DeLonghi AWR-MTD2-XEH, AWR-MTD2-XE-0031, AWR-MTD2-XE-0041, AWR-MTD2-XE-0051, AWR-MTD2-XE-0061 Installation, Operation And Service Manual

...
INSTALLATION - OPERATING - SERVICE MANUAL
Reverse-cycle air/water heat pumps with domestic hot water production, axial-flow fans and water pump assembly.
EN
AWR-MTD2-XE 0011÷0091
2 AWR-MTD2-XE EN 11/2010
U I A
User
Installer
Assistance
Important
Prohibition
Danger voltage
Danger high temperatures
INDEX
U I A
The manufacturer reserves the right to modify the data in this manual without warning.
Eurovent certification program.
The following symbols are used in this publication and inside the unit:
U
I
A
General warnings 3
Waiver of liability 3
Fundamental safety rules 3
Receiving and handling the product 4
Unit identification 5
Description of standard unit 6
Dimensioned drawings 7
Installation 7
Water connections 8
Electrical connections 11
Installer connections 12
Mains power supply connections 15
Installer connections 14
General technical data 32
Operating limits 33
Pump curve 34
Checking and starting up the unit 36
Description of room controller buttons and 38 display
Operation and functions of the room controller 39
Control and operating characteristics 48
System configuration 53
Maintenance and service 59
Peak limiter alarm signals 61
Shutting down for long periods 62
Scheduled maintenance 62
Unscheduled maintenance 63
Disposal 63
List of parameters 64
Installer operations CHECKLIST 66
U I A A
UUI A
I A
I
IU
I A
A
A
I
I
IIA
A
I A
I A
I A
I A
I A
I A
A
A
A
AIU
A
A
A
A
A
A
AIU
AIU
3EN 11/2010 AWR-MTD2-XE
GENERAL WARNINGS
U I A
FUNDAMENTAL SAFETY RULES
U I A
These appliances have been designed to chill and/or
heat water and must be used in applications compatible with their performance characteristics; these appliances are designed for residential or similar applications. Incorrect installation, regulation and maintenance or improper use absolve the manufacturer from all liability, whether contractual or otherwise, for damage to people, animals or things. Only those applications specifically indicated in this list are permitted Read this manual carefully. All work must be carried out by qualified personnel in conformity with legislation in force in the country concerned.
The warranty is void if the above instructions are not respected and if the unit is started up for the first time without the presence of personnel authorised by the Company (where specified in the supply contract) who should draw up a “start-up” report.
The documents supplied with the unit must be con­signed to the owner who should keep them carefully for future consultation in the event of maintenance or service. All repair or maintenance work must be carried out by the Company’s Technical Service or qualified personnel following the instructions in this manual. The air-conditioner must under no circumstances be modified or tampered with as this may create situations of risk. Failure to observe this condition absolves the manufacturer of all liability for resulting damage.
When operating equipment involving the use of electricity and water, a number of fundamental safety rules must be observed, namely:
The unit must not be used by children or by unfit per­sons without suitable supervision. Do not touch the unit with bare feet or with wet or damp parts of the body. Never perform any cleaning operations before having disconnected the unit from the mains power supply. Do not modify safety or control devices without authori­sation and instructions from the manufacturer. Do not pull, detach or twist the electrical cables coming from the unit, even when disconnected from the mains electricity supply. Do not open doors or panels providing access to the internal parts of the unit without first ensuring that the switch QF1 is in the OFF position (see the wiring dia­gram). Do not introduce pointed objects through the air intake and outlet grills. Do not dispose of, abandon or leave within reach of children packaging materials (cardboard, staples, plastic bags, etc.) as they may represent a hazard.
Respect safety distances between the unit and other equipment or structures. Guarantee adequate space for access to the unit for maintenance and/or service opera­tions. Power supply: the cross section of the electrical cables must be adequate for the power of the unit and the pow­er supply voltage must correspond with the value indicat­ed on the respective units. All units must be earthed in conformity with legislation in force in the country con­cerned.
Terminals 6, 7, 9, 10, 11, 12, 13, 21, 22, 23, 24, may be live even after the unit is disconnected. Make sure power is not connected before proceeding. Water connections should be carried out as indicated in the instructions to guarantee correct operation of the unit. Add glycol to the water circuit if the unit is not used during the winter or the circuit is not emptied. Handle the unit with the utmost care (see weight distrib­ution table) to avoid damage.
WAIVER OF LIABILITY
This publication is the sole property of Manufacturer. Any reproduction or disclosure of such is strictly prohibited with­out the written authorisation of Manufacturer. This document has been prepared with maximum care and attention paid to the content shown. Nonetheless, Manufac- turer waives all liability deriving from the use of such docu­ment.
Read this document carefully. All work must be performed, components selected and materials used in complete accor­dance with the legislation in force in material in the country concerned, and considering the operating conditions and intended uses of the system, by qualified personnel.
U I A
4
AWR-MTD2-XE EN 11/2010
Dimensions 0011 0025 0031 0041 0051 0061 0091
Dimension L mm 970 970 970 970 970 1600 1600 Dimension P mm 525 525 525 525 525 610 610 Dimension H mm 1450 1450 1450 1600 1600 1360 1850 Gross weight Kg 165 170 175 190 200 275 360
VISUAL INSPECTION
When the items are consigned by the carrier:
- make sure that the goods delivered correspond to the description on the delivery note, comparing this against the data on the packaging label.
- make sure the packaging and the unit are intact.
If damage or missing components are noted, indicate this on the delivery note. A formal complaint should be sent via fax or registered post to the After Sales Department within eight days from the date of receipt of the items.
HANDLING PACKAGED UNITS
The unit should always be handled by qualified personnel using equipment adequate for the weight of the unit, in com­pliance with the safety standards in force (and subsequent amendments).
Lifting by forklift (1) Insert the forks under the long side of base, opening the forks as fare as possible.
Lifting by crane (2) Use slings with hooks suitable for the weight being lifted. Secure the hook to the lifting bracket fixed to the unit, use always four equal length slings, as shown in the figure, to ensure the weight is balanced.
REMOVING THE PACKAGING
The packaging must be removed by the operator using suit­able protective equipment (gloves, glasses, etc.). Take special care not to damage the unit. Observe the local standards in force as regards disposal of the packaging, using specialist collection or recycling centres.
Do not dispose of packaging materials in the environ­ment or leave them within reach of children as they may represent a hazard.
Envelope A, located in the compressor compartment, con­tains:
• instruction manual;
• warranty certificate;
• CE declaration;
• list of the main components and sub-assemblies fitted on the product
• remote room control unit A5 (must be installed)
• DHW storage water temperature probe BT8
• outside air temperature probe BT11 (must be installed)
• probe BT9 only to be installed when supplementary source is available
Make sure the components listed above are not lost or mis­placed.
The instruction manual is an integral part of the unit and should therefore be read and kept carefully.
STORING THE UNITS
The units must be stored sheltered from direct sunlight, rain, wind or sand. Avoid exposing the units to direct sunlight, as the pressure inside the refrigerant circuit may reach dangerous values and cause the activation of the safety valves, where fitted. The units cannot be stacked.
RECEIVING AND HANDLING THE PRODUCT
I A
H
P
L
Bar code
(compressor side)
A
1
2
5EN 11/2010 AWR-MTD2-XE
RECEIVING AND HANDLING THE PRODUCT
I A
HANDLING UNPACKAGED UNITS
When the packaging has been removed:
• Remove the wooden base.
• Fit the vibration damping feet (accessories).
• Handle the unit using equipment that is suitable for its weight (forklift or crane), in compliance with the safety standards in force (and subsequent amendments).
• Do not drag the unit as the feet may be damaged or break.
Hole Ø22
UNIT IDENTIFICATION
U I A
The heat pump can be identified from:
PACKAGING LABEL
Describes the product identification data
RATING PLATE
Describes the unit technical and performance specifications. Shows the serial number used to uniquely identify the unit. The serial number is also used to identify the unit’s spare parts.
If service is required, the following information must be pro­vided to the service centre: Model, serial number, year of production.
Installation and maintenance operations are much more difficult if the identification plates or anything else need­ed to clearly identify the product are tampered with, removed or missing.
NOMENCLATURE
Packaging label
Rating plate with serial number
AWR MTD2 XE 0011 m s
Power supply voltage: m = 230V/50Hz/1ph t = 400V/3N/50Hz
size
s = peak limiter
Model
6 AWR-MTD2-XE EN 11/2010
DESCRIPTION OF STANDARD UNIT
I A
These air cooled reverse-cycle chillers with axial-flow fans operate with R410A refrigerant fluid and are suitable for out­door installation. The units are CE marked, as established by the EU directives, including the latest amendments, and the corresponding approximated national legislation.
They are factory tested and on site installation is limited to water and electrical connections.
VERSIONS AVAILABLE
AWR-MTD2-XE
Reverse-cycle air/water heat pump with domestic hot water production. Built-in water pump assem­bly without electric heaters.
11
10
15
13
4
20
14
6
8 5
12
3
19
18
17
16
21
9
1
2
7
1 Electrical panel 2 NadiSystem controller 3 System plate heat exchanger 4 Low pressure switch 5 High pressure switch 6 Liquid sight glass (0041 - 0061) 7 Scroll compressor 8 Filter 9 Thermostatic valve 10 Axial-flow fan 11 Airside finned heat exchanger 12 Pump 13 Liquid recipient 14 Expansion vessel 15 Reversing valve 17 Safety valve 18 Air vent valve 19 Pressure gauge 20 Base electric heater 21 Pressure transducer
7EN 11/2010 AWR-MTD2-XE
U I A
DIMENSIONED DRAWINGS
I
600
W1
W2
W4
W3
900
D
B
C
=E
A
=
400
Dimensions 0011 0025 0031 0041 0051 0061 0091
A mm 900 900 900 900 900 1550 1550 B mm 1240 1240 1240 1390 1390 1200 1700 C mm 420 420 420 420 420 450 450 D mm 370 370 370 370 370 497 497 E mm 580 580 580 580 580 1477 1477
Weight distribution 0011 0025 0031 0041 0051 0061 0091
W1 lato rear dx kg 60 62 64 67 71 88 117 W2 lato rear sx kg 17 18 20 23 24 39 54 W3 front sx kg 17 18 18 22 22 36 51 W4 front dx kg 51 52 53 58 63 87 113 tot kg 145 150 155 170 180 250 335
INSTALLATION
I
CHOICE OF INSTALLATION SITE
Before installing the unit, agree with the customer the site where it will be installed, taking the following points into con­sideration:
• check that the support surface is adequate to support the weight of the unit;
• respect safety distances between the unit and other equip­ment or structures so that the fan air intake and outlet are not blocked in any way.
