Delta 230 User Manual

Fig 1
Fig 2
GENERAL
The unit is manufactured, checked and supplied in accordance with our published specification, and when installed and used in normal or prescribed applications, with the lid in place and within the parameters set for mechanical and electrical performance, will not cause danger or hazard to life or limb.
HEALTH AND SAFETY AT WORK ACT 1974 WARNINGS
1. THE USERS ATTENTION IS DRAWN TO THE FACT THAT, WHEN THE UNIT IS "LIVE" WITH RESPECT TO ELECTRICAL OR PRESSURE SUPPLIES, A HAZARD MAY EXIST IF THE UNIT IS OPENED OR DISMANTLED.
2. UNITS MUST BE SELECTED AND INSTALLED BY SUITABLY TRAINED AND QUALIFIED PERSONNEL IN ACCORDANCE WITH APPROPRIATE CODES OF PRACTICE SO THAT THE POSSIBILITY OF FAILURE RESULTING IN INJURY OR DAMAGE CAUSED BY MISUSE OR MIS-APPLICATION IS AVOIDED.
OPERATING PRINCIPLES
Pressure applied to the Bourdon Tube actuates the Primary mechanism and hence rotates the motion Transfer shaft. The motion transfer shaft in turn actuates the secondary mechanism and hence operates the microswitch. When the pressure is decreased the motions are reversed thereby resetting the microswitch.
INSTALLATION
The instruments are designed to be mounted vertically, with the process connection underneath, onto a wall or panel using the backplate provided. Select the mounting point so as to avoid excessive shock, vibration or temperature fluctuations. Instruments should be mounted to avoid excessive heat transfer from the process lines or adjacent plant.
Set Point Adjustment: Model 233, 234 (Fig 3)
Model 234 provides 2 microswitches that can be set independently using a special mechanism, which fulfils the need for HI LO switching. Adjust as follows:
1. Isolate the instrument from process and power.
2. Remove the instrument lid.
3. Loosen either locking screw.
4. Move the indicator to the desired position. Move the indicators to the right to raise the set point and to the left to lower the set point.
5. The indicators can be set independently of each other, thus giving a range of HI/LO separation from approximately 15% to 100% of span.
6. Tighten the locking screws taking care not to over tighten.
7. Replace the instrument lid (see maintenance).
Switching Differential Adjustment: Model 232 (Fig 4)
1. Isolate the instrument from process and power.
2. Remove the instrument lid.
3. Rotate the knurled plastic wheel on the microswitch to adjust the switch differential. Rotate clockwise to increase the differential and counter clockwise to reduce the differential.
4. Replace the instrument lid (see maintenance).
Switching Differential Adjustment: Model 233 (Fig 3)
The model 233 provides a single microswitch, which can have the set and resets points independently adjusted over a range of approximately 15% to 100% of span.
Note: For accurate setting a suitable pressure gauge must be used in conjunction with the above procedure. Do not attempt to set the switch outside the scale limits. Though the unit may be set anywhere within its operation range, for optimum performance, it is good practice to have a set point value between 25% and 75% of span.
INSTALLATION, OPERATING AND
MAINTENANCE INSTRUCTIONS FOR
BOURDON TUBE ACTUATED
SERIES 230 PRESSURE SWITCHES
(Models 231, 232, 233, 234)
ISSUE E 02/10
PRODUCT CODE
ENCLOSURE
MODEL
ELECTRICAL ENTRY
MATERIAL OF WETTED PARTS
RANGE
SWITCHING OPTIONS
PROCESS CONNECTION
OPTIONS AND TREATMENTS
SPECIAL ENGINEERING
Use a spanner to support the process connection when fitting the instrument. When fitting the instrument lid make sure gaskets and ‘O’ rings are in good condition and fitted correctly.
WARNING: CHECK THE CONNECTION THREAD SIZE AND SPECIFICATION ON THE UNIT TO AVOID MIS-MATCHING WITH THE PROCESS CONNECTION ADAPTOR. SEE DIGIT 6 OF PRODUCT CODE.
