect” on the screen.
y Do not write the inexistent Bit address, or HMI will show “….Write …. Command Can Not be
Executed” on the screen.
For example: CW470/1. The valid value of CW470/1 is within the range of 0 ~ 0xFF. Therefore, Bit
8 ~31 is not existed. Although HMI will show the value of Bit 8 ~31 is 0, the user can not write or set
the value.
y The settings of ASCII hexadecimal format (VH) and ASCII decimal format (VD) should be correct. If
the VD data is set in VH format in HMI (m value is undefined, or m=22 or 23) or the VH data is set
in VD format in HMI (m=0 ~ 21), when HMI write the data, HMI will show “….Write …. Command
Can Not be Executed” on the screen or tell the user the write value is incorrect.
y The decimal place of ASCII decimal format (VD) should be set correctly, or the write value will not
be correct. The decimal place displayed on HMI should also be correct, or the display value will be
incorrect.
y ASCII hexadecimal format (VH), 2 numbers (m = 22). The value is limited to 2 numbers. Using this
format the write value will be limited within the range of 0 ~ 0xFF (low byte) automatically.
3) Station Number and Broadcast
y The valid station number is from 0 to 99. If exceeds this range, HMI will stop read/write operation
and show “Controller Station Number Error …”on the screen.
1-54 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
y 00 indicates the global broadcasting number (1~99).
y 10, 20, 30, 40, 50, 60, 70, 80, 90 are local broadcasting number.
The affected ranges are: 11~19, 21~29, 31~39, 41~49, 51~59, 61~69, 71~79, 81~89 and 91~99
respectively. Only choose setting value/setting constant (button), and then the broadcast function
can be used. If choosing other devices, the system will be confused while reading back the drive
setting value via broadcast function, so please ensure to choose the correct device. If choosing the
incorrect devices, a “Controller Station Number Error…” fault message will display on HMI screen.
y Use in LECOM-A/B protocol. 82XX frequency AC drives and 93XX servo drives all use this protocol.
4) Explanation of communication error address
y Registers: display CW n, CWy n, CD n, CDy n in order
y Contacts: display CB n, CByn in order (n: address value)
5) HMI data format explanation
y Some controller parameters are in Word and some are in Double Word. Therefore, there are two
kinds of data format: Word ( CWn (CWn.m), CWn/y(CWn/y.m) ) and Double Word ( CDn (CDn.m),
CDn/y(CDn/y.m) ).
y Furthermore, regarding to Bit No., HMI only read/write 32Bit (Bit0 ~ Bit31) of parameters in VH
format.
y CWn(CWn.m), CDn(CDn.m), or CBn.b: read/write address is the same (address n), but
When symbol is set to CW, read/write value is the low word of parameters (n) only,
When symbol is set to CD, read/write value is the Double Word of whole parameters (n),
When symbol is set to CB, read/write value is the Bit (b) No. of parameters (n).
(m : HMI communication data format)
y (CWn/y(CWn/y.m), CDn/y(CDn/y.m), CBn/y.b: read/write address, which y subcode is the
same(address n), but
When symbol is set to CW, read/write value is the low word of parameters (n) only,
When symbol is set to CD, read/write value is the Double Word of whole parameters (n),
When symbol is set to CB, read/write value is the Bit (b) No. of parameters (n).
(m : HMI communication data format)
y Actually when using HMI,
i) When using devices that the unit is in Word (e.g. numeric devices (numeric value display,
numeric value input…)…), the read/write value will be the same no matter the read/write
address format is set to CWn or CDn as read/write value is the low word of parameters (n)
only.
ii) When using devices that the unit is in Double Word (e.g. numeric devices (numeric value
display, numeric value input…)…), if the read/write address format is set to CWn,
read/write value is coming from the low word of CWn and CWn+1 these two addresses.
(The low word of CWn is regarded as “low word” and the low word of CWn+1 is regarded
as “high word”, and then combining “low word” and “high word” to a Double Word.)
Revision January, 2008, Doc. Name: 2007PDD23000007 1-55
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
If the read/write address format is set to CDn, read/write value is the whole Double Word
of CDn (1 address).
iii) When using character device (e.g. character display, character input…), if the read/write
address format is set to CWn, the read/write value is coming from the low word of CWn,
CWn+1, CWn+2, …every address.
If the read/write address format is set to CDn, read/write value is the whole Double Word
of CDn, CDn+1, CDn+2,…every address.
iv) When using “Multiple Duplicate” function, if the Word and Bit addresses exceed the valid
range, the Word and Bit addresses will be set to 0 automatically. Sometime error will
occur to remind the user when compiling.
v) CBn.b, CBn/y.b are added for the user to read and write Bit No. of parameters in VH
format more easily.
vi) Only can read or write 1 parameter for each communication.
C. Connections (Connector Pinouts)
Pin 2, 3, 5 are for RS-232 communication. Pin 7, 8 are for RS-485 communication.
RS-232
DOP
9 pin D-SUB male (RS-232)
9 pin D-SUB male (RS-232)
Controller
RXD (2) (3) TXD
TXD (3)
GND (5)
RS-485
DOP
9 pin D-SUB male (RS-485)
D- (1)
(2) RXD
(5) GND
9 pin D-SUB male (RS-485)
Controller
(7) T/R (A)
D- (4)
D+ (2)
D+ (3)
(8) T/R (B)
Controller
9 pin D-SUB male
(RS-232)
Pin1
Top View
Controller
9 pin D-SUB male
(RS-485)
Pin1
Top View
1-56 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
LG Master K120S/200S Back to Table
A. HMI factory settings
Baud rate: 38400, 8, None, 1. (RS-232)
Controller station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)
Control area/status area: DW0 / DW10.
B. Definition of controller Read/Write address
Registers
Register Type Format Word No. Bit No. Data Size
WORD_DEVICE_PW PWn n: 0 ~ 15 N/A Word
WORD_DEVICE_MW MWn n: 0 ~ 191 N/A Word
WORD_DEVICE_KW KWn n: 0 ~ 31 N/A Word
WORD_DEVICE_LW LWn n: 0 ~ 63 N/A Word
WORD_DEVICE_FW FWn n: 0 ~ 63 N/A Word
WORD_DEVICE_TW TWn n: 0 ~ 255 N/A Word
WORD_DEVICE_CW CWn n: 0 ~ 255 N/A Word
WORD_DEVICE_DW DWn n: 0 ~ 9999 N/A Word
Contacts
Contact type Format Word No. Bit No.
BIT_DEVICE_P Pnb n: 0 ~ 15 b: 0 ~ f
BIT_DEVICE_M Mnb n: 0 ~ 191 b: 0 ~ f
BIT_DEVICE_K Knb n: 0 ~ 31 b: 0 ~ f
BIT_DEVICE_L Lnb n: 0 ~ 63 b: 0 ~ f
BIT_DEVICE_F Fnb n: 0 ~ 63 b: 0 ~ f
BIT_DEVICE_T Tn N/A n: 0 ~ 255
BIT_DEVICE_C Cn N/A n: 0 ~ 255
C. Connections (Connector Pinouts)
Revision January, 2008, Doc. Name: 2007PDD23000007 1-57
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
RS-232
DOP
9 pin D-SUB male (RS-232)
RXD (2)
TXD (3)
GND (5)
NOTE
1) If connecting to Pin 4 (RXD), Pin 7 (TXD) and Pin5 (SG), it indicates that CNet protocol is used (Please
refer to the section “LG Master-K CNET
simultaneously. The users only can select either 120S/200S protocol or CNet protocol.
