Delta VFD015B23A, VFD007B23A, VFD015B43A, VFD015B53A, VFD007B53A User Manual

...
Page 1
A..:LT"
DELTA
ELEC11U)NICS,
INC
.
h-
-
Range:
3-phase
230V
aerlN:
0. 76-37kW{1.0-60HP)
3-phaae
460V
aerlN:
0. 76-76kW{1.0-tOOHP)
3-phaae
676V
aerlN:
0.76-76kW{1.0-tOOHP)
Page 2
A..:1.r•
DELTAELECTAONICS,
INC.
-.delte.com.twllnd111tr1111utom1t1on
AalA
D•ll•
l!l-""111••,
lnc
.
'l&o111•n1 31-1,Xlngbang Road, Oul1han lndu11lfalZon.,
T.0111•n C:ountyl!HTO, T-1"9n,
R.O.C:.
TEL: 81e-3-lMl2-4301 J FAX: 81M-3-H2-7287
D•ll•
El.olron
lH (.Jl•n1
lu)
LUI.
WuJlang Plants 1888
Jlanplng
e"t
Rof.d,
WuJl1n11
Econorny Dev1lopmentZone,
WuJl•n11
City,
Jlln(I
Su
PIOllll'IU,
Peopl•'s
R•publlcot
China
(Poet
code: 21G200)
TEL: IM-512-4340.lOOB
/FAX:
88-789-8340-7280
D•ll•
Electronl
ca
(.l•IMlft),
lnc.
Takyc>Otllca
Delta 8hlbed•lmon
Bulldlnt.
2·1·14
8hlbed•lmon,
Mlnate>-Ku,
Tokyo, 105..0012, Japan
TEL:
e1-a..ms-1111
IFAX:81~73S.1211
D•ll•
l!l.ctronlc•
(Ko-).
Ine.
234-9,
DuokSoo
BD7F, Nonttyun-don9,
Kllngnam-ku, Seoul,
Kor"
Poatcode:
1llli-410
TEL:
82·2·515~0315
/FAX:
82·2·515-6302
Delta l!l
eclronlca
(lllnoapon) "*·Ltd
.
8
Kald
Buklt Road
2,
~4-18
Ruby Wlreha111e ComplH,
Slngapore417841 TEL: 66-474 7-5166 t FAX:
66.f
744-l2:28
Delta l!n
eru
a,.e.-
(lndla)
l'Yt.
Ltd.
Plot
No.
27
& 31, S•otor-34, EHTP,
Gurgaon-122001 Haryana,
lndla
TEL:fl1-124-41U040/F.AX: 81-1:M-4()38046
A•l!lllCA
!»>la
l'roduota
Corporallon
(lllA)
Ralelgh
Olllce
P.O. Box
12173,11101
DIJV!sDrlve,
R-rch
Tllengi.
Perte.
NC
27709,
U.S.11.
TEL: 1-918-787-3113/FAX:
1-91fl-787-38llt
EUROPE
Deltronlca (11.U.•rl•nlll•) a . Y.
Elndhownófftoe
O.Wllbogt
15,
5852AO
Eindhoven,
ibeNethe~1nda
TEL: 31-40-2tiD-23-iO/ FAX: 31-40-2fiD-28-61
-W.
rM1rw.tM
rtght
u..
die.nae
tM
lnf<lm'll&l"l
lnthle
menu.al
Vrltttlout
pt1Gr
na1k:e
5011025714
200807-25
l l
lll
lll
Il Il
l l l l l l
lll
l l
lll
lll
I
BE16
Page 3
r
Page 4
Preface
Thank you for choosing DELTA’s high-performance VFD-B Series. The VFD-B Series is
manufactured with high-quality components and materials and incorporates the latest
microprocessor technology available.
This manual is to be used for the installation, parameter setting, troubleshooting, and daily
maintenance of the AC motor drive. To guarantee safe operation of the equipment, read the
following safety guidelines before connecting power to the AC motor drive. Keep this operating
manual at hand and distribute to all users for reference.
To ensure the safety of operators and equipment, only qualified personnel familiar with AC motor
drive are to do installation, start-up and maintenance. Always read this manual thoroughly before
using VFD-B series AC Motor Drive, especially the WARNING, DANGER and CAUTION notes.
Failure to comply may result in personal injury and equipment damage. If you have any questions,
please contact your dealer.
PLEASE READ PRIOR TO INSTALLATION FOR SAFETY.
DANGER!
1. AC input power must be disconnected before any wiring to the AC motor drive is made.
2. A charge may still remain in the DC-link capacitors with hazardous voltages, even if the power
has been turned off. To prevent personal injury, please ensure that power has been turned off
before opening the AC motor drive and wait ten minutes for the capacitors to discharge to safe
voltage levels.
3. Never reassemble internal components or wiring.
4. The AC motor drive may be destroyed beyond repair if incorrect cables are connected to the
input/output terminals. Never connect the AC motor drive output terminals U/T1, V/T2, and
W/T3 directly to the AC mains circuit power supply.
5. Ground the VFD-B using the ground terminal. The grounding method must comply with the laws
of the country where the AC motor drive is to be installed. Refer to the Basic Wiring Diagram.
6. VFD-B series is used only to control variable speed of 3-phase induction motors, NOT for 1-
phase motors or other purpose.
7. VFD-B series shall NOT be used for life support equipment or any life safety situation.
Page 5
WARNING!
1. DO NOT use Hi-pot test for internal components. The semi-conductor used in the AC motor
drive is easily damaged by high-pressure.
2. There are highly sensitive MOS components on the printed circuit boards. These components
are especially sensitive to static electricity. To prevent damage to these components, do not
touch these components or the circuit boards with metal objects or your bare hands.
3. Only qualified persons are allowed to install, wire and maintain AC motor drives.
CAUTION!
1. Some parameter settings will cause the motor to run immediately after applying power.
2. DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight,
high humidity, excessive vibration, corrosive gases or liquids, or airborne dust or metallic
particles.
3. Only use AC motor drives within specification. Failure to comply may result in fire, explosion or
electric shock.
4. To prevent personal injury, please keep children and unqualified people away from the
equipment.
5. When the motor cable between the AC motor drive and motor is too long, the layer insulation of
the motor may be damaged. Please use a frequency inverter duty motor or add an AC output
reactor to prevent damage to the motor. Refer to appendix B Reactor for details.
6. The rated voltage for the AC motor drive must be 240V ( 480V for 460V models, 600V for 575V models) and the mains supply current capacity must be 5000A RMS (10000A RMS for the 40hp (30kW) models).
Page 6
Table of Contents
Preface ............................................................................................................. i
Table of Contents .......................................................................................... iii
Chapter 1 Introduction................................................................................ 1-1
1.1 Receiving and Inspection ...................................................................1-1
1.1.1 Nameplate Information................................................................ 1-1
1.1.2 Model Explanation ...................................................................... 1-1
1.1.3 Series Number Explanation ........................................................ 1-2
1.1.4 Drive Frames .............................................................................. 1-2
1.2 Appearances ...................................................................................... 1-2
1.3 Preparation for Installation and Wiring ............................................... 1-4
1.3.1 Remove Keypad ......................................................................... 1-4
1.3.2 Remove Front Cover................................................................... 1-6
1.4 Lifting.................................................................................................. 1-7
1.5 Storage............................................................................................... 1-8
Chapter 2 Installation and Wiring .............................................................. 2-1
2.1 Ambient Conditions ............................................................................ 2-1
2.2 Installation .......................................................................................... 2-1
2.3 Dimensions......................................................................................... 2-3
2.4 Wiring ............................................................................................... 2-12
2.4.1 Basic Wiring.............................................................................. 2-13
Page 7
2.4.2 External Wiring.......................................................................... 2-18
2.4.3 Main Terminals Connections..................................................... 2-19
2.4.4 Control Terminals ...................................................................... 2-21
2.4.5 Main Circuit Terminals............................................................... 2-26
Chapter 3 Start Up .......................................................................................3-1
3.1 Preparations before Start-up...............................................................3-1
3.2 Operation Method ...............................................................................3-2
3.3 Trial Run .............................................................................................3-2
Chapter 4 Digital Keypad Operation ..........................................................4-1
4.1 Description of the Digital Keypad VFD-PU01......................................4-1
4.2 How to Operate the Digital Keypad VFD-PU01 ..................................4-3
Chapter 5 Parameters..................................................................................5-1
5.1 Summary of Parameter Settings.........................................................5-2
5.2 Parameter Settings for Applications..................................................5-18
5.3 Description of Parameter Settings ....................................................5-23
Chapter 6 Fault Code Information ..............................................................6-1
6.1 Common Problems and Solutions ......................................................6-1
6.2 Reset ..................................................................................................6-4
Chapter 7 Troubleshooting.........................................................................7-1
7.1 Over Current (OC) ..............................................................................7-1
7.2 Ground Fault.......................................................................................7-2
7.3 Over Voltage (OV) ..............................................................................7-2
7.4 Low Voltage (Lv).................................................................................7-3
7.5 Over Heat (OH)...................................................................................7-4
7.6 Overload .............................................................................................7-4
Page 8
7.7 Display of PU01 is Abnormal.............................................................. 7-5
7.8 Phase Loss (PHL) .............................................................................. 7-5
7.9 Motor cannot Run............................................................................... 7-6
7.10 Motor Speed cannot be Changed..................................................... 7-7
7.11 Motor Stalls during Acceleration....................................................... 7-8
7.12 The Motor does not Run as Expected .............................................. 7-8
7.13 Electromagnetic/Induction Noise ...................................................... 7-9
7.14 Environmental Condition .................................................................. 7-9
7.15 Affecting Other Machines ............................................................... 7-10
Chapter 8 Maintenance and Inspections ................................................... 8-1
Appendix A Specifications ........................................................................ A-1
Appendix B Accessories ........................................................................... B-1
B.1 All Brake Resistors & Brake Units Used in AC Motor Drives..............B-1
B.1.1 Dimensions and Weights for Brake Resistors ............................ B-4
B.1.2 Specifications for Brake Unit ......................................................B-6
B.1.3 Dimensions for Brake Unit.......................................................... B-7
B.2 AMD - EMI Filter Cross Reference.....................................................B-8
B.2.1 Dimensions...............................................................................B-12
B.3 PG Card (for Encoder) .....................................................................B-20
B.3.1 PG02 Installation ...................................................................... B-20
B.3.1.1 PG Card and Pulse Generator (Encoder) ......................... B-21
B.3.1.2 PG-02 Terminal Descriptions............................................ B-23
B.3.2 PG03 ........................................................................................ B-25
B.3.2.1 Installation......................................................................... B-25
Page 9
B.3.2.2 PG Card and Pulse Generator (Encoder)..........................B-26
B.3.2.3 PG-03 Terminal Descriptions ............................................B-27
B.4 Remote Controller RC-01 ................................................................ B-30
B.5 Remote Panel Adapter (RPA 01) .................................................... B-31
B.6 AC Reactor...................................................................................... B-32
B.6.1 AC Input Reactor Recommended Value ...................................B-32
B.6.2 AC Output Reactor Recommended Value ................................B-33
B.6.3 Applications for AC Reactor......................................................B-35
B.7 Zero Phase Reactor (RF220X00A) ................................................. B-37
B.8 DC Choke Recommended Values................................................... B-36
B.9 No-fuse Circuit Breaker Chart ......................................................... B-38
B.10 Fuse Specification Chart ............................................................... B-39
B.11 PU06 ............................................................................................. B-40
B.11.1 Description of the Digital keypad VFD-PU06 ..........................B-40
B.11.2 Explanation of Display Message .............................................B-40
B.11.3 Operation Flow Chart..............................................................B-41
Appendix C How to Select the Right AC Motor Drive.............................. C-1
C.1 Capacity Formulas ............................................................................ C-2
C.2 General Precaution ........................................................................... C-4
C.3 How to Choose a Suitable Motor....................................................... C-5
Page 10
Revision July 2008, BE16, SW V4.08 & V5.00 1-1
Chapter 1 Introduction
1.1 Receiving and Inspection
This VFD-B AC motor drive has gone through rigorous quality control tests at the factory before
shipment. After receiving the AC motor drive, please check for the following:
Check to make sure that the package includes an AC motor drive, the User Manual/Quick
Start and CD, dust covers and rubber bushings.
Inspect the unit to assure it was not damaged during shipment.
Make sure that the part number indicated on the nameplate corresponds with the part
number of your order.
1.1.1 Nameplate Information
Example for 1HP/0.75kW 3-phase 230V AC motor drive
Serial Number & Bar Code
AC Drive Model
Input Spec.
Output Spec.
Output Frequency Range
Enclosure type
MODE : VFD007B23A INPUT : 3PH 200-240V 50/60Hz 5.7A OUTPUT : 3PH 0-240V 5.0A 1.9kVA 1HP Freq. Range : 0.1~400Hz
ENCLOSURE: TYPE 1
007B23A0T5011230
1.1.2 Model Explanation
VFD
A
Version Type
23
Mains Input Voltage 21: Single phase230V
23: Three phase230V
43: Three phase460V
B
B Series
007
Applicable motor capacity
007: 1 HP(0.7kW) 150: 20HP(15kW)
022: 3 HP(2.2kW) 220: 30 HP(22kW) 037: 5 HP(3.7kW) 300: 40HP(30kW) 055: 7.5HP(5.5kW) 370: 50 HP(37kW) 075: 10 HP(7.5kW) 450: 60HP(45kW) 110: 15 HP(11kW) 550: 75HP(55kW)
750: 100HP(75kW)
Series Name ( ariable requency rive)
VF D
53:575 Three phaseV
Page 11
Chapter 1 Introduction|VFD-B Series
1-2 Revision July 2008, BE16, SW V4.08 & V5.00
1.1.3 Series Number Explanation
0170T007B23A
Production number
Production year 2007 Production factory
Production week
(Taoyuan)
Model
230V 3-phase 1HP(0.75kW)
If the nameplate information does not correspond to your purchase order or if there are any problems, please contact your distributor.
1.1.4 Drive Frames
Frame Power range Models
A 1hp (0.75kW) VFD007B23A/43A/53A
A1 1-2hp (0.75-1.5kW) VFD007B21A, VFD015B21A/23A/43A/53A
A2 2-3hp (1.5-2.2kW) VFD015B21B/23B, VFD022B23B/43B/53A
B 3-5hp (2.2-3.7kW) VFD022B21A, VFD037B23A/43A/53A
C 7.5-15hp (5.5-11kW)
VFD055B23A/43A/53A,
VFD075B23A/43A/53A,
VFD110B23A/43A/53A
D 20-30hp (15-22kW)
VFD150B23A/43A/53A,
VFD185B23A/43A/53A,
VFD220B23A/43A/53A
E 40-60hp (30-45kW)
VFD300B43A/53A, VFD370B43A/53A,
VFD450B43A/53A
E1 40-100hp (30-75kW)
VFD300B23A, VFD370B23A,
VFD550B43C/53A, VFD750B43C/53A
Please refer to Chapter 2.3 for exact dimensions.
1.2 Appearances
(Refer to chapter 2.3 for exact dimensions)
1-3HP/0.75-2.2kW (Frame A, A1, A2) 3-5HP/2.2-3.7kW (Frame B)
Page 12
Chapter 1 Introduction|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 1-3
7.5-15HP/5.5-11kW (Frame C) 20-30HP/15-22kW (Frame D)
Page 13
Chapter 1 Introduction|VFD-B Series
1-4 Revision July 2008, BE16, SW V4.08 & V5.00
40-100HP/30-75kW (Frame E, E1) 75-100HP/55-75kW (Frame F)
1.3 Preparation for Installation and Wiring
1.3.1 Remove Keypad
1-3HP/0.75-2.2kW (Frame A, A1, A2) 3-5HP/2.2-3.7kW (Frame B)
Page 14
Chapter 1 Introduction|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 1-5
7.5-15HP/5.5-11kW (Frame C) 20-30HP/15-22kW (Frame D)
40-100HP/30-75kW (Frame E, E1) 75-100HP/55-75kW (Frame F)
Page 15
Chapter 1 Introduction|VFD-B Series
1-6 Revision July 2008, BE16, SW V4.08 & V5.00
1.3.2 Remove Front Cover
1-3HP/0.75-2.2kW (Frame A, A1, A2) 3-5HP/2.2-3.7kW (Frame B)
7.5-15HP/5.5-11kW (Frame C) 20-30HP/15-22kW (Frame D)
Page 16
Chapter 1 Introduction|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 1-7
40-100HP/30-75kW (Frame E, E1) 75-100HP/55-75kW (Frame F)
1.4 Lifting
Please carry only fully assembled AC motor drives as shown in the following.