• Follow the instructions shown in the chapter on DIMEN­SIONED DRAWINGS to allow room for maintenance oper­ations.
If installing multiple units the clearances must be doubled.
POSITIONING
• Install the vibration damping feet (accessories).
• Check the unit supports and weights before positioning
• Make sure that the unit is level, adjust the height of the support feet if necessary
• Use the flexible joints supplied for the water connections
• Make sure there is easy access to the water circuit and electrical parts
• For installation, if the site is exposed to strong winds, fix the unit adequately using tie rods if necessary.
• In heating mode the unit produces a significant quantity of condensate, which must be suitably drained. Condensate drainage must not cause problems to objects or people.
• If the outside air temperature is less than 0°C, the conden­sate may freeze; in these case fit a frost protection heater on the drain line.
• Consider the maximum height that may be reached by snow to avoid blocking the air intake or outlet (outdoor installation)
• Unit for outdoor installation
For correct operation of the unit, avoid the following:
• obstacles to air flow, such as leaves that may block the heat exchange coil
• strong winds that stop or reinforce air flow
• sources of heat too close to the unit
• air recirculation between intake and outlet
• poor air change
• stratification of air
8 AWR-MTD2-XE EN 11/2010
WATER CONNECTIONS
I A
Warnings
- The choice and installation of components is the responsi­bility of the installer who should follow good working prac­tice and current legislation.
Before connecting the pipes make sure that these:
- do not contain stones, sand, rust, scale or any foreign objects that may damage the system.
- wash the system with clean water
Water connection dimensions
Components
The following components should be installed for correct installation of the unit:
1. Two pressure gauges with a suitable scale (inlet and out­let);
2. Two vibration damper joints (inlet and outlet).
3. Shut-off valves at the inlet and outlet.
4. A flow switch at the unit outlet on the system circuit (compulsory). The flow switch must be calibrated by the installer to a value equal to 70% of rated flow.
5. Two thermometers (inlet and outlet);
6. An inlet filter (compulsory) as close as possible to the unit and positioned to allow easy access for scheduled maintenance (both on the system circuit and domestic hot water circuit).
7. All the pipes must be insulated with suitable material to prevent the formation of condensate and heat loss. The insulating material must be a vapour barrier. Make sure that the control and shut off devices protrude from the insulation.
8. At the lowest points in the system, install drain valves for easy emptying.
9. At the highest points in the system, install automatic or manual air vent valves.
10. The unit is fitted as standard with an expansion vessel; make sure this is correctly sized for the water content of the system and the expected operating temperature, oth­erwise install an additional expansion vessel.
D
100
B
C
528.5
563.5
A
A = C
D
EB
85
35
328
85
0011-0051
SAFETY VALVE DISCHARGE
UNIT VENT
WATER INLET
WATER OUTLET
SYSTEM FILL G1/2
0061-0091
SYSTEM FILL G1/2
WATER OUTLET
WATER INLET
UNIT VENT
SAFETY VALVE DISCHARGE
OPENING FOR CONDENSATE DRAIN CONNECTION
Dimensions 0011 0025 0031 0041 0051 0061 0091
A mm 61,5 61,5 61,5 61,5 61,5 90,5 90,5 B mm 617 617 617 717,5 717,5 575 770 C mm 57 57 57 57 57 90,5 90,5 D mm 454,5 454,5 454,5 549,5 549,5 120 120 E mm - - - - - 560 551 Water in fittings Ø 1" 1" 1" 1" 1/4 1" 1/4 1" 1/4 1" 1/4 Water out fittings Ø 1" 1" 1" 1" 1/4 1" 1/4 1" 1/4 1" 1/4
9EN 11/2010 AWR-MTD2-XE
11. The connection piping should be supported in such a way as to avoid it weighing on the unit.
Failure to install the flow switches will mean the heat exchangers are not protected in the event of no flow of liquid. The Manufacturer cannot be held liable for any damage to the unit and/or the system following the fail­ure to install these devices or the filter.
The correct operation of the components that help ensure the safety of the appliance and the system should be checked regularly:
• make sure the filters are clean
• check operation of the flow switches installed.
• Make sure that the frost protection heaters on the heat exchanger are powered when the unit is OFF
Water flow to the heat pump must conform to the values shown in the section on “General Technical Data”. The flow of water must be maintained constant during oper­ation. The water content of the unit must be such as to avoid dis­turbing operation of the refrigerant circuits.
Risk of freezing
The unit must be prevented from freezing at outside air tem­peratures around 0°C. The following are recommended:
• use suitable percentages of antifreeze (see “Ethylene gly­col solutions”)
• protect the piping with heating sheaths,
• empty the system, making sure no water remains at the lowest points in the circuit or there are closed valves where water may stagnate.
It is recommended to use non-toxic food grade antifreeze, compliant with the standards in force in the countries where the unit is used, if domestic hot water production is also fea­tured. The antifreeze used must be corrosion inhibited and com­patible with the water circuit components.
Ethylene glycol solutions
Water and ethylene glycol solutions used as a heat carrier in the place of water reduce the performance of the unit. Multiply the performance figures by the values given in the following table.
The heat pumps must be fitted with a filling/top-up sys­tem connected to the return line and a drain valve in the lowest part of the system. Systems containing antifreeze or covered by specific legislation must be fitted with low-loss headers.
cPf
cQ
cdp
0 1 1 1
12%
0,985
1,02 1,07
20% 0,98 1,04 1,11
28% 0,974 1,075
1,18
35% 0,97
1,11
1,22
40%
0,965
1,14 1,24
0 -5 -10 -15 -20 -25
Freezing point (°C)
Percentage of ethylene glycol by weight
cPf: cooling capacity correction factor cQ: flow rate correction factor cdp: pressure drop correction factor
Fouling factors
The performance data given refer to conditions with clean evaporator plates (fouling factor = 1). For different fouling factors, multiply the figures in the perfor­mance tables by the coefficient given in the following table.
f1: capacity correction factor fk1: compressor power input correction factor fx1: total power input correction factor
4,4 x 10
-5
0,86 x 10
-4
1,72 x10
-4
­0,96 0,93
­0,99 0,98
­0,99 0,98
Fouling factors
(m2°C/W) f1
Evaporator
fk1 fx1
Water quality
The water used in the system and domestic hot water cir­cuits must comply with the following characteristics:
PH 6-8 Electrical conductivity less than 200 mV/cm (25°C) Chlorine ions less than 50 ppm Sulphuric acid ions less than 50 ppm Total iron less than 0.3 ppm Alkalinity M less than 50 ppm Total hardness less than 50 ppm Sulphur ions none Ammonia ions none Silicon ions less than 30 ppm
WATER CONNECTIONS
I A
10 AWR-MTD2-XE EN 11/2010
WATER CONNECTIONS
I A
Water content in the system
Size 0011 0025 0031 0041 0051 0061 0091
Minimum water content l 24 31,5 40 46 65 74 110
Expansion vessel size
Size 0011 0025 0031 0041 0051 0061 0091
Expansion vessel l 2222244
Safety valve calibration
Size 0011 0025 0031 0041 0051 0061 0091
Safety valve bars 6666666
Factory connections Installer connections
1
2
12
12
13
14
14
UTILITY RETURN
UTILITY OUTLET
9
8
7
16
3
11
T
6
15
16
T
6
F
5
4
2
10
1
1
9
Utility water circuit connection diagram
1 Pressure gauge 2 Vibration damper joint 3 Shut off valve 4 Calibrating valve
5 Flow switch 6 Thermometer 7 Pump 8 Safety valve
9 Expansion vessel 10 Wire mesh filter 11 Unit fill/drain valve 12 Temperature sensor
13 Differential pressure switch 14 Drain / chemical washing valve 15 System vent
Condensate drain
In heating mode the unit produces a significant quantity of condensate, which must be suitably drained. Proceed as follows:
• Connect the unit condensate drain
• Make sure the drain hose has a incline of at least 2 cm/m, without obstructions or choking.
• Connect the condensate drain hose to a rainwater drain. Do not connect to the sewage system as odours may be sucked up if the water in the drain trap evaporates.
• After connecting, check correct drainage of the conden­sate by pouring water into the pan.
• If necessary, suitably insulate the condensate drain hose.
• Condensate drainage must not cause problems to objects or people.
• If the outside air temperature is less than 0°C, the conden­sate may freeze.
The unit comes with frost protection for the condensate col­lection basin inside the unit. Use hot wires on the condensate drain hose downstream of the unit to protect against frost.
FILLING THE SYSTEM
- Before starting to fill, place the unit mains switch QF1 in the OFF position.
- Before filling, check that the system drain valve is closed.
- Open all system and terminal air vents.
- Open system shut off valves.
- Start filling by slowly opening the system water fill valve out­side the unit.
- When water begins to leak out of the terminal air vent valves,
close them and continue filling until the pressure gauge indi­cates a pressure of 1.5 bar.
The system must be filled to a pressure of between 1 and 2 bars. It is recommended that this operation be repeated after the unit has been operating for a number of hours. The pressure in the system should be checked regularly and if it drops below 1 bar, the water content should be topped-up. Check the tightness of the joints.