REPLACEMENT PARTS
Use only factory authorised parts and procedures. The only parts normally recommended for site replacement are the microswitches. However, in some circumstances other spares kits are available. Apply for details quoting the serial number and full product code.
WARRANTIES – SEE CONDITIONS OF SALE
In the interest of development and improvement Delta Controls Ltd, reserve the right to amend without notice,
details contained in this publication. No legal liability will be accepted by Delta Controls Ltd, for any errors,
DELTA CONTROLS LIMITED, ISLAND FARM AVENUE, WEST MOLESEY, SURREY KT8 2UZ
T +44 (0) 208 939 3511 F +44 (0) 208 783 1163 E sales@delta-controls.com W www.delta-controls.com
WIRING (Fig 1)
Wire in accordance with local and National codes. Use cables no larger than 2.5 mm2 (14AWG). Deliver electrical connection through a suitable cable gland, which will maintain the IP rating of the instrument. Insert bare wires fully into the terminal block and tighten securely. Keep wiring tails to a minimum and check that wires do not interfere with the operating mechanism. Use the earthing points provided.
CERTIFIED ENCLOSURES
All Series 230 Pressure Switches can be supplied with BASEEFA certified enclosures to the following standards: Zone 1 (Div 1) IEC 79-1 BS 5501 Parts 1 and 5: EN50 014 and EN50 018 CENELEC Codes ‘H’ for aluminium and ‘K’ for cast iron. EExd IIC T6 BS 4683 Part 2 Code ‘M’ Cast Iron Exd I T6 for mining.
Electrical Adaptors Zone 1. Use only certified adaptors for Zone 1.
WARNING: IT IS A REQUIREMENT OF SAFETY THAT AT LEAST 5 FULL THREADS ARE ENGAGED BETWEEN THE ADAPTOR AND CONDUIT ENTRY. TAKE CARE TO SELECT AND INSTALL ADAPTORS THAT DO NOT REDUCE THE ENCLOSURE IP RATING.
Zone 2. Adaptors used must have equivalent
IP rating to the enclosure and be impact resistant to 7 Nm.
References for Selection and Installation
BS 5345 Part 3 for Enclosure Codes H and K BS 5345 Part 4 for all Enclosure Codes (Intrinsic Safety) BS 5345 Part 7 for Enclosure Code N BS 5501 Part 1 for Enclosure Codes H and K (BS EN50 014) BS 5490 IEC 529 IP RATING (Ingress Protection)
MAINTENANCE
Inspections should be carried out at quarterly to yearly intervals depending upon conditions. Isolate the unit from process and power and remove the lid. Check all terminals for tightness. Check that cable tails are not fouled or chafed. Check for internal condensation. Rectify as necessary. It is recommended that instruments used to provide an alarm are operated periodically to ensure they are functioning correctly.
If further maintenance is required seek advice from DELTA CONTROLS before attempting repair or replacement of parts.
Fig 4
Fig 4
Fig 5
YOUR TRUSTED PARTNER IN PROCESS INSTRUMENTATION
omissions or amendments.
CAUTION
Moving parts have been treated with a water repelling lubricant before leaving the factory. Occasional inspection and the application of a water repelling lubricant is recommended to ensure moving parts remain free under all conditions.
Zone 1 enclosures
Thread seal and contact surfaces must be lightly lubricated using non-setting non­corrosive grease compatible with the lid seal (Nitrile). Do not use copper bearing grease on aluminium. Screw on lid hand tight making sure that mating surfaces of the lid and enclosure are in contact. Re-tighten the lid lock screw.
WARNING: IT IS A SAFETY REQUIREMENT THAT AT LEAST 5 FULL THREADS ARE ENGAGED WHEN THE UNIT IS IN OPERATION. NEVER OPERATE THE UNIT UNLESS THIS CONDITION IS MET. DO NOT USE GREASES OR LUBRICANTS NOT COMPATIBLE WITH THE ENVIRONMENT OR PROCESS.