For 40-100HP (Frame E, E1 and F)
Step 1 Step 2
Page 17
Chapter 1 Introduction|VFD-B Series
1-8 Revision July 2008, BE16, SW V4.08 & V5.00
Step 3 Step 4
1.5 Storage
The AC motor drive should be kept in the shipping carton or crate before installation. In order to
retain the warranty coverage, the AC motor drive should be stored properly when it is not to be
used for an extended period of time. Storage conditions are:
Store in a clean and dry location free from direct sunlight or corrosive fumes.
Store within an ambient temperature range of -20 °C to +60 °C.
Store within a relative humidity range of 0% to 90% and non-condensing environment.
Store within an air pressure range of 86 kPA to 106kPA.
CAUTION!
1. DO NOT store in an area with rapid changes in temperature. It may cause condensation and
frost.
2. DO NOT place on the ground directly. It should be stored properly. Moreover, if the surrounding
environment is humid, you should put exsiccator in the package.
3. If the AC motor drive is stored for more than 3 months, the temperature should not be higher
than 30 °C. Storage longer than one year is not recommended, it could result in the degradation
of the electrolytic capacitors.
4. When the AC motor drive is not used for a long time after installation on building sites or places
with humidity and dust, it’s best to move the AC motor drive to an environment as stated above.
Page 18
Revision July 2008, BE16, SW V4.08 & V5.00 2-1
Chapter 2 Installation and Wiring
2.1 Ambient Conditions
Install the AC motor drive in an environment with the following conditions:
Operation Air Temperature: -10 ~ +40°C (14 ~ 104°F)
Relative Humidity: <90%, no condensation allowed
Atmosphere pressure: 86 ~ 106 kPa Installation Site Altitude: <1000m Vibration: <20Hz: 9.80 m/s
2
(1G) max
20 ~ 50Hz: 5.88 m/s
2
(0.6G) max
Storage Transportation
Temperature: -20°C ~ +60°C (-4°F ~ 140°F) Relative Humidity: <90%, no condensation allowed Atmosphere pressure: 86 ~ 106 kPa Vibration: <20Hz: 9.80 m/s
2
(1G) max
20 ~ 50Hz: 5.88 m/s
2
(0.6G) max
Pollution Degree 2: good for a factory type environment.
CAUTION!
1. Operating, storing or transporting the AC motor drive outside these conditions may cause
damage to the AC motor drive.
2. Failure to observe these precautions may void the warranty!
2.2 Installation
1. Mount the AC motor drive vertically on a flat vertical surface by using bolts or screws. Other
directions are not allowed.
2. The AC motor drive will generate heat during operation. Allow sufficient space around the unit
for heat dissipation.
3. The heat sink temperature may rise to 90°C when running. The material on which the AC motor
drive is mounted must be noncombustible and be able to withstand this high temperature.
4. When the AC motor drive is installed in a confined space (e.g. cabinet), the surrounding
temperature must be within 10 ~ 40°C with good ventilation. DO NOT install the AC motor drive
in a space with bad ventilation.
Page 19
Chapter 2 Installation and Wiring|VFD-B Series
2-2 Revision July 2008, BE16, SW V4.08 & V5.00
5. When installing multiple AC motor drives in the same cabinet, they should be adjacent in a row
with enough space in-between. When installing one AC motor drive below another one, use a
metal separation barrier between the AC motor drives to prevent mutual heating.
6. Prevent fiber particles, scraps of paper, saw dust, metal particles, etc. from adhering to the
heatsink.
Minimum Mounting Clearances
H
DATA
PROG
REV
FWD
Air Flow
H
W
W
HP
W
mm (inch)
H
mm (inch)
1-5HP 50 (2) 150 (6)
7.5-20HP 75 (3) 175 (7) 25-75HP 75 (3) 200 (8)
100HP and above 75 (3) 250 (10)
Page 20
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-3
2.3 Dimensions
(Dimensions are in millimeter and [inch])
Frame A: VFD007B23A/43A/53A
5.5[0.22]
108.0 [4.25]
118.0 [4.65]
173.0 [6.81]
185.0 [7.28]
5.5[0.22]
R
2.7
5[0.1
1
]
145.0 [5.71]
8.7 [0.34]
22.
0[
0
.
8
7]
2
8
.
0
[
1
.
1
0
](
2
X
)
Page 21
Chapter 2 Installation and Wiring|VFD-B Series
2-4 Revision July 2008, BE16, SW V4.08 & V5.00
Frame A1: VFD007B21A, VFD015B21A/23A/43A/53A
5.5[0.22]
R
2
.
7
5
[0
.
1
1
]
5.5[0.22]
185.0 [7.28]
173.0 [6.81]
160.0 [6.30]
118.0 [4.65]
108.0 [4.25]
8.7 [0.34]
2
8.
0[
1
.
1
0
]
(
2
X
)
2
2
.
0
[ 0
.
8
7
]
Page 22
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-5
Frame A2: VFD015B21B/23B, VFD022B23B/43B/53A
5.5[0.22]
R
2.75
[0.11]
2
8
.
0
[
1
.1
0
](
2
X
)
2
2
.
0
[
0
.
8
7]
8.7 [0.34]
145.0 [5.71]
118.0 [4.65]
108.0 [4.25]
5.5[0.22]
185.0 [7.28]
173.0 [6.81]
Page 23
Chapter 2 Installation and Wiring|VFD-B Series
2-6 Revision July 2008, BE16, SW V4.08 & V5.00
Frame B: VFD022B21A, VFD037B23A/43A/53A
11.3 [0.44]
6
.
5
[
0
.
2
6
]
2
2
.
0
[
0
.
8
7
]
(
2
X
)
2
8
.
0
[
1
.
1
0
]
(2
X
)
R
3
.
2
5
[R
0
.1
3
]
6.5[0.26]
260.0[10.24]
UNIT : mm(inch)
135.0 [5.32]
160.2 [6.31]
244.3 [9.63]
150.0 [5.91]
Page 24
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-7
Frame C: VFD055B23A/43A/53A, VFD075B23A/43A/53A, VFD110B23A/43A/53A
200.0 [7.88]
323.0 [12.72]
185.6 [7.31]
303.0 [11.93]
R3
.
5
[
R
0
.
1
4
]
7.0 [0.28]
13.5 [0.53]
183.2 [7.22]
7
.0
[
0
.2
8
]
Page 25
Chapter 2 Installation and Wiring|VFD-B Series
2-8 Revision July 2008, BE16, SW V4.08 & V5.00
Frame D: VFD150B23A/43A/53A, VFD185B23A/43A/53A, VFD220B23A/43A/53A
13.0 [0.51]
10.0 [0.39]
R5
.
0
[
R
0
.
2
0
]
403.8 [15.90]
384.0 [15.12]
4
2
.
0
[
1
.
6
5
]
(
2
X
)
250.0 [9.84]
226.0 [8.90]
2
8
.
0
[
1
.
1
0
]
205.4 [8.08]
10.0 [ 0.39]
Page 26
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-9
Frame E: VFD300B43A/53A, VFD370B43A/53A, VFD450B43A/53A
335.0 [13.19]
370.0 [14.57] 260.0 [10.24]
589.0 [23.19]
560.0 [22.05]
18.0 [0.71]
132.5 [5.22]
R6.5[0.25]
13.0[0.51]
21.0[0.83]
Page 27
Chapter 2 Installation and Wiring|VFD-B Series
2-10 Revision July 2008, BE16, SW V4.08 & V5.00
Frame E1: VFD300B23A, VFD370B23A, VFD550B43C/53A, VFD750B43C/53A
132.5 [5.22]
18.0 [0.71]
21.0[0.83]
335.0 [13.19]
370.0 [14.57] 260.0 [10.24]
589.0 [23.19]
560.0 [22.05]
R6.5[0.25]
13.0[0.51]
595.0 [23.43]
Page 28
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-11
Page 29
Chapter 2 Installation and Wiring|VFD-B Series
2-12 Revision July 2008, BE16, SW V4.08 & V5.00
VFD-PU01
RUN
JOG
DATA
RESET
STOP
PROG
MODE
RUN
STOP
F H
U
VFD- PU0 1
REVFWDJOG
2.4 Wiring
After removing the front cover, check if the power and control terminals are clear of debris. Be sure
to observe the following precautions when wiring.
General Wiring Information
Applicable Codes
All VFD-B series are Underwriters Laboratories, Inc. (UL) and Canadian Underwriters Laboratories
(cUL) listed, and therefore comply with the requirements of the National Electrical Code (NEC) and
the Canadian Electrical Code (CEC).
Installation intended to meet the UL and cUL requirements must follow the instructions provided in
“Wiring Notes” as a minimum standard. Follow all local codes that exceed UL and cUL
requirements. Refer to the technical data label affixed to the AC motor drive and the motor
nameplate for electrical data.
The "Line Fuse Specification" in Appendix B, lists the recommended fuse part number for each
VFD-B Series part number. These fuses (or equivalent) must be used on all installations where
compliance with U.L. standards is a required.
Page 30
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-13
2.4.1 Basic Wiring
Make sure that power is only applied to the R/L1, S/L2, T/L3 terminals. Failure to comply
may result in damage to the equipment. The voltage and current should lie within the range
as indicated on the nameplate.
Check the following items after completing the wiring:
1. Are all connections correct?
2. No loose wires?
3. No short-circuits between terminals or to ground?
A charge may still remain in the DC bus capacitors with hazardous voltages even if the power has
been turned off. To prevent personal injury, please ensure that the power is turned off and wait ten
minutes for the capacitors to discharge to safe voltage levels before opening the AC motor drive.
DANGER!
1. All the units must be grounded directly to a common ground terminal to prevent electric shock,
fire and interference.
2. Only qualified personnel familiar with AC motor drives are allowed to perform installation, wiring
and commissioning.
3. Make sure that the power is off before doing any wiring to prevent electric shocks.
Basic Wiring Diagrams
Users must connect wires according to the circuit diagrams on the following pages. Do not plug a
modem or telephone line to the RS-485 communication port or permanent damage may result. The
pins 1 & 2 are the power supply for the optional copy keypad PU06 only and should not be used for
RS-485 communication.
Page 31
Chapter 2 Installation and Wiring|VFD-B Series
2-14 Revision July 2008, BE16, SW V4.08 & V5.00
AVI
ACI AUI
ACM
+2/B1
B2
4~20mA
-10~+10V
+10V
5K
3
2
1
Figure 1 for models of VFD-B Series VFD007B21A/23A/43A/53A, VFD015B21A/21B/23A/23B/43A/53A, VFD022B23B/43B/53A
Jumper
Brake resistor (optional)
Power supply +10V 20mA
Master Frequency 0 to 10V 4 7 K
Analog Signal Common
DC choke (optional)
E
Main circuit (power) terminals
Control circuit terminals
Shielded leads & Cable
FWD REV JOG
EF MI1 MI2 MI3 MI4
MI6 TRG
MI5
DCM
+24V
Sw1
Sink
Source
Factory setting: SINK Mode
FWD/STOP
REV/STOP
JOG
E.F.
Multi-s tep 1
Multi-step 2
Mult i-step 3
Mult i-step 4
RESET
Accel/Decel prohibit
Counter
Digital Signal Common
Factory sett ing
* Don't apply the mains voltage directly to above terminals.
E
Please refer to Figure 4 for wiring of SIN K mode and SOU R CE mode.
R(L1) S(L2)
T(L3)
Fuse/NFB(None Fuse Breaker)
SA
OFF
ON
MC
MC
RB
RC
+1
Recommended Circuit when power supply is turned OFF by a fault output.
R(L1)
S(L2)
T(L3)
E
Analog Multi-function Output Te r m i n al factory setting: Analog freq. / current meter
0~10VDC/2mA
U(T1)
V(T2)
W(T3)
IM
3~
MO1
MO2
MO3
AFM
ACM
RA
RB
RC
MCM
RS-485
Motor
factory setting: indicates during operation 48V50mA
factory setting: Freq. Setting Indication
factory setting: Low-voltage Indication
Multi-function Photocoulper Output
Analog Signal common
Serial interface
1: EV 2: GND
5:Reserved
6: Reserved
3: SG-
4: SG+
DFM
DCM
Digital Frequency Output Te r m i n al factory setting: 1:1 Duty=50%
Digital Signal Comm on
48V50mA
48V50mA
E
E
Refer to Control Ter mi n al Ex pl ana t ion
* For the single phase drives, the AC input line can be connected to any two of the three input terminals R,S,T
* Three phase input power may apply to single phase drives.
The contact will be ON when the fault occurs to turn off the power and protect the power system.
Page 32
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-15
Figure 2 for models of VFD-B Series VFD022B21A, VFD037 B23A/43A/5 3A, VFD055B23A /4 3A/53A, VFD075B23A/43A/5 3A, VFD110B23A/43A/53A
Br ake r esi st o r (o p t ional ) Refer to Appendix B for the use of special brake resi stor
+1
+2/B1
B2
Jumper
* For the single phase drives, the AC input line can be connected to any two of the three input terminals R,S,T
* Three phase input power may apply to single phas e drives.
-(minus sign)
BR
DC chock (optional)
AVI
ACI
AUI ACM
4~20mA
-10~+10V
+10V
5K
3
2
1
Power supply +10V 20mA
Master Frequency 0 to 10V 4 7 K
Analog Signal Common
E
FWD REV JOG
EF MI1 MI2 MI3 MI4
MI6 TRG
MI5
DCM
+24V
Sw1
Sink
Source
Factory Settin g: SINK Mode
FWD/STOP
REV/STOP
JOG
E.F.
Multi-s tep 1
Multi-s tep 2
Multi-s tep 3
Multi-s tep 4
RESET
Accel/Decel prohibit
Counter
Digital Signal Common
Factory setting
* Don't apply the mains voltage directly to above terminals.
E
Please refer to Figure 4 for wiring of SINK mode and SOURCE mode.
R(L1) S(L2)
T(L3)
Fuse/NFB(None Fuse Breaker)
SA
OFF
ON
MC
MC
RB
RC
R(L1)
S(L2)
T(L3)
E
Analog Multi-function Output Terminal Factory default: Anal og freq. / current meter
0~10VDC/2 mA
MO3
U(T1)
V(T2)
W(T3)
IM
3~
MO1
MO2
AFM
ACM
RA
RB
RC
MCM
RS-485
Motor
Factor y setting: indicates during operation 48V50mA
Factor y setting: Freq. Setting Indication
Factor y setting: Low-voltage Indication
Multi-function Photocoulper Output
Analog Signal common
Serial int erf ace
1: EV 2: GND
5:Reserved
6: Reserv ed
3: SG-
4: SG+
DFM
DCM
Digital Frequency Output Terminal Factor y setting: 1:1 Duty=50%
Digital Signal Common
48V50mA
48V50mA
E
E
Please refer to Contr ol Terminal Ex planation.
6 1
Main circui t (power) terminals
Control circuit terminals
Shielded leads & Cable
Recommended Circuit when power supply is turned OFF by a fault output.
The contact will be ON when the fault occur s to turn off the power and protect the power system.