ON
OFF
11EN 11/2010 AWR-MTD2-XE
ELECTRICAL CONNECTIONS
I A
The heat pumps must be installed downstream of a main switch (QF1, see wiring diagram), as required by the stan­dards in force in the country where the unit is installed. Con­nection to the mains power supply and the connection of the flow switch to the corresponding terminals must be per­formed by authorised personnel in compliance with the stan­dards in force.
For all electrical work, refer to the electrical wiring diagrams in this manual. It is also recommended to check that:
- The characteristics of the mains electricity supply are ade­quate for the power ratings indicated in the electrical spec­ifications below, also bearing in mind the possible use of other equipment at the same time.
Power to the unit must be turned on only after installa­tion work (plumbing and electrical) has been completed. All electrical connections must be carried out by quali­fied personnel in accordance with legislation in force in the country concerned Respect instructions for connecting phase, neutral and earth conductors.. The power line should be fitted upstream with a suitable device to protect against short-circuits and leakage to earth, isolating the installation from other equipment.
Voltage must be within a tolerance of ±10% of the rated power supply voltage for the unit (for three phase units, the unbalance between the phases must not exceed 3%). If these parameters are not respected, contact the elec­tricity supply company. For electrical connections, use double insulation cable in conformity with legislation in force in the country con­cerned..
A thermal overload switch and a lockable mains dis­connect switch, in compliance with the CEI-EN stan­dards (contact opening of at least 3mm), with ade­quate switching and residual current protection capacity based on the electrical data table shown below, must be installed as near as possible to the appliance.
An efficient earth connection is obligatory. The manufacturer cannot be held liable for any damage caused by the failure to correctly earth the unit. In the case of three phase units, ensure the phases are connected correctly.
Do not use water pipes to earth the unit.
Electrical data at maximum conditions allowed (full load)
F.L.I. Maximum power input F.L.A. Maximum current input L.R.A. Start-up current
Maximum values for sizing the protection switches and power supply cables.
Size
Power
supply
Maximum values Fuses
(5x20T 250V)
Heater
Power consumption without heater
Total power consumption
L.R.A.
[A]
FU1 FU5 FU6
(V-Ph-Hz) P MAX [kW] I MAX [A] P MAX TOT [kW] I MAX TOT [A] F.L.I. [kW] F.L.A. [A] [A] [A] [A]
0011ms 230-1N-50 - - - - 2,82 13,5 27 1,6 4 1,25 0025ms 230-1N-50 - - - - 3,56 16,7 30 1,6 4 1,25 0031ms 230-1N-50 - - - - 5,11 23,6 45 1,6 4 1,25 0041ms 230-1N-50 - - - - 6,15 30,1 45 1,6 4 1,25
0031t 400-3N-50 - - - - 4,76 10,0 48 1,6 4 1,25 0041t 400-3N-50 - - - - 6,38 12,4 64 1,6 4 1,25 0051t 400-3N-50 - - - - 6,43 12,7 64 1,6 4 1,25 0061t 400-3N-50 - - - - 7,77 14,8 75 1,6 4 1,25 0091t 400-3N-50 - - - - 10,86 24,6 111 2 4 1,25
12
AWR-MTD2-XE EN 11/2010
INSTALLER CONNECTIONS
I A
PE
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55
C90051683E_00
A4
A2
FU3
C1
A1
C2
C3
A3
QS1
QM1
KA1
KA1
KA6
KA7
KA15
FU1
FU5
FU6
A7
TC1
INSTALLER TERMINAL BLOCK
Power supply
13EN 11/2010 AWR-MTD2-XE
MAINS POWER SUPPLY CONNECTIONS
I A
AWR MTD2 XE heat pump terminal block
Installer connections
UVWN
400V - 3N ~50Hz
U N
PE
230V - 1Ph - 50Hz
QS1
QS1
• Before connecting the unit to the power supply, makes sure that switch QF1 is open, suitably padlocked and marked.
• Remove the inspection panel by unscrewing the screws.
• Use cable gland A for the main electrical power cable and cable gland B for other external cables to be connected by the installer.
• Identify the terminals used for electrical connections on the layout drawing shown in this manual.
• Make the connections as shown in the wiring diagram pro­vided in this manual.
• The figures show the power supply connection terminals for 230V and 400V.
• Replace the covers on the electrical panel and the closing panel.
• Make sure that all the covers removed to make the electri­cal connections have been replaced before powering up the unit.
• Position the main switch QF1 (outside the unit) in the “ON” position.
• Once the remote terminal has been switched on, “OFF” and “init” are displayed.
• The room unit is ready to use after a few seconds, when “init” is shown and the clock is displayed
A
B
* Compliant with standards in force in the place where the unit is installed
Power supply 230V 400V Number of power wires 2 + PE 4 + PE Power wire size* 6 mmq 6 mmq
14 AWR-MTD2-XE EN 11/2010
Outside air probe (BT11) connection
The outside air probe allows the system water temperature set point to be compensated during heating or cooling opera­tion.
Installation instructions
The outside air probe must be installed:
• outside of the home
• not in direct sunlight, away from flue gas discharges, air outlets, or doors and windows.
• on a perimeter wall facing north/north-west
• at a minimum height of 2.5 metres above the ground or at most half way up the house.
H
H
2
/
1
N
N-W
m 5,2nim
Mounting method:
• Open the cover of the sensor.
• Attach a probe to the wall and the correct position as described above.
• For the electrical connections see “Connection diagram”.
• Re-place the cover of the sensor.
INSTALLER CONNECTIONS
I A
12
45 46
BT11
TECHNICAL DATA
Sensing element NTC 10Kohm ± 1% (25°C) Degree of protection IP65 Perm. ambient / carriage temperatur
e -50°C...+100°C Measuring range -50°C...+100°C Materials PA 15% GK, Colour RAL 9010
15EN 11/2010 AWR-MTD2-XE
A5 room controller connection
Installation instructions
The room controller must be installed in the best reference position for temperature control. Position the room controller as follows:
• around 1.5 metres from the floor, in a part of the room that allows the sensor to accurately measure the room temper­ature;
• away from cold air flows, sunlight or other sources of heat.
• leave enough space above the room controller to allow assembly and removal where necessary.
• If the room controller is removed from its base, it discon­nects from the power supply and consequently is no longer operating.
min. 10 cm
Installation procedure
Assembly
• Separate the front from the rear of the terminal using a screwdriver r (1)
• Disconnect the 4-pin connector from the front part (2)
• Remove the cover A1, unscrewing the screw A2 (3).
• Fix the controller support to the wall using the holes A3 (4). Support hole size and spacing in figure (5).
• Make the electrical connections as shown in the figure (6), also see the wiring diagram.
A2
A1
A3
A3
E
131
83,5
86
51
52 53 54 55
TxRx -
TxRx +
GND
24 VAC
GND
A5 room controller terminal block Installer terminal block
Number of wires 5 shielded Power supply wire size 0.5 mm
2
Maximum distance 500 m
1
3
6
4 5
2
INSTALLER CONNECTIONS
I A
16 AWR-MTD2-XE EN 11/2010
INSTALLER CONNECTIONS
I A
YV5 3-way valve for domestic hot water production
The 3-way valve installed outside of the unit deviates the flow of hot water produced by the unit to the DHW storage tank. During domestic hot water production, the cooling/heating demand is not satisfied. Wire the three-way valve supplied as an accessory by Man­ufacturer following the instructions shown in the figure.
The valve is also fitted with a limit switch. The limit switch contact is either closed or open based on the position of the valve. Limit switch (red and green wires): Auxiliary contact closed = Valve open Auxiliary contact open = Valve closed
If not supplied by Manufacturer, the 3-way valve for domes­tic hot water production should have the following character­istics:
• Voltage 230V AC, 50/60 Hz
• Opening/closing time 10s.
• Delta P 500 kPa
• Fluid temperature 0°C to 90°C Use three-way valves with pressure drop below 20 kPa. For further details see the chapter “Operating characteris­tics”.
If three-way valves with a travel time greater than 10 sec­onds are used, modify the setting of parameter 0231
• Close the cover A1 and secure it with the screw A2
• Plug in the 4-pin connector, figure (7)
• Replace the terminal, starting with the lower tabs, applying a hinge movement. Make sure that the electrical wires are inside to ensure correct fastening (click on).
• Dimensions of A5 room controller figure (8).
68
8 28
143
Wall
7
8
9 12 13
YV5
Yellow/Green
Red
Blue Green
Black
Brown
Auxiliary contact
INSTALLER CONNECTIONS
I A
43 44
6 7
230V / 400V
BT9
N
1
Description
Three-way valve travel time for domestic hot water production
Menu
Mn02
Parameter
no.
0231
Default
12
Value to be set
Set the travel time
for valves not supplied by the heat pump manufacturer
UOM
sec.
Optional connection
KM2 System outlet electric heater
An electric heater installed at the outlet can be activated as a supplementary heater for the system.
Solution 1
System with heat pump and electric heater with storage tank. Position probe BT9 in the storage tank.
17EN 11/2010 AWR-MTD2-XE
INSTALLER CONNECTIONS
I A
B) SUPPLEMENTARY: the electric heater operates in sup-
plementary heating mode, together with the compressor, to satisfy the heating load.
Supplementary heating for low outside air temperature
The electric heater is enabled only when the outside tem­perature is less than the value of parameter 0304, figure 3. To enable supplementary heating for low outside air temper­ature set parameter 0303 = 1 and 010G = 0
Electric heater operation reflects the trend in water outlet temperature, as shown on the graph in figure 4.