Controller 9 pin D-SUB male
(RS-232 for LG K120S/200S)
(3) TXD
(2) RXD
(5) GND
”. 120S/200S protocol and CNet protocol cannot be used
Controller 9 pin D-SUB male
(RS-232 for LG K120S/200S)
Pin1
Top View
1-58 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
LG Glofa GM6 CNET Back to Table
A. HMI factory settings
Baud rate: 19200, 8, None, 1. (RS-232)
Controller station number: 0.
Control area/status area: %MW0 / %MW10.
NOTE
1) HMI default setting is predefined for CPU Port. If the user want to connect to CNET communication
module, the baud rate should be changed to 38400, 8, None, 1. (RS-422 / RS-485).
B. Definition of controller Read/Write address
Registers
Register Type Format Word No. Bit No. Data Size
Input Image IWb.s.w
w(word):0 ~ 3
s(slot): 0 ~ 7
b(base): 0 ~ 1 Word
Input Image IDb.s.w
Output Image QWb.s.w
Output Image QDb.s.w
Internal Memory MWn n: 0 ~ 4095 N/A Word
Internal Memory MDn n: 0 ~ 2047 N/A DWord
Contacts
Contact type Format Word No. Bit No.
Input Image IXb.s.n s(slot): 0 ~ 7
Output Image QXb.s.n s(slot): 0 ~ 7
Internal Memory MXn N/A n: 0 ~ 65535
w(word):0 ~ 1
s(slot): 0 ~ 7
w(word):0 ~ 3
s(slot): 0 ~ 7
w(word):0 ~ 1
s(slot): 0 ~ 7
b(base): 0 ~ 1 DWord
b(base): 0 ~ 1 Word
b(base): 0 ~ 1 DWord
n(bit): 0 ~ 63
b(base): 0 ~ 1
n(bit): 0 ~ 63
b(base): 0 ~ 1
Revision January, 2008, Doc. Name: 2007PDD23000007 1-59
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
C. Connections (Connector Pinouts)
RS-232
via CPU Port
9 pin D-SUB male (RS-232)
RS-422
via G6L-CUEC CNET communication module
DOP
RXD (2) (7) TXD
TXD (3)
GND (5)
DOP
9 pin D-SUB male (RS-422)
9 pin D-SUB male (RS-232)
(4) RXD
(5) GND
RXD+ (2) SD
RXD- (1)
Controller
Controller
9 pin D-SUB male (RS-232)
Pin1
Top View
Controller
Cable Connector (RS-422)
SDB
TXD- (4)
RDB
TXD+ (3) RDA
GND ( 5)
SG
1-60 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
LG Master-K CNET Back to Table
A. HMI factory settings
Baud rate: 38400, 8, None, 1. (RS-422)
Controller station number: 0.
Control area/status area: DW0 / DW10.
NOTE
1) HMI default setting is predefined for G6L-CUEC CNET communication module.
B. Definition of controller Read/Write address
Registers
Register Type Format Word No. Bit No. Data Size
I/O Relay PWn n: 0 ~ 31 N/A Word
Auxiliary Relay MWn n: 0 ~ 191 N/A Word
Keep Relay KWn n: 0 ~ 31 N/A Word
Link Relay LWn n: 0 ~ 63 N/A Word
Special Relay FWn n: 0 ~ 63 N/A Word (Read Only)
Timer Elapsed Value TWn n: 0 ~ 255 N/A Word
Counter Elapsed Value CWn n: 0 ~ 255 N/A Word
Data Register DWn n: 0 ~ 9999 N/A Word
Contacts
Contact type Format Word No. Bit No.
I/O Relay PXnb n: 0 ~ 31 b: 0 ~ F
Auxiliary Relay MXnb n: 0 ~ 191 b: 0 ~ F
Keep Relay KXnb n: 0 ~ 31 b: 0 ~ F
Link Relay LXnb n: 0 ~ 63 b: 0 ~ F
Special Relay FXnb n: 0 ~ 63 b: 0 ~ F
Timer Contact Relay TXb N/A b: 0 ~ 255
Counter Contact Relay CXb N/A b: 0 ~ 255
Revision January, 2008, Doc. Name: 2007PDD23000007 1-61
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
C. Connections (Connector Pinouts)
RS-422
via G6L-CUEC CNET communication module
DOP
9 pin D-SUB male (RS-422)
RXD+ (2) SD
RXD- (1)
TXD- (4)
TXD+ (3) RDA
GND ( 5)
RS-232
via LG-120S PLC (Master K)
DOP
9 pin D-SUB male (RS-232)
RXD (2) (7) TXD
TXD (3)
GND (5)
9 pin D-SUB male (RS-232)
(4) RXD
(5) GND
Controller
Controller
Cable Connector (RS-422)
SDB
RDB
SG
Controller
9 pin D-SUB male (RS-232)
Pin1
Top View
1-62 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
LG XGT CNET Back to Table
A. HMI factory settings
Baud rate: 9600, 8, None, 1.
Controller station number: 0.
Control area/status area: DW0 / DW10.
NOTE
1) HMI default setting is predefined for XGL-CH2A CNET communication module.
B. Definition of controller Read/Write address
Registers
Register Type Format Word No. Bit No. Data Size
I/O Relay PWn n: 0 ~ 2047 N/A Word
Auxiliary Relay MWn n: 0 ~ 2047 N/A Word
Keep Relay KWn n: 0 ~ 2047 N/A Word
Link Relay LWn n: 0 ~ 11263 N/A Word
Special Relay FWn n: 0 ~ 2047 N/A Word (Read Only)
Timer Elapsed Value TWn n: 0 ~ 2047 N/A Word
Counter Elapsed Value CWn n: 0 ~ 2047 N/A Word
Data Register DWn n: 0 ~ 32767 N/A Word
Contacts
Contact type Format Word No. Bit No.
I/O Relay PXnb n: 0 ~ 2047 b: 0 ~ F
Auxiliary Relay MXnb n: 0 ~ 2047 b: 0 ~ F
Keep Relay KXnb n: 0 ~ 2047 b: 0 ~ F
Link Relay LXnb n: 0 ~ 11263 b: 0 ~ F
Special Relay FXnb n: 0 ~ 2047 b: 0 ~ F
Timer Contact Relay TXb N/A b: 0 ~ 2047
Counter Contact Relay CXb N/A b: 0 ~ 2047
Data Relay DXn.b n: 0 ~ 32767 b: 0 ~ F
Revision January, 2008, Doc. Name: 2007PDD23000007 1-63
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
C. Connections (Connector Pinouts)
RS-422
via XGL-CH2A CNET communication module (Channel 2)
DOP
9 pin D-SUB male (RS-422)
RX D + (2
RX D - ( 1)
TX D- ( 4)
TXD+ (3) R X+
G ND (5)
RS-232
via XGL-CH2A CNET communication module (Channel 1)
DOP
9 pin D-SUB male (RS-232)
RXD (2) (3) TXD
TXD (3)
GND (5)
9 pin D-SUB male (RS-232)
Controller
(2 ) RXD
(5 ) GN D
Controller
Cable Connector (RS-422)
TX
TX-
RX-
SG
9 pin D-SUB male (RS-232)
Controller
Pin1
Top View
1-64 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
LIYAN LYPLC EX Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1.
Controller station number: 0.
Control area/status area: D0 / D10.
B. Definition of controller Read/Write address
Registers
Register Type Format
Auxiliary Relay Mn n: 0 ~ 3064 N/A Byte
Special Auxiliary Relay Mn n: 8000 ~ 8248 N/A Byte
Status Relay Sn n: 0 ~ 992 N/A Byte
Input Relay Xn n: 0 ~ 360(octal) N/A Byte
Output Relay Yn n: 0 ~ 360(octal) N/A Byte
Read/Write Range
Data length
Word No. Bit No.