Page 33
Chapter 2 Installation and Wiring|VFD-B Series
2-16 Revision July 2008, BE16, SW V4.08 & V5.00
Figure 3 for models of VFD-B Serie
s
VFD150B23A/4 3A/53A, VFD220B23A/4 3A/53A, VFD300B23A/43A/53A, VFD370B23A/4 3A/53A, VFD450B43A/53A, VFD550B43C/53A, VFD750B43C/53A
VFD185B23A/43A/53A,
Brake resistor/unit(optional) Refer to Appendi x B for the use of special brake resi stor/uni t
+1
+2
Jumper
VFDB
-(minus sign)
DC chock (optional)
Main circuit (power) t erm inals
Control c ircuit terminals
Shielded leads & Cable
Analog Multi-function Output Te r m in a l factory setti ng: Analog freq. / c urrent meter
0~10VDC/2 mA
MO3
U(T1)
V(T2)
W(T3)
IM
3~
MO1
MO2
AFM
ACM
RA
RB
RC
MCM
RS-485
Motor
Factory setting: indicates during operation 48V50mA
Factory setting: Freq. Setting Indication
Factory setting: Low-voltage Indication
Multi-function Photocoulper Output
Analog Signal common
Seri al int erf ace
1: EV 2: GND
5:Reserv ed
6: Reserved
3: SG-
4: SG+
DFM
DCM
Digital Frequency Output Te r m in a l Factory setting: 1:1 Duty=50%
Digital Signal Common
48V50mA
48V50mA
E
E
Pleas e refer to C on t r ol Terminal Explanation
6
1
AVI
ACI AUI ACM
4~20mA
-10~+10V
+10V
5K
3
2
1
Power supply +10V 20mA
Master Frequency 0 to 10V 4 7 K
Analog Signal Common
E
FWD REV JOG
EF MI1 MI2 MI3 MI4
MI6 TRG
MI5
DCM
+24V
Sw1
Sink
Source
Factory setting: SINK Mode
FWD/STOP
REV/STOP
JOG
E.F.
Mult i-step 1
Multi-step 2
Multi-step 3
Multi-step 4
RESET
Accel/Decel prohibit
Counter
Digital Signal Common
Factory setting
* Don't apply the mains voltage directly to above terminals.
E
Please refer to Figure 4 for w ir ing of SI NK mode and SOURCE mode.
R(L1) S(L2)
T(L3)
Fuse/NFB(None Fuse Breaker)
SA
OFF
ON
MC
MC
RB
RC
+1
R(L1)
S(L2)
T(L3)
E
* For the single phase drives, the AC input line can be connected to any two of the three input terminals R,S,T
* Three phase input power may apply to single phase drives.
Recommended Circui t when power supply is turned OFF by a fault output.
The contact will be ON when the fault occurs to turn off the power and protect the power sys tem.
Page 34
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-17
Figure 4 Wiring for SINK mode and SOURCE mode
Factory setting
SINK Mode
*Don't apply the mains voltage directly to above terminals.
FWD/STOP
REV/STOP
Multi-step1
Multi-step2
Multi-step3
Multi-step4
Digital Signal Common
+24V
MI1
MI2
MI3
MI4
MI5
MI6
DCM
E
Sink
Source
SW1
FWD
REV
JOG
EF
TRG
JOG
E.F.
RESET
Accel./Decel. prohibit
Counter
Sw1
Sink
Source
Factory setting
SOURCE Mode
*Don't apply the mains voltage directly to above terminals.
FWD/STOP
REV/STOP
Multi-step1
Multi-step2
Multi-step3
Multi-step4
Digital Signal Common
+24V
MI1
MI2
MI3
MI4
MI5
MI6
DCM
E
FWD
REV
JOG
EF
TRG
JOG
E.F.
RESET
Accel./Decel. prohibit
Counter
Page 35
Chapter 2 Installation and Wiring|VFD-B Series
2-18 Revision July 2008, BE16, SW V4.08 & V5.00
2.4.2 External Wiring
Motor
Output AC Line Reactor
Power Suppl
y
Magnetic contact or
Input AC Line Reactor
EMI Filter
R/L1
S/L2
T/L3
U/T1 V/T2
W/T3
+2/B1
Zero-pha se Reactor
Zero-phase Reactor
FUSE/NFB
B2
-
BR
BUE
BR
E
+1 DC
Chock
Items Explanations
Power supply
Please follow the specific power supply requirements shown in Appendix A.
Fuse/NFB (Optional)
There may be an inrush current during power up. Please check the chart of Appendix B and select the correct fuse with rated current. Use of an NFB is optional.
Magnetic contactor (Optional)
Please do not use a Magnetic contactor as the I/O switch of the AC motor drive, as it will reduce the operating life cycle of the AC drive.
Input AC Line Reactor (Optional)
Used to improve the input power factor, to reduce harmonics and provide protection from AC line disturbances (surges, switching spikes, short interruptions, etc.). AC line reactor should be installed when the power supply capacity is 500kVA or more or advanced capacity is activated .The wiring distance should be
10m. Refer to appendix B for
details.
Zero-phase Reactor (Ferrite Core Common Choke) (Optional)
Zero phase reactors are used to reduce radio noise especially when audio equipment is installed near the inverter. Effective for noise reduction on both the input and output sides. Attenuation quality is good for a wide range from AM band to 10MHz. Appendix B specifies the zero phase reactor. (RF220X00A)
EMI filter (Optional)
To reduce electromagnetic interference, please refer to Appendix B for more details.
Brake Resistor (Optional)
Used to reduce the deceleration time of the motor. Please refer to the chart in Appendix B for specific Brake Resistors.
Output AC Line Reactor (Optional)
Motor surge voltage amplitude depends on motor cable length. For applications with long motor cable (>20m), it is necessary to install a
Page 36
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-19
2.4.3 Main Terminals Connections
Terminal Symbol Explanation of Terminal Function
R, S, T R/L1, S/L2, T/L3 AC line input terminals (1-phase/3-phase)
U, V, W U/T1, V/T2, W/T3
AC drive output terminals for connecting 3-phase
induction motor
P1, P2 +1, +2 Connections for DC Choke (optional)
P-B, P2/B1~B2 +2/B1~B2 Connections for Brake Resistor (optional)
P2~N, P2/B1~N +2~(-), +2/B1~(-) Connections for External Brake Unit (VFDB series)
Earth connection, please comply with local regulations.
Mains power terminals (R/L1, S/L2, T/L3)
Connect these terminals (R/L1, S/L2, T/L3) via a no-fuse breaker or earth leakage breaker to
3-phase AC power (some models to 1-phase AC power) for circuit protection. It is
unnecessary to consider phase-sequence.
It is recommended to add a magnetic contactor (MC) in the power input wiring to cut off
power quickly and reduce malfunction when activating the protection function of AC motor
drives. Both ends of the MC should have an R-C surge absorber.
Do NOT run/stop AC motor drives by turning the power ON/OFF. Run/stop AC motor drives
by RUN/STOP command via control terminals or keypad. If you still need to run/stop AC
drives by turning power ON/OFF, it is recommended to do so only ONCE per hour.
Do NOT connect 3-phase models to a 1-phase power source.
Control circuit terminals (U, V, W)
When the AC drive output terminals U/T1, V/T2, and W/T3 are connected to the motor
terminals U/T1, V/T2, and W/T3, respectively, the motor will rotate counterclockwise (as
viewed on the shaft end of the motor) when a forward operation command is received. To
permanently reverse the direction of motor rotation, switch over any of the two motor leads.
Forward running
Page 37
Chapter 2 Installation and Wiring|VFD-B Series
2-20 Revision July 2008, BE16, SW V4.08 & V5.00
DO NOT connect phase-compensation capacitors or surge absorbers at the output terminals
of AC motor drives.
With long motor cables, high capacitive switching current peaks can cause over-current, high
leakage current or lower current readout accuracy. To prevent this, the motor cable should
be less than 20m for 3.7kW models and below. And the cable should be less than 50m for
5.5kW models and above. For longer motor cables use an AC output reactor.
Use a well-insulated motor, suitable for inverter operation.
Terminals [+1, +2] for connecting DC reactor
+1
Jumper
DC reactor
To improve the power factor and reduce harmonics, connect a DC reactor between terminals
[+1, +2]. Please remove the jumper before connecting the DC reactor.
NOTE
Models of 15kW and above have a built-in DC reactor.
Terminals [+2/B1, B2] for connecting brake resistor and terminals [+1, +2/B1] for connecting
external brake unit
B2
VFDB
-(minus sign)
BR
BR
Connect a brake resistor or brake unit in applications with frequent deceleration ramps, short
deceleration time, too low brake torque or requiring increased brake torque.
If the AC motor drive has a built-in brake chopper (all models of 11kW and below), connect
the external brake resistor to the terminals [+2/B1, B2].
Models of 15kW and above don’t have a built-in brake chopper. Please connect an external
optional brake unit (VFDB-series) and brake resistor. Refer to VFDB series user manual for
details.
Connect the terminals [+(P), -(N)] of the brake unit to the AC motor drive terminals
[+2(+2/B1), (-)]. The length of wiring should be less than 5m with twisted cable.
When not used, please leave the terminals [+2/B1, -] open.
Page 38
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-21
WARNING!
1. Short-circuiting [B2] or [-] to [+2/B1] can damage the AC motor drive.
Grounding terminals (
)
Make sure that the leads are connected correctly and the AC drive is properly grounded.
(Ground resistance should not exceed 0.1Ω.)
Use ground leads that comply with local regulations and keep them as short as possible.
Multiple VFD-B units can be installed in one location. All the units should be grounded
directly to a common ground terminal, as shown in the figure below. Ensure there are no
ground loops.
goodexcellent
not allowed
2.4.4 Control Terminals
Circuit diagram for digital inputs (SINK current 16mA.)
+24
SINK Mode
multi-input terminal
Internal Circuit
DCM
+24V
Multi-Input Terminal
DCM
Internal Circuit
SOURCE Mode
Terminal symbols and functions
Terminal
Symbol
Terminal Function
Factory Settings (SINK)
ON: Connect to DCM
FWD Forward-Stop command
ON: Run in FWD direction
OFF: Stop acc. to Stop Method
REV Reverse-Stop command
ON: Run in REV direction
OFF: Stop acc. to Stop Method
Page 39
Chapter 2 Installation and Wiring|VFD-B Series
2-22 Revision July 2008, BE16, SW V4.08 & V5.00
Terminal
Symbol
Terminal Function
Factory Settings (SINK)
ON: Connect to DCM
JOG Jog command
ON: JOG operation
OFF: Stop acc. to Stop Method
EF External fault
ON: External Fault. Display “EF” and stop
acc. To Stop Method.
OFF: No fault
TRG External counter input
ON: At every pulse counter is advanced
by 1.
MI1 Multi-function Input 1
MI2 Multi-function Input 2
MI3 Multi-function Input 3
MI4 Multi-function Input 4
MI5 Multi-function Input 5
MI6 Multi-function Input 6
Refer to Pr.04-04 to Pr.04-09 for programming the Multi-function Inputs.
DFM
Digital Frequency Meter
(Open Collector Output)
Max: 48V
50mA
DFM-DCM
100%
50%
internal circuit
Pulse voltage output monitor signal,
proportional to output frequency
Duty-cycle: 50%
Ratio: Pr.03-07
Min. load: 10K
Max. current: 50mA
Max. voltage: 48VDC.
+24V DC Voltage Source
+24VDC, 20mA
used for SOURCE mode.
DCM Digital Signal Common
Common for digital inputs and used for SINK mode.
RA
Multi-function Relay output (N.O.) a
RB
Multi-function Relay output (N.C.) b
RC Multi-function Relay common
Resistive Load:
5A(N.O.)/3A(N.C.) 240VAC
5A(N.O.)/3A(N.C.) 24VDC
Inductive Load:
1.5A(N.O.)/0.5A(N.C.) 240VAC
1.5A(N.O.)/0.5A(N.C.) 24VDC
Refer to Pr.03-00 for programming
Page 40
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-23
Terminal
Symbol
Terminal Function
Factory Settings (SINK)
ON: Connect to DCM
MO1
Multi-function Output 1 (Photocoupler)
MO2
Multi-function Output 2 (Photocoupler)
MO3
Multi-function Output 3 (Photocoupler)
Maximum 48VDC, 50mA
Refer to Pr.03-01 to Pr.03-03 for programming
MO1~MO3-DCM
MO1~MO3
MCM
Internal Circuit
Max: 48Vdc 50mA
MCM Multi-function output common Common for Multi-function Outputs
+10V Potentiometer power supply +10VDC 20mA
AVI
Analog voltage Input
ACM
AVI
+10V
internal circuit
AVI ci rcu it
Impedance: 47k
Resolution: 10 bits
Range: 0 ~ 10VDC =
0 ~ Max. Output
Frequency (Pr.01-00)
Selection: Pr.02-00, Pr.02-13,
Pr.10-00
Set-up: Pr.04-00 ~ Pr.04-03
ACI
Analog current Input
ACM
ACI
internal circuit
ACI circuit
Impedance: 250
Resolution: 10 bits
Range: 4 ~ 20mA =
0 ~ Max. Output
Frequency (Pr.01-00)
Selection: Pr.02-00, Pr.02-13,
Pr.10-00
Set-up: Pr.04-11 ~ Pr.04-14
AUI
Auxiliary analog voltage input
ACM
AUI
+10
~
-10V
internal circuit
AUI circuit
Impedance: 47k
Resolution: 10 bits
Range: -10 ~ +10VDC =
0 ~ Max. Output
Frequency (Pr.01-00)
Selection: Pr.02-00, Pr.02-13,
Pr.10-00
Set-up: Pr.04-15 ~ Pr.04-18
Page 41
Chapter 2 Installation and Wiring|VFD-B Series
2-24 Revision July 2008, BE16, SW V4.08 & V5.00
Terminal
Symbol
Terminal Function
Factory Settings (SINK)
ON: Connect to DCM
AFM
Analog output meter
AFM
ACM
0~10V
Max. 2mA
potentiometer
ACM circuit
internal circuit
0 to 10V, 2mA
Impedance: 470
Output current 2mA max
Resolution: 8 bits
Range: 0 ~ 10VDC
Function: Pr.03-05
ACM
Analog control signal (common)
Common for AVI, ACI, AUI, AFM
Control signal wiring size: 18 AWG (0.75 mm2) with shielded wire.
Analog input terminals (AVI, ACI, AUI, ACM)
Analog input signals are easily affected by external noise. Use shielded wiring and keep it as
short as possible (<20m) with proper grounding. If the noise is inductive, connecting the
shield to terminal ACM can bring improvement.
If the analog input signals are affected by noise from the AC motor drive, please connect a
capacitor and ferrite core as indicated in the following diagrams:
C
AVI/ACI/AUI
ACM
ferrite core
wind each wires 3 times or more around the core
Digital inputs (FWD, REV, JOG, EF, TRG, MI1~MI6, DCM)
When using contacts or switches to control the digital inputs, please use high quality
components to avoid contact bounce.
Digital outputs (MO1, MO2, MO3, MCM)
Make sure to connect the digital outputs to the right polarity, see wiring diagrams.
When connecting a relay to the digital outputs, connect a surge absorber or fly-back diode
across the coil and check the polarity.
Page 42
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-25
General
Keep control wiring as far away as possible from the power wiring and in separate conduits
to avoid interference. If necessary let them cross only at 90º angle.
The AC motor drive control wiring should be properly installed and not touch any live power
wiring or terminals.
NOTE
If a filter is required for reducing EMI (Electro Magnetic Interference), install it as close as
possible to AC drive. EMI can also be reduced by lowering the Carrier Frequency.
When using a GFCI (Ground Fault Circuit Interrupter), select a current sensor with sensitivity
of 200mA, and not less than 0.1-second detection time to avoid nuisance tripping. For the
specific GFCI of the AC motor drive, please select a current sensor with sensitivity of 30mA
or above.
DANGER!
Damaged insulation of wiring may cause personal injury or damage to circuits/equipment if it
comes in contact with high voltage.