Description
Activation electrical heater 0 = Electrical Heater not enabled 1 = Electrical Heater enabled Type of outlet electric heater oper­ation 0 = Supplementary 1 = Replacement Enable boiler 0 = Boiler not enabled 1 = Boiler enabled Activation with low outside air temperature 0 = Function not enabled 1 = Function enabled Outside air temperature to enable elec­tric heater Minimum outside air temperature for heat pump operation (make sure the value set is the same as shown in the table) Electric heater delay time (allows the heat pump to reach steady operation and thus avoid activating the heater when not needed) Integration time to activate outlet elec­tric heaters
Menu
Mn01
Mn03
Mn03
Mn03
Mn03
Mn03
Mn06
Mn06
Parameter
no
0300
010G
0301
0303
0304
0311
0616
0617
Value to be
set
1*
0
0*
1
Example
-5°C
-15
60
600
UOM
°C
°C
min.
°C*sec
Outlet electric heater control
A) REPLACEMENT: The electric heater is enabled when
the outside temperature is less than the value of parameter 0304 and the compressor is off, figure 3. To enable heater activation in REPLACEMENT mode set parameter 0303 = 1 and 010G = 1.
Electric heater operation reflects the trend in water outlet temperature, as shown on the graph in figure 4.
If the heat pump shuts down due to an alarm, the electric heater is activated automatically regardless of the outside air temperature. In REPLACEMENT mode the electric heater activation delay time is ignored, and the device is activated immediate­ly if necessary.
Outlet electric heater operating parameters in REPLACE­MENT mode
Outlet electric heater operating parameters in SUPPLE­MENTARY mode for OUTSIDE AIR TEMP.
Description
Activation electrical heater 0 = Electrical Heater not enabled
1 = Electrical Heater enabled Type of outlet electric heater oper­ation 0 = Supplementary 1 = Replacement Enable boiler 0 = Boiler not enabled 1 = Boiler enabled Activation with low outside air temperature 0 = Function not enabled 1 = Function enabled Outside air temperature to enable elec­tric heater Integration time to activate outlet elec­tric heaters
Menu
Mn03
Mn01
Mn03
Mn03
Mn03
Mn06
Parameter
no
0300
010G
0301
0303
0304
0617
Value to be
set
1*
1
0*
1
Example
-5°C 600
UOM
°C
°C*sec
43 446 7
230V / 400V
BT9
N
Solution 2
System with heat pump and outlet electric heater WITHOUT storage tank. Position probe BT9 on the system outlet pipe.
2
Set the parameters following the sequence described in the table
Set the parameters following the sequence described in the table
18 AWR-MTD2-XE EN 11/2010
INSTALLER CONNECTIONS
I A
Supplementary heating always enabled
Supplementary heating with the electric heater is enabled for all outside air temperatures. To enable heating at all times set parameter 0303 = 0 and 010G = 0
Electric heater operation reflects the trend in water outlet temperature, as shown on the graph in figure 4.
Once the heater is enabled, supplementary heating is activated when the integra­tion time set for parameter 0617 is reached and the delay time 0616 has elapsed. The delay time is ignored when the unit is first started.
Example: Value 0617 = 600°C*sec Outlet temperature set point= 50°C Actual temperature = 40°C
(50 – 40) x 60 sec = 600°Csec. ----> Electric heater ON
Low values of 0617 mean frequent activation of the heater. Too high values of 0617 mean long delays in activating the heater
Description
Activation electrical heater 0 = Electrical Heater not enabled 1 = Electrical Heater enabled Type of outlet electric heater oper­ation 0 = Supplementary 1 = Replacement Enable boiler 0 = Boiler not enabled 1 = Boiler enabled Activation with low outside air temperature 0 = Function not enabled 1 = Function enabled Minimum outside air temperature for heat pump operation (make sure the value set is the same as shown in the table) Electric heater delay time (allows the heat pump to reach steady operation and thus avoid activating the heater when not needed) Integration time to activate outlet electric heaters
Menu
Mn03
Mn01
Mn03
Mn03
Mn03
Mn06
Mn06
Parameter
no
0300
010G
0301
0303
0311
0616
0617
Value to be
set
1*
0
0*
0
-15
60
600
UOM
°C
min.
°C*sec
3 4
Outlet electric heater operating parameters in SUPPLE­MENTARY mode when always ENABLED
Outside air T
OFF
Enabled
Outlet heater
0304 Outside temperature to enable outlet heaters
3°C
OFF
ON
ON
OFF
Compressor
Heater
Electric heater activation delay time 0616
Integration time 0617
System water control set point
Actual water temperature
System HP control hysteresis
Set the parameters following the sequence described in the table
19EN 11/2010 AWR-MTD2-XE
INSTALLER CONNECTIONS
U I A
Boiler control
A) REPLACEMENT: the boiler is only enabled if the outside
air temperature is less than the value of parameter 0307 and the compressor is off, figure 3. To enable boiler activation in REPLACEMENT mode set parameter 0306=1 and 010H = 1
Boiler operation reflects the trend in water temperature, as shown on the graph in figure 4.
If the heat pump shuts down due to an alarm the boiler is activated automatically regardless of the outside air temper­ature. In REPLACEMENT mode the activation delay time is ignored, and the boiler is activated immediately if necessary.
Description
Enable electric heater 0 = Heater not enabled 1 = Heater enabled Activation Boiler 0 = Boiler not enabled 1 = Boiler enabled Type of boiler operation 0 = Supplementary 1 = Replacemen Activation with low outside air temperature 0 = Function not enabled 1 = Function enabled Outside air temperature to enable boiler Integration time to activate boiler
Menu
Mn03
Mn03
Mn01
Mn03
Mn03
Mn06
Parameter
no.
0300
0301
010H
0306
0307
0619
Value to be
set
0
1
1
1
Example
-5°C 600
UOM
°C
°C*sec
B) SUPPLEMENTARY: the boiler operates in supplemen­tary heating mode, together with the compressor, to satisfy the heating load.
Supplementary heating for low outside air temperature The boiler is enabled only when the outside air temperature is less than the value of parameter 0307, figure 3. To enable the supplementary heating for outside air temper­ature set parameter 0306 = 1 and 010H = 0
Boiler operation reflects the trend in water temperature, as shown on the graph in figure 4.
Description
Enable electric heater 0 = Heater not enabled 1 = Heater enabled Activation Boiler 0 = Boiler not enabled 1 = Boiler enabled Type of boiler operation 0 = Supplementary 1 = Replacemen Activation with low outside air temperature 0 = Function not enabled 1 = Function enabled Outside air temperature to enable boiler Minimum outside air temperature for heat pump operation (make sure the value set is the same as shown in the table) Boiler activation delay time (allows the heat pump to reach steady operation and thus avoid activat­ing the boiler when not needed) Integration time to activate boiler
Menu
Mn03
Mn03
Mn01
Mn03
Mn03
Mn03
Mn06
Mn06
Parameter
no.
0300
0301
010H
0306
0307
0311
0618
0619
Value to be
set
0
1
0
1
Example
-5°C
-15
60
600
UOM
°C
°C
min.
°C*sec
Boiler operating parameters in REPLACEMENT mode
Boiler operating parameters in SUPPLEMENTARY mode for outside temperature
Boiler
43 44
BT9
67
BT9
Boiler
43 4467
1
2
Set the parameters following the sequence described in the table
Set the parameters following the sequence described in the table
KM2 Boiler
A boiler can be used as a supplementary or replacement heat source for the system.
Solution 1
System with heat pump and boiler with storage tank.
Solution 2
System with heat pump and boiler without storage tank.
20 AWR-MTD2-XE EN 11/2010
INSTALLER CONNECTIONS
U I A
Supplementary heating always enabled
Supplementary heating by boiler is enabled for all outside air temperatures. To enable heating at all times set parameter 0306 = 0 and 010H = 0
Boiler operation reflects the trend in water temperature, as shown on the graph in figure 4.
Description
Enable electric heater 0 = Heater not enabled 1 = Heater enabled Activation Boiler 0 = Boiler not enabled 1 = Boiler enabled Type of boiler operation 0 = Supplementary 1 = Replacement Activation with low outside air temperature 0 = Function not enabled 1 = Function enabled Outside air temperature to enable boiler Minimum outside air temperature for heat pump operation (make sure the value set is the same as shown in the table) Boiler activation delay time (allows the heat pump to reach steady operation and thus avoid activat­ing the boiler when not needed) Integration time to activate boiler
Menu
Mn03
Mn03
Mn01
Mn03
Mn03
Mn03
Mn06
Mn06
Parameter
no.
0300
0301
010H
0306
0307
0311
0618
0619
Value to be
set
0
1
0
0
Example
-5°C
-15
60
600
UOM
°C
°C
min.
°C*sec
3 4
Boiler operating parameters in SUPPLEMENTARY mode when always ENABLED
Once the boiler has been enabled, supplementary heating is activated when the integration time set for parameter 0619 is reached and the delay time 0618 has elapsed. The delay time is ignored when the unit is first started.
Example: Value 0619 = 600°C*sec Outlet temperature set point= 50°C Actual temperature = 40°C
(50 – 40) x 60 sec = 600°Csec. ----> Boiler ON
Low values of 0619 mean frequent activation of the boiler. Too high values of 0619 mean long delays in activating the boiler
Outside air T
OFF
Enabled
Boiler
0304 Outside temperature to enable boiler
3°C
OFF
ON
ON
OFF
Compressor
Boiler
Boiler activation delay time 0618
Integration time 0619
System outlet temperature set point
Actual water temperature
System HP control hysteresis
Set the parameters following the sequence described in the table
ON
OFF
ON
OFF
Heater
Compressor
0023
0209
t
21EN 11/2010 AWR-MTD2-XE
INSTALLER CONNECTIONS
U I A
Description
Domestic hot water heating 0 = heat pump only 1 = electric heater only 2 = heat pump + electric heater Legionella prevention function with: 0 = heat pump only 1 = electric heater only 2 = heat pump + electric heater Domestic hot water temperature set point for Legionella prevention Legionella prevention cycle day MONDAY (0=no; 1=yes) Legionella prevention cycle day TUESDAY (0=no; 1=yes) Legionella prevention cycle day WEDNESDAY (0=no; 1=yes) Legionella prevention cycle day THURSDAY (0=no; 1=yes) Legionella prevention cycle day FRIDAY (0=no; 1=yes) Legionella prevention cycle day SATURDAY (0=no; 1=yes) Legionella prevention cycle day SUNDAY (0=no; 1=yes) Legionella prevention cycle time
Enable Legionella prevention function 0 = Not enabled 1 = Enabled Maximum Legionella prevention function duration
Menu
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Parameter
no.