Timer PV Tn n: 0 ~ 255 N/A Word
16-bit Counter PV Cn n: 0 ~ 199 N/A Word
32-bit Counter PV Cn n: 200 ~ 255 N/A Double Word
Data Register Dn n: 0 ~ 7999 N/A Word
Special Data Register Dn n: 8000 ~ 8255 N/A Word
Auxiliary Relay / Special Auxiliary Relay / Status Relay / Input Relay / Output Relay: Address must be the
multiple of 8.
Contacts
Contact type Format
Word No. Bit No.
Auxiliary Relay Mn N/A n: 0 ~ 3071
Special Auxiliary Relay Mn N/A n: 8000 ~ 8255
Status Relay Sn N/A n: 0 ~ 999
Input Relay Xn N/A n: 0 ~ 377(octal)
Output Relay Yn N/A n: 0 ~ 377(octal)
Timer Flag Tn N/A n: 0 ~ 255
Read/Write Range
Counter Flag Cn N/A n: 0 ~ 255
Revision January, 2008, Doc. Name: 2007PDD23000007 1-65
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
C. Connections (Connector Pinouts)
RS-232
DOP
9 pin D-SUB male (RS-232)
Controller
8 pin Mini DIN male (RS-232)
RXD (2) (2) TXD
TXD (3)
GND (5)
(7) RXD
(3) GND
(6) GND
Controller
8 pin Mini DIN male (RS-232)
2
3
6
7
Top View
1-66 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
M2i Master Back to Table
A. HMI factory settings
Baud rate: 38400, 8, None, 1.
Controller station number: 1.
Control area/status area: SB0 / SB10.
B. Definition of controller Read/Write address
Registers
Register Type Format
Word Address SBn n: 0000 ~ FFFF N/A Word
Contacts
Contact type Format
Read/Write Range
Data length
Word No. Bit No.
Read/Write Range
Word No. Bit No.
Bit Address SBn.b n: 0000 ~ FFFF b: 0 ~ F
Revision January, 2008, Doc. Name: 2007PDD23000007 1-67
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
M2i Slave Back to Table
A. HMI factory settings
Baud rate: 38400, 8, None, 1.
Controller station number: 1 (no function)
Control area/status area: SB0 / SB10.
NOTE
1) HMI station number is Slave station number. (default setting is 0)
2) The relation between M2i communication address and HMI internal registers.
SB0000 ~ SB7FFF
SB8000 ~ SB83FF
SB8400
SB8500 ~ SBFFFF RCP0 ~ RCP31487
B. Definition of controller Read/Write address
Registers
Register Type Format Word No. Bit No. Data Size
Word Address SBn n: 0000 ~ FFFF N/A Word
Modbus address Data definition in HMI
$0 ~ $32767
$M0 ~ $M1023
RCPNO
Contacts
Contact type Format
Word No. Bit No.
Bit Address SBn.b n:0000 ~ FFFF b: 0 ~ F
C. Connections (Connector Pinouts):
Please refer to 1.1 Pin Definition of Serial Communication for detail.
Read/Write Range
1-68 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Matsushita FP PLC Back to Table
A. HMI factory settings
Baud rate: 9600, 8, ODD, 1.
Controller station number: 238.
Control area/status area: DT0 / DT10.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format
Data length
Word No. Bit No.
Internal Relay WRn n: 0 ~ 886, N/A Word
Special Internal Relay 900 ~ 910
Link Relay WLn n: 0 ~ 639 N/A Word
External Input Relay WXn n: 0 ~ 511 N/A Word
External Output Relay WYn n: 0 ~ 511 N/A Word
Timer/Counter P.V. EVn n: 0 ~ 3071 N/A Word
Timer/Counter S.V. SVn n: 0 ~ 3071 N/A Word
Data Register DTn n: 0 ~ 32764 N/A Word
Link Data Register LDn n: 0 ~ 8447 N/A Word
File Register FLn n: 0 ~ 32764 N/A Word
Special Data Register DT9_n n: 0 ~ 511 N/A Word
DT9_0 ~ DT9_511 are applicable for FP0 T32C, FP2, FP2SH, FP10SH controllers. (Special data
¾
registers are all within the range of DT90000 ~ DT9XXXX).
The actual transmitted address of DT9_n is 90000 + n (for DT). For example, the actual transmitted
¾
address of DT9_1 is 90001 (for DT), the actual transmitted address of DT9_2 is 90002 (for DT) and vise
versa.
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
Internal Relay Rnb n: 0 ~ 886 b: 0 ~ f
Special Internal Relay n: 900 ~ 910 b: 0 ~ f
Link Relay Lnb n: 0 ~ 639 b: 0 ~ f
External Input Relay Xnb n: 0 ~ 511 b: 0 ~ f
External Output Relay Ynb n: 0 ~ 511 b: 0 ~ f
Timer Flag Contact Tn N/A n: 0 ~ 3071
Counter Flag Contact Cn N/A n: 0 ~ 3071
Revision January, 2008, Doc. Name: 2007PDD23000007 1-69
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Increase the range of read / write address (for FP2SH / FP10SH controllers).
¾
C. Connections (Connector Pinouts)
RS-232
RS-232
DOP Series
9 pin D-SUB male
(RS-232)
RXD (2)
TXD (3)
GND (5)
DOP Series
9 pin D-SUB male
(RS-232)
RXD (2)
TXD (3)
GND (5)
Controller
5 pin Mini DIN male
(RS-232 for FP0)
(2) TXD
(3) RXD
(1) SG
9 pin D-SUB male
Controller
(RS-232 for FP1)
(2) TXD
(3) RXD
(7) GND
(4) RTS
Controller
5 pin Mini DIN male
(RS-232 for FP0)
1
3
2
Top View
Controller
9 pin D-SUB male
(RS-232 for FP1)
Pin1
(5) CTS
Top View
1-70 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Mirle FAMA SC Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1.
Controller station number: 0.
Control area/status area: 40100 / 40200.
B. Definition of controller Read/Write address
Registers
Register Type Format
Output Registers Wn n: 40001 ~ 50000 N/A Word
Input Registers Wn n: 30001 ~ 40000 N/A Word
Input Registers is “read only”.
¾
Contacts
Read/Write Range
Data Length
Word No. Bit No.
Contact type Format
Discrete Outputs Bn N/A n: 1 ~ 10000
Discrete Inputs Bn N/A n: 10001 ~ 20000
Discrete Inputs is “read only”.
¾
C. Connections (Connector Pinouts)
RS-232
DOP Series
9 pin D-SUB male
(RS-232)
RXD (2)
TXD (3)
GND (5)
9 pin D-SUB male
(3) TXD
(2) RXD
(5) SG
Word No. Bit No.
Controller
(RS-232)
Read/Write Range
Controller
9 pin D-SUB male
(RS-232)
Pin1
Top View
Revision January, 2008, Doc. Name: 2007PDD23000007 1-71
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Mitsubishi FX/FX2N PLC Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1.
Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)
Control area/status area: D0 / D10.
NOTE
1) If connecting to Mitsubishi FXxN series PLC, the user can use both FX2N and FX series communication
protocol.
2) If connecting to Mitsubishi FX series PLC, the user can only use FX series communication protocol.
3) Some registers of Mitsubishi PLCs are “read only”, however, when you write these “read only” registers,
PLCs will not report any communication error to HMI and this will cause HMI errors. Please be aware of
this when editing PLC program (this normally occurs when using FX series protocol when connecting to
a FXxN series PLC).