Page 43
Chapter 2 Installation and Wiring|VFD-B Series
2-26 Revision July 2008, BE16, SW V4.08 & V5.00
2.4.5 Main Circuit Terminals
Frame A, A1, A2: VFD007B21A/23A/43A/53A, VFD015B21A/21B//23A/23B/43A/53A,
VFD022B23B/43B/53A
L1
/
T
S
/
/
U
V
W
/
/
/
T3
T2
T1
+2
/
B1
R
L2
L3
+1 B2
Control Terminal
Torque: 4Kgf-cm (3 in-lbf)
Wire: 12-24 AWG (3.3-0.2 mm
2
)
Power Terminal
Torque: 18 kgf-cm (15.6 in-lbf)
Wire Gauge: 10-18 AWG (5.3-0.8 mm
2
) stranded wire, 12-18 AWG (3.3-0.8 mm2) solid wire
Wire Type: Copper only, 75°C
Page 44
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-27
Frame B: VFD022B21A, VFD037B23A/43A/53A
+1
+2
B
1
-
B
2
R/L1 S/L2 T/L3
Screw Torque :
Wire Gauge :
18Kgf-cm
18~10AWG
U/T1 V/T2 W/T3
Control Terminal
Torque: 4Kgf-cm (3 in-lbf)
Wire: 12-24 AWG (3.3-0.2mm
2
)
Power Terminal
Torque: 18 kgf-cm (15.6 in-lbf)
Wire Gauge: 10-18 AWG (5.3-0.8mm
2
)
Wire Type: Stranded copper only, 75°C
Page 45
Chapter 2 Installation and Wiring|VFD-B Series
2-28 Revision July 2008, BE16, SW V4.08 & V5.00
Frame C: VFD055B23A/43A/53A, VFD075B23A/43A/53A, VFD110B23A/43A/53A
POWER
IM
MOTOR3
Control Terminal
Torque: 4Kgf-cm (3 in-lbf)
Wire: 12-24 AWG (3.3-0.2mm
2
)
Power Terminal
Torque: 30Kgf-cm (26 in-lbf)
Wire: 8-12 AWG (8.4-3.3mm
2
)
Wire Type: Stranded Copper only, 75°C
NOTE
To connect 6 AWG (13.3 mm
2
) wires, use Recognized Ring Terminals
Page 46
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-29
Frame D: VFD150B23A/43A/53A, VFD185B23A/43A/53A, VFD220B23A/43A/53A
3
IM
POWER
S/L2
R/L1
- ( ) ( )
+ DC DC
T/L3
+1-+2
MOTOR
W/T3V/T2
Control Terminal
Torque: 4Kgf-cm (3 in-lbf)
Wire: 12-24 AWG (3.3-0.2 mm
2
)
Power Terminal
Torque: 30Kgf-cm (26 in-lbf)
Wire: 2-8 AWG (33.6-8.4 mm
2
)
Wire Type: Stranded Copper only, 75°C
NOTE
To connect 6 AWG (13.3 mm2) wires, use Recognized Ring Terminals
Page 47
Chapter 2 Installation and Wiring|VFD-B Series
2-30 Revision July 2008, BE16, SW V4.08 & V5.00
Frame E1: VFD300B23A, VFD370B23A, VFD550B43C, VFD750B43C, VFD550B53A,
VFD750B53A
POWER
ALARM
W/T3S/L2R/L1 T/L3 +2+1 U/T1 V/T2
(173in-lbf)
Screw Torque:
200kgf-cm
POWER
IM
MOTOR
3
CHARGE
Control Terminal
Torque: 4Kgf-cm (3 in-lbf)
Wire: 12-24 AWG (3.3-0.2 mm
2
)
Power Terminal
Torque: 200kgf-cm (173 in-lbf)
Wire Gauge: 1 - 3/0 AWG (42.4-85 mm
2
)
Wire Type: Stranded copper only, 75°C
Page 48
Chapter 2 Installation and Wiring|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 2-31
Frame E: VFD300B43A, VFD370B43A, VFD450B43A, VFD300B53A, VFD370B53A,
VFD450B53A
R/L1
+1
+2
-
S/L2 T/L3 U/T1 V/T2 2/T3
POWER
IM
MOTOR
3
CHARGE
POWER
ALARM
Control Terminal
Torque: 4Kgf-cm (3 in-lbf)
Wire: 12-24 AWG (3.3-0.2 mm
2
)
Power Terminal
Torque: 58.7kgf-cm (50.9 in-lbf) max.
Wire Gauge: 2-6AWG (33.6-13.3 mm
2
)
Wire Type: Stranded copper only, 75°C
Page 49
Chapter 2 Installation and Wiring|VFD-B Series
2-32 Revision July 2008, BE16, SW V4.08 & V5.00
Page 50
Revision July 2008, BE16, SW V4.08 & V5.00 3-1
Chapter 3 Start Up
3.1 Preparations before Start-up
Carefully check the following items before proceeding.
Make sure that the wiring is correct. In particular, check that the output terminals U, V, W.
are NOT connected to power and that the drive is well grounded.
Verify that there are no short-circuits between terminals and from terminals to ground or
mains power.
Check for loose terminals, connectors or screws.
Verify that no other equipment is connected to the AC motor
Make sure that all switches are OFF before applying power to ensure that the AC motor
drive doesn’t start running and there is no abnormal operation after applying power.
Make sure that the front cover is correctly installed before applying power.
Do NOT operate the AC motor drive with humid hands.
Check the following items after applying power:
- The keypad should light up as follows (normal status with no error)
U
F
H
STOP
RUN REV
VFD-PU01
FWD
JOG
JOG
RUN
RESET
STOP
When powe r is ON , LEDs "F", "STOP" an d "FWD" should light up. The display will show "60.00" with the least signification "0" flashing.
- If the drive has built-in fan (2.2kW and above) it should run. The factory setting of Fan Control Pr.03-12=00 (Fan always on).
Page 51
Chapter 3 Start Up|VFD-B Series
3-2 Revision July 2008, BE16, SW V4.08 & V5.00
3.2 Operation Method
Refer to 4.2 How to operate the digital keypad VFD-PU01 and chapter 5 parameters for setting.
Please choose a suitable method depending on application and operation rule. The operation is
usually used as shown in the following table.
3.3 Trial Run
After finishing checking the items in “3.1 preparation before start-up”, you can perform a trial run.
The factory setting of the operation source is from the keypad (Pr.02-01=00).
1. After applying power, verify that LED “F” is on and the display shows 60.00Hz.
2. Setting frequency to about 5Hz by using
key.
3. Pressing
RUN
key for forward running. And if you want to change to reverse running,
you should press
key in
U
F H
page. And if you want to decelerate to stop,
please press
RESET
STOP
key.
4. Check following items:
 Check if the motor direction of rotation is correct.
 Check if the motor runs steadily without abnormal noise and vibration.
 Check if acceleration and deceleration are smooth.
If the results of trial run are normal, please start the formal run.
Operation Method Frequency Source
Operation
Command Source
PU01 keypad
RUN
RESET
STOP
MI1
MI2
DCM
Parameter
setting:
04-04=11
04-05=12
Operate from
external signal
AVI, ACI, AUI
External terminals
input:
FWD-DCM
REV-DCM
Page 52
Chapter 3 Start Up|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 3-3
NOTE
1. Stop running immediately if any fault occurs and refer to the troubleshooting guide for solving
the problem.
2. Do NOT touch output terminals U, V, W when power is still applied to L1/R, L2/S, L3/T even
when the AC motor drive has stopped. The DC-link capacitors may still be charged to
hazardous voltage levels, even if the power has been turned off.
3. To avoid damage to components, do not touch them or the circuit boards with metal objects or
your bare hands.
Page 53
Chapter 3 Start Up|VFD-B Series
3-4 Revision July 2008, BE16, SW V4.08 & V5.00
This page intentionally left blank.
Page 54
Revision July 2008, BE16, SW V4.08 & V5.00 4-1
Chapter 4 Digital Keypad Operation
4.1 Description of the Digital Keypad VFD-PU01
U
F H
VFD-PU01
JOG
RUN
RESET
STOP
LED Display
Display frequency, current, voltage and error, etc.
Status Display
Display of drive status
Part Number
RUN key
STOP/RESET
MODE
Display mode selector
Left key
M
oves cursor to the left
UP and DOWN Key
Sets the parameter
number and changes the
numerical data, such as
Master Frequency.
JOG
Jog operation selector
Display Message Descriptions
Displays the AC drive Master Frequency.
Displays the actual output frequency present at terminals U/T1, V/T2, and W/T3.
User defined unit (where U = F x Pr.00-05)
Displays the output current present at terminals U/T1, V/T2, and W/T3.
Displays the AC motor drive forward run status.
Page 55
Chapter 4 Digital Keypad Operation|VFD-B Series
4-2 Revision July 2008, BE16, SW V4.08 & V5.00
Display Message Descriptions
Displays the AC motor drive reverse run status.
The counter value (C).
Displays the selected parameter.
Displays the actual stored value of the selected parameter.
External Fault.
Display “End” for approximately 1 second if input has been accepted by
pressing
key. After a parameter value has been set, the new
value is automatically stored in memory. To modify an entry, use the
, and keys.
Display “Err”, if the input is invalid.
Page 56
Chapter 4 Digital Keypad Operation|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 4-3
4.2 How to Operate the Digital Keypad VFD-PU01
MODE
MODE
MODEMODE
MODE
MODE
START
U
F
H
Selection mode
START
To shif t curs or
To modify data
To set direction
or
To set paramete rs
U
F
H
U
F H
U
F H
GO START
U
F H
U
F H
U
F H
U
F H
U
F H
U
F H
to set the parameters.
NOTE: In the selection mode, press
to return to the selection mode.
NOTE: In the parameter setting mode, you can press
move to previous display
U
F
H
U
F
H
U
F
H
U
F
H
U
F
H
START
U
F
H
U
F
H
U
F
H
U
F H
or
U
F H
U
F H
parameter set successfully
parameter set error
MODE
Page 57
Chapter 4 Digital Keypad Operation|VFD-B Series
4-4 Revision July 2008, BE16, SW V4.08 & V5.00
This page intentionally left blank.
Page 58
Revision July 2008, BE16, SW V4.08 & V5.00 5-1
Chapter 5 Parameters
The VFD-B parameters are divided into 12 groups by property for easy setting. In most
applications, the user can finish all parameter settings before start-up without the need for re-
adjustment during operation.
The 12 groups are as follows:
Group 0: User Parameters
Group 1: Basic Parameters
Group 2: Operation Method Parameters
Group 3: Output Function Parameters
Group 4: Input Function Parameters
Group 5: Multi-Step Speed and PLC Parameters
Group 6: Protection Parameters
Group 7: Motor Parameters
Group 8: Special Parameters
Group 9: Communication Parameters
Group 10: PID Control Parameters
Group 11: Fan & Pump Control Parameters
Page 59
Chapter 5 Parameters|VFD-B Series
5-2 Revision July 2008, BE16, SW V4.08 & V5.00
5.1 Summary of Parameter Settings
: The parameter can be set during operation.
Group 0 User Parameters
Parameter Explanation Settings
Factory
Setting
Customer
00-00 Identity Code of
the AC motor drive
Read-only ##
00-01 Rated Current
Display of the AC motor drive
Read-only #.#
08: Keypad lock 09: All parameters are reset to factory settings
(50Hz, 220V/380V/575V)
00-02 Parameter Reset
10: All parameters are reset to factory settings
(60Hz, 220V/440V/575V)
00
00: Display the frequency command value (LED
F) 01: Display the actual output frequency (LED H) 02: Display the content of user-defined unit
(LED U) 03: Multifunction display, see Pr.00-04
00-03
Start-up Display Selection
04: FWD/REV command
00
00: Display output current (A) 01: Display counter value (C) 02: Display process operation (1.tt)
03: Display DC-BUS voltage (u)
04: Display output voltage (E) 05: Output power factor angle (n)
06: Display output power (P) 07: Display actual motor speed (HU)
08: Display the estimated value of torque as it
relates to current (t) 09: Display PG numbers/10ms (G) 10: Display analog feedback signal value (b)(%) 11: Display AVI (U1.) (%) 12: Display ACI (U2.) (%) 13: Display AUI (U3.) (%)
00-04
Content of Multi Function Display
14: Display the temperature of heat sink (°C)
00
00-05
User-Defined Coefficient K
0.01 to 160.00 1.00
00-06 Software Version Read-only #.## 00-07 Password Input 00 to 65535 00 00-08 Password Set 00 to 65535 00
00: V/f Control 01: V/f + PG Control 02: Vector Control
00-09 Control Method
03: Vector + PG Control
00
Page 60
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-3
Parameter Explanation Settings
Factory Setting
Customer
00-10 Reserved
Group 1 Basic Parameters
Parameter Explanation Settings
Factory Setting
Customer
01-00
Maximum Output Frequency (Fmax)
50.00 to 400.00 Hz 60.00
01-01
Maximum Voltage Frequency (Fbase)
0.10 to 400.00 Hz 60.00
230V series: 0.1V to 255.0V 220.0
460V series: 0.1V to 510.0V 440.0
01-02
Maximum Output Voltage (Vmax)
575V series: 0.1V to 637.0V 575.0
01-03
Mid-Point Frequency (Fmid)
0.10 to 400.00 Hz 0.50
230V series: 0.1V to 255.0V 1.7 460V series: 0.1V to 510.0V 3.4
01-04
Mid-Point Voltage (Vmid)
575V series: 0.1V to 637.0V 4.8
01-05
Minimum Output Frequency (Fmin)
0.10 to 400.00 Hz 0.50
230V series: 0.1V to 255.0V 1.7 460V series: 0.1V to 510.0V 3.4
01-06
Minimum Output Voltage (Vmin)
575V series: 0.1V to 637.0V 4.8
01-07
Output Frequency Upper Limit
1 to 120%
100
01-08
Output Frequency Lower Limit
0 to100 %
0
01-09 Accel Time 1 0.01 to 3600.0 sec 10.0 01-10 Decel Time 1 0.01 to 3600.0 sec 10.0 01-11 Accel Time 2 0.01 to 3600.0 sec 10.0 01-12 Decel Time 2 0.01 to 3600.0 sec 10.0
01-09 ~ 01-12: Factory setting for models of 30hp (22kW) and above is 60sec.
01-13 Jog Acceleration
Time
0.1 to 3600.0 sec
1.0
01-14 Jog Frequency 0.10 Hz to 400.00 Hz 6.00
00: Linear Accel/Decel
01: Auto Accel, Linear Decel 02: Linear Accel, Auto Decel 03: Auto Accel/Decel (Set by load)
01-15
Auto acceleration / deceleration (refer to Accel/Decel time setting)
04: Auto Accel/Decel (set by Accel/Decel
Time setting)
00
01-16
Acceleration S­Curve
00 to 07 00
01-17
Deceleration S­Curve
00 to 07 00
01-18 Accel Time 3 0.01 to 3600.0 sec 10.0 01-19 Decel Time 3 0.01 to 3600.0 sec 10.0 01-20 Accel Time 4 0.01 to 3600.0 sec 10.0
Page 61
Chapter 5 Parameters|VFD-B Series
5-4 Revision July 2008, BE16, SW V4.08 & V5.00
Parameter Explanation Settings
Factory
Setting
Customer
01-21 Decel Time 4 0.01 to 3600.0 sec 10.0
01-18 ~ 01-21: Factory setting for models of 30hp (22kW) and above is 60sec.
01-22 Jog Deceleration
Time
0.1 to 3600.0 sec
1.0
00: Unit: 1 sec 01: Unit: 0.1 sec
01-23
Accel/Decel Time Unit
02: Unit: 0.01 sec
01
Group 2 Operation Method Parameters
Parameter Explanation Settings
Factory
Setting
Customer
00: Digital keypad (PU01) UP/DOWN keys or
Multi-function Inputs UP/DOWN. Last used frequency saved.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI 03: -10 to +10Vdc from AUI
04: RS-485 serial communication (RJ-11).
Last used frequency saved.
05: RS-485 serial communication (RJ-11).
Last used frequency not saved.
02-00
Source of First Master Frequency Command
06: Combined use of master and auxiliary
frequency command
(See Pr. 02-10 to 02-12)
00
00: Digital keypad (PU01)
01: External terminals. Keypad STOP/RESET
enabled.
02: External terminals. Keypad STOP/RESET
disabled.
03: RS-485 serial communication (RJ-11).
Keypad STOP/RESET enabled.
02-01
Source of First Operation Command
04: RS-485 serial communication (RJ-11).
Keypad STOP/RESET disabled.