0202
0223
0211
0213
0214
0215
0216
0218
0219
0220
0221
0222
0225
Value to be
set
2
1
Example
65°C
0
0
Example 1
0
0
0
0
02
1
20
UOM
°C
h
min.
KM4 DHW storage electric heater
An electric heater can be managed for heating the DHW storage.
DHW storage electric heater control
The electric heater is activated to reach a temperature value that the heat pump on its own is not able to reach.
Example: Domestic hot water temperature produced with heat pump 0023 = 55°C Domestic hot water temperature produced with electric heater 0209 = 65°C. The electric heater works so as to increase the DHW stor­age temperature from 55°C to 65°C, figure 1
Legionella prevention function with electric heater
The Legionella prevention function ensures the elimination of the Legionella bacteria that reside in domestic water stor­age tanks. The temperature and duration of the Legionella prevention cycles are typically:
• 2 minutes > 70°C
• 4 minutes > 65°C
• 60 minutes > 60°C
To enable the Legionella prevention function, set 0222=1
Description
Electric heater operating mode 0 = Heat pump only 1 = Electric heater only 2 = Heat pump + Electric heater
Domestic hot water temperature set point with heat pump Domestic hot water temperature set point with heater
Menu
Mn02
Mn00
Mn02
Parameter
no.
0202
0023
0209
Value to be
set
2
Example
55
Example
65
UOM
°C
°C
1
Domestic hot water electric heater
NU
10 11
22 AWR-MTD2-XE EN 11/2010
INSTALLER CONNECTIONS
U I A
N
L
2
21 22
NU
230V 50Hz
1
1 Storage tank 2 System pump HL1
HL1 Configurable contact
This contact can be configured for the following functions:
• Alarm signal
• Secondary circuit pump
• Dehumidifier
Alarm signal
A visual or audible signal device can be activated if the unit shuts down due to a malfunction.
Configure the contact, selecting the desired function by set­ting parameter 015A:
Secondary circuit pump
If the system features a low-loss header, contact HL1 can be used to activate the circulating pump on the secondary circuit.
Configure the contact, selecting the desired function by set­ting parameter 015A:
Description
Enable the contact as: 0= Alarm signal 1= Dehumidifier 3= Secondary circuit pump
Menu
Mn01
Parameter
no.
015A
Value to be
set
0
UOM
-
Description
Enable the contact as: 0= Alarm signal 1= Dehumidifier 3= Secondary circuit pump
Menu
Mn01
Parameter
no.
015A
Value to be
set
3
UOM
-
Dehumidifier
A dehumidifier can be activated in radiant panel systems to reduce humidity in cooling mode. The contact closes and the dehumidifier is activated when the humidity measured by the probe on the A5 room con­troller exceeds the value set for parameter 0172. Configure the contact, selecting the desired function by set­ting parameter 015A:
Dehumidifier
21 22
Description
Enable the contact as: 0= Alarm signal 1= Dehumidifier 3= Secondary circuit pump
Menu
Mn01
Parameter
no.
015A
Value to be
set
1
UOM
-
NU
230V 50Hz
21 22
23EN 11/2010 AWR-MTD2-XE
INSTALLER CONNECTIONS
U I A
HL2 Compressor ON signal
A remote visual signal device can be activated to indicate compressor operation.
NU
230V 50Hz
23 24
SA1 Remote ON/OFF
The unit can be switched on/off from a remote control unit, for example a timer or room thermostat. The remote off function stops the compressor, fan and pumps, while frost protection remains active.
- The unit can be switched on/off from contact SA1 only when the unit has been switched on using the but­ton on the A5 room controller
Contact closed = Heat pump ON Contact open = Heat pump OFF
25 26
SA1
SA2 Remote cooling/heating
Cooling/heating operating mode can be managed from a remote control unit. If remote cooling/heating changeover is enabled, the operat­ing mode cannot be changed on the keypad.
Set the following parameters:
Contact closed = Cooling Contact open = Heating
27 28
SA2
Description
Enable remote contact 0= remote contact enabled 1= remote contact disabled (only from keypad)
Menu
Mn01
Parameter
no.
0100
Value to be
set
0
UOM
-
SA3 Remote system/domestic water priority
The priority of heat pump operation can be selected using a remote contact. Use a switch to select the following functions:
Contact closed = Domestic hot water only Contact open = Domestic hot water + System
Set the following parameters:
Description
Enable remote contact 0= remote contact enabled 1= remote contact disabled (selection from keypad only)
Menu
Mn01
Parameter
no.
0100
Value to be
set
0
UOM
-
29 30
SA3
INSTALLER CONNECTIONS
24 AWR-MTD2-XE EN 11/2010
U I A
SA5 Deactivation contact for excess power con­sumption
The heat pump accepts an external deactivation signal from contact SA5 if a power consumption management system is used to disconnect devices based on set priority, thus avoid­ing activation of the contactor on the power meter. Configure the contact, selecting the desired function by set­ting parameter 015D:
Contact closed: heat pump operation not allowed. Contact open: heat pump operation allowed.
33 34
SA5
33 34
SA5
SA5 Reduced electricity rate contact
Forced refilling of the reserve storage tanks can be activat­ed based on different electricity rates during the day. During reduced rate periods, the heat pump can be forced on so as to heat the domestic hot water or system storage tank, where fitted. Configure the contact, selecting the desired function by set­ting parameter 015D:
Description
Enable the contact as: 0= Reduced electricity rate 1= Stop operation due to excess
power consumption
Menu
Mn01
Parameter
no.
015D
Value to be
set
1
UOM
-
Contact closed: forced operation during the reduced rate period. Contact open: heat pump operation at full electricity rate.
During operation at reduced electricity rate, contact closed, the domestic hot water set point is 50°C, as shown in the example, with the contact open it’s 47°C. This allows operation at a higher temperature, within the unit’s operating limits, exploiting the lower electricity cost.
Description
Enable the contact as: 0= Reduced electricity rate 1= Stop operation due to excess
power consumption Enable the set point as: 0= Economy 1= Comfort Set the value of the domestic hot water ECONOMY set point Set the value of the domestic hot water COMFORT set point
Menu
Mn01
Mn00
Mn00
Mn00
Parameter
no.
015D
0015
0022
0023
Value to be
set
0
0
Example
47
Example
50
UOM
-
-
°C
°C
25EN 11/2010 AWR-MTD2-XE
F3 System flow switch
System flow switch connection, compulsory component.
F3
39 40
BT8 Domestic hot water storage temperature probe
The domestic hot water temperature inside the storage tank is measured using probe BT8
41 42
BT8
INSTALLER CONNECTIONS
I A
26 AWR-MTD2-XE EN 11/2010
INSTALLER CONNECTIONS
I A
ELECTRICAL PANEL LAYOUT AWR-MTD2-XE 0011÷0041 SINGLE-PHASE
C90051683E_00
A4
A2
FU3
C1
A1
C2
C3
A3
QS1
QM1
KA1
KA1
KA6
KA7
KA15
FU1
FU5
FU6
A7
TC1
A1 Radio interference suppresser A2 Peak limiter A3 Electronic controller A4 Fan control module A7 Electric heater actuator C1 Compressor start capacitor C2-3 Fan start capacitor FU1 System water pump protection fuse FU3 Fan protection fuse FU5 Auxiliary circuit protection fuse
FU6 Controller protection fuse TCI Autotransformer KA1 Compressor control relay KA6 Outlet heater or boiler relay KA7 Alarm/secondary pump/dehumidifier relay KA15 High pressure switch relay QM1 Compressor circuit breaker QS1 Door interlock disconnect switch
27EN 11/2010 AWR-MTD2-XE
INSTALLER CONNECTIONS
I A
ELECTRICAL PANEL LAYOUT AWR-MTD2-XE 0031÷0051 THREE-PHASE
C90051687E_00
A4
FU3
A1
C2
C3
A3
QS1
QM1
KA6
KA7
KA15
FU1
FU5
FU6
A7
TC1
KA2
KM1
A1 Radio interference suppresser A3 Electronic controller A4 Fan control module A7 Electric heater actuator C2-3 Fan start capacitor FU1 System water pump protection fuse FU3 Fan protection fuse FU5 Auxiliary circuit protection fuse FU6 Controller protection fuse TCI Autotransformer
KA2 Phase sequence control relay KA6 Outlet heater or boiler relay KA7 Alarm/secondary pump/dehumidifier relay KA15 High pressure switch relay KM1 Compressor contact QM1 Compressor circuit breake QS1 Door interlock disconnect switch
28 AWR-MTD2-XE EN 11/2010
ELECTRICAL PANEL LAYOUT AWR-MTD2-XE 0061 AND 0091 THREE-PHASE
INSTALLER CONNECTIONS
I A
C90051689E_00
A3
KA2
QS1
FU6
KA6
KA7
KA15
A1
TC1
C2
A7
FU5
FU1
QM1
KM1
A4
FU3
C3
C4
A1 Radio interference suppresser A3 Electronic controller A4 Fan control module A7 Electric heater actuator C2-3-4 Fan start capacitor FU1 System water pump protection fuse FU3 Fan protection fuse
FU5 Auxiliary circuit protection fuse FU6 Controller protection fuse TCI Autotransformer KA2 Phase sequence control relay KA6 Outlet heater or boiler relay KA7 Alarm/secondary pump/dehumidifier relay KA15 High pressure switch relay
KM1 Compressor contact QM1 Compressor circuit breaker QS1 Door interlock disconnect switch
29EN 11/2010 AWR-MTD2-XE
INSTALLER CONNECTIONS
I A
SINGLE-PHASE WIRING DIAGRAM AWR-MTD2-XE 0011÷0041
N4
L2
A1
C65403050E_03
1L
1N
U-N
PE
230V
50Hz
L-N
QS1
U3
U1
1
INSTALLER TERMINAL BLOCK
1
2 0
4 4 5
7474
55
44
1
4321
brown black blue
C2
EV1
B
M
0
38
42
40
38
42
61
40
40 38
40 38
38
42
F4
65
white
8
P
6721
BP1
79
321
543
2 0
5
7575
55
1
4321
brown black blue
C3
EV2
C
M
0
YV1
98A
38
0
2
0
9
FU6
0
8
R1
KA1
KA1
KA15
SA3
920
3
HL1
230VAC 1A MAX
F2 F1
0
9
FU1
2 0
43
A5
RX-/TX-RX+/TX+
GND
0
E1
M
1
green
BT7
+po
BT2
+to
BT1
+to
10
6543
F1
2
SA1 SA5
334372
8 2
2
E1
8
FU5
D
1
00
1
blue
brown
brown
white
blue
black
40
38
38
42
22
21
+to
BT8
YV5 KM2
A
KA15
0
456 D
R5
403842
45
R2
0
8
0
0
10
0
37
37
11
12
12
12
11
11
13
14
70
70
70
25
25
8
8
454545
38
38
38
38
38
51
38
38
38
38
252525
474747
38
35
464646
38
58
56
58
56
55
56
55
39
55
57
57
57
KA1
22
23
23 24
HL2
38
40
GG0
J1
GND DI3
B2 B4 GNDB1NO5C2
.J12
GND
RX+/TX+ RX-/TX-
J10
NO1NO3 NO2
C1
DI7 DI2 DI1.
