11EN 11/2010 AWR-MTD2-XE
ELECTRICAL CONNECTIONS
I A
The heat pumps must be installed downstream of a main
switch (QF1, see wiring diagram), as required by the standards in force in the country where the unit is installed. Connection to the mains power supply and the connection of the
flow switch to the corresponding terminals must be performed by authorised personnel in compliance with the standards in force.
For all electrical work, refer to the electrical wiring diagrams
in this manual.
It is also recommended to check that:
- The characteristics of the mains electricity supply are adequate for the power ratings indicated in the electrical specifications below, also bearing in mind the possible use of
other equipment at the same time.
Power to the unit must be turned on only after installation work (plumbing and electrical) has been completed.
All electrical connections must be carried out by qualified personnel in accordance with legislation in force in
the country concerned
Respect instructions for connecting phase, neutral and
earth conductors..
The power line should be fitted upstream with a suitable
device to protect against short-circuits and leakage to
earth, isolating the installation from other equipment.
Voltage must be within a tolerance of ±10% of the rated
power supply voltage for the unit (for three phase units,
the unbalance between the phases must not exceed 3%).
If these parameters are not respected, contact the electricity supply company.
For electrical connections, use double insulation cable
in conformity with legislation in force in the country concerned..
A thermal overload switch and a lockable mains disconnect switch, in compliance with the CEI-EN standards (contact opening of at least 3mm), with adequate switching and residual current protection
capacity based on the electrical data table shown
below, must be installed as near as possible to the
appliance.
An efficient earth connection is obligatory.
The manufacturer cannot be held liable for any damage
caused by the failure to correctly earth the unit.
In the case of three phase units, ensure the phases
are connected correctly.
Do not use water pipes to earth the unit.
Electrical data at maximum conditions allowed (full load)
F.L.I. Maximum power input
F.L.A. Maximum current input
L.R.A. Start-up current
Maximum values for sizing the protection switches and power supply cables.
Size
Power
supply
Maximum values Fuses
(5x20T 250V)
Heater
Power consumption without heater
Total power consumption
L.R.A.
[A]
FU1 FU5 FU6
(V-Ph-Hz) P MAX [kW] I MAX [A] P MAX TOT [kW] I MAX TOT [A] F.L.I. [kW] F.L.A. [A] [A] [A] [A]
0011ms 230-1N-50 - - - - 2,82 13,5 27 1,6 4 1,25
0025ms 230-1N-50 - - - - 3,56 16,7 30 1,6 4 1,25
0031ms 230-1N-50 - - - - 5,11 23,6 45 1,6 4 1,25
0041ms 230-1N-50 - - - - 6,15 30,1 45 1,6 4 1,25
0031t 400-3N-50 - - - - 4,76 10,0 48 1,6 4 1,25
0041t 400-3N-50 - - - - 6,38 12,4 64 1,6 4 1,25
0051t 400-3N-50 - - - - 6,43 12,7 64 1,6 4 1,25
0061t 400-3N-50 - - - - 7,77 14,8 75 1,6 4 1,25
0091t 400-3N-50 - - - - 10,86 24,6 111 2 4 1,25