4) If connecting to Mitsubishi FXxN series PLC, it is recommended for the user to use FX2N protocol.
B. Definition of controller Read/Write address
Registers
Register Type Format
Auxiliary Relay Mn n: 0 ~ 3064 N/A Byte
Read/Write Range
Data length
Word No. Bit No.
Special Auxiliary Relay Mn n: 8000 ~ 8248 N/A Byte
Status Relay Sn n: 0 ~ 992 N/A Byte
Input Relay Xn n: 0 ~ 360(octal) N/A Byte
Output Relay Yn n: 0 ~ 360(octal) N/A Byte
Timer PV Tn n: 0 ~ 255 N/A Word
16-bit Counter PV Cn n: 0 ~ 199 N/A Word
32-bit Counter PV Cn n: 200 ~ 255 N/A Double Word
Data Register Dn n: 0 ~ 7999 N/A Word
Special Data Register Dn n: 8000 ~ 8255 N/A Word
Auxiliary Relay/ Special Auxiliary Relay/ Status Relay/ Input Relay /Output Relay: Address must be the
¾
multiple of 8.
1-72 Revision January, 2008, Doc. Name: 2007PDD23000007
Contacts
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Contact type Format
Auxiliary Relay Mn N/A n: 0 ~ 3071
Special Auxiliary Relay Mn N/A n: 8000 ~ 8255
Status Relay Sn N/A n: 0 ~ 999
Input Relay Xn N/A n: 0 ~ 377(octal)
Output Relay Yn N/A n: 0 ~ 377(octal)
Timer Flag Tn N/A n: 0 ~ 255
Counter Flag Cn N/A n: 0 ~ 255
C. Connections (Connector Pinouts)
RS-422
DOP Series
9 pin D-SUB male (RS-422)
8pin Mini DIN male (RS-422)
RXD+ (2)
RXD- (1)
TXD+ (3)
TXD- (4)
GND (5)
Word No. Bit No.
Controller
(7) TXD+
(4) TXD-
(2) RXD+
(1) RXD-
(3) SG
Read/Write Range
8pin Mini DIN male
Controller
(RS-422)
2
1
4
3
7
Top View
RS-422
DOP
9 pin D-SUB male (RS-422)
Pi n 2 ( RXD +
Pin 1 (RXD-)
Pin 4 (TXD-)
Pin 3 (TXD+)
Pi n 7 ( RT S+) Pi n 4 (C TS +)
Pin 8 (CTS+)
Pin 6 (RTS-)
Pin 9 (CTS-)
Controller
25 pin D-SUB male (RS-422)
Pi n3 SDB ( TXD +
Pi n16 SDA (TXD-)
Pin 15 RDA (RXD-)
Pin 2 RDB (RXD+)
Pi n5 (R TS+)
Pin 17 (CTS-)
Pin 18 (RTS-)
Pin 20
Pin 21
Controller
25 pin D-SUB male (RS-422)
Pin1
Revision January, 2008, Doc. Name: 2007PDD23000007 1-73
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Mitsubishi FX3U PLC Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1.
Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)
Control area/status area: D0 / D10.
B. Definition of controller Read/Write address
Registers
Register Type Format
Data length
Word No. Bit No.
Auxiliary Relay Mn n: 0 ~ 7679 N/A Word
Special Auxiliary Relay Mn n: 8000 ~ 8511 N/A Word
Status Relay Sn n: 0 ~ 4095 N/A Word
Input Relay Xn n: 0 ~ 377(octal) N/A Word
Output Relay Yn n: 0 ~ 377(octal) N/A Word
Timer PV Tn n: 0 ~ 255 N/A Word
16-bit Counter PV Cn n: 0 ~ 199 N/A Word
32-bit Counter PV Cn n: 200 ~ 255 N/A Double Word
Data Register Dn n: 0 ~ 7999 N/A Word
Special Data Register Dn n: 8000 ~ 8511 N/A Word
Read/Write Range
Auxiliary Relay/ Special Auxiliary Relay/ Status Relay/ Input Relay /Output Relay: Address must be the
¾
multiple of 16.
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
Auxiliary Relay Mn N/A n: 0 ~ 7679
Special Auxiliary Relay Mn N/A n: 8000 ~ 8511
Status Relay Sn N/A n: 0 ~ 4095
Input Relay Xn N/A n: 0 ~ 377(octal)
Output Relay Yn N/A n: 0 ~ 377(octal)
Timer Flag Tn N/A n: 0 ~ 255
Counter Flag Cn N/A n: 0 ~ 255
1-74 Revision January, 2008, Doc. Name: 2007PDD23000007
C. Connections (Connector Pinouts)
RS-422
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
DOP Series
9 pin D-SUB male (RS-422)
RXD+ (2)
RXD- (1)
TXD+ (3)
TXD- (4)
GND (5)
Controller
8pin Mini DIN male (RS-422)
(7) TXD+
(4) TXD-
(2) RXD+
(1) RXD-
(3) SG
Controller
8pin Mini DIN male
(RS-422)
2
1
4
3
7
Top View
Revision January, 2008, Doc. Name: 2007PDD23000007 1-75
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Mitsubishi A Series AJ71UC24 Communication Module Back to Table
A. HMI factory settings
Baud rate: 9600, 8, ODD, 1.
Controller Station number: 0.
Control area/status area: D0 / D10.
NOTE
1) This driver utilizes CheckSum.
2) Please set “PLC Mode” switch to position 5.
3) If OUTPUT Relay (Y) and Special Data Relay (SM) are set to 1, PLC will stop communication and the
communication will not recover automatically. PLC will need to be manually reset.
B. Definition of controller Read/Write address
Registers
Register Type Format
Input Xn n: 0 ~ 7FF N/A Word (multiple of 16)
Output Yn n: 0 ~ 7FF N/A Word (multiple of 16)
Link Relay Bn n: 0 ~ FFF N/A Word (multiple of 16)
Internal Relay Mn n: 0 ~ 8191 N/A Word (multiple of 16)
Special Internal Relay SMn n: 9000 ~ 9255 N/A Word (9000 + multiple of 16)
Read/Write Range
Data length
Word No. Bit No.
Latch Relay Ln n: 0 ~ 2047 N/A Word (multiple of 16)
Annunciator Fn n: 0 ~ 2047 N/A Word (multiple of 16)
Timer Value TNn n: 0 ~ 999 N/A Word
Counter Value CNn n: 0 ~ 999 N/A Word
Data Register Dn n: 0 ~ 8191 N/A Word
Special Data Register SDn n: 9000 ~ 9255 N/A Word
File Register Rn n: 0 ~ 8191 N/A Word
Link Register Wn n: 0 ~ FFF N/A Word
1-76 Revision January, 2008, Doc. Name: 2007PDD23000007
Contacts
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Contact type Format
Word No. Bit No.
Input Xn N/A n: 0 ~ 7FF
Output Yn N/A n: 0 ~ 7FF
Link Relay Bn N/A n: 0 ~ FFF
Internal Relay Mn N/A n: 0 ~ 8191
Special Internal Relay SMn N/A n: 9000 ~ 9255
Latch Relay Ln N/A n: 0 ~ 2047
Annunciator Fn N/A n: 0 ~ 2047
Timer Contact TSn N/A n: 0 ~ 999
Timer Coil TCn N/A n: 0 ~ 999
Counter Contact CSn N/A n: 0 ~ 999
Counter Coil CCn N/A n: 0 ~ 999
C. Connections (Connector Pinouts)
RS-422
Read/Write Range
DOP
9 pin D-SUB male (RS-422)
Cable Connector (RS-422)
Controller
RXD+ (2) SDA
RXD- (1)
TXD+ (3)
TXD- (4)
SDB
RDA
RDB
Revision January, 2008, Doc. Name: 2007PDD23000007 1-77
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Mitsubishi A2A/A2AS/A2USH A1SH/A3N/A2ASH (CPU-S1) CPU Port Back to Table
A. HMI factory settings
Baud rate: 9600, 8, ODD, 1.
Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)
Control area/status area: D0 / D10.
NOTE
1) This driver supports all Mitsubishi A series CPU port. Mitsubishi A series CPU port can be divided into
the following five categories according the used CPU code (used during communication):
y A0J2…
y A1N…
y A1S ( / A2S / A2N …)
y A3N ( / A1SH / A2SH …)
y A2A ( / A2AS / A2USH …)
Delta HMI can support A2USH CPU port (same as A2A, A2AS CPU port.) and A1SH CPU port (same as
A3N, A2ASH CPU port.).
2) L and M: The communication address of L is the same as communication address of M.
3) PX and X:
In Mitsubishi A2A PLC, the communication address of PX and X are the same.
In other Mitsubishi A series PLCs, X is from odd address and PX is from even address. That is one place
where PX and X differ.
4) X, Y, B, M, SM, L, F, PX ----(Word),
X, Y, B, M, SM, L, F, PX ----(Bit),
When PLC station number is set to 255, only the value of even addresses will be read/written.
When PLC station number is set to other number (not 255), all value of all addresses will be read/written.
5) R address: R address will be different according to the size of File Register responded from PLC.
For example, A2USH: 1K: 3800 ~ 4000H
2K: 3000 ~ 4000H
3K: 2800 ~ 4000H
4K: 2000 ~ 4000H
5K: 4000 ~ 6800H(cy)
6K: 4000 ~ 7000H(cy)
File Register
1-78 Revision January, 2008, Doc. Name: 2007PDD23000007
: PLC must be started correctly or the read / write value will be incorrect.
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
6) Max. read/write registers & relays for communication once
128 Words (256 bytes) Registers
64 Words (128 bytes) Relays
B. Definition of controller Read/Write address
Registers
Register Type Format
Data length
Word No. Bit No.
Input Xn n: 0 ~ 7FF N/A Word (multiple of 16)
Output Yn n: 0 ~ 7FF N/A Word (multiple of 16)
Link Relay Bn n: 0 ~ FFF N/A Word (multiple of 16)
Internal Relay Mn n: 0 ~ 8191 N/A Word (multiple of 16)
Special Internal Relay SMn n: 9000 ~ 9255 N/A Word (9000 + multiple of 16)
Latch Relay Ln n: 0 ~ 8191 N/A Word (multiple of 16)
Annunciator Fn n: 0 ~ 2047 N/A Word (multiple of 16)
Timer Value TNn n: 0 ~ 2047 N/A Word
Counter Value CNn n: 0 ~ 1023 N/A Word
Data Register Dn n: 0 ~ 8191 N/A Word
Special Data Register SDn n: 9000 ~ 9255 N/A Word
File Register Rn n: 0 ~ 8191 N/A Word
Link Register Wn n: 0 ~ FFF N/A Word
Input Card Register PXn n: 0 ~ 7FF N/A Word (multiple of 16)
Read/Write Range
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
Input Xn N/A n: 0 ~ 7FF
Output Yn N/A n: 0 ~ 7FF
Link Relay Bn N/A n: 0 ~ FFF
Internal Relay Mn N/A n: 0 ~ 8191
Special Internal Relay SMn N/A n: 9000 ~ 9255
Latch Relay Ln N/A n: 0 ~ 2047
Annunciator Fn N/A n: 0 ~ 2047
Timer Contact TSn N/A n: 0 ~ 2047
Timer Coil TCn N/A n: 0 ~ 2047
Counter Contact CSn N/A n: 0 ~ 1023
Counter Coil CCn N/A n: 0 ~ 1023
Input Card Register PXn N/A n: 0 ~ 7FF
Revision January, 2008, Doc. Name: 2007PDD23000007 1-79
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
C. Connections (Connector Pinouts)
RS-422
DOP Series
9 pin D-SUB male (RS-422)
Pi n 2 ( RXD +
Pin 1 (RXD-)
Pin 4 (TXD-)
Pin 3 (TXD+)
Pi n 7 ( RT S+) Pi n 4 (C TS +)
Pin 8 (CTS+)
Pin 6 (RTS-)
Pin 9 (CTS-)
Explanation
How to set File Register (R) for Mitsubishi A serial PLC:
1. Startup MELSOFT series GX Developer.
25 pin D-SUB male (RS-422)
Pi n3 SDB ( TXD +
Pi n16 SDA (TXD-)
Pin 15 RDA (RXD-)
Pin 2 RDB (RXD+)
Pi n5 (R TS+)
Pin 17 (CTS-)
Pin 18 (RTS-)
Pin 20
Pin 21
Controller
Controller
25 pin D-SUB male(RS-422)
Pin1
2. Open “Project Data List” windows. (“View” Option)
3. Double click Parameter \ PLC Parameter, and open “Setting” window.
4. Set Memory Capacity \ File Register (0 ~8).
5. Press “End” button on the bottom and complete the setting.
6. Execute OnLine\Write to PLC.
7. Enable the “Parameter \ PLC/Network” and “File register \ Main” option (check the check box next to
“Parameter \ PLC/Network” and “File register \ Main”).
8. Press “Execute” button.
9. Complete
1-80 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Mitsubishi Q Series CPU Port Back to Table
A. HMI factory settings
Baud rate: 19200, 8, ODD, 1.
Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC)
communication is allowed.)
Control area/status area: D-0 / D-10.
NOTE
1) Please notice that no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication
is allowed.
2) If communication baud rate is not correct, HMI will set PLC baud rate as HMI baud rate automatically.
Therefore, do not worry if the baud rate is set incorrectly.
3) This driver support Mitsubishi Q00 and Q00J series with password protection models.
B. Definition of controller Read/Write address
Registers
Register Type Format
Input X-n n: 0 ~ 1FFF N/A Word (multiple of 16)
Output Y-n n: 0 ~ 1FFF N/A Word (multiple of 16)
Direct Input DX-n n: 0 ~ 1FFF N/A Word (multiple of 16)
Direct Output DY-n n: 0 ~ 15 N/A Word (multiple of 16)
Latch Relay L-n n: 0 ~ 8191 N/A Word (multiple of 16)
Annunciator F-n n: 0 ~ 2047 N/A Word (multiple of 16)
Edge Relay V-n n: 0 ~ 2047 N/A Word (multiple of 16)
Step Relay S-n n: 0 ~ 8191 N/A Word (multiple of 16)
Link Relay B-n n: 0 ~ 1FFF N/A Word (multiple of 16)
Special Link Relay SB-n n: 0 ~ 7FF N/A Word (multiple of 16)
Internal Relay M-n n: 0 ~ 8191 N/A Word (multiple of 16)
Special Internal Relay SM-n n: 0 ~ 2047 N/A Word (multiple of 16)
Timer Value TN-n n: 0 ~ 2047 N/A Word
Read/Write Range
Data length
Word No. Bit No.