.. .. . ...... ....
A3
... .....
NO6
.
Y3
J13
Y2
.
Y1
..
.
.
.
.
.DI4
.
J5
DI6
.
+Vdc
.
GND
.
J4 J2
DI5
.
J3
B7
.
B3
.
B5
.
B6
.
RX-/TX-
RX+/TX+
GNDVout
J8
NO4
.
NC7
.
2424
LOAD
+
A4
L N
FU3
-
KA15
37
38
444444
25 26
SA2
35 50 5050
F3
+5Vref
.
black
38
39
38
39
.
DIC1
38 38
59
59
59
60
60
60
+to
BT9
+to
BT11
38
38
8
..
.
26
26
KM4
24
24
J14
C3 NO7
.
12
NO4
KA6
KA6
76
77
21
21
KA7
8
KA7
78
79
67119
38 38
444
4
0
0
0
0
10
25
24
43
43
44
45
52
47
50
46
38
38
39
55
56
58
38
61
58
3838
61 61
57
59
60
38
QF1
1
I d
A7
43
38
7
Nc
6
Com
5
No
1Y2
Y
2143
G0
G
68 69
230VAC
24VAC
8 0
68
69
RX-/TX-
RX+/TX+
GND
Vout
BT12
GND
24V
54 55
68
69
4343
43
69
68
69
68
69
68
13
8
12
40 38
4 5
70
8
8
8
1L 1N
C1
1
M
SRC
Z1
L1 N
SRC
R
ON
KA1
A2
GY
BU
BN
BN BN
GY
BU
RD
BU
BU
BK BK
21
3
QM1
KA1
0
3
TC1
80
80
80
80
81
81
81
81
82
82
82
82
83
83
83
83
84
84
84
84
85
85
85
85
86
86
86
86
47 48 49 50 51 52 5339 40 41 42 43 44 45 46
21
A1 Radio interference suppresser
A2 Compressor start
A3 Electronic controller
A4 Fan control module
A5 User interface
A7 Drain pan heater actuator
BP1 Condenser/evaporator control pressure transducer
BT1 Heat exchanger water inlet temperature probe
BT2 Heat exchanger water outlet temperature probe
BT7 Unit control air temperature probe
BT8 Hot water storage temperature probe
BT9 Storage tank probe
BT11 Outside air temperature probe for set point management
C1 Compressor start capacitor
C2-3 Fan start capacitor
E1 Water pump
EV1-2 Fan
F1 High pressure switch
F2 Low pressure switch
F3 Flow switch
F4 Water differential pressure switch
FU1 System water pump protection fuse
FU3 Fan protection fuse
FU5 Auxiliary circuit protection fuse
FU6 Controller protection fuse
HL1 Alarm indicator light / Dehumidifier/high temperature
zone 1
HL2 Compressor ON indicator light
KA1 Compressor control relay
KA6 Outlet heater / boiler relay
KA7 Alarm / secondary pump / dehumidification relay
KA15 High pressure switch relay
KM2 Outlet heater / boiler contactor
KM4 DHW storage heater control contactor
QF1 Unit circuit breaker
QM1 Compressor circuit breaker
QS1 Door interlock disconnect switch
R1 Compressor oil sump heater
R2 Heat exchanger frost protection heater
R5 Drain pan frost protection heater
SA1 Remote on-off switch input
SA2 Summer-winter switch input
SA3 Input to enable DHW only / system + DHW
SA5 Input for demand limit / low energy rate contactor
TC1 230/24 VAC transformer
YV1 Reversing valve
YV5 3-way valve (system/DHW)
Z1 Compressor
1 Not supplied
2 Optional
3 Sizes 0031-0041 only
30 AWR-MTD2-XE EN 11/2010
INSTALLER CONNECTIONS
I A
THREE-PHASE WIRING DIAGRAM AWR-MTD2-XE 0031÷0051
N4
L2
A1
C65403051E_02
1L
1N
U-V-W-N
PE
400V-3N ~ 50Hz
L1-L2-L3-N
QS1
U3
U1
1
INSTALLER TERMINAL BLOCK
1
2 0
4 4 5
7474
55
44
1
4321
brown black blue
C2
EV1
B
M
0
38
42
40
38
42
61
40
40 38
40 38
38
42
F4
65
white
8
P
6721
BP1
79
321
543
2 0
5
7575
55
1
4321
brown black blue
C3
EV2
C
M
0
YV1
98A
38
0
2
0
9
FU6
0
8
R1
KM1
KM1
KA15
SA3
920
3
HL1
230VAC 1A MAX
F2 F1
0
9
FU1
2 0
43
A5
43
RX-/TX-RX+/TX+
GND
0
E1
M
1
green
BT7
+po
BT2
+to
BT1
+to
10
6543
F1
2
SA1 SA5
334372
8 2
2
E1
8
FU5
D
1
00
1
blue
brown
brown
white
blue
black
40
38
38
42
22
21 41
+to
BT8
YV5 KM2
A
KA15
0
456 D
R5
403842
45
R2
0
8
0
0
10
0
37
37
11
12
12
12
11
11
13
14
70
70
70
25
25
8
8
454545
38
38
38
38
38
51
38
38
38
38
252525
474747
53
35
464646
38
58
56
58
56
55
56
55
39
55
57
57
57
KM1
22
23
23 24
HL2
38
40
GG0
J1
GND DI3 B2 B4 GNDB1NO5C2
.J12
GND
RX+/TX+ RX-/TX-
J10
NO1NO3 NO2
C1
DI7 DI2 DI1.
.. .. . ...... ....
A3
... .....
NO6
.
Y3
J13
Y2
.
Y1
..
.
.
.
.
.DI4
.
J5
DI6
.
+Vdc
.
GND
.
J4 J2
DI5
.
J3
B7
.
B3
.
B5
.
B6
.
RX-/TX-RX+/TX+
GNDVout
J8
NO4
.
NC7
.
2424
LOAD
+
A4
L N
FU3
-
KA15
37
38
444444
25 26
SA2
35 50 5050
9304
F3
+5Vref
.
black
38
39
38
39
.
DIC1
38 38
59
59
59
60
60
60
42 44
+to
BT9
+to
BT11
38
38
8
..
.
26
26
KM4
24
24
J14
C3 NO7
.
