Delta Electronics CME-COP01 User Manual

http://www.delta .com.tw/ind ustrialautoma tion/
2006-09-21
Production series
Production year (2006 )
Production plant (Taoyuan)
Production Model
1
2
3
4
5
6
7
9
A
B
C
D
BR
1
2
3
4
5
6
7
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
ID_L
PORT
1234567
8
8 7 6 5 4 3 2 1
DATA-
DATA+
(5)
(3) GND
3 This instruction sheet only provides descriptions on electricalspecifications, general specifications, installation and
wiring and is only an introductory guide to CME-COP01. For more informaion on CANopen protocol, please refer to relevant literature.
3 CME-COP01 is an OPEN TYPE controller and therefore should be installed in an enclosure free of airborn dust,
humidity, electric shock and vibration. The enclosure should protect non-maintenance staff from operating the device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may occur.
3 CME-COP01 is for controlling the machine and equipment in operation. In order not to damange it, please allow only
qualified staff who is familiar with the structure and operation of it to intall, operate, wire and maintain it.
3 Please read this instruction carefully and follow this instruction to operation the device in order to prevent damages on
the device or injuries to staff.
3 DO NOT connect input AC power supply to any of the input/output terminals; otherwise serious damage may occur.
Check all the wiring again before switching on the power and DO NOT touch any terminal when the power is switched on.
X Introduction
1.1 Model Explanation
Thank you for choosing Delta CME-COP01 CANopen communication module. CME-COP01 is specifically for connecting to CANopen communication module of Delta VFD-E AC motor drive.
Functions of CME-COP01:
Supports Process Data Objects (PDO) Protocol Supports Special Object Protocols (SOP) Supports Service Data Object (SDO) Protocol Supports Network Management (NMT) Protocol
Nameplate Explanation
Firmware version
Barcode & series No.
1.2 Product Profile
Y Specifications
CANopen Connection
Interface Pluggable connector (5.08mm)
Transmission method CAN
Transmission cable 2-wire twisted shielded cable
Electrical isolation 500V DC
Communication
Message type
Warning
Model name
MODEL:CME-COP01
USED ON:VFD-E SERIES VERSION:XX.XX
CMECOP01T6160001
7
634
Unit: mm
Process Data Objects (PDO)
Service Data Object (SDO)
Synchronization (SYNC)
Emergency (EMCY)
Network Management (NMT)
5
2
MADE IN XXXXXX
1
5011648700-MPE0
CANopen Network Adapter
Serial No. Explanation
COP0100 T 6160001
COM port
c
CANopen connection port
d
RUN indicator
e
ERROR indicator
f
SP (Scan Port) indicator
g
Baud rate switch
h
Address switch
i
10 Kbps
20 Kbps
50 Kbps
Baud rate
125 Kbps
250 Kbps
500 Kbps
800 Kbps
1 Mbps
Production week
Serial number of version
Product code Delta VFD-E AC motor drive 22
Device type 402
Vendor ID 477
Environmental Specifications
ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Noise Immunity
Analog & Communication I/O: 1KV Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV RS(IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Environment
Vibration / Shock Resistance
Operation: 0°C ~ 55°C (Temperature), 50 ~ 95% (Humidity), Pollution degree 2; Storage: -40°C ~ 70°C (Temperature), 5 ~ 95% (Humidity)
Standard: IEC1131-2, IEC 68-2-6(TEST Fc/IEC1131-2 & IEC 68-2-27 (TEST Ea)
Certifications Standard: IEC 61131-2,UL508
3.4.1 COM PORT
Port Pin Definition
PORT Sketch Terminal No. Description
1 N.C. 2 N.C. 3 N.C. 4 DATA+ 5 DATA­6 GND
7 V+ 8 N.C.
L The communication port supports RS-485/Modbus communication only.
[ Connecting CME-COP01 with VFD-E
When CME-COP01 communicates with VFD-E through PORT, the power of CME-COP01 is supplied by VFD-E. See the figure below for the wiring of connection.