00
00: STOP: ramp to stop; E.F.: coast to stop 01: STOP: coast to stop; E.F.: coast to stop
02: STOP: ramp to stop; E.F.: ramp to stop
02-02 Stop Method
03: STOP: coast to stop; E.F.: ramp to stop
00
230V&460V:1-5hp/0.75-3.7kW: 1-15kHz 15
7.5-25hp/5.5-18.5kW: 01-15kHz 09
30-60hp/22-45kW: 01-09kHz 06
75-100hp/55-75kW: 01-06kHz 06
575V: 1-15hp/0.75-11kW: 01-10 kHz 06
20-60hp/15-45kW: 01-08 kHz 06
02-03
PWM Carrier Frequency Selections
75-100hp/55-75kW: 01-06kHz 06
Page 62
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-5
Parameter Explanation Settings
Factory Setting
Customer
00: Enable forward/reverse operation 01: Disable reverse operation
02-04
Motor Direction Control
02: Disabled forward operation
00
00: 2-wire: FWD/STOP, REV/STOP 01: 2-wire: FWD/REV, RUN/STOP
02-05
2-wire/3-wire Operation Control Modes
02: 3-wire operation
00
00: Disable. Operation status is not changed
even if operation command source Pr.02­01 and/or Pr.02-14 is changed.
01: Enable. Operation status is not changed
even if operation command source Pr.02­01 and/or Pr.02-14 is changed.
02: Disable. Operation status will change if
operation command source Pr.02-01 and/or Pr.02-14 is changed.
02-06 Line Start Lockout
03: Enable. Operation status will change if
operation command source Pr.02-01 and/or Pr.02-14 is changed.
00
00: Decelerate to 0 Hz 01: Coast to stop and display “EF”
02-07
Loss of ACI Signal (4-20mA)
02: Continue operation by last frequency
command
00
00: Based on accel/decel time 01: Constant speed
02-08 Up/Down Mode
02: Based on accel/decel time, but frequency
command will be 0 when stopped.
00
02-09
Accel/Decel Rate of Change of UP/DOWN Operation with Constant Speed
0.01~1.00 Hz/msec 0.01
00: Digital keypad (PU01) UP/DOWN keys or
Multi-function Inputs UP/DOWN. Last
used frequency saved. 01: 0 to +10V from AVI 02: 4 to 20mA from ACI 03: -10 to +10Vdc from AUI
02-10
Source of the Master Frequency Command
04: RS-485 serial communication (RJ-11).
Last used frequency saved.
00
00: Digital keypad (PU01) UP/DOWN keys or
Multi-function Inputs UP/DOWN. Last
used frequency saved. 01: 0 to +10V from AVI 02: 4 to 20mA from ACI 03: -10 to +10Vdc from AUI
02-11
Source of the Auxiliary Frequency Command
04: RS-485 serial communication (RJ-11).
Last used frequency saved.
00
00: Master frequency + auxiliary frequency
02-12
Combination of the Master and Auxiliary Frequency Command
01: Master frequency - auxiliary frequency
00
Page 63
Chapter 5 Parameters|VFD-B Series
5-6 Revision July 2008, BE16, SW V4.08 & V5.00
Parameter Explanation Settings
Factory
Setting
Customer
00: Digital keypad (PU01) UP/DOWN keys or
Multi-function Inputs UP/DOWN. Last
used frequency saved. 01: 0 to +10V from AVI 02: 4 to 20mA from ACI 03: -10 to +10Vdc from AUI 04: RS-485 serial communication (RJ-11).
Last used frequency saved 05: RS-485 serial communication (RJ-11).
Last used frequency not saved.
02-13
Source of Second Frequency Command
06: Combined use of master and auxiliary
frequency command (See Pr. 02-10 to 02-
12)
00
00: Digital keypad (PU01) 01: External terminals. Keypad STOP/RESET
enabled. 02: External terminals. Keypad STOP/RESET
disabled. 03: RS-485 serial communication (RJ-11).
Keypad STOP/RESET enabled.
02-14
Source of Second Operation Command
04: RS-485 serial communication (RJ-11).
Keypad STOP/RESET disabled.
00
02-15
Keypad Frequency Command
0.00 ~ 400.00Hz 60.00
Group 3 Output Function Parameters
Parameter Explanation Settings
Factory
Setting
Customer
00: No function 01: AC drive operational
02: Master frequency attained
03-00
Multi-Function Output Relay (RA1, RB1, RC1)
03: Zero speed
08
04: Over torque detection 05: Base-Block (B.B.) indication
06: Low-voltage indication
03-01
Multi-Function Output Terminal MO1
07: Operation mode indication
01
08: Fault indication 09: Desired frequency attained 1 10: PLC program running
03-02
Multi-Function Output Terminal MO2
11: PLC program step completed
02
12: PLC program completed
13: PLC program operation paused
14: Terminal count value attained 15: Preliminary count value attained 16: Auxiliary motor No.1
03-03
Multi-Function Output Terminal MO3
17: Auxiliary motor No.2
20
Page 64
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-7
Parameter Explanation Settings
Factory Setting
Customer
18: Auxiliary motor No.3 19: Heat sink overheat warning 20: AC motor drive ready 21: Emergency stop indication 22: Desired frequency attained 2 23: Software brake signal
24: Zero speed output signal 25: Under-current detection 26: Operation indication (H>=Fmin) 27: Feedback signal error 28: User-defined low-voltage detection 29: Brake control (Desired frequency attained
3)
03-04 Desired Frequency
Attained 1
0.00 to 400.00 Hz 0.00
00: Analog frequency meter
01: Analog current meter 02: Output voltage 03: Output frequency command 04: Output motor speed
03-05
Analog Output Signal
05: Load power factor (cos90
o
to Cos0o)
00
03-06 Analog Output Gain 01 to 200% 100 03-07 Digital Output
Multiplying Factor
01 to 20 01
03-08 Terminal Count
Value
00 to 65500 00
03-09
Preliminary Count Value
00 to 65500 00
03-10
Desired Frequency Attained 2
0.00 to 400.00 Hz 0.00
00: Preliminary count value attained, no EF
display
03-11
EF Active When Preliminary Count Value Attained
01: Preliminary count value attained, EF
active
00
00: Fan always ON 01: 1 minute after AC motor drive stops, fan
will be OFF
02: AC motor drive runs and fan ON, AC
motor drive stops and fan OFF
03-12 Fan Control
03: Fan ON to run when preliminary heatsink
temperature attained
00
03-13
Brake Release Frequency
0.00 to 400.00Hz 0.00
03-14
Brake Engage Frequency
0.00 to 400.00Hz 0.00
Page 65
Chapter 5 Parameters|VFD-B Series
5-8 Revision July 2008, BE16, SW V4.08 & V5.00
Group 4 Input Function Parameters
Parameter Explanation Settings
Factory
Setting
Customer
04-00
AVI Analog Input Bias
0.00~200.00 % 0.00
00: Positive bias
04-01 AVI Bias Polarity
01: Negative bias
00
04-02 AVI Input Gain 1 to 200 % 100
00: No AVI negative bias command
01: Negative bias: REV motion enabled
04-03
AVI Negative Bias, Reverse Motion Enable/Disable
02: Negative bias: REV motion disabled
00
00: No function
01
01: Multi-Step speed command 1
04-04 Multi-Function Input
Terminal 1 (MI1)
02: Multi-Step speed command 2
03: Multi-Step speed command 3
04: Multi-Step speed command 4 02
05: External reset (N.O.)
06: Accel/Decel inhibit
07: Accel/Decel time selection command 1
04-05 Multi-Function Input
Terminal 2 (MI2)
08: Accel/Decel time selection command 2
09: External base block (N.O.) 03 10: External base block (N.C.)
04-06 Multi-Function Input
Terminal 3 (MI3)
11: Up: Increment master frequency 12: Down: Decrement master frequency
04
13: Counter reset 14: Run PLC program
04-07 Multi-Function Input
Terminal 4 (MI4)
15: Pause PLC program
16: Auxiliary motor No.1 output disable
05 17: Auxiliary motor No.2 output disable 18: Auxiliary motor No.3 output disable
04-08 Multi-Function Input
Terminal 5 (MI5)
19: Emergency stop (N.O.) 20: Emergency stop (N.C.) 06 21: Master frequency selection AVI/ACI 22: Master frequency selection AVI/AUI 23: Operation command selection
(keypad/external terminals) 24: Auto accel/decel mode disable 25: Forced stop (N.C.) 26: Forced stop (N.O.)
27: Parameter lock enable (N.O.)
28: PID function disabled
29: Jog FWD/REV command
04-09 Multi-Function Input
Terminal 6 (MI6)
30: External reset (N.C.)
Page 66
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-9
Parameter Explanation Settings
Factory Setting
Customer
31: Source of second frequency command
enabled
32: Source of second operation command
enabled
33: One shot PLC
34: Proximity sensor input for simple Index
function
35: Output shutoff stop (NO)
36: Output shutoff stop (NC)
04-10
Digital Terminal Input Debouncing Time
1 to 20 (*2ms) 01
04-11
ACI Analog Input Bias
0.00~200.00 % 0.00
00: Positive bias
04-12 ACI Bias Polarity
01: Negative bias
00
04-13 ACI Input Gain 01 to 200 % 100
00: No ACI negative bias command
01: Negative bias: REV motion enabled
04-14
ACI Negative Bias, Reverse Motion Enable/Disable
02: Negative bias: REV motion disabled
00
04-15
AUI Analog Input Bias
0.00~200.00 % 0.00
00: Positive bias
04-16 AUI Bias Polarity
01: Negative bias
00
04-17 AUI Input Gain 01 to 200 % 100
00: No AUI negative bias command
01: Negative bias: REV motion enabled
04-18
AUI Negative Bias Reverse Motion Enable/Disable
02: Negative bias: REV motion disabled
00
04-19
AVI Analog Input Delay
0.00 to 10.00 sec 0.05
04-20
ACI Analog Input Delay
0.00 to 10.00 sec 0.05
04-21
AUI Analog Input Delay
0.00 to 10.00 sec 0.05
00: 0.01Hz
04-22
Analog Input Frequency Resolution
01: 0.1Hz
01
04-23
Gear Ratio for Simple Index Function
4 ~ 1000 200
04-24
Index Angle for Simple Index Function
0.0 ~360.0
o
180.0
04-25
Deceleration Time for Simple Index Function
0.00 ~100.00 sec 0.00
Page 67
Chapter 5 Parameters|VFD-B Series
5-10 Revision July 2008, BE16, SW V4.08 & V5.00
Group 5 Multi-Step Speed and PLC Parameters
Parameter Explanation Settings
Factory
Setting
Customer
05-00 1st Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-01 2nd Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-02 3rd Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-03 4th Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-04 5th Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-05 6th Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-06 7th Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-07 8th Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-08 9th Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-09 10th Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-10 11th Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-11 12th Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-12 13th Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-13 14th Step Speed
Frequency
0.00 to 400.00 Hz 0.00
05-14 15th Step Speed
Frequency
0.00 to 400.00 Hz 0.00
00: Disable PLC operation 01: Execute one program cycle
02: Continuously execute program cycles
03: Execute one program cycle step by step
05-15 PLC Mode
04: Continuously execute program cycles
step by step
00
05-16 PLC Forward/
Reverse Motion
00 to 32767 (00: FWD, 01: REV) 00
05-17 Time Duration of 1st
Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-18 Time Duration of 2nd
Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-19 Time Duration of 3rd
Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-20 Time Duration of 4th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-21 Time Duration of 5th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
Page 68
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-11
Parameter Explanation Settings
Factory
Setting
Customer
05-22 Time Duration of 6th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-23 Time Duration of 7th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-24 Time Duration of 8th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-25 Time Duration of 9th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-26 Time Duration of
10th Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-27 Time Duration of
11th Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-28 Time Duration of
12th Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-29 Time Duration of
13th Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-30 Time Duration of
14th Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-31 Time Duration of
15th Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
00: 1 sec
05-32 Time Unit Settings
01: 0.1 sec
00
05-33
The Amplitude of Wobble Vibration
0.00~400.00 Hz
0.00
05-34
Wobble Skip Frequency
0.00~400.00 Hz 0.00
Group 6 Protection Parameters
Parameter Explanation Settings
Factory
Setting
Custome
r
230V series: 330.0V to 410.0V 390.0V 460V series: 660.0V to 820.0V 780.0V 575V series: 825.0V to1025.0V 975.0V
06-00
Over-Voltage Stall Prevention
00: Disable over-voltage stall prevention
06-01
Over-Current Stall Prevention during Accel
20 to 250% 170
06-02
Over-Current Stall Prevention during Operation
20 to 250% 170
00: Disabled
01: Enabled during constant speed operation.
After the over-torque is detected, keep running until OL1 or OL occurs.
06-03
Over-Torque Detection Mode (OL2)
02: Enabled during constant speed operation.
After the over-torque is detected, stop running.
00
Page 69
Chapter 5 Parameters|VFD-B Series
5-12 Revision July 2008, BE16, SW V4.08 & V5.00
Parameter Explanation Settings
Factory
Setting
Custome
r
03: Enabled during accel. After the over­torque is detected, keep running until OL1 or OL occurs.
06-03
Over-Torque Detection Mode (OL2)
04: Enabled during accel. After the over­torque is detected, stop running.
06-04
Over-Torque Detection Level
10 to 200% 150
06-05
Over-Torque Detection Time
0.1 to 60.0 sec 0.1
00: Standard motor (self cooled by fan)
01: Special motor (forced external cooling)
06-06
Electronic Thermal Overload Relay Selection
02: Disabled
02
06-07
Electronic Thermal Characteristic
30 to 600 sec 60
00: No fault 01: Over current (oc) 02: Over voltage (ov)
03: Over heat (oH) 04: Over load (oL)
06-08
Present Fault Record
05: Over load (oL1)
06: External fault (EF)
07: IGBT protection (occ)
08: CPU failure (cF3)
09: Hardware protection failure (HPF)
06-09 Second Most Recent
Fault Record
10: Excess current during acceleration (ocA)
11: Excess current during deceleration (ocd)
12: Excess current during steady state (ocn)
13: Ground fault (GFF)
14: Reserved
15: CF1 16: CF2
17: Reserved
18: Motor over-load (oL2)
19: Auto Acel/Decel failure (CFA)
06-10 Third Most Recent
Fault Record
20: SW/Password protection (codE)
21: External Emergency Stop (EF1)
22: Phase-Loss (PHL)
23: Preliminary count value attained, EF
active (cEF) 24: Under-current (Lc) 25: Analog feedback signal error (AnLEr)
06-11 Fourth Most Recent
Fault Record
26: PG feedback signal error (PGErr)
00
Page 70
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-13
Parameter Explanation Settings
Factory
Setting
Custome
r
06-12
Under-Current Detection Level
00~100% (00: Disabled)
00
06-13
Under-Current Detection Time
0.1~ 3600.0 sec
10.0
00: Warn and keep operating
01: Warn and ramp to stop
02: Warn and coast to stop
06-14
Under-Current Detection Mode
03: Warn, after coast to stop, restart (delay
06-15 setting time)
00
06-15
Under-Current Detection Restart Delay Time (Lv)
1~600 Min.
10
00: Disabled
230V: 220 to 300VDC
460V: 440 to 600VDC
00
06-16
User-Defined Low­Voltage Detection Level
575V: 520 to 780VDC
06-17
User-Defined Low­Voltage Detection Time
0.1~ 3600.0 sec 0.5
06-18 Reserved
Group 7 Motor Parameters
Parameter Explanation Settings
Factory
Setting
Custome
r
07-00 Motor Rated Current 30 to 120% 100
07-01
Motor No-Load Current
01 to 90% 40
07-02
Torque Compensation
0.0 to 10.0 0.0
07-03 Slip Compensation
(Used without PG)
0.00 to 3.00 0.00
07-04 Number of Motor
Poles
02 to 10 04
07-05
Motor Parameters Auto Tuning
00: Disable 01: Auto tuning R1 02: Auto tuning R1 + no-load test
00
07-06
Motor Line-to-line Resistance R1
00~65535 mΩ
00
07-07 Reserved 07-08 Motor Rated Slip 0.00 to 20.00 Hz 3.00
07-09
Slip Compensation Limit
0 to 250% 200
07-10 Reserved 07-11 Reserved
Page 71
Chapter 5 Parameters|VFD-B Series
5-14 Revision July 2008, BE16, SW V4.08 & V5.00
Parameter Explanation Settings
Factory
Setting
Custome
r
07-12
Torque Compensation Time Constant
0.01 ~10.00 Sec 0.05
07-13
Slip Compensation Time Constant
0.05 ~10.00 sec 0.10
07-14
Accumulative Motor Operation Time (Min.)