Retentive Timer Value SN-n n: 0 ~ 2047 N/A Word
Counter Value CN-n n: 0 ~ 1023 N/A Word
Data Register D-n n: 0 ~ 12287 N/A Word
Special Data Register SD-n n: 0 ~ 2047 N/A Word
Index Register Z-n n: 0 ~ 15 N/A Word
File Register R-n n: 0 ~ 32767 N/A Word
Revision January, 2008, Doc. Name: 2007PDD23000007 1-81
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Register Type Format
Read/Write Range
Word No. Bit No.
File Register ZR-n n: 0 ~ 32767 N/A Word
Link Register W-n n: 0 ~ 1FFF N/A Word
Special Link Register SW-n n: 0 ~ 7FF N/A Word
Xn, Yn, DXn, Bn, SBn, Wn, SWn : n is in hexadecimal.
¾
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
Input X-n N/A n: 0 ~ 1FFF
Output Y-n N/A n: 0 ~ 1FFF
Direct input DX-n N/A n: 0 ~ 1FFF
Direct output DY-n N/A n: 0 ~ 15
Latch Relay L-n N/A n: 0 ~ 8191
Annunciator F-n N/A n: 0 ~ 2047
Edge Relay V-n N/A n: 0 ~ 2047
Data length
Step Relay S-n N/A n: 0 ~ 8191
Link Relay B-n N/A n: 0 ~ 1FFF
Special Link Relay SB-n N/A n: 0 ~ 7FF
Internal Relay M-n N/A n: 0 ~ 8191
Special Internal Relay SM-n N/A n: 0 ~ 2047
Timer Contact TS-n N/A n: 0 ~ 2047
Timer Coil TC-n N/A n: 0 ~ 2047
Retentive timer Contact SS-n N/A n: 0 ~ 2047
Retentive timer Coil SC-n N/A n: 0 ~ 2047
Counter Contact CS-n N/A n: 0 ~ 1023
Counter Coil CC-n N/A n: 0 ~ 1023
Xn, Yn, DXn, Bn, SBn : n is in hexadecimal.
¾
1-82 Revision January, 2008, Doc. Name: 2007PDD23000007
C. Connections (Connector Pinouts)
RS-232
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
DOP
9 pin D-SUB male (RS-232)
RXD (2)
TXD (3)
GND (5)
Controller
6 pin Mini DIN male (RS-232)
(2) SD (TXD)
(1) RD (RXD)
(3) GND
(5) DSR (DR)
(6) DTR (ER)
Controller
6 pin Mini DIN male
(RS-232)
1
2
3
5
6
Top View
Revision January, 2008, Doc. Name: 2007PDD23000007 1-83
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Mitsubishi Q Series Computer Link Back to Table
A. HMI factory settings
Baud rate: 19200, 8, None, 1.
Controller Station number: 0.
Control area/status area: D0 / D10.
NOTE
1) This communication protocol supports Q series RS232 communication module (QJ71C24-R2) and
RS422 communication protocol (QJ71C24N).
2) Before using this communication protocol, the user needs to set communication module via PC software ,
GX Developer. For more detailed information regarding the setting method, please refer to Mitsubishi
User Manual named “User’s Manual (Basic) - Q Corresponding Series Communication Module”.
B. Definition of controller Read/Write address
Registers
Register Type Format
Input Xn n: 0-1FFF N/A Word (multiple of 16)
Output Yn n: 0-1FFF N/A Word (multiple of 16)
Internal Relay Mn n: 0-8191 N/A Word (multiple of 16)
Special Internal Relay Mn n: 9000-9255 N/A Word (9000 + multiple of 16)
Read/Write Range
Data length
Word No. Bit No.
Link Relay Bn n: 0-1FFF N/A Word (multiple of 16)
Annunciator Fn n: 0-2047 N/A Word (multiple of 16)
Timer Value TNn n: 0-2047 N/A Word
Counter Value CNn n: 0-2047 N/A Word
Data Register Dn n: 0-8191 N/A Word
Special Data Register Dn n: 9000-9255 N/A Word
Link Register Wn n: 0-1FFF N/A Word
Xn, Yn, Bn, Wn : n is in hexadecimal.
¾
Contacts
Contact type Format
Word No. Bit No.
Input Xn N/A n: 0-1FFF
Output Yn N/A n: 0-1FFF
Internal Relay Mn N/A n: 0-8191
Special Internal Relay Mn N/A n: 9000-9255
Read/Write Range
1-84 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Contact type Format
Link Relay Bn N/A n: 0-1FFF
Annunciator Fn N/A n: 0-2047
Timer Contact TSn N/A n: 0-2047
Timer Coil TCn N/A n: 0-2047
Counter Contact CS-n N/A n: 0-2047
Counter Coil CC-n N/A n: 0-2047
Xn, Yn, Bn : n is in hexadecimal.
¾
C. Connections (Connector Pinouts)
RS-232
DOP Series
9 pin D-SUB male (RS-232)
RX D (2)
TXD (3)
GND (5)
9 pin D-SUB male (RS-232)
(2) TXD
(3) RXD
(5) SG
Word No. Bit No.
Controller
(8) RTS
(7) CTS
(4) DSR (DR)
(6) DTR (ER)
Read/Write Range
Controller
9 pin D-SUB male (RS-232)
Top View
Pin1
RS-422
DOP
9 pin D-SUB male (RS-422)
RXD+ (2
RXD- (1)
TXD+ (3)
TXD- (4) RDB (4)
GND (5)
Controller
Cable Connector (RS-422)
SDA (1
SDB (2)
RDA ( 3)
SG
Revision January, 2008, Doc. Name: 2007PDD23000007 1-85
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Mitsubishi FX Series PLC via Computer Link Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1.
Controller Station number: 0.
Control area/status area: D0 / D10.
NOTE
1) This communication protocol supports FX series RS485 and RS232 communication module.
2) The default setting of this communication protocol is to support RS485 communication module. If the
user needs to use RS232 communication module, the user must change the communication setting from
RS485 to RS232 manually.
3) For more detailed information regarding the communication setting method, please refer to Mitsubishi
Communication User Manual named “User’s Manual - Data Communication Edition”.
B. Definition of controller Read/Write address
Registers
Register Type Format
Auxiliary Relay Mn n: 0-7679 N/A Word
Special Auxiliary Relay Mn n: 8000-8511 N/A Word
Status Relay Sn n: 0-4095 N/A Word
Read/Write Range
Data length
Word No. Bit No.
Input Relay Xn n: 0-377(octal) N/A Word
Output Relay Yn n: 0-377(octal) N/A Word
Timer PV Tn n: 0-255 N/A Word
16-bit Counter PV Cn n: 0-199 N/A Word
32-bit Counter PV Cn n: 200-255 N/A Double Word
Data Register Dn n: 0-7999 N/A Word
Special Data Register Dn n: 8000-8511 N/A Word
Auxiliary Relay / Special Auxiliary Relay / Status Relay / Input Relay / Output Relay: Address must be
¾
the multiple of 16.
Contacts
Contact type Format
Word No. Bit No.
Auxiliary Relay Mn N/A n: 0-7679
Special Auxiliary Relay Mn N/A n: 8000-8511
Status Relay Sn N/A n: 0-4095
Read/Write Range
1-86 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Contact type Format
Input Relay Xn N/A n: 0-377(octal)
Output Relay Yn N/A n: 0-377(octal)
Timer Flag Tn N/A n: 0-255
Counter Flag Cn N/A n: 0-255
C. Connections (Connector Pinouts)
RS-232
DOP Series
9 pin D-SUB male (RS-232)
RXD (2
TXD (3)
GND (5)
9 pin D-SUB male (RS-232)
TX D ( 3)
RXD (2)
GND (5)
Word No. Bit No.
