Delta 600VA, 1500VA, 1000VA Installation And Operation Manual

600VA
1
2
3
Delta UPS – Agilon Family
VX Series, Line-interactive
600-1500 VA
Installation & Operation Quick Guide
ENGLISH
Package Inspection
1
No. Item No. Item
1
2
3
Operation
3
LED Indicator (Only For 600VA Model)
LCD Touch Panel (Only For 1000VA/ 1500VA Model)
ON/ OFF Button
Output Socket
4
AC Input
5
Fuse
6
USB Port
Cooling Fan
7
(Only For 1500VA Model)
LED Indicator
4
LED Alarm UPS Status
ON OFF
ON Sounds all the time UPS fault.
Flashing
Flashing Sounds every second Low battery.
(Only For 600VA Model)
The main AC power is normal and the UPS runs normally.
Sounds every
10 seconds
Power failure occurs and the UPS runs in battery mode.
No. Item Q'ty
1 UPS 1 PC
2 Quick Guide 1 PC
3 USB Cable 1 PC
4 Output Power Cord (10A) 1 PC
Remove the UPS from its package and inspect it for damage that may have occurred during shipping. If any damage is discovered, re-pack the unit and return it to the place of purchase.
Front Panel & Rear Panel
2
(Front Panel) (Rear Panel)
1
2
1000VA
(Front Panel) (Rear Panel)
1
2
6
4
5
3
Connect to Utility Power
yy
Connect the AC power cord to the utility power. Then, the UPS will start to charge its inside battery (batteries). For best result, charge the battery (batteries) for 6 hours prior to initial use. It is not recommended to connect the UPS’s AC power cord to any generator.
Plug in Equipment
yy
Plug your equipment to the Output Socket on the rear panel of the UPS.
WARNING:
1. Make sure that the UPS is powered on to protect all important devices from data loss during power failure.
2. NEVER connect a laser printer or scanner to the Output Socket of the UPS. The equipment may draw significant power to overload the UPS.
Connect to USB Port and Install Software
yy
Connect one end of the supplied USB cable to your PC and the other to the USB port located at the rear of the UPS. Download the latest version of ViewPower software (http://www.deltapowersolutions.com/en/mcis/600va-
3
6
4
5
1500va-single-phase-ups-vx-series-software-download.php) to your hard drive. Follow on-screen instructions to complete the software installation.
Turn On/ Off the UPS
yy
When the UPS is OFF, press the ON/ OFF Button to turn on the UPS and the LED/ LCD will be on. When the UPS is ON, press the ON/ OFF Button to turn off the UPS and the LED/ LCD will shut off.
Fuse Replacement
yy
When the UPS always runs in battery mode, it might be because the fuse is damaged. If yes, please follow the following procedures to replace the fuse.
Remove the fuse cover from the rear panel.
(1500VA)
Original Fuse (Provided)
OFF OFF The UPS is off.
LCD Display
5
Operation Display:
yy
UPS Mode LCD Touch Panel Description
UPS Power On
AC Mode
When AVR is functioning,
second.
Overload In AC Mode
Battery Mode
When battery level is low,
(Only For 1000VA/ 1500VA Model)
When the UPS is powered on, it will enter this mode for 4 seconds.
LCD information will be displayed in the following order when the LCD is touched.
1. Output voltage
icon will ash every
icon will ash.
icon will ash.
2. Input voltage
3. Load level
4. Battery capacity
When overload occurs, alarm will beep every 0.5 second.
Alarm will beep every 10 seconds and LCD information will be displayed in the following order when the LCD is t ouched.
1. Output voltage
2. Input voltage
3. Load level
4. Battery capacity
1500VA
1
(Front Panel) (Rear Panel)
www.deltapowersolutions.com
Overload In Battery
2
7
6
Replace the original fuse with the provided backup fuse .
(Fuse Cover)
1
(Pull)
Backup Fuse (Provided)
2
Mode
NOTE:
If backlight shuts off, you can activate it by touching the screen.
icon will ash.
Continue to the Next Page
3
4 5
1
Replace the fuse cover back to the rear panel.
(Take Out) (Install)
2
When overload occurs, alarm will beep every 0.5 second.

Fault Code Table:
yy
Fault Condition LCD Touch Panel Solutions
Output Short Circuited
Overload Fault
Over Charge Fault
Battery Too Low Fault
Battery Mode Output High Fault
Over Temperature
If any fault alarm occurs, please call for service immediately.
Safety Caution
6
SAVE THESE INSTRUCTIONS-This quick guide contains important instructions that should be followed during installation and maintenance of the UPS and battery (batteries).
The UPS utilizes voltage that may be hazardous. Do not attempt to dis-
yy
assemble the unit. The unit contains no user replaceable parts. Only fac­tory service personnel may perform repairs.
This pluggable type A equipment with battery (batteries) already installed
yy
by the supplier is operator installable and may be operated by laymen.
The mains socket outlet that supplies the UPS shall be installed near the
yy
UPS and shall be easily accessible.
During the installation of this equipment it should be assured that the
yy
sum of the leakage current of the UPS and the connected loads does not exceed 3.5mA.
Connection to any other type of receptacle other than a two-pole, three-
yy
wire grounded receptacle may result in shock hazard as well as violate local electrical codes.