00 to 1439 Min. 00
07-15
Accumulative Motor Operation Time (Day)
00 to 65535 Day 00
Group 8 Special Parameters
Parameter Explanation Settings
Factory
Setting
Custome
r
08-00
DC Brake Current Level
00 to 100% 00
08-01
DC Brake Time during Start-Up
0.0 to 60.0 sec 0.0
08-02
DC Brake Time during Stopping
0.0 to 60.0 sec 0.0
08-03
Start-Point for DC Brake
0.00 to 400.00Hz 0.00
00: Operation stops after momentary power
loss
01: Operation continues after momentary
power loss, speed search starts with the Master Frequency reference value
08-04
Momentary Power Loss Operation Selection
02: Operation continues after momentary
power loss, speed search starts with the minimum frequency
00
08-05
Maximum Allowable Power Loss Time
0.1 to 5.0 sec 2.0
08-06
B.B. Time for Speed Search
0.1 to 5.0 sec 0.5
08-07
Current Limit for Speed Search
30 to 200% 150
08-08
Skip Frequency 1 Upper Limit
0.00 to 400.00 Hz 0.00
08-09
Skip Frequency 1 Lower Limit
0.00 to 400.00 Hz 0.00
08-10
Skip Frequency 2 Upper Limit
0.00 to 400.00 Hz 0.00
08-11
Skip Frequency 2 Lower Limit
0.00 to 400.00 Hz 0.00
08-12
Skip Frequency 3 Upper Limit
0.00 to 400.00 Hz 0.00
08-13
Skip Frequency 3 Lower Limit
0.00 to 400.00 Hz 0.00
Page 72
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-15
Parameter Explanation Settings
Factory
Setting
Custome
r
08-14 Auto Restart After
Fault
00 to 10 (00=disable) 00
00: Disable
08-15 Auto Energy Saving
01: Enable
00
00: AVR function enable 01: AVR function disable
08-16 AVR Function
02: AVR function disable for decel.
00
230V series: 370 to 430V 380 460V series: 740 to 860V 760
08-17
Software Brake Level
575V series: 925 to1075V 950
00: Speed search starts with last frequency
command
08-18
Base-block Speed Search
01: Starts with minimum output frequency
00
00: Speed search disable
08-19
Speed Search during Start-up
01: Speed search enable
00
00: Setting frequency
08-20
Speed Search Frequency during Start-up
01: Maximum operation frequency (01-00)
00
08-21
Auto Reset Time at Restart after Fault
00 to 60000 sec
600
08-22
Compensation Coefficient for Motor Instability
00~1000
00
Group 9 Communication Parameters
Parameter Explanation Settings
Factory
Setting
Custome
r
09-00
Communication Address
01 to 254 01
00: Baud rate 4800bps 01: Baud rate 9600bps
02: Baud rate 19200bps
09-01 Transmission Speed
03: Baud rate 38400bps
01
00: Warn and keep operating 01: Warn and ramp to stop
02: Warn and coast to stop
09-02
Transmission Fault Treatment
03: No warning and keep operating
03
0.0 ~ 60.0 seconds
09-03 Time-out Detection
0.0: Disable
0.0
00: 7,N,2 (Modbus, ASCII) 01: 7,E,1 (Modbus, ASCII) 02: 7,O,1 (Modbus, ASCII) 03: 8,N,2 (Modbus, RTU)
04: 8,E,1 (Modbus, RTU)
09-04
Communication Protocol
05: 8,O,1 (Modbus, RTU)
00
Page 73
Chapter 5 Parameters|VFD-B Series
5-16 Revision July 2008, BE16, SW V4.08 & V5.00
Parameter Explanation Settings
Factory
Setting
Custome
r
09-05 Reserved
09-06 Reserved
09-07 Response Delay
Time
00 ~ 200 msec
00
Group 10 PID Control Parameters
Parameter Explanation Settings
Factory
Setting
Custome
r
00: Inhibit PID operation
01: Negative PID feedback from external
terminal (AVI) 0 to +10V 02: Negative PID feedback from external
terminal (ACI) 4 to 20mA 03: Positive PID feedback from external
terminal (AVI) 0 to +10V
10-00
Input terminal for PID Feedback
04: Positive PID feedback from external
terminal (ACI) 4 to 20mA
00
10-01
Gain over PID Detection value
0.00 to 10.00 1.00
10-02 Proportional Gain (P) 0.0 to 10.0 1.0
10-03 Integral Gain (I)
0.00 to 100.00 sec (0.00=disable)
1.00
10-04
Derivative Control (D)
0.00 to 1.00 sec
0.00
10-05
Upper Bound for Integral Control
00 to 100% 100
10-06
Primary Delay Filter Time
0.0 to 2.5 sec 0.0
10-07
PID Output Freq Limit
0 to 110% 100
10-08
Feedback Signal Detection Time
0.0 to 3600.0 sec 60.0
00: Warn and keep operation
01: Warn and RAMP to stop
10-09
Treatment of the Erroneous Feedback Signals
02: Warn and COAST to stop
00
10-10 PG Pulse Range 1 to 40000 600
00: Disable PG 01: Single phase
02: Forward / Counterclockwise rotation
10-11 PG Input
03: Reverse / Clockwise rotation
00
10-12
ASR (Auto Speed Regulation) control (with PG only) (P)
0.0 to 10.0 1.0
Page 74
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-17
Parameter Explanation Settings
Factory
Setting
Custome
r
10-13
ASR (Auto Speed Regulation) control (with PG only) (I)
0.00 to 100.00 (0.00 disable) 1.00
10-14
Speed Control Output Frequency Limit
0.00 to 100.00 Hz 10.00
10-15
Sample time for refreshing the content of 210DH and 210EH
0.01~1.00 seconds 0.10
10-16
Deviation Range of PID Feedback Signal Error
0.00~100.00% 100.00
Group 11 Fan & Pump Control Parameters
Parameter Explanation Settings
Factory
Setting
Custome
r
00: V/f curve determined by Pr.01-00 to
Pr.01-06 01: 1.5 power curve 02: 1.7 power curve 03: Square curve
11-00 V/f Curve Selection
04: Cube curve
00
11-01
Start-Up Frequency of the Auxiliary Motor
0.00 to 400.00 Hz 0.00
11-02
Stop Frequency of the Auxiliary Motor
0.00 to 400.00 Hz 0.00
11-03
Time Delay before Starting the Auxiliary Motor
0.0 to 3600.0 sec 0.0
11-04
Time Delay before Stopping the Auxiliary Motor
0.0 to 3600.0 sec 0.0
11-05
Sleep/Wake Up Detection Time
0.0 ~6550.0 sec 0.0
11-06 Sleep Frequency 0.00~Fmax 0.00
11-07 Wakeup Frequency 0.00~Fmax 0.00
Page 75
Chapter 5 Parameters|VFD-B Series
5-18 Revision July 2008, BE16, SW V4.08 & V5.00
5.2 Parameter Settings for Applications
Speed Search
Applications Purpose Functions
Related
Parameters
Windmill, winding machine, fan and all inertia load
Restart free­running motor
Before the free-running motor is completely stopped, it can be restarted without detecting motor speed. The AC motor drive will auto search motor speed and will accelerate when its speed is the same as the motor speed.
08-06 08-07 08-19 08-20
DC Brake before Running
Applications Purpose Functions
Related
Parameters
When e.g. windmills, fans and pumps rotate freely by wind or flow without applying power
Keep the free­running motor at standstill.
If the running direction of the free­running motor is not steady, please execute DC brake before start-up.
08-00 08-01
Motor power switch-over between AC motor drive and commercial power
Applications Purpose Functions
Related
Parameters
Windmills, pumps, extruders
Switching motor power between AC motor drive and commercial power
When switching motor power between the AC motor drive and commercial power, it is unnecessary to stop the motor or start by commercial power with heavy duty before switching to by AC motor drive control
03-00 03-01 03-02 03-03
Energy Saving
Applications Purpose Functions
Related
Parameters
Punching machines and precision machinery
Energy saving and less vibrations
Energy saving when the AC motor drive runs at constant speed, yet full power acceleration and deceleration For precision machinery it also helps to lower vibrations.
08-15
Multi-step Operation
Applications Purpose Functions
Related
Parameters
Conveying machinery
Cyclic operation by multi-step speeds.
To control 15-step speeds and duration by simple contact signal.
04-04~04-09 05-00~05-14
Page 76
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-19
Switching acceleration and deceleration times
Applications Purpose Functions
Related
Parameters
Auto turntable for conveying machinery
Switching acceleration and deceleration times by external signal
Switching the multi-step acceleration/deceleration by external signals. When an AC motor drive drives two or more motors, it can reach high-speed but still start and stop smoothly.
01-09~01-12 01-18~01-21 04-04~04-09
Overheat Warning
Applications Purpose Functions
Related
Parameters
Air conditioner Safety measure
When the AC motor drive overheats, it uses a thermal sensor to generate a overheat warning.
03-00~03-03 04-04~04-09
Two-wire/three-wire
Applications Purpose Functions
Related
Parameters
General application
To run, stop, forward and reverse by external terminals
V
FD-B
FWD:("OPEN":STOP)
("CLOSE":FWD)
REV:("OPEN": STOP)
("CLOSE": REV)
DCM
FWD/STOP
REV/STOP
V
FD-B
FWD:("OPEN":STOP)
("CLOSE":RUN)
REV:("OPEN": F
("CLOSE": REV)
DCM
RUN/STOP
FWD/REV
WD)
V
FD-B
FWD:("CLOSE":RUN) EF: ("OPEN":STOP)
REV:("OPEN": F
("CLOSE": REV)
DCM
STOP RUN
REV/FWD
WD)
02-05
04-04~04-09
Operation Command
Applications Purpose Functions
Related
Parameters
General application
Selecting the source of control signal
Selection of AC motor drive control by external terminals, digital keypad or RS485.
03-01
04-04~04-09
Frequency Hold
Applications Purpose Functions
Related
Parameters
General application
Acceleration/ deceleration pause
Hold output frequency during Acceleration/deceleration
04-04~04-09
Page 77
Chapter 5 Parameters|VFD-B Series
5-20 Revision July 2008, BE16, SW V4.08 & V5.00
Auto Restart after Fault
Applications Purpose Functions
Related
Parameters
Air conditioners, remote pumps
For continuous and reliable operation without operator intervention
The AC motor drive can be restarted/reset automatically up to 10 times after a fault occurs.
08-14~08-21
Emergency Stop by DC Brake
Applications Purpose Functions
Related
Parameters
High-speed rotors
Emergency stop without brake resistor
AC motor drive can use DC brake for emergency stop when a quick stop is needed without brake resistor. When used often, take motor cooling into consideration.
08-00 08-02 08-03
Over-torque Setting
Applications Purpose Functions
Related
Parameters
Pumps, fans and extruders
To protect machines and to have continuous/ reliable operation
The over-torque detection level can be set. Once OC stall, OV stall and over­torque occurs, the output frequency will be adjusted automatically. It is suitable for machines like fans and pumps that require continuous operation.
06-00~06-05
Upper/Lower Limit Frequency
Applications Purpose Functions
Related
Parameters
Pump and fan
Control the motor speed within upper/lower limit
When user cannot provide upper/lower limit, gain or bias from external signal, it can be set individually in AC motor drive.
01-07 01-08
Skip Frequency Setting
Applications Purpose Functions
Related
Parameters
Pumps and fans
To prevent machine vibrations
The AC motor drive cannot run at constant speed in the skip frequency range. Three skip frequency ranges can be set. It is used to smooth vibration at certain frequencies.
08-00~08-13
Page 78
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-21
Carrier Frequency Setting
Applications Purpose Functions
Related
Parameters
General application Low noise
The carrier frequency can be increased when required to reduce motor noise.
02-03
Keep Running when Frequency Command is Lost
Applications Purpose Functions
Related
Parameters
Air conditioners
For continuous operation
When the frequency command is lost by a system malfunction, the AC motor drive can still run. Suitable for intelligent air conditioners.
02-07
Display the Speed of Load
Applications Purpose Functions
Related
Parameters
General application
Display running status
Display motor speed(rpm) and machine speed(rpm) on keypad.
00-04 03-05
Output Signal during Running
Applications Purpose Functions
Related
Parameters
General application
Provide a signal for running status
Signal available to stop braking when the AC motor drive is running. (This signal will disappear when the AC motor drive is free-running.)
03-00~03-03
Output Signal in Zero Speed
Applications Purpose Functions
Related
Parameters
General application
Provide a signal for running status
When the output frequency is lower than the min. output frequency, a signal is given for external system or control wiring.
03-00~03-03
Output Signal at Desired Frequency
Applications Purpose Functions
Related
Parameters
General application
Provide a signal for running status
When the output frequency is at the desired frequency (by frequency command), a signal is sent by an external system or control wiring.
03-00~03-03
Page 79
Chapter 5 Parameters|VFD-B Series
5-22 Revision July 2008, BE16, SW V4.08 & V5.00
Output Signal for Base Block
Applications Purpose Functions
Related
Parameters
General application
Provide a signal for running status
When executing Base Block, a signal is sent by an external system or control wiring.
03-00~03-03
Overheat Warning for Heat Sink
Applications Purpose Functions
Related
Parameters
General application For safety
When heat sink is overheated, it will send a signal by an external system or control wiring.
03-00~03-03
Multi-function Analog Output
Applications Purpose Functions
Related
Parameters
General application
Display running status
The value of frequency, output current/voltage can be read by adding a frequency meter or voltage/current meter.
03-05
Page 80
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-23
5.3 Description of Parameter Settings
Group 0: User Parameters : This parameter can be set during operation.
00 - 00 Identity Code of the AC motor drive
Settings Read Only Factory setting: ##
00 - 01 Rated Current Display of the AC motor drive
Settings Read Only Factory setting: #.#
Pr. 00-00 displays the identity code of the AC motor drive. The capacity, rated current, rated
voltage and the max. carrier frequency relate to the identity code. Users can use the following
table to check how the rated current, rated voltage and max. carrier frequency of the AC motor
drive correspond to the identity code.
Pr.00-01 displays the rated current of the AC motor drive. By reading this parameter the user
can check if the AC motor drive is correct.
230V Series
kW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37
HP 1.0 2.0 3.0 5.0 7.5 10 15 20 25 30 40 50
Pr.00-00 04 06 08 10 12 14 16 18 20 22 24 26
Rated Output
Current (A)
5.0 7.0 11 17 25 33 49 65 75 90 120 146
Max. Carrier
Frequency
15kHz 9 kHz
460V Series
kW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75
HP 1.0 2.0 3.0 5.0 7.5 10 15 20 25 30 40 50 60 75 100
Pr.00-00 05 07 09 11 13 15 17 19 21 23 25 27 29 31 33
Rated Output
Current (A)
2.7 4.2 5.5 8.5 13 18 24 32 38 45 60 73 91 110 150
Max. Carrier
Frequency
15 kHz 9 kHz 6 kHz
575V Series kW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 HP 1.0 2.0 3.0 5.0 7.5 10 15 20 25 30 40 50 60 75 100
Pr.00-00 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114
Rated Output
Current (A)
1.7 3.5 4.5 7.5 10 13.5 19 22 27 34 41 52 62 80 100
Max. Carrier
Frequency
10 kHz 8 kHz 6 kHz
Page 81
Chapter 5 Parameters|VFD-B Series
5-24 Revision July 2008, BE16, SW V4.08 & V5.00
00 - 02
Parameter Reset
Factory Setting: 00
Settings 08 Keypad Lock
09 All parameters are reset to factory settings (50Hz, 220V/380V/575V)
10 All parameters are reset to factory settings (60Hz, 220V/440V/575V)
This parameter allows the user to reset all parameters to the factory settings except the fault
records (Pr.06-08 ~ Pr.06-11).