Controller
Read/Write Range
9 pin D-SUB male (RS-232)
Controller
Pin1
RS-485
DOP
9 pin D-SUB male (RS-485)
GND (5)
D- (1
D- (4)
D+ (2)
D+ (3)
Controller
Communication Module
SDB
RDB
SDA
RDA
GND
Top View
Revision January, 2008, Doc. Name: 2007PDD23000007 1-87
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Mitsubishi J2s Series Servo Back to Table
A. HMI factory settings
Baud rate: 9600, 8, Even, 1 (RS-232).
Controller Station number: 0.
Control area/status area: None / None.
B. Definition of controller Read/Write address
Registers
Register Type Format
Parameter List
(cmd: 05/84)
Status Display
(cmd: 01,8n/NA)
Alarm Number in history
(cmd: 33,1n/NA)
Alarm Occurrence time in history (AO)
(cmd: 33,2n/NA)
Current Alarm Number (AC)
(cmd: 02/NA)
Status Display at alarm occurrence (AS)
(cmd: 35,8/NA)
External input pin status (EI)
(cmd: 12,40/92,00)
External output pin status (EO)
(cmd: 12,C0/92,A0)
Operation mode selection (OP)
(cmd: NA/8B,00)
(NOTE 1)
(NOTE 1)
(NOTE 1)
(NOTE 1)
(NOTE 1)
(NOTE 1)
(NOTE 1)
(NOTE 1)
(NOTE 1)
Read/Write Range
Data length
Word No. Bit No.
Pn n: 0 – 84 N/A Double word
Sn n: 0 – E N/A Double word
ANn n: 0 – 5 N/A Word
AOn n: 0 – 5 N/A Double word
ACn n: 0 N/A Word
ASn n: 0 N/A Double word
EIn n: 0 N/A Double word
EOn n: 0 N/A Double word
OPn n: 0 N/A Word
Speed for test operation (TSPD)
(cmd: NA/A0,10)
(NOTE 1)
TSPDn n: 0 N/A Word
Acceleration/deceleration for test
operation (TACC)
(cmd: NA/A0,11)
Distance for test operation (TDIS)
(cmd: NA/A0,13)
(NOTE 1)
(NOTE 1)
TACCn n: 0 N/A Double word
TDISn n: 0 N/A Double word
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
Status display clear (SRST)
(cmd: NA/81,00)
Alarm history clear (ACLR)
(cmd: NA/82,20)
(NOTE 1)
(NOTE 1)
SRSTb N/A b: 0
ACLRb N/A b: 0
1-88 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Contact type Format
Alarm reset (ARST)
(cmd: NA/82,00)
Turn off the external input signals (DI) (OFDI)
(cmd: NA/90,00)
Changes the external output signals (DO) (CHDO)
(cmd: NA/90,03)
Enable the disabled external input signals (ENDI)
(cmd: NA/90,10)
Enable the disabled external output signals (ENDO)
(cmd: NA/90,13)
(NOTE 1)
(NOTE 1)
(NOTE 1)
(NOTE 1)
(NOTE 1)
Clear the time constant of acceleration in test
operation mode (TCLR)
(cmd: NA/A0,12)
(NOTE 1)
Temporary stop of position mode in test operation
(TSTP)
(cmd: NA/A0,15)
(NOTE 1)
C. Connections (Connector Pinouts)
Read/Write Range
Word No. Bit No.
ARSTb N/A b: 0
OFDIb N/A b: 0
CHDOb N/A b: 0
ENDIb N/A b: 0
ENDOb N/A b: 0
TCLRb N/A b: 0
TSTPb N/A b: 0
RS-232
DOP Series
9 pin D-SUB male (RS-232)
RXD (2
TXD (3)
GND (5)
NOTE
TXD ( 12
RXD (2)
GND (1)
GND (11)
Controller
20 pin CN3
1) Read / Write Limit
This communication protocol uses devices to simulate the operation of Servo, so there is a limit for the
device to read and write the command. In the column of register type and contact type, the string of
characters after “cmd:” indicates the corresponding Servo command that the device will read and write.
For example, the string of characters after “cmd:” of the register, Status display is 01,8n/NA. It means
that the device can read it but cannot write it. One more example, the string of characters after “cmd:” of
the Operation mode selection (OP) is N/A/8B,00. It means that the device can write it but cannot read it.
Revision January, 2008, Doc. Name: 2007PDD23000007 1-89
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
MKS BY125 Low Cost Synchrocontroller Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1.
(NOTE 1)
Controller Station number: 11
.
Control area/status area: None / None.
B. Definition of controller Read/Write address
Registers
Register Type Format
Data Length
Word No. Bit No.
n: 0 ~ 17,
40 ~ 41,
Read/Write Range
Data In Register / Setup
Register
Cn
45 ~ 48,
N/A Double Word
50,
90 ~ 92
Synchronizing (Differential
Counter)
SYN_ERRn n: 0 N/A Double Word
Integration register IRn n: 0 N/A Double Word
Actual Master speed MAS_SPDn n: 0 N/A Double Word
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
Reset RSTn N/A n: 0
Jog Trim+ JOGTRIM_INCn N/A n: 0
Jog Trim- JOGTRIM_DECn N/A n: 0
Activate Data ACT_DATAn N/A n: 0
Store EEPROM STR_EEPROMn N/A n: 0
Index Slave IND_SLAn N/A n: 0
Index Master IND_MASn N/A n: 0
1-90 Revision January, 2008, Doc. Name: 2007PDD23000007
C. Connections (Connector Pinouts)
RS-232
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
DOP
9 pin D-SUB male (RS-232)
RS-485
DOP
9 pin D-SUB male (RS-485)
RXD (2)
TXD (3)
GND (5)
RXD (2)
TXD (3)
GND (5)
Controller
20 pin CN3
20 pin CN3
(3) TXD
(2) RXD
(5) SG
Controller Controller
(3) TXD
(2) RXD
(5) SG
Controller
Pin1
Top View
Pin1
Top View
NOTE
1) The valid station number is in the range of 11 to 99. However, 20, 30, 40, 50, 60, 70, 80 and 90 cannot
be used as they are all broadcast station number.
00 for all broadcast
10 for the broadcast to 11 ~ 19
20 for the broadcast to 21 ~ 29
and vise versa.
2) Now the broadcast function is not provided, therefore, 20, 30, 40, 50, 60, 70, 80 and 90 cannot be used.
3) Only one data (1 Word/ 1 Double Word / 1 Bit) can be read and written for each communication. So, the
“Optimize” (Optimization for reading) selection in “Communication” tab in the “Configuration” dialog box
in “Options” menu (Options Æ Configuration Æ Communication) is cancelled.
4) When using RS-232 communication, the user only can use 3 pins (Pin 2, Pin 3 and Pin 5). DO NOT use
5 pins for RS-232 communication. Also, Pin 9 is for +5V. Do not confuse and connect to the wrong pin;
otherwise the serious damage may occur.
5) The effective addresses of Cn are not consecutive (5 blocks: C0~17, C40~41, C45~C48, C50,
C90~C92). When setting the addresses, do not exceed the block range. For example, when using a
Numeric Entry or Character Entry element, if the address is C15, the data length only can be 6 Words
Revision January, 2008, Doc. Name: 2007PDD23000007 1-91
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
(C15, C16, C17). If the data length is out of this range, i.e. occupy other addresses except C0~C17, an
error may occur.
6) The effective addresses of Cn are not consecutive (5 blocks: C0~17, C40~41, C45~C48, C50,
C90~C92). However, when executing duplicate function (Decrease Address), the addresses will be
regarded as consecutive addresses. For example, the next address of C90 is C50; the next address of
C50 is C48; the next address of C45 is C41; the next address of C40 is C17.