Weatherproof Enclosure (W) and N
If lid gasket is damaged, replace with new gasket. Make sure gasket aligns correctly with sealing faces.
Stainless Steel Weatherproof Enclosure (A)
Check gasket, if damaged replace.
OPERATION
Pressure switches are calibrated against falling pressure unless otherwise specified. Set Point adjustment refers to falling pressure. Switching differential is the difference between the set point and the operating value on rising pressure. For opening details see Fig 5, 6, 7.
Set Point Adjustment: Models 231, 232 (Fig
2)
1. Isolate the instrument from process and power.
2. Remove the instrument lid.
3. Loosen either locking screw.
4. Rotate the adjuster to move the indicator along the calibrated scale. Rotate clockwise to raise the set point and anti-clockwise to lower the set point.
5. Retighten the locking screw taking care not to over tighten.
6. Replace the instrument lid (see maintenance).
NOTE: FIGS 5, 6, 7 SHOW STANDARD MOUNTING ARRANGEMENTS
Registered Office Registered in England No 5369683
Fig 6
Stock No: 002522/231
Machinery Safety Directive MSD
– 2006/42/EC
WIRING
Pollution degree
C O D E
U L / C S A
D e s i g n a t i o n
R A T I N G
0 . 6 / 0 . 3 A @
A C 1 4 /
AC 4 3 2
7 2
0 . 8 k V
2 5 0
0 . 2 2 / 0 . 1 A @
D C 1 3 /
D C
2 8 2 8
0 . 6 / 0 . 3 A @
A C 1 4 /
A C
4 3 2 7 2
0 . 8 k V
250V
0 . 2 2 / 0 . 1 A @
D C 1 3 /
D C
2 8 2 8
0 4
1 A @ 1 2 5 V AC R E S I S T I V E ( I E C 1 0 5 8
-
1 / E N 6 1 0 5 8
-
1 )
0 . 6 / 0 . 3 A @
A C 1 4 /
AC
4 3 2 7 2
0 . 5 k V
2 5 0 V
0 . 2 2 / 0 . 1 A @
D C 1 3 /
D C
2 8 2 8
0 G
A C 1 4 /
A C
2 1 6 3 6
0 . 5 k V
1 2 5 V
0 . 3 A @ 1 2 0
V A C
0 C
0 . 8 k V
2 5 0 V
0 . 6 / 0 . 3 A @
A C 1 4 /
A C
4 3 2 7 2
0 . 6 / 0 . 3 A @
A C 1 4 /
A C
4 3 2 7 2
0 . 8 k V
250V
0 . 2 2 / 0 . 1 A @
D C 1 3 /
D C
2 8 2 8
0 . 6 / 0 . 3 A @
A C 1 4 /
AC
4 3 2 7 2
0 . 5 k V
250V
0 . 2 2 / 0 . 1 A @
D C 1 3 /
D C
2 8 2 8
REDUCER
‘W’ CABLE GLAND ASSY
½" NPT Pg 13.5
EN CLOSURE W A LL
Low Voltage Directive (LVD) – 2006/95/AC. Switch products with enclosure codes ‘W’ and ‘A’ supplied CE-marked must be installed and used in accordance with the main instructions and this addendum supplied with each product. Products rated lower than 50V ac and 75 V dc are outside the scope of the LVD, and therefore, do not require CE-marking under this directive. The LVD does not apply to products with enclosure codes ‘H’, ‘K’, ‘R’, ‘M’, ‘N’ for use in hazardous areas. Switch products with enclosure codes ‘H’, ‘K’, ‘R’, ‘M’, ‘N’, are covered by the Explosive Atmospheres Directive ATEX – 94/9/EC and when CE-marked will indicate compliance with this directive alone. The following directives do not apply to switch products manufactured by Delta Controls: Electromagnetic Compatibility EMC – 2004/08/EC
ENCLOSURE ‘W’ Cable Glands and adaptors – If enclosure ‘W’ is supplied with a through hole of 22 mm
blanked with a blind grommet. Discard the grommet and fit a suitable proprietary brass or nylon M20 cable gland with thread length of 10 mm and locknut. Fit the nylon reducer provided to the inside and a fibre washer to the outside. See diagram 1. Alternately, the enclosure may be supplied from the factory with a threaded adaptor ready to accept the customer’s gland or conduit system. Alternatives: i) a metal or nylon adaptor may be used to accommodate other sizes of gland eg NPT, or conduit system. See diagram 2. ii) an elbow kit may be supplied to enable the entry to be rotated axially through 90° and radially through 360°. See diagram 3.