In the event of an emergency, press the ON/ OFF Button and disconnect
yy
the power cord from the AC power supply to properly disable the UPS.
Do not allow any liquid or any foreign object to enter the UPS. Do not
yy
place beverages or any other liquid-containing vessels on or near the unit.
The unit is intended for installation in a controlled environment (tempera-
yy
ture controlled, indoor area free of conductive contaminants). Avoid in­stalling the UPS in any location where there is standing or running water, or excessive humidity.
Do not plug the UPS input into its own output.
yy
Do not attach a power strip or surge suppressor to the UPS.
yy
Do not attach non-computer-related items, such as medical equipment,
yy
life-support equipment, microwave ovens, or vacuum cleaners to the UPS.
Do not dispose of battery (batteries) in a re as they may explode.
yy
Disconnect short-circuited loads and restart the UPS again.
Disconnect all output loads and restart the UPS again.
Call for service immediately.
Please replace the battery (batteries).
Call for service immediately.
1. Turn off the UPS and wait for cooling.
2. Or remove excessive loads and wait for cooling.
www.deltapowersolutions.com
A battery can present a risk of electrical shock and high short circuit cur-
yy
rent. The following precautions should be observed when working on bat­teries:
1. Remove watches, rings, or other metal objects from the hands.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of battery (batteries).
5. Disconnect charging source prior to connecting or disconnecting
the terminals of battery (batteries).
Internal battery voltage is 12Vdc. Battery type is sealed, lead-acid, 6-cell
yy
battery.
Servicing of batteries should be performed or supervised by personnel
yy
knowledgeable of batteries and the required precautions. Keep unauthor­ized personnel away from batteries.
When replacing battery (batteries), replace with the same number and
yy
type of sealed lead-acid battery (batteries).
Do not open or mutilate the battery or batteries. Release electrolyte is
yy
harmful to the skin and eyes. It may be toxic.
Attention! Hazardous through electric shock. Even disconnection of this
yy
unit from the mains, hazardous voltage still may be accessible through supply from the battery (batteries). The battery supply should be therefore disconnected in the plus and minus pole at the connectors of the battery (batteries) when maintenance or service work inside the UPS is neces­sary.
To reduce the risk of overheating the UPS, do not cover the UPS’s cooling
yy
vents and avoid exposing the unit to direct sunlight or installing the unit near heat emitting appliances such as heaters or furnaces.
Unplug the UPS prior to cleaning and do not use liquid or spray detergent.
yy
Troubleshooting
7
Problem Possible Cause Solutions
LED doesn’t illuminate or nothing is displayed on the LCD panel.
The UPS always runs in battery mode.
The UPS continuously beeps.
Backup time is too short.
If any abnormal situations occur that are not listed above, please call for service immediately.
The UPS is not on.
Battery voltage is too low.
Battery fault. Replace the battery (batteries).
The power cord becomes loose.
The fuse is damaged.
Please check the Fault Code Table for the details.
Battery voltage is too low.
Overload.
Battery defect. Replace the battery (batteries).
Press the ON/ OFF Button again to turn on the UPS.
Charge the battery (batteries) at least 6 hours.
Re-plug the power cord.
Replace the fuse. For how to replace the fuse, please refer to
Operation
3
Please check the Fault Code Table for the details.
Charge the battery (batteries) at least 6 hours.
Remove some unnecessary loads. Before reconnecting equipment, please verify that the load matches
the UPS capability specied in the
specs.
.
Technical Specifications
8
Model 600VA 1000VA 1500VA
Capacity 600VA/360W 1kVA/600W 1.5kVA/900W
Nominal Input Voltage
Input Voltage Range 170 ~ 280 Vac
Output Voltage 230 Vac ± 10% (Bat. mode)
Transfer Time Typical 2 ~ 6 ms
Waveform Simulated Sine Wave
Battery Type & No. 12V/7Ah x 1 12V/7Ah x 2 12V/7Ah x 2
Charging Time Typical 6 ~ 8 hours
Dimensions (D x W x H)
Net Weight (kgs) 4.2 8.2 9.7
Humidity 0 - 90% RH @ 0 - 40°C (non-condensing)
Noise Level Less than 40dB
* Specications are subject to change without notice.
Warranty
9
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship within the warranty period. If the product has any failure problem within the warranty period, Seller will repair or replace the product at its sole discretion according to the failure situation. This warranty does not apply to normal wear or to damage resulting from improper installation, operation, usage, maintenance or irresistible force (i.e.
war, re, natural disaster, etc.), and this warranty also expressly excludes
all incidental and consequential damages. Maintenance service for a fee is provided for any damage out of the warranty period. If any maintenance is required, please directly contact the supplier or Seller.
WARNING:
The individual user should take care to determine prior to use whether the environment and the load characteristic are suitable, adequate or safe for the installation and the usage of this product. The Quick Guide must be carefully followed. Seller makes no representation or warranty as to the suitability or fitness of this
product for any specic application.
Copyright © 2017 by Delta Electronics Inc. All Rights Reserved.
Quick Guide is subject to change without prior notice.
This
Ver
sion Date : 2017_08_16
279 x 101 x
142 mm
230 Vac
320 x 130 x 182 mm
Less than
45dB