A. Introduction 
Device CME-LW01 is used for communication interface between 
Modbus and LonTalk. CME-LW01 needs be configured via 
LonWorks network tool first, so that it can perform the function on 
LonWorks network. No need to set CME-LW01 address. 
This manual provides instructions for the installation and setup for 
CME-LW01 that is used to communicate with Delta VFD-E 
(firmware version of VFD-E should conform with CME-LW01 
according to the table below) via LonWorks Network. The content 
of this instruction sheet may be revised without prior notice. 
Please consult our distributors or download the most updated 
version at http://www.delta.com.tw/industrialautomation.
Delta AC Drive 
Series  Firmware Version 
VFD-E  Version 2.02 or higher 
B. Dimensions 
72.2 [2.84]
]
]
5
7
3
.
3
.
2
[
0
[
7
.
5
.
9
9
5
CME-LW01
]
SP
6 
2
. 
2
[ 
3
. 
7 
5
 Terminal definition for LonTalk system 
Ter minal Symbol  Function 
1 
2 
3 
4 
E. LEDs Indications 
There are three LEDs in front panel of CME-LW01. If the 
communication is normal, power LED, SP LED should be green 
(red LED means abnormal communication) and service LED 
should be OFF. If LEDs display do not match, refer to user 
manual for details. 
 Power LED 
State  Description  Corrective Actions 
Green LED
LED is OFF
Power is on and 
CME-LW01 works 
Power on or program is 
abnormal 
 SP LED 
3.5 [0.14]34.8 [1.37]
State  Description  Corrective Actions 
Green LED
Blinked Green 
LED 
Red LED  Disconnect or time-out 
It communicates to AC 
drive 
CME-LW01 reads default 
setting from AC drive 
C. Specification 
Power supply  16-30VDC, 750mW 
Communication Modbus in ASCII format, protocol: 9600, 7, N, 2 
LonTalk  free topology with FTT-10A 78 Kbps 
LonTalk terminal 
RS-485 port  8 pins with RJ-45 
4-pin terminal, wire gauge: 28-12 AWG, wire strip 
length: 7-8mm 
D. Wiring 
Service LED
SP
CME-LW01
SP LED
1: Reserved  
2: EV   
3: GND 
4: SG -      
5: SG+  
6: Reserved 
7: Reserved  
8: Reserved
1
LonTalk
Service Pin
Power LED
234
LonTalk
 Service LED 
State  Description  Corrective Actions 
LED blinks at 
1/2 Hz rate 
LED is OFF Bad hardware device  
LED is ON 
continuously, 
even when 
power is first 
applied to the 
device. 
LED blinks at 
power-up, 
goes OFF, 
then ON 
solid. 
NOTE
Please download the XIF file and user manual at 
This is the normal 
situation for an 
un-configured device 
Bad hardware device 
This is the normal 
situation for an 
application-less device. 
http://www.delta.com.tw/industrialautomation/
These are twisted pair cables 
to connect to LonTalk system. 
Terminals 1 and 2 should be 
used as one group, and the 
same for terminals 3 and 4. 
1. Check if power is 24V or 
plug is loose. 
2. Check if flash memory IC is 
well-inserted to the socket.
1. Check if cable is loose. 
2. Check if the communication 
protocol is properly set. 
Check if anything wrong with 
power supply, clock or 
Neuron chip. 
1. Check if anything wrong 
with power supply, clock or 
Neuron chip. 
2. Check if there is a short 
circuit between pin 17 and 
18. 
If the device is not an 
application-less, then it could 
be memory problems or 
application code errors. A 
self-test failure can also turn 
the LED ON solid. 

LonWorks 通訊模組(CME-LW01)說明書 
 Lonworks 是 Echelon Corporation 的註冊商標。  
請詳細閱讀下列說明後才使用本産品,以確保使用安全。  
由於産品精益求精,當內容規格有所修正時,請洽詢代理商或至台達網站
(http://www.delta.com.tw/ch/product/em/em_main.asp)下載最新版本。
A.  前言 
本產品為 Modbus 與 LonTalk 通訊的轉換界面,透過 LonWorks 網 
路整合工具對 CME-LW01 組態(Configure)完成後,CME-LW01 
即可運行於 LonWorks 網路。 
下列內容提供 CME-LW01 的安裝與設定,以使台達變頻器可藉由 
CME-LW01 而連接至 LonWorks 網路。(CME-LW01 所支援變頻器 
的版本如下表所示。)由於產品精益求精,當內容規格有所修正時, 
請洽詢代理商或至台達網站 
(http://www.delta.com.tw/industrialautomation/)下載最新版本。
台達變頻器 
變頻器機種  韌體版本 
VFD-E 
Version 2.02 以上 
B.  尺寸 
72.2 [2.84]
]
]
5
7
3
.
