DeviceNet Communication Module (CME-DN01) Instruction Sheet
DeviceNet is a trademark of the Open DeviceNet Vendor Association, Inc.
Please thoroughly read and understand the following contents to ensure correct use before operation.
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or
download the most updated version at http://www.delta.com.tw/industrialautomation
A. Panel Appearance and Dimensions
543
125K
250K
500K
MODNET
SP
BAUD
CME-DN01
2
57.3 [2.26]
UNIT: mm(inch)
1
3.5 [0.14]35.8 [1.41]
59.7 [2.35]
ADD1 ADD2
14.3 [0.57]
72.2 [2.84]
1. For RS-485 connection to VFD-E
2. Communication port for connecting DeviceNet network
3. Address selector
4. Baud rate selector
5. Three LED status indicators for monitor
B. Wiring and Settings
Dimensions
STEP 1
UNIT: mm(inch)
STEP 2
Refer to following diagram for details.
MAC address Date Rate
125K
250K
500K
ADD1 ADD2
BAUD
MODNET
CME-DN01
Setting baud rate
0
BAUD
Switch
Value
Baud
Rate
SP
Empty
CAN-H V-
CAN-LV+
pin
Setting MAC addresses:
use decimal system.
ADD1
1: Reserved
2: EV
3: GND
4: SG -
5: SG+
6: Reserved
7: Reserved
8: Reserved
ADD2
0 125K
1 250K
2 500K
Other
NOT
used
C. Mounting Method
Step1 and step2 show how to mount this communication
module onto VFD-E. The dimension in the following is for
your reference.
D. Power Supply
No external power is needed. Power is supplied via
RS-485 port that is connected to VFD-E. An 8 pins RJ-45
cable, which is packed together with this communication
module, is used to connect the RS-485 port between
VFD-E and this communication module for power. This
communication module will perform the function once it is
connected. Refer to the following paragraph for LED
indications.
E. LEDs Display
1. SP: Green LED means in normal condition, Red LED
means abnormal condition.
2. Module: Green blinking LED means no I/O data
transmission, Green steady LED means I/O data
transmission OK. Red LED blinking or steady LED
means module communication is abnormal.
3. Network: Green LED means DeviceNet
communication is normal, Red LED means abnormal.
NOTE
Please download the auto EDS generator and user manual
at http://www.delta.com.tw/industrialautomation/
DeviceNet 通訊模組(CME-DN01)說明書
DeviceNet 是 ODVA(Open Device Vendor Association) 的註冊商標。
請詳細閱讀下列說明後才使用本產品,以確保使用安全。
由於產品精益求精,當內容規格有所修正時,請洽詢代理商或至台達網站
(http://www.delta.com.tw/ch/product/em/em_main.asp)下載最新版本。
A. 面板尺寸外觀
543
125K
250K
500K
MODNET
ADD1 ADD2
59.7 [2.35]
14.3 [0.57]
72.2 [2.84]
SP
BAUD
CME-DN01
2
57.3 [2.26]
3.5 [0.14]35.8 [1.41]
UNIT: mm(inc h)
1. 與 VFD-E 系列連接的 RS-485 通訊接口
2. 連接 DeviceNet 通訊網路接口
3. 位址的選擇開關
4. 鮑率的選擇開關
5. 三個狀態顯示燈以顯示目前此通訊模組運行狀態
B. 接線
MAC address Date Rate
1: Reserved
2: EV
3: GND
4: SG -
5: SG+
6: Reserved
7: Reserved
8: Reserved
ADD1 A DD2
125K
BAUD
250K
500K
SP
MODNET
CME-DN01
Empty
CAN-LV+
CAN-H V-
pin
尺寸
1
UNIT: mm(inch)
步驟 1
步驟 2
設定傳輸速率
0
BAUD
Switch
Value
Baud
Rate
設定 MAC 位址:
請用十進位設定。
ADD1
ADD2
0 125K
1 250K
2 500K
Other
NOT
used
C. 安裝方式
步驟 1 及步驟 2 顯示如何將此通訊模組安裝至VFD-E 變頻
器。附上尺寸供您參考。
D. 電源供應
不需額外的電源。電源是由連接至變頻器(VFD-E)的RS-485
所提供。CME-DN01 包裝盒內的八支腳 RJ-45 通訊線是用來
連接變頻器的 RS-485 與 CME-DN01 以供應電源。一旦連接
完成,CME-DN01 即可操作。
E. 燈號指示
1. SP:綠燈表 VFD 系列通訊正常,紅燈表異常。
2. Module:綠燈閃爍表無 I/O data 傳輸;綠燈則表有 I/O
data 傳輸。紅燈閃爍及亮紅燈則表此通訊模組模組異常。
3. Network:綠燈表 DeviceNet 通訊正常,紅燈表異常。
NOTE
請至台達網站下載 DeviceNet EDS file 產生器及其使用手冊
http://www.delta.com.tw/ch/product/em/em_main.asp