50Hz: Pr.01-01 is set to 50Hz and Pr.01-02 is set to 230V, 400V or 575V.
60Hz: Pr.01-01 is set to 60Hz and Pr.01-02 is set to 230V, 460V or 575V.
When Pr.00-02=08, the VFD-PU01 keypad is locked. To unlock the keypad, set Pr.00-02=00.
00 - 03
Start-up Display Selection
Factory Setting: 00
Settings 00 Display the frequency command value. (LED F)
01 Display the actual output frequency (LED H)
02 Display the content of user-defined unit (LED U)
03 Multifunction display, see Pr.00-04
04 FWD/REV command
This parameter determines the start-up display page after power is applied to the drive.
00 - 04 Content of Multi-Function Display
Factory Setting: 00
Settings 00 Display the output current in A supplied to the motor
01
Display the counter value which counts the number
of pulses on TRG terminal
02
When the PLC function is active, the current step and its remaining operation time in s are shown.
03
Display the actual DC BUS voltage in VDC of the AC motor drive
04
Display the output voltage in VAC of terminals U, V, W to the motor.
05
Display the power factor angle in º of terminals U, V, W to the motor.
06
Display the output power in kW of terminals U, V and W to the motor.
Page 82
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-25
00 - 04 Content of Multi-Function Display
07
Display the actual motor speed in rpm (enabled in vector control mode or PG (Encoder) feedback control) (LED H and LED U).
08
Display the estimated value of torque in Nm as it relates to current.
09
Display PG encoder feedback pulses/10ms. Display value= (rpm*PPR)/6000 (see note)
10 Display analog feedback signal value in %.
11
Display the signal of AVI analog input terminal in %. Range 0~10V corresponds to 0~100%. (LED U)
12
Display the signal of ACI analog input terminal in %. Range 4~20mA corresponds to 0~100%. (LED U)
13
Display the signal of AUI analog input terminal in %. Range -10V~10V corresponds to 0~100%. (LED U)
14
Display the temperature of heat sink in °C.
This parameter sets the display when Pr. 00-03 is set to 03.
Pr.00-04=09. The display value is (((rpm/60)*PPR)/1000ms)*10ms
with rpm=motor speed in revs/min and PPR=encoder pulse per revolution
When the display shows the multi-function display (Pr.00-03=03), the user also can view other
information by pressing the “LEFT” key
on the VFD-PU01 keypad.
00 - 05 User Defined Coefficient K Unit: 0.01
Settings 0.01 to d 160.00 Factory Setting: 1.00
The coefficient K determines the multiplying factor for the user-defined unit.
The display value is calculated as follows:
U (User-defined unit) = Frequency Command * K (Pr.00-05)
H (actual output) = Actual output frequency * K (Pr.00-05)
Example:
A conveyor belt runs at 13.6m/s at motor speed 60Hz.
K = 13.6/60 = 0.23 (0.226667 rounded to 2 decimals), therefore Pr.00-05=0.23
With Frequency command 35Hz, display shows LED U and 35*0.23=8.05m/s.
(To increase accuracy, use K=2.27 or K=22.67 and disregard decimal point.)
Page 83
Chapter 5 Parameters|VFD-B Series
5-26 Revision July 2008, BE16, SW V4.08 & V5.00
00 - 06 Software Version
Settings Read Only
Display #.##
00 - 07 Password Input Unit: 1
Settings 00 to 65535 Factory Setting: 00
Display 00~02 (times of wrong password)
The function of this parameter is to input the password that is set in Pr.00-08. Input the correct
password here to enable changing parameters. You are limited to a maximum of 3 attempts.
After 3 consecutive failed attempts, a blinking “PcodE” will show up to force the user to restart
the AC motor drive in order to try again to input the correct password.
00 - 08
Password Set Unit: 1
Settings 00 to 65535 Factory Setting: 00
Display 00 No password set or successful input in Pr. 00-07
01 Password has been set
To set a password to protect your parameter settings.
If the display shows 00, no password is set or password has been correctly entered in Pr.00-
07. All parameters can then be changed, including Pr.00-08.
The first time you can set a password directly. After successful setting of password the display
will show 01.
Be sure to record the password for later use.
To cancel the parameter lock, set the parameter to 00 after inputting correct password into Pr.
00-07.
The password consists of min. 2 digits and max. 5 digits.
How to make the password valid again after decoding by Pr.00-07:
Method 1: Re-input original password into Pr.00-08 (Or you can enter a new password if you
want to use a changed or new one).
Method 2: After rebooting, password function will be recovered.
Page 84
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-27
Password Decode Flow Chart
3 chances to enter the correct password. 1st time displays "01" if password is incorrect. 2nd time displays "02", if password is incorrect. 3rd time displays "P code" (blinking)
If the password was entered incorrectly after three tries, the keypad will be locked. Turn the power OFF/ON to re-enter the password.
Incorrect Password
END
Displays 00 when entering correct password into Pr.00-07.
00-08 00-07
00-07
Displays 00 when entering correct password into Pr.00-07.
Correct Password
END
00-08
00 - 09 Control method
Factory Setting: 00
Settings 00 V/f control
01 V/f + PG Control
02 Vector Control
03 Vector + PG Control
This parameter determines the control method of the AC motor drive.
PG is encoder (Pulse Generator) feedback for which an option PG card is required.
00 - 10 Reserved
Page 85
Chapter 5 Parameters|VFD-B Series
5-28 Revision July 2008, BE16, SW V4.08 & V5.00
Group 1: Basic Parameters
01 - 00
Maximum Output Frequency (Fmax) Unit: 0.01
Settings 50.00 to 400.00 Hz Factory Setting: 60.00
This parameter determines the AC motor drive’s Maximum Output Frequency. All the AC
motor drive frequency command sources (analog inputs 0 to +10V, 4 to 20mA and -10V to
+10V) are scaled to correspond to the output frequency range.
01 - 01 Maximum Voltage Frequency (Fbase) Unit: 0.01
Settings 0.10 to 400.00Hz Factory Setting: 60.00
This value should be set according to the rated frequency of the motor as indicated on the
motor nameplate. Maximum Voltage Frequency determines the v/f curve ratio. For example, if
the drive is rated for 460 VAC output and the Maximum Voltage Frequency is set to 60Hz, the
drive will maintain a constant ratio of 7.66 V/Hz (460V/60Hz=7.66V/Hz). This parameter value
must be equal to or greater than the Mid-Point Frequency (Pr.01-03).
01 - 02 Maximum Output Voltage (Vmax) Unit: 0.1
Settings 230V series 0.1 to 255.0V Factory Setting: 220.0
460V series 0.1 to 510.0V Factory Setting: 440.0
575V series 0.1 to 637.0V Factory Setting: 575.0
This parameter determines the Maximum Output Voltage of the AC motor drive. The Maximum
Output Voltage setting must be smaller than or equal to the rated voltage of the motor as
indicated on the motor nameplate. This parameter value must be equal to or greater than the
Mid-Point Voltage (Pr.01-04).
01 - 03 Mid-Point Frequency (Fmid) Unit: 0.01
Settings 0.10 to 400.00Hz Factory Setting: 0.50
This parameter sets the Mid-Point Frequency of the V/f curve. With this setting, the V/f ratio
between Minimum Frequency and Mid-Point frequency can be determined. This parameter
must be equal to or greater than Minimum Output Frequency (Pr.01-05) and equal to or less
than Maximum Voltage Frequency (Pr.01-01).
Page 86
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-29
01 - 04 Mid-Point Voltage (Vmid) Unit: 0.1
Settings 230V series 0.1 to 255.0V Factory Setting: 1.7
460V series 0.1 to 510.0V Factory Setting: 3.4
575V series 0.1 to 637.0V Factory Setting: 4.8
This parameter sets the Mid-Point Voltage of any V/f curve. With this setting, the V/f ratio
between Minimum Frequency and Mid-Point Frequency can be determined. This parameter
must be equal to or greater than Minimum Output Voltage (Pr.01-06) and equal to or less than
Maximum Output Voltage (Pr.01-02).
This parameter is ineffective when Pr.11-00 is set to 1 to 4.
01 - 05 Minimum Output Frequency (Fmin) Unit: 0.01
Settings 0.10 to 400.00Hz Factory Setting: 0.50
This parameter sets the Minimum Output Frequency of the AC motor drive. This parameter
must be equal to or less than Mid-Point Frequency (Pr.01-03).
The settings of 01-03, 01-04, and 01-06 are invalid in Vector Control mode.
01 - 06 Minimum Output Voltage (Vmin) Unit: 0.1
Settings 230V series 0.1 to 255.0V Factory Setting: 1.7
460V series 0.1 to 510.0V Factory Setting: 3.4
575V series 0.1 to 637.0V Factory Setting: 4.8
This parameter sets the Minimum Output Voltage of the AC motor drive. This parameter must
be equal to or less than Mid-Point Voltage (Pr.01-04).
The settings of Pr.01-01 to Pr.01-06 have to meet the condition of Pr.01-02 Pr.01-04 Pr.01-
06 and Pr.01-01 Pr.01-03 Pr.01-05.
01 - 07 Output Frequency Upper Limit Unit: 1
Settings 1 to 120% Factory Setting: 100
This parameter must be equal to or greater than the Output Frequency Lower Limit (Pr.01-08).
The Maximum Output Frequency (Pr.01-00) is regarded as 100%.
Output Frequency Upper Limit value = (Pr.01-00 * Pr.01-07)/100.
Page 87
Chapter 5 Parameters|VFD-B Series
5-30 Revision July 2008, BE16, SW V4.08 & V5.00
1-05 1-03 1-01
1-06
1-04
1-02
1-00
1-07
1-08
V
/f Curve
Voltage
Frequency
Output Frequency Lower Limit
Output Frequency Upper Limit
The limit of Output Frequency
Mid-point Freq.
Maximum Output Frequency
Maximum Output Vol tag e
Mid-point Vol tag e
Minimum Output Vol tag e
Minimum Output Freq.
Maximum Voltage Frequency (Base Frequency)
01 - 08 Output Frequency Lower Limit Unit: 1
Settings 0 to 100% Factory Setting: 0
The Upper/Lower Limits are to prevent operation errors and machine damage.
If the Output Frequency Upper Limit is 50Hz and the Maximum Output Frequency is 60Hz, the
Output Frequency will be limited to 50Hz.
If the Output Frequency Lower Limit is 10Hz, and the Minimum Output Frequency (Pr.01-05) is
set to 1.0Hz, then any Command Frequency between 1.0-10Hz will generate a 10Hz output
from the drive.
This parameter must be equal to or less than the Output Frequency Upper Limit (Pr.01-07).
The Output Frequency Lower Limit value = (Pr.01-00 * Pr.01-08) /100.
01 - 09 Acceleration Time 1 (Taccel 1) Unit: 0.1/0.01
01 - 10 Deceleration Time 1 (Tdecel 1) Unit: 0.1/0.01
01 - 11 Acceleration Time 2 (Taccel 2) Unit: 0.1/0.01
01 - 12 Deceleration Time 2 (Tdecel 2) Unit: 0.1/0.01
01 - 18 Acceleration Time 3 (Taccel 3) Unit: 0.1/0.01
01 - 19 Deceleration Time 3 (Tdecel 3) Unit: 0.1/0.01
01 - 20 Acceleration Time 4 (Taccel 4) Unit: 0.1/0.01
01 - 21 Deceleration Time 4 (Tdecel 4) Unit: 0.1/0.01
Settings 0.01 to 3600.0 sec Factory Setting: 10.0
Factory setting for models of 30hp (22kW) and above is 60sec.
Page 88
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-31
01 - 23 Accel/Decel Time Unit
Factory Setting: 01
Settings 00 Unit: 1 sec
01 Unit: 0.1 sec
02 Unit: 0.01 sec
The Acceleration Time is used to determine the time required for the AC motor drive to ramp
from 0 Hz to Maximum Output Frequency (Pr.01-00). The rate is linear unless S-Curve is
“Enabled”, see Pr.01-16.
The Deceleration Time is used to determine the time required for the AC motor drive to
decelerate from the Maximum Output Frequency (Pr.01-00) down to 0 Hz. The rate is linear
unless S-Curve is “Enabled.”, see Pr.01-17.
The Acceleration/Deceleration Time 1, 2, 3, 4 are selected according to the Multi-Function
Input Terminals Settings. See Pr.04-04 to Pr.04-09 for more details.
In the diagram shown below, the Acceleration/Deceleration Time of the AC motor drive is the
time between 0 Hz to Maximum Output Frequency (Pr.01-00). Suppose the Maximum Output
Frequency is 60 Hz, Minimum Output Frequency (Pr.01-05) is 1.0 Hz, and
Acceleration/Deceleration Time is 10 seconds. The actual time for the AC motor drive to
accelerate from start-up to 60 Hz and to decelerate from 60Hz to 1.0Hz is in this case 9.83
seconds. ((60-1) * 10 /60=9.83secs).
01-00
01-09
01-11
01-18
01-20
01-10
01-12
01-19 01-21
Frequency
TimeAccel. Time
Decel. Time
The definition of Accel./Decel. Time
Max. output Frequency
se tt i ng operation frequen cy
Min. output frequen cy
01-05
Resulting Resulting
Accel. Time
Decel. Time
Resulting Accel./Decel. Time
0 Hz
Page 89
Chapter 5 Parameters|VFD-B Series
5-32 Revision July 2008, BE16, SW V4.08 & V5.00
01 - 13 Jog Acceleration Time Unit: 0.1
Settings 0.1 to 3600.0 sec Factory Setting: 1.0
01 - 22 Jog Deceleration Time Unit: 0.1
Settings 0.1 to 3600.0 sec Factory Setting: 1.0
01 - 14 Jog Frequency Unit: 0.1
Settings 0.10 to 400.00Hz Factory Setting: 1.0
Both external terminal JOG and key “JOG” on the keypad can be used. When the Jog
command is “ON”, the AC motor drive will accelerate from Minimum Output Frequency (Pr.01-
05) to Jog Frequency (Pr.01-14). When the Jog command is “OFF”, the AC motor drive will
decelerate from Jog Frequency to zero. The used Accel/Decel time is set by the Jog
Accel/Decel time (Pr.01-13, Pr.01-22).
Before using the JOG command, the drive must be stopped first. And during Jog operation,
other operation commands cannot be accepted, except command via the FORWARD,
REVERSE and STOP keys on the digital keypad.
01-13
Frequency
Time
JOG Accel. Time
JOG Decel. Time
The definition of JOG Accel./Decel. Time
01-14 JOG Frequency
Min. output frequency
01-05
0 Hz
01-22
01 -15 Auto-Acceleration / Deceleration
Factory Setting: 00
Settings 00 Linear acceleration / deceleration
01 Auto acceleration, linear Deceleration.
02 Linear acceleration, auto Deceleration.
03 Auto acceleration / deceleration (set by load)
04 Auto acceleration / deceleration (set by Accel/Decel Time setting)
Page 90
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-33
With Auto acceleration / deceleration it is possible to reduce vibration and shocks during
starting/stopping the load.
During Auto acceleration the torque is automatically measured and the drive will accelerate to
the set frequency with the fastest acceleration time and the smoothest start current.
During Auto deceleration, regenerative energy is measured and the motor is smoothly stopped
with the fastest deceleration time.
But when this parameter is set to 04, the actual accel/decel time will be equal to or more than
parameter Pr.01-09 ~Pr.01-12 and Pr.01-18 to Pr.01-21.
Auto acceleration/deceleration makes the complicated processes of tuning unnecessary. It
makes operation efficient and saves energy by acceleration without stall and deceleration
without brake resistor.
In applications with brake resistor or brake unit, Auto deceleration shall not be used.
01 - 16 Acceleration S-Curve
01 - 17 Deceleration S-Curve
Factory Setting: 00
Settings 00 S-curve disabled
01 to 07 S-curve enabled (07 is smoothest)
This parameter is used to ensure smooth acceleration and deceleration via S-curve.
The S-curve is disabled when set to 00 and enabled when set to 01 to 07.
Setting 01 gives the quickest and setting 07 the longest and smoothest S-curve.