12
NO4
KA6
KA6
76
77
21
21
KA7
8
KA7
78
79
67119
38 38
444
4
0
0
0
0
10
25
24
43
43
44
45
52
47
50
46
38
38
39
55
56
58
38
61
58
3838
61 61
57
59
60
38
3
M
T1 T2 T3
1L1
1L2
1L3
KM1
Z1
QM1
1L
2L
KA2
L3
1L2
1L1
1L3
QF1
1
I d
KA2
A7
43
38
7
Nc
6
Com
5
No
1Y2
Y
2143
G0
G
68 69
230VAC
24VAC
8 0
68
69
RX-/TX-
RX+/TX+
GND
Vout
BT12
GND
24V
54 55
68
69
4343
43
69
68
69
68
69
68
13
8
12
40 38
4 5
70
8
8
8
TC1
45 46 47 48 49 50 51 52 53
80
80
80
80
81
81
81
81
82
82
82
82
83
83
83
83
84
84
84
84
85
85
85
85
86
86
86
86
2
1
A1 Radio interference suppresser
A3 Electronic controller
A4 Fan control module
A5 User interface
A7 Drain pan heater actuator
BP1 Condenser/evaporator control pressure transducer
BT1 Heat exchanger water inlet temperature probe
BT2 Heat exchanger water outlet temperature probe
BT7 Unit control air temperature probe
BT8 Hot water storage temperature probe
BT9 Storage tank probe
BT11 Outside air temperature probe for set point management
BT12 Ambient temperature sensor
C2-3 Fan start capacitor
E1 Water pump
EV1-2 Fan
F1 High pressure switch
F2 Low pressure switch
F3 Flow switch
F4 Water differential pressure switch
FU1 System water pump protection fuse
FU3 Fan protection fuse
FU5 Auxiliary circuit protection fuse
FU6 Controller protection fuse
HL1 Alarm indicator light / Dehumidifier/high temperature
zone 1
HL2 Compressor ON indicator light
KA2 Phase sequence control relay
KA6 Outlet heater / boiler relay
KA7 Alarm / secondary pump / dehumidification relay
KA15 High pressure switch relay
KM1 Compressor contactor
KM2 Outlet heater / boiler contactor
KM4 DHW storage heater control contactor
QF1 Unit circuit breaker
QM1 Compressor circuit breaker
QS1 Door interlock disconnect switch
R1 Compressor oil sump heater
R2 Heat exchanger frost protection heater
R5 Drain pan frost protection heater
SA1 Remote on-off switch input
SA2 Summer-winter switch input
SA3 Input to enable DHW only / system + DHW
SA5 Input for demand limit / low energy rate contactor
YV1 Reversing valve
YV5 3-way valve (system/DHW)
Z1 Compressor
1 Not supplied
2 Optional
31EN 11/2010 AWR-MTD2-XE
INSTALLER CONNECTIONS
I A
THREE-PHASE WIRING DIAGRAM AWR-MTD2-XE 0061÷0091
C65403052E_03
FOR WIRING, PLEASE
SEE INSTRUCTION
SHEET
2222
70
70
70
70
DB5 6
N4
L2
A1
1L
1N
U-V-W-N
PE
400V-3N ~ 50Hz
U-V-W-N
L1-L2-L3-N
QS1
U3
U1
1
INSTALLER TERMINAL BLOCK
1
0
4 4 555
44
1~
4321
brown black blue
EV1
C
M
0
38
42
40
38
42
61
40
40 38
40 38
38
42
F4
65
white
8
P
12
BP1
79
321543
0
5
8787
55
1~
9876
brown black blue
C4
EV2
A
M
0
YV1
38
0
0
9
FU6
0
8
R1
KM1
KM1
KA15
SA3
920
3
HL1
230VAC 1A MAX
F2 F1
0
9
FU1
0
43
A5
43
RX-/TX-RX+/TX+
GND
0
E1
M
1~
green
BT7
+po
BT2
+to
BT1
+to
10
6543
F1
2
SA1 SA5
334372
8 2
2
E1
8
FU5
D
1
00
1
blue
brown
brown
white
40
38
38
42
22
21 41
+to
BT8
YV5 KM2
A
KA15
0
456
R5
403842
45
R2
0
8
0
0
10
0
37
37
11
12
12
12
11
11
13
14
25
25
8
8
454545
38
38
38
38
38
51
38
38
38
38
252525
474747
53
35
464646
38
58
56
58
56
55
56
55
39
55
57
57
57
KM1
22
23
23 24
HL2
38
40
GG0
J1
GND DI3 B2 B4 GNDB1NO5C2
.J12
GND
RX+/TX+ RX-/TX-
J10
NO1NO3 NO2
C1
DI7 DI2 DI1.
.. .. . ...... ....
A3
... .....
NO6
.
Y3
J13
Y2
.
Y1
..
.
.
.
.
.DI4
.
J5
DI6
.
+Vdc
.
GND
.
J4 J2
DI5
.
J3
B7
.
B3
.
B5
.
B6
.
RX-/TX-RX+/TX+
GNDVout
J8
NO4
.
NC7
.
2424
LOAD
+
A4
L N
FU3
-
KA15
37
38
444444
25 26
SA2
35 50 5050
9304
F3
+5Vref
.
black
38
39
38
39
.
DIC1
38 38
59
59
59
60
60
60
42 44
+to
2
BT9
+to
BT11
38
38
8
..
.
26
26
KM4
24
24
J14
C3 NO7
.
12
NO4
KA6
KA6
76
77
21
21
KA7
8
KA7
78
79
67119
38 38
444
4
0
0
0
0
10
25
24
43
43
44
45
52
47
50
46
38
38
39
55
56
58
38
61
58
3838
61 61
57
59
60
38
3~
M
T1 T2 T3
1L1
1L2
1L3
KM1
Z1
QM1
1 L2
L
KA2
L3
1L2
1L1
1L3
QF1
1
I d
KA2
A7
43
38
7
Nc
6
Com
5
No
1Y2
Y
2143
G0
G
68 69
230VAC
24VAC
8 0
68
69
GND
24V
54 55
68
69
4343
43
69
68
69
68
69
68
13
8
12
40 38
4 5
8
8
8
TC1
45 46 47 48 49 50 51 52 53
80
80
80
80
81
81
81
81
82
82
82
82
83
83
83
83
84
84
84
84
85
85
85
85
86
86
86
86
4 4 5
7474
55
44
1~
4321
brown black blue
C2
B
M
7575
C3
3
2 1
EV3
21
3
2
C5
A1 Radio interference suppresser
A3 Electronic controller
A4 Fan control module
A5 User interface
A7 Drain pan heater actuator
BP1 Condenser/evaporator control pressure transducer
BT1 Heat exchanger water inlet temperature probe
BT2 Heat exchanger water outlet temperature probe
BT7 Unit control air temperature probe
BT8 Hot water storage temperature probe
BT9 Storage tank probe
BT11 Outside air temperature probe for set point management
C2-3-4 Fan start capacitor
C5 Noise suppression filter
E1 Water pump
EV1-2-3 Fan
F1 High pressure switch
F2 Low pressure switch
F3 Flow switch
F4 Water differential pressure switch
FU1 System water pump protection fuse
FU3 Fan protection fuse
FU5 Auxiliary circuit protection fuse
FU6 Controller protection fuse
HL1 Alarm indicator light / Dehumidifier/high temperature
zone 1
HL2 Compressor ON indicator light
KA2 Phase sequence control relay
KA6 Outlet heater / boiler relay
KA7 Alarm / secondary pump / dehumidification relay
KA15 High pressure switch relay
KM1 Compressor contactor
KM2 Outlet heater / boiler contactor
KM4 DHW storage heater control contactor
QF1 Unit circuit breaker
QM1 Compressor circuit breaker
QS1 Door interlock disconnect switch
R1 Compressor oil sump heater
R2 Heat exchanger frost protection heater
R5 Drain pan frost protection heater
SA1 Remote on-off switch input
SA2 Summer-winter switch input
SA3 Input to enable DHW only / system + DHW
SA5 Input for demand limit / low energy rate contactor
YV1 Reversing valve
YV5 3-way valve (system/DHW)
Z1 Compressor
1 Not supplied
2 Optional
3 Size 0091 only
32 AWR-MTD2-XE EN 11/2010
Data measured in the following conditions: (1) Water in-out 30/35°C (plant side), outdoor air temperatur 7°C b.s./ 6°C b.u. (2) Total input is obtained from compressor input and fan input. (3) Water in-out 23/18°C (plant side), outdoor air temperature 35°C b.s. (4) Water in-out 40/45°C (plant side), outdoor air temperature 7°C b.s./ 6°C b.u. (5) Water in-out 12/7°C (plant side), outdoor air temperature 35°C b.s. (6) Sound power level according to ISO 9614 and Eurovent 8/1 (7) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit.
GENERAL TECHNICAL DATA
I A
AWR MT2 XE 0011 0025 0031 0041 0031 0041 0051 0061 0091
Heating capacity (1) kW 6,3 7,4 11,2 14 10,9 14 15,9 17,9 25,1 Power input (2) kW 1,5 1,8 2,6 3,3 2,6 3,3 3,8 4,2 6 COP Eurovent 4,23 4,23 4,26 4,19 4,18 4,19 4,14 4,28 4,19 COP EN14511 4,13 4,15 4,22 4,16 4,15 4,15 4,11 4,25 4,19 Heating capacity (3) kW 6,1 7,3 10,8 13,6 10,6 13,8 15,4 17,5 24,6 Power input (2) kW 1,9 2,3 3,3 4,1 3,2 4,3 4,6 5,2 7,4 COP Eurovent 3,29 3,24 3,32 3,29 3,28 3,25 3,35 3,38 3,32 Rated water flow (1) m3/h 1,1 1,3 1,9 2,4 1,9 2,4 2,8 3,1 4,3 Useful pressure head (1) kPa 50 45 87 67 87 67 53 54 104 Cooling capacity (4) kW 7,2 8,3 12,3 15,7 11,7 15,8 17,7 20,2 29,2 Power input (2) kW 1,9 2,2 3,3 4,1 3,1 4,2 4,7 5,3 7,8 EER Eurovent 3,79 3,77 3,73 3,83 3,77 3,76 3,77 3,81 3,74 EER EN 14511 3,82 3,82 3,81 3,84 3,84 3,81 3,81 3,81 3,85 Cooling capacity (5) kW 5,2 6,3 9,2 11,7 8,6 11,9 13,2 15,2 22,1 Power input(2) kW 1,7 2,2 3,1 4 3 4 4,6 5 7,2 EER Eurovent 3,06 2,86 2,97 2,93 2,87 2,98 2,87 3,04 3,07 ESEER 3,62 3,63 3,52 3,46 3,42 3,65 3,24 3,55 3,57 Rated water flow(4) m3/h 1,2 1,4 2,1 2,7 2 2,7 3,1 3,5 5 Useful pressure head(4) kPa 43 40 80 55 80 55 43 42 88 No. of fans 1 1 2 2 2 2 2 2 3 Air flow m3/s 1,08 1,08 1,8 1,9 1,8 1,9 1,9 2,01 3 Type of compressor SCROLL Number of compressors 1 1 1 1 1 1 1 1 1 Number of circuits 1 1 1 1 1 1 1 1 1 Refrigerant R410a Kg
2,55 2,9 3,5 4,35 3,5 4,35 4,5 6,1 8,5
Oil Mobil EAL ARTIC 22cc Kg
0,7 0,7 1,2 1,2 1,2 2,0 1,7 1,8 3,2
Type of pump Circulator Number pumps 1 1 1 1 1 1 1 1 1 Operating weight kg 145 150 155 170 155 170 180 250 335 Water fittings inches 1 1 1 1-1/4 1 1-1/4 1-1/4 1-1/4 1-1/4 Sound power (6) dB(A) 69 69 71 71 71 71 71 72 74 Sound pressure (7) dB(A) 54 54 56 56 56 56 56 57 59 Power supply V/ph/Hz 230~50 400-3N~50
33EN 11/2010 AWR-MTD2-XE
Outside air temperature (°C)
Outlet water temperature (°C)
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
25 30 35 40 45 50 55 60
Water temperature head min/max= 3/8 °C Water circuit pressure min/max = 1/3 bar Maximum glycol percentage = 40%
HEATING
U I A
OPERATING LIMITS
I A
Outside air temperature (°C)
Outlet water temperature (°C)
0
5
10
15
20
25
30
35
40
45
50
-15 -10 -5 0 5 10 15 20 25 30
COOLING
34
AWR-MTD2-XE EN 11/2010
The pressure head refers to the values at the fittings.