Earthing / grounding – The user must make suitable local earthing arrangements, if required, to ensure that metal glands are earthed. An earthing point is provided inside the enclosure. If this is disturbed in any way it must be reassembled correctly to be an effective earth and prevent ingress. See diagram 4. When removing the lid slacken the M4 nut first and ensure it is re tightened whenever the lid is replaced. See diagram 4.1.
ENCLOSURE ‘A’ Cable Glands and adaptors – Enclosure ‘A’ is supplied with an M20 x 1.5 tapped hole. Use a
suitable stainless steel cable gland and sealing washer. Alternately the enclosure may be supplied with a threaded adaptor fitted at the factory ready to accept the customer’s gland or conduit system. See diagram 5.
Earthing / grounding – Bonding between the enclosure and gland / adaptor will be achieved when both parts are screwed together. An earthing point is provided inside the enclosure. If this is disturbed in any way it must be reassembled correctly to be an effective earth and prevent ingress. See diagram 4.
EARTHING / GROUNDING OF PROCESS CONNECTION AND BACK PLATES – All the internal dead metal work is bonded to the enclosure earthing point. Due to requirements of sealing, the process connection and back plates may be isolated from the earthing point. Do not, therefore, rely on either for earthing, instead always use the earthing point provided. If required, the process connection and back plates may be bonded locally. Never use the process connection or inlet pipe for locally grounding welding equipment unless it is separately earth bonded.
Declaration of Conformity
We: Delta Controls Ltd Island Farm Avenue West Molesey Surrey, UK KT8 2UZ
As the manufacturers of the apparatus listed, declare under our sole responsibility that the products listed below:
Pressure, Pressure Difference, Temperature & Flow switches series “W” or “A”: 201, 202, 203, 281, 204, 207, 208, 209, 231, 232, 233, 234, S21, S22, S24, GR2, GR4, VM2, VM4. 301, 303, 304, 381, 384, 306, 386, 310, 316, S31, S34, GR3, GR6. 721, 731, 771, 722, 732, 772, 723, 733, 773, 781, 734, 774, 741, 742, 743, 744, S71, GR7.
131. To which this declaration relates are in conformity with the following relevant standards or parts thereof: EN 60947-1 :1992 Low voltage switch gear and control-gear-general rules.
EN 60947-5-1:1992 Low voltage switch gear and control-gear-control circuit devices and switching elements. EN 60529: 1991 Specification for classification of degrees of protection provided by enclosures. EN 60950:1992 Safety of information technology equipment including electrical business equipment: section 2.5. BS 6134:1991 Specification for pressure and vacuum switches.
And thereby conforms to the requirements of the Low Voltage Directive 73/23/EC amended by 93/68/EEC.
…………………. R. Harrison Managing Director
Original dated 22nd June 2000 Rev. B dated 12
th
August 2009
Signed:
conditions where condensation may readily form, then sealed contacts should be used. See Table A codes 08/09, 0G/0H, H2/H3/H6.
Electrical isolation – These products are not suitable for electrical isolation. Always isolate circuit separately to carry out any electrical work.