The AC motor drive will not follow the Accel/Decel Times in Pr.01-09 to Pr.01-12 and Pr.01-18
to Pr.01-21 when S-curve is enabled.
The diagram below shows that the original setting of the Accel/Decel Time is only for reference
when the S-curve is enabled. The actual Accel/Decel Time depends on the selected S-curve
(01 to 07).
3
1
2
4
1
3
4
2
1 2
Disable S curve
3 4
Enable S curve
A
cceleration/deceleration Characteristics
Page 91
Chapter 5 Parameters|VFD-B Series
5-34 Revision July 2008, BE16, SW V4.08 & V5.00
Group 2: Operation Method Parameters
02 - 00 Source of First Master Frequency Command
Factory Setting: 00
Settings 00 Digital keypad (PU01) UP/DOWN keys or Multi-function Inputs
UP/DOWN. Last used frequency saved.
01 AVI 0 ~ +10VDC
02 ACI 4 ~ 20mA
03 AUI -10 ~ +10VDC
04 RS-485 serial communication (RJ-11). Last used frequency saved.
05 RS-485 serial communication (RJ-11). Last used frequency not
saved.
06 Combined use of master and auxiliary frequency command
See Pr. 02-10 to 02-12
02 - 13 Source of Second Master Frequency Command
Factory Setting: 00
Settings 00 Digital keypad UP/DOWN keys or Multi-function Inputs UP/DOWN.
Last used frequency saved.
01 AVI 0 ~ +10VDC
02 ACI 4 ~ 20mA
03 AUI -10 ~ +10VDC
04 RS-485 serial communication (RJ-11). Last used frequency saved.
05 RS-485 serial communication (RJ-11). Last used frequency not
saved.
06 Combined use of master and auxiliary frequency command
See Pr. 02-10 to 02-12
These parameters set the Master Frequency Command Source of the AC motor drive.
02 - 01 Source of First Operation Command
Factory Setting: 00
Settings 00 Digital keypad (PU01)
01 External terminals. Keypad STOP/RESET enabled.
02 External terminals. Keypad STOP/RESET disabled.
03 RS-485 serial communication (RJ-11). Keypad STOP/RESET
enabled.
04 RS-485 serial communication (RJ-11). Keypad STOP/RESET
disabled.
Page 92
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-35
02 - 14 Source of Second Operation Command
Factory Setting: 00
Settings 00 Digital keypad (PU01)
01 External terminals. Keypad STOP/RESET enabled.
02 External terminals. Keypad STOP/RESET disabled.
03 RS-485 serial communication (RJ-11). Keypad STOP/RESET
enabled.
04 RS-485 serial communication (RJ-11). Keypad STOP/RESET
disabled.
When the AC motor drive is controlled by external terminal, please refer to Pr.02-05 for details.
The first /second frequency/operation command is enabled/disabled by Multi Function Input
Terminals. Please refer to of Pr.04-04 ~ 04-09.
02 - 10 Source of the Master Frequency Command
Factory Setting: 00
Settings 00 Digital keypad (PU01) UP/DOWN keys or Multi-function Inputs
UP/DOWN. Last used frequency saved.
01 AVI 0 ~ +10VDC
02 ACI 4 ~ 20mA
03 AUI -10 ~ +10VDC
04 RS-485 serial communication (RJ-11). Last used frequency saved.
02 - 11 Source of the Auxiliary Frequency Command
Factory Setting: 00
Settings 00 Digital keypad (PU01) UP/DOWN keys or Multi-function Inputs
UP/DOWN. Last used frequency saved.
01 AVI 0 ~ +10VDC
02 ACI 4 ~ 20mA
03 AUI -10 ~ +10VDC
04 RS-485 serial communication (RJ-11). Last used frequency saved.
02 - 12
Combination of the Master and Auxiliary Frequency Command
Factory Setting: 00
Settings 00 Master frequency + Auxiliary frequency
01 Master frequency - Auxiliary frequency
These three parameters (Pr.02-10~02-12) are enabled when Pr.02-00 or Pr.02-13 are set to
06. If they are enabled, the frequency command will be determined by these parameters.
Page 93
Chapter 5 Parameters|VFD-B Series
5-36 Revision July 2008, BE16, SW V4.08 & V5.00
02 - 02 Stop Method
Factory Setting: 00
Settings 00 STOP: ramp to stop E.F.: coast to stop
01 STOP: coast to stop E.F.: coast to stop
02 STOP: ramp to stop E.F.: ramp to stop
03 STOP: coast to stop E.F.: ramp to stop
The parameter determines how the motor is stopped when the AC motor drive receives a valid
stop command or detects External Fault.
1. Ramp: the AC motor drive decelerates to Minimum Output Frequency (Pr.01-05)
according to the deceleration time and then stops.
2. Coast: the AC motor drive stops the output instantly upon command, and the motor
free runs until it comes to a complete standstill.
3. The motor stop method is usually determined by the characteristics of the motor load and
how frequently it is stopped.
(1) It is recommended to use “ramp to stop” for safety of personnel or to prevent
material from being wasted in applications where the motor has to stop after the
drive is stopped. The deceleration time has to be set accordingly.
(2) If the motor free running is allowed or the load inertia is large, it is
recommended to select “coast to stop”.
For example: blowers, punching machines, centrifuges and pumps.
RUN
STOP RUN
STOP
Frequency
Frequency
Time
Time
output frequency
output frequency
motor speed
motor speed
operation command
operation command
stops according to decel eration time
free run to stop
ramp to stop and free run to stop
Page 94
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-37
EF
Frequency
Frequency
frequency output
motor speed
EF
operation command
stops according to decel eration time
When Pr.02-02 is set to 2 or 3
frequency output
free run to stop
operation command
When Pr.02-02 is set to 0 or 1
motor speed
02 - 03
PWM Carrier Frequency Selections
Unit: 1
230V/460V Series
Power
1-5hp
0.75-3.7kW
7.5-25hp
5.5-18.5kW
30-60hp
22-45kW
75-100hp
55-75kW
Setting Range 01-15 kHz 01-15 kHz 01-09 kHz 01-06 kHz
Factory Setting 15 kHz 09 kHz 06 kHz 06 kHz
575V Series
Power
1-15hp
0.75-11kW
20-60hp
15-45kW
75-100hp
55-75kW
Setting Range 01-10 kHz 01-08 kHz 01-06 kHz
Factory Setting 06 kHz 06 kHz 06 kHz
This parameter determines the PWM carrier frequency of the AC motor drive.
1kHz
8kHz
15kHz
Carrier Frequency
Acoustic Noise
Electromagnetic Noise or leakage current
Heat Dissipation
Current Wave
Significant
Minimal
Significant
Minimal
Minimal
Significant
Minimal
Significant
From the table, we see that the PWM carrier frequency has a significant influence on the
electromagnetic noise, AC motor drive heat dissipation, and motor acoustic noise.
Page 95
Chapter 5 Parameters|VFD-B Series
5-38 Revision July 2008, BE16, SW V4.08 & V5.00
02 - 04 Motor Direction Control
Factory Setting: 00
Settings 00 Enable Forward/Reverse operation
01 Disable Reverse operation
02 Disabled Forward operation
The parameter determines the AC motor drive direction of rotation. See Chapter 2 for definition
of direction of rotation.
02 - 05 2-wire/ 3-wire Operation Control Modes
Factory Setting: 00
Settings 00 2-wire: FWD/STOP, REV/STOP
01 2-wire: FWD/REV, RUN/STOP
02 3-wire Operation
There are three different types of control modes:
02-05
External Terminal
00
2-wire FWD /STOP REV / STOP
V
FD-B
FWD:("OPEN":STOP)
("CLOSE":FWD)
REV:("OPEN": STOP)
("CLOSE": REV)
DCM
FWD/STOP
REV/STOP
01
2-wire
FWD/ REV
RUN / STOP
V
FD-B
FWD:("OPEN":STOP)
("CLOSE":RUN)
REV:("OPEN": F
("CLOSE": REV)
DCM
RUN/STOP
FWD/REV
WD)
02 3-wire
V
FD-B
FWD:("CLOSE":RUN) EF: ("OPEN":STOP)
REV:("OPEN": F
("CLOSE": REV)
DCM
STOP RUN
REV/FWD
WD)
Page 96
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-39
02- 06 Line Start Lockout
Factory Setting: 00
Settings 00 Disable. Operation status is not changed even if operation
command source Pr.02-01 and/or Pr.02-14 is changed.
01 Enable. Operation status is not changed even if operation command
source Pr.02-01 and/or Pr.02-14 is changed.
02 Disable. Operation status will change if operation command source
Pr.02-01 and/or Pr.02-14 is changed.
03 Enable. Operation status will change if operation command source
Pr.02-01 and/or Pr.02-14 is changed.
This parameter determines the response of the drive when power is on and the operation
command source is changed.
Pr.02-06 Start lockout (Run when power is ON)
Operation status when operation
command source is changed
0 Disable (AC motor drive will run) Keep previous status
1 Enable (AC motor drive won’t run) Keep previous status
2 Disable (AC motor drive will run)
Change according to the new
operation command source
3 Enable (AC motor drive won’t run)
Change according to the new
operation command source
When the operation command source is from an external terminal and operation command is
ON (FWD/REV-DCM=close), the AC motor drive will operate according to Pr.02-06 after
power is applied. <For terminals FWD and REV only>
1. When Pr.02-06 is set to 0 or 2, AC motor drive will run immediately.
2. When Pr.02-06 is set to 1 or 3, AC motor drive will remain stopped until operation
command is received after previous operation command is cancelled.
Page 97
Chapter 5 Parameters|VFD-B Series
5-40 Revision July 2008, BE16, SW V4.08 & V5.00
RUN
RUN
STOP
STOP
Pr.02-01=1 or 2
This action will follow FWD/DCM or REV/DCM status (ON is close/OFF is open)
ON
OFF
FWD-DCM (close)
Pr.02-01=0
output frequency Pr.02-06=2 or 3
Change operation command source
output frequency Pr.02-06=0 or 1
When the operation command source isn’t from the external terminals, independently from
whether the AC motor drive runs or stops, the AC motor drive will operate according to Pr.02-
06 if the two conditions below are both met.
1. When operation command source is changed to external terminal (Pr.02-01=1 or 2, Pr.02-
14=1 or 2)
2. The status of terminal and AC motor drive is different.
And the operation of the AC motor drive will be:
1. When setting 0 or 1, the status of AC motor drive is not changed by the terminal status.
2. When setting 2 or 3, the status of AC motor drive is changed by the terminal status.
It needs to received a run command after previous command is cancelled
ON
OFF
FWD-DCM (close)
power is applied
output frequency Pr.02-06=0 or 2
output frequency Pr.02-06=1 or 3
ON
OFF
ON
it will run
it won't run when power is applied
The Line Start Lockout feature does not guarantee that the motor will never start under this
condition. It is possible the motor may be set in motion by a malfunctioning switch.
Page 98
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-41
02- 07 Loss of ACI Signal (4-20mA)
Factory Setting: 00
Settings 00 Decelerate to 0Hz
01 Coast to stop and display “EF”
02 Continue operation by the last frequency command
This parameter determines the behavior when ACI is lost.
When set to 00 or 02, it will display warning message “AnLEr” on the keypad in case of loss of
ACI signal and execute the setting. When ACI signal is recovered, the warning message
usually disappears automatically. If the warning message is still displayed, please press
“MODE” key to make it disappear.
02 - 08 Up/Down Mode
Factory Setting: 00
Settings 00 Based on Accel/Decel time acc. to Pr.01-09 to 01-12 and Pr.01-18
to 01-21
01 Constant speed (acc. to Pr. 02-09)
02 Based on Accel/Decel time acc. to Pr.01-09 to 01-12 and Pr.01-18
to 01-21, but frequency command will be 0 when stopped
02 - 09
Accel/Decel Rate of Change of UP/DOWN Operation with Constant Speed
Unit: 0.01
Settings 0.01~1.00 Hz/ms Factory Setting: 0.01
These parameters determine the increase/decrease of the master frequency when operated
via the Multi-Function Inputs when Pr.04-04~Pr.04-09 are set to 11 (Up command) or 12
(Down command).
02 - 15 Keypad Frequency Command Unit: 0.01
Settings 0.00 ~ 400.00Hz Factory Setting: 60.00
This parameter can be used to set frequency command or read keypad frequency command.
Page 99
Chapter 5 Parameters|VFD-B Series
5-42 Revision July 2008, BE16, SW V4.08 & V5.00
Group 3: Output Function Parameters
03 - 00 Multi-function Output Relay (RA1, RB1, RC1)
Factory Setting: 08
03 - 01 Multi-function Output Terminal MO1
Factory Setting: 01
03 - 02 Multi-function Output Terminal MO2
Factory Setting: 02
03 - 03 Multi-function Output Terminal MO3
Factory Setting: 20
Settings Function Description
00 No Function
01 AC Drive Operational
Active when there is an output from the drive or RUN
command is “ON”.
02
Master Frequency
Attained
Active when the AC motor drive reaches the output
frequency setting.
03 Zero Speed
Active when Command Frequency is lower than the
Minimum Output Frequency.
04 Over-Torque Detection
Active as long as over-torque is detected. (Refer to Pr.06-03
~ Pr.06-05)
05
Baseblock (B.B.)
Indication
Active when the output of the AC motor drive is shut off
during baseblock. Base block can be forced by Multi-function
input (setting 9 or 10).
06 Low-Voltage Indication Active when low voltage(Lv) is detected.
07
Operation Mode
Indication
Active when operation command is controlled by external
terminal.
08 Fault Indication
Active when faults occur (oc, ov, oH, oL, oL1, EF, cF3, HPF,
ocA, ocd, ocn, GFF).
09
Desired Frequency
Attained 1
Active when the desired frequency (Pr.03-04) is attained.
10 PLC Program Running Active when PLC Program is running.
11
PLC Program Step
Completed
Active for 0.5 sec each time the multi-step speed is attained.
12 PLC Program Completed
Active for 0.5 sec when the PLC program cycle has
completed
13 PLC Operation Paused Active when PLC operation is paused.
Page 100
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-43
Settings Function Description
14
Terminal Count Value
Attained
Active when the counter reaches Terminal Count Value.
15
Preliminary Count Value
Attained
Active when the counter reaches Preliminary Count Value.
16
17
18
Auxiliary Motor 1, 2 and 3
For the fan & pump control applications, one can use the
Multi-function Output Terminals (1-3) to define the auxiliary
motor. When using with group 10 PID Controls and group 11
Fan and Pump Control, it can control flow of many motors.
19
Heat Sink Overheat
Warning (OH1)
When the heatsink overheats, it will signal to prevent OH
from turning off the drive. When it is higher than 85
o
C
(185
o
F), it will be ON. If not, it will be OFF.
20 AC Motor Drive Ready Active when the drive is on and no abnormality detected.
21
Emergency Stop
Indication
Active once the drive’s emergency stop function is activated.
22
Desired Frequency
Attained 2
Active when the desired frequency (Pr.03-10) is attained.
23 Software Brake Signal
This function is used in conjunction with a VFDB Brake Unit.
The output will be activated when the drive needs help
braking the load. A smooth deceleration is achieved by using
this function.
24
Zero Speed Output
Signal
Active unless there is an output frequency present at
terminals U/T1, V/T2, and W/T3.
25 Under-current Detection
Active once the drive’s current has fallen below its minimum
allowable value. (Refer to Pr.06-12, 06-13)
26
Operation Indication
(H>=Fmin)
Active when there is output voltage from U, V, W.
27 Feedback Signal Error
Active when the feedback signal is abnormal. (Refer to
Pr.10-08, Pr.10-16)
28
User-defined Low-
voltage Detection
Active once the DC Bus voltage is too low. (Refer to Pr.06-
16, Pr.06-17)
29
Brake Control (Desired
Frequency Attained 3)
Active when output frequency Pr.03-13. Deactivated when output frequency Pr.03-14 after STOP command.
03 - 04 Desired Frequency Attained 1 Unit: 0.01
Settings 0.00 to 400.00 Hz Factory Setting: 0.00
Loading...