RS-485 Communication
Z Components
3.1 Pin Definition on CANopen Connection Port
(Using standard cable with RJ-45 connectors at its two ends is suggested)
CME-COP01
RJ-45 (RS-485)
VFD-E
RJ-45 (RS-485)
To connect with CANopen, use the connector enclosed with CME-COP01 or any connectors you can buy in the store for wiring.
Pin Signal Content
1 CAN_GND Ground / 0 V / V-
8 7 6 5 4 3 2 1
GND (6) DATA- DATA+
V+ (7)
(2) V+
(5) (4)
2 CAN_L Signal-
3 SHIELD Shield
4 CAN_H Signal+
1 2 3 4 5
5 - Reserved
3.2 Baud Rate Setting
Rotary switch (BR) sets up the communication speed on CANopen network in hex. Setup range: 0 ~ 7 (8 ~F are forbidden)
Example: If you need to set up the communication speed of CME-COP01 as 500K, simply switch BR to “5”
BR Value Baud rate BR Value Baud rate
0 10K 4 250K
1 20K 5 500K
2 50K 6 800K
3 125K 7 1M
L The changed communication speed of CANopen is only valid when CME-COP01 is re-powered. When CME-COP01 is
operating, changing the set value of communication speed is invalid.
3.3 MAC ID Setting
8
9
A
ID_H
B
E
F
0
Rotary switches (ID_L and ID_H) set up the Node-ID on CANopen network in hex. Setup range: 00 ~ 7F (80 ~FF are forbidden)
Example: If you need to set up the communication address of CME-COP01 as 26(1AH), simply switch ID_H to “1” and ID_L to “A”.
Switch Setting Content
0 … 7F Valid CANopen MAC ID setting
Other Invalid CANopen MAC ID setting
The changed values on ID_H and ID_L are only valid when CME-COP01 is re-powered. When CME-COP01 is
L
operating, changing the address is invalid.
3.4 CME-COP01 Connector
\ LED Indicator Explanation & Troubleshooting
There are 3 LED indicators, RUN, ERROR and SP, on CME-COP01 to indicate the communication status of CME-COP01.
8
E
F
0
5.1 RUN LED
LED Status Stat e Indication OFF No power No power on CME-COP01 card
Single Flash (Green)
Blinking (Green)
STOPPED CME-COP01 is in STOPPED state
PRE-OPERATIONAL CME-COP01 is in the PRE-OPERATIONAL state
Green ON OPERATIONAL CME-COP01 is in the OPERATIONAL state
Red ON Configuration error Node-ID or Baud rate setting error
5.2 ERROR LED
LED Status State Indication OFF No error CME-COP01 is working condition
Single Flash (Red)
Double Flash (Red)
C
D
0
Red ON Bus-off The CANopen controller is bus-off
5.3 SP LED
LED Status State Indication OFF No Power No power on CME-COP01 card
LED Blinking (Red)
Warning limit reached
Error control event A guard event or heartbeat event has occurred
CRC check error
At least one of error counter of the CANopen controller has reached or exceeded the warning level (too many error frames)
Check your communication setting in VFD-E drives (19200,<8,N,2>,RTU)
1. Check the connection between VFD-E drive
Red ON Connection failure/No connection
and CME-COP01 card is correct
2. Re-wire the VFD-E connection and ensure that the wire specification is correct
LED Blinking (Green)
CME-COP01 returns error code
Check the PLC program, ensure the index and sub-index is correct
Green ON Normal Communication is normal
5.4 LED Descriptions
Stat e Description
LED ON Constantly on The communication port of CME-COP01 is used for connecting with Delta VFD-E AC motor drive.
LED OFF Constantly off
LED blinking Flash, on for 0.2s and off for 0.2s
LED single flash On for 0.2s and off for 1s
LED double flash On for 0.2s off for 0.2s, on for 0.2s and off for 1s
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or
download the most updated version at http://www.delta.com.tw/industrialautomation