TABLE A – MICROSWITCH RATINGS
M4 SINGL E COIL WAS HER
M I C R O S W I T C H
( R E S I S T I V E )
* S E E N O T E
S W I T C H
5 A @ 1 1 0 / 2 5 0
0 0
&
0 1
5 A @ 1 1 0 / 2 5 0
0 2
&
0 3
2 A @ 3 0 V D C
1 A @ 1 2 5 V A C
&
0 5
* 1 0 0 m A @ 3 0
0 8
&
0 9
&
0 H
0 D
H 2
&
H 3
&
H 6
1 1 0 / 2 5 0 V A C 5 A @ 3 0 V D C
* 1 A @ 3 0 V A C
5 A @ 1 1 0 / 2 5 0
5 A @ 1 1 0 / 2 5 0
2 A @ 3 0 V D C
5 A @ 1 1 0 / 2 5 0
2 A @ 3 0 V D C
T h e e l e ct r i c a l r at i n g i s d e p e n d en t on t h e m i cr o s w i t ch f i t t ed t o t h e in s t r u m e nt . T he e l e c t r i c a l r a t i n g is d ef i n e d b y e a c h ap p r o v a l th a t t h e m i c ro s w i tc h c o m pl i e s w i t h a n d i s sh o w n o n t h e pr o d u c t n a m e p l a t e , i e UL / CS A , o r I E C . I t s h o u ld be no t e d th a t t h e sw i t c h m us t b e u s e d wi t h i n t he el e c t r i c al r a t i n g s p ec i f i e d f r o m t h e a pp r o v al yo u r e qu i re . T a b l e A l i s t s t he ac t u a l I E C ra t i ng s ag a i n s t th e D e si g n a t i o n & U t i l is a t i on C at e g o r y m a r k e d on th e n am e pl a t e . In th e a b s e nc e o f a n y ve r i f i c a ti on b y UL / C S A th e m i c ro s w i tc h *ma n u f ac t u r er ’s r a t i ng i s s p ec i fi e d i n b o l d i t a l i c s . If i n do u b t , s e e k g u i d an c e fr om f a c t o r y .
DIAG 1
LOCKNUT
NYLON 22/20
DIAG 3
GLAND
FIBRE
SCREW
WASHER
DIAG 4.1
M4 NUT
M4 STU D
LID
EARTH STRAP
– all products are suitable for use in pollution degree 3. For extreme
IEC 947-5-1 / EN 60947-5-1 RATING
R A T I N G
Ui mp
V A C
V A C
V D C
* 5 A @
& 3 0 V D C
V A C
V A C
V A C
ENCLOSURE WALL
PROPRIETARY
GLAND
M20 X 1.5 ¾ ET
FIBRE WASHER
ENCLOSURE
WALL
O RING SEAL
ELBOW ASSY
M4 PLAIN WASHER
EARTH STRAP
GASKET
BASE
Ui
V
M4 SCR EW
( I e I U e )
1 2 0 / 2 4 0 V A C
1 2 5 / 2 5 0 V D C
1 2 0 / 2 4 0 V A C
1 2 5 / 2 5 0 V D C
1 2 0 / 2 4 0 V A C
1 2 5 / 2 5 0 V D C
1 2 0 / 2 4 0
V A C
1 2 0 / 2 4 0 V A C
1 2 5 / 2 5 0 V D C
1 2 0 / 2 4 0 V A C
1 2 5 / 2 5 0 V D C
DIAG 2
‘W’ ADAPTOR ASSY
EA R TH L ABE L
SINGL E COIL WASHER
NUT
PL AIN WAS HERS
&
U t i l i s a t i o n
C a t e g o r y
D 3 0 0
R 3 0 0
D 3 0 0
R 3 0 0
D 3 0 0
R 3 0 0
E 1 5 0
D 3 0 0
D 3 0 0
R 3 0 0
D 3 0 0
R 3 0 0
NUT
ST AR WAS HER
DIAG 5
M20 x 1.5
VA
Ma ke
CABLE GLAND / CONDUIT ADAPTOR
DIAG 4
(EXT ERIOR )
BON DED S EAL
EARTHING A SSY
FIBRE WASHER
ENCLOSURE
ADAPTOR
‘A’ ADAPTOR
Br ea k
SC REW
Loading...