U I A
PUMP CURVE
I A
CHARACTERISTICS AVAILABLE PRESSURE HEAD IN SYSTEM CIRCUIT
0
10
20
30
40
50
60
70
80
0 0,5 1 1,5 2 2,5
Curve 4
Curve 3
Curve 2
Curve 1
Useful pressure head [kPa]
Water flow-rate [m3/h]
AWR MTD2 XE 11 ms
0
10
20
30
40
50
60
70
80
0 0,5 1 1,5 2 2,5
Curve 4
Curve 3
Curve 2
Curve 1
Useful pressure head [kPa]
Water flow-rate [m3/h]
AWR MTD2 XE 25 ms
0
20
40
60
80
100
120
0 1 2 3 4
Curve 4
Curve 3
Curve 2
Curve 1
Useful pressure head [kPa]
Water flow-rate [m3/h]
AWR MTD2 XE 31 ms - AWR MTD2 XE 31 t
0
20
40
60
80
100
120
0 1 2 3 4
Curve 4
Curve 3
Curve 2
Curve 1
Useful pressure head [kPa]
Water flow-rate [m3/h]
AWR MTD2 XE 41 ms - AWR MTD2 XE 41 t
35EN 11/2010 AWR-MTD2-XE
The pressure head refers to the values at the fittings.
U I A
PUMP CURVE
I A
CHARACTERISTICS AVAILABLE PRESSURE HEAD IN SYSTEM CIRCUIT
0
20
40
60
80
100
120
0 1 2 3 4
Curve 4
Curve 3
Curve 2
Curve 1
Useful pressure head [kPa]
Water flow-rate [m3/h]
AWR MTD2 XE 51 t
0
20
40
60
80
100
120
0 1 2 3 4 5
Curve 4
Curve 3
Curve 2
Curve 1
Useful pressure head [kPa]
Water flow-rate [m3/h]
AWR MTD2 XE 61 t
0
20
40
60
80
100
120
0 1 2 3 4 5 6 7 8 9
Curve 4
Curve 3
Curve 2
Curve 1
Useful pressure head [kPa]
Water flow-rate [m3/h]
AWR MTD2 XE 91 t
36 AWR-MTD2-XE EN 11/2010
ON
0 OFF
CHECKING AND STARTING UP THE UNIT
A
CHECKS BEFORE STARTING THE UNIT
• the vibration damping feet are fitted
• inlet filters are fitted on the system
• suitably-sized expansion vessel and safety valve installed on the DHW circuit
• an expansion vessel is installed if the expansion vessel on the unit is undersized
• make sure vibration damper joints are installed on water connections
• a low-loss header is installed if the water content is insuffi­cient
• make sure the position of the outside air probe corre­sponds to the instructions shown in the manual
• make sure the position of the room control unit corre­sponds to the instructions shown in the manual
• make sure that the electrical power available is adequate for the unit installed
• make sure the non-return valve is installed on the DHW circuit
PREPARING FOR FIRST START UP
The unit must be started up for the first time by the Techni­cal Service. Before starting up the unit, make sure that:
• the unit has been properly installed as described in this manual
• All safety conditions have been respected;;
• The unit is adequately fixed to the surface it rests on;
• Clearances have been respected;
• Water connections have been carried out as indicated in the instruction manual;
• All water connections are tight.
• Make sure the water circuit has been washed and drained.
• The water circuit is filled and vented.
• Make sure there is no air in the system. If necessary vent the system using the vent valve. If venting after operation in heat pump mode, be careful as the water may be hot;
• The water valves are open;
• Electrical connections have been carried out correctly;
• Voltage is within a tolerance of 10% of the rated voltage for the unit;
• Make sure that unbalance between phases is less than 3%, for three-phase units.
• The unit is correctly earthed;
• All electrical connections are tight.
• make sure that the outside air and water temperature are within the unit operating limits shown in this manual.
Before starting up, power up the unit for at least two hours by switching QF1 and QS1 to ON (see the wiring diagram) to allow the oil in the compressor sump to heat up.
STARTING UP FOR THE FIRST TIME
Before starting the unit:
• Make sure the switch QF1 is in the OFF position, Fig. 1.
• Make sure the contact of the on/off device SA1 (see the wiring diagram) is open (if featured).
• Make sure the “A5” room controller is off.
• Position the main unit switch QS1 in the ON position, Fig.
2.
• Move switch QF1 (outside the unit) to “ON”, Fig. 3.
ON
OFF
ON
OFF
1
2
3
37EN 11/2010 AWR-MTD2-XE
mode
3
4
5
CHECKING AND STARTING UP THE UNIT
A
• Once having powered up the heat pump, the display on the room control unit shows this message (1):
• Followed by (2):
• Wait a few minutes, the unit is ready to operate when the display shows (3):
Before starting up, power up the unit for at least two hours, with the compressor off, so as to allow the oil in the compressor sump to heat up.
When commissioning the heat pump, the user must config­ure the type of system. See the chapter “System configuration”, check the applica­tion diagrams that the control unit is able to manage.
• Set the current date and time on the A5 room controller
• Configure the type of system and the number of A5 room controllers. See the chapter "System configuration".
• Switch on the unit by pressing button 3
• Select the required operating mode by pressing button 5
• Select the required room temperature by turning knob 4
For further information on the operation and functions of the room controller, see "Operation and functions of the room controller".
1
3
2
A5 room controller
38 AWR-MTD2-XE EN 11/2010
DESCRIPTION OR ROOM CONTROLLER BUTTONS AND DISPLAY
A
BUTTONS
mode
1
2
3
4
7
6
5
1
3
4
7
8
10
9
5
2
6
NO. Description
1 Temperature and humidity probe 2 Domestic hot water (DHW) production button
3
ON/OFF button ESC button in parameter programming mode Knob
4 - Turning: scroll room temperature values,
parameters and menus
- Pressing: Confirm settings 5 Select operating mode button 6 Set time bands button 7 Backlit display
Description Symbol
1 Operating mode
2 Main field
3 Temperature unit of measure
4 Set point
5 Relative humidity
6 Time band
7 Day of the week
8 Actuator operating
9 Secondary field
10 Active time band
Function
Heating
Cooling
automatic mode changeover based on outside air temperature
Domestic hot water production enabled
Room temperature/humidity, room set point, parameter val-
ue display
On indicates room set point programming
Indicates the type of active time band
error message
system pump active
- flashing: compressor timer, delay
- fixed: compressor active
Defrost active
Fan active
Boiler or electric heater active
Frost protection active
Time, menu, parameter number display
On indicates active time band
DISPLAY
39EN 11/2010 AWR-MTD2-XE
OPERATION AND FUNCTIONS OF THE ROOM CONTROLLER
A
2
3
4
1
5
Symbol Meaning
Press and release
Hold for 3 seconds
Turn the knob
x3 sec.
Meaning of the symbols
Display
During normal operation of the unit, the display shows the following information:
Additional information displayed
During operation of the unit, pressing the knob displays the information described below.
Press the knob Room temperature set point
Press the knob
Humidity set point
Press the knob
1 operating mode selected 2 domestic hot water production enabled 3 room temperature 4 hour and minutes 5 day
Outside air temperature
Press the knob
Domestic hot water set point
Press the knob
Room humidity
Press the knob
40
AWR-MTD2-XE EN 11/2010
x3 sec.
Setting the time and date
** Mon = Lunedi, Tue = Martedi, Wed = Mercoledi, Thu = Giovedi, Fri = Venerdi, Sat = Sabato, Sun = Domenica
Press the button for 3 seconds
Press the knob
• The hours flash
• Turn the knob to select the hour value
• Press the knob to confirm • The minutes flash
• Turn the knob to select the minutes value
• Press the knob to confirm
• The day flashes
• Turn the knob to select the day**
• Press the knob to confirm
• Press the button to exit.
• Main display
1 2 3
4 5 6
7 8 9
10
OPERATION AND FUNCTIONS OF THE ROOM CONTROLLER
A
41EN 11/2010 AWR-MTD2-XE
x3 sec.
** The heat pump is not yet operating, the mode has to be selected: heating, cooling, auto or domestic hot water production.
** AUTO automatic mode changeover based on the outside air temperature
ZONE OFF
Press the button for 3 seconds
ZONE ON**
Selecting the operating mode
No operating mode selected. Heat in OFF.
None Automatic mode changeover Cooling Heating
• Press the mode button
• AUTOMATIC** mode changeover selected
• Press the mode button
• COOLING mode selected
• Press the mode button
• HEATING mode selected
Selecting the room temperature set point
• Turn the knob
• The room temperature set point is displayed
• Turn the knob to change the room temperature set point
• Wait a few seconds for confirmation
• The display shows the room tem­perature
1 2 3
1 2 3 4
OPERATION AND FUNCTIONS OF THE ROOM CONTROLLER
A
Switching ON
The button enables operation of the pump or the zone valve controlled by the room controller, the heat pump is activated by selecting the operating mode using the button, as shown below.
42 AWR-MTD2-XE EN 11/2010
OPERATION AND FUNCTIONS OF THE