3
.
2
[
0
[
7
.
5
.
9
9
5
CME-LW01
]
SP
6 
2
. 
2
[ 
3
. 
7 
5
3.5 [0.14]34.8 [1.37]
C.  電氣規格 
電源  16-30VDC, 750mW 
傳輸速率  Modbus:ASCII 7,N,2,鮑率:9600。 
LonTalk  free topology with FTT-10A 78 Kbps。 
LonTalk 連接埠 
4 PIN 端子座;適用導線線徑:28-12 AWG;剝線 
長度:7-8mm。 
RS-485 連接埠  8 PIN RJ-45 座 
D.  配線 
Service LED
SP
CME-LW01
SP LED
1: Reserved  
2: EV   
3: GND 
4: SG -      
5: SG+  
6: Reserved 
7: Reserved  
8: Reserved
1
LonTalk
234
LonTalk
Service Pin
Power LED
 LonTalk 端 Pin 腳定義 
Pin 腳  符號  功能 
1 
2 
3 
4 
以雙絞線方式接到 LonWorks 
裝置通訊口。 
配線時,pin 腳 1、2 需為一組, 
而 pin 腳 3、4 需為一組,不可 
配錯。 
E.  燈號指示 
CME-LW01 正面面板有三個 LED 指示燈,如下圖所示。當通訊正 
常,power LED、SP LED 應是亮綠色(若紅色指示燈亮起,則表示 
通訊異常)且 service LED 指示燈需是熄滅。若 LED 指示燈與上述 
不同時,請參考使用手冊。 
 Power LED 
狀態  功能描述  改善對策 
綠色 LED 亮
電源正常且CME-LW01正 
常運作 
1. 檢查輸入電源接頭是否有鬆 
脫 
LED 不亮 電源或程式異常 
2. 檢查 CME-LW01 的flash 
memory IC 是否已依 IC 座
的方向性平整的放置於 IC 座 
內。 
 SP LED 
狀態  功能描述  改善對策 
綠色 LED 亮
綠色 LED 閃爍
紅色 LED 亮
CME-LW01 與變頻器通訊 
正常 
CME-LW01 正在讀取變頻 
器預設值 
CME-LW01 與變頻器通訊 
異常或通訊逾時 
1. 檢查通訊線是否鬆脫 
2. 檢查通訊格式與鮑率是否符 
合 CME-LW01 之設定條件
 Service LED 
狀態  功能描述  改善對策 
LED 以1/2 Hz 的 
頻率閃爍組態 
(configure)完成 
後,LED 熄滅 
對於一個尚未組態
(unconfigure)的 
CME-LW01 而言,此乃正
常現象。CME-LW01 正常 
現象 
透過網路整合工具對
CME-LW01 進行組態,完成後 
LED 會熄滅。 
1. 檢查電源接頭與輸入規格
尚未組態
(unconfigure), 
LED 即不亮 
CME-LW01 硬體電路異 
常 
2. 檢查 CME-LW01 電路板上
的震盪器之震盪頻率是否 
在 20MHz 
3. 檢查神經元晶片外觀有無 
損毀 
1. 檢查電源接頭與輸入規格
2. 檢查 CME-LW01 電路板上
的震盪器之震盪頻率是否 
LED 恆亮,即使第 
一次給電亦如此。
CME-LW01 硬體電路異 
常 
在 20MHz 
3. 檢查神經元晶片外觀有無 
損毀 
4. 檢查神經元晶片接腳 17、 
18 之間有無短路 
若非本身沒有 Application 
LED 於上電初期
紅色閃爍,然後熄 
滅,最後紅色 LED 
恆亮。 
對於一個尚未運作
(Applicationless Device)
的 CME-LW01 而言,此 
乃正常現象 
Image 而導致 Applicationless 
的話,可能是 CME-LW01 程 
式或 CME-LW01 硬體問題導 
致此現象。自我測試檢查失 
敗,也可能使此 LED 恆亮。
NOTE
請至台達網站下載 XIF 檔案及其使用手冊 
http://www.delta.com.tw/ch/product/em/em_main.asp