7) When all Word address is written, the controllers all response ACK(0x06). But when all Word address is
read, the receive value will not change. The user needs to press ACT_DATA0 again and then the
receive value will be updated.
1-92 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
MKS CT150 Back to Table
A. HMI factory settings
Baud rate: 9600, 7, E, 1. (RS-232)
Controller Station number: 11.
Control area/status area: None / None.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format
Word No. Bit No.
Data In Register Cn n: 0 ~ 25 N/A
Setup Register Cn n: 40 ~ 43 N/A
45 ~ 50
90 ~ 97
Error Count Err_CNT 0 N/A
LV Value LV_VAL 0 N/A
Printmark Error PRTMARK_ERR 0 N/A
Batch Counter BAT_CNT 0 N/A
Waste Counter WASTE_CNT 0 N/A
Line Speed LINE_SPD 0 N/A
Actual Cutting Length ACT_CUT_LEN 0 N/A
Contacts
Contact type Format
Reset RST N/A 0
Jog Trim+ JOGTRIM_INC N/A 0
Jog Trim- JOGTRIM_DEC N/A 0
Read PI READ_PI N/A 0
Activate Data ACT_DATA N/A 0
Store Eeprom STR_EEPROM N/A 0
Start/Stop START_STOP N/A 0
Read/Write Range
Word No. Bit No.
Reset Mark Counter RSTMARK_CNT N/A 0
Revision January, 2008, Doc. Name: 2007PDD23000007 1-93
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
C. Connections (Connector Pinouts)
RS-232
DOP
9 pin D-SUB male (RS-232)
RXD (2)
TXD (3)
GND (5)
Controller
9 pin D-SUB male (RS-232)
(3) TXD
(2) RXD
(5) SG
Controller
9 pin D-SUB male (RS-232)
Pin1
Top View
1-94 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
MKS MC700/720 Motion Controller Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1.
(NOTE 1)
Controller Station number: 11
.
Control area/status area: None / None.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format
Data Length
Word No. Bit No.
General Parameters GPn n: 0 ~ 31 N/A Double Word
Parameter Block for Slave 1 PB1_n n: 0 ~ 31 N/A Double Word
Parameter Block for Slave 2 PB2_n n: 0 ~ 31 N/A Double Word
Parameter Block for Slave 3 PB3_n n: 0 ~ 31 N/A Double Word
Parameter Block for Slave 4 PB4_n n: 0 ~ 31 N/A Double Word
Process Data PRODn n: 0 ~ 31 N/A Double Word
Communication Settings CSETn n: 0 ~ 31 N/A Double Word
Setup Settings STUPn n: 0 ~ 31 N/A Double Word
Status of Commands and
Outputs
S_COn n: 0 ~ 4 N/A Double Word
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
Commands CMDb N/A b: 0 ~ 31
Outputs OUTb N/A b: 0 ~ 31
Status of Commands and
Outputs
S_COn.b n: 0 ~ 4 b: 0 ~ 31
Revision January, 2008, Doc. Name: 2007PDD23000007 1-95
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
C. Connections (Connector Pinouts)
RS-232
DOP
9 pin D-SUB male (RS-232)
RS-422
DOP
9 pin D-SUB male (RS-422)
9 pin D-SUB male (RS-232)
RXD (2)
TXD (3)
GND (5)
RXD- (1
RXD+ (2)
TXD+ (3)
TXD- (4) (1)R-
(3) TXD
(2) RXD
(5) GND
9 pin D-SUB male (RS-422)
(7)T
(8)T+
(6)R+
Controller
Controller
Controller
9 pin D-SUB male (RS-232)
Pin1
Top View
Controller
9 pin D-SUB male (RS-422)
Pin1
Top View
RS-485
DOP
9 pin D-SUB male (RS-485)
D+ (2
D+ (3)
D- (1)
D- (4)
NOTE
1) The valid station number is in the range of 11 to 99. However, 20, 30, 40, 50, 60, 70, 80 and 90 cannot
be used as they are all broadcast station number.
00 for all broadcast
10 for the broadcast to 11 ~ 19
20 for the broadcast to 21 ~ 29
9 pin D-SUB male (RS-485)
T+ (8)
T-( 7)
DOP
DOP
9 pin D-SUB male (RS-485)
Pin1
Top View
and vise versa.
2) Now the broadcast function is not provided, therefore, 20, 30, 40, 50, 60, 70, 80 and 90 cannot be used.
1-96 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
3) Only one data (1 Word/ 1 Double Word / 1 Bit) can be read and written for each communication. So, the
“Optimize” (Optimization for reading) selection in “Communication” tab in the “Configuration” dialog box
in “Options” menu (Options Æ Configuration Æ Communication) is cancelled.
4) When using RS-232 communication, the user only can use 3 pins (Pin 2, Pin 3 and Pin 5). DO NOT use
5 pins for RS-232 communication. Also, Pin 9 is for +5V. Do not confuse and connect to the wrong pin;
otherwise the serious damage may occur.
Revision January, 2008, Doc. Name: 2007PDD23000007 1-97
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Modbus(Master) --- 984 RTU / ASCII mode Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1. (ASCII)
9600, 8, EVEN, 1. (RTU)
Controller station number: 0.
Control area/status area: W40100 / W40200.
B. Definition of controller Read/Write address
Registers
Register Type Format
Data length
Word No. Bit No.
Output Registers Wn n: 40001 ~ 50000 N/A Word
Input Registers Wn n: 30001 ~ 40000 N/A Word
Read/Write Range
Input Registers is “read only”.
¾
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
Discrete Outputs Bn N/A n: 1 ~ 10000
Discrete Inputs Bn N/A n: 10001 ~ 20000
Discrete Inputs is “read only”.
¾
C. Connections (Connector Pinouts)
Please refer to 1.1 Pin Definition of Serial Communication for detail.
1-98 Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual| DOP-A/AE/AS Series
Modbus Hexadecimal Address (Master) --- RTU / ASCII mode Back to Table
A. HMI factory settings
Baud rate: 9600, 7, EVEN, 1. (ASCII)
9600, 8, EVEN, 1. (RTU)
Controller station number: 0.
Control area/status area: RW-0 / RW-10.
NOTE
1) The valid communication address starts from 0 and the format is hexadecimal. So the settable range are
0 to 65535 (i.e. 0 ~ FFFF in hexadecimal format).
2) The difference than “Standard Modbus” communication: (Protocol is the same)
The usage of setting communication address is different.
The range of communication address is different
The “Standard Modbus” communication is in decimal format. The start addresses are 40001, 30001, 1,
10001 and contains 10000 addresses respectively (40001 ~ 50000, 30001 ~ 40000, 1 ~ 10000, 10001 ~
20000).
The Modbus Hexadecimal Address (Master) is in hexadecimal format. The starting addresses are all
from 0 and there is 65536 addressing space (from 0 to FFFF) in each PDU (protocol data unit).
B. Definition of controller Read/Write address
Registers
Register Type Format
Output Registers RW-n n: 0 ~ FFFF N/A Word
Input Registers R-n n: 0 ~ FFFF N/A Word
RW- : can Read and Write.
¾
Converting the address to decimal format and plus 40001, it will immediately become the corresponding
“Standard Modbus” communication address.
R- (Input Registers) : Read only.
¾
Read/Write Range
Data length
Word No. Bit No.
Converting the address to decimal format and plus 30001, it will immediately become the corresponding
“Standard Modbus” communication address.
Revision January, 2008, Doc. Name: 2007PDD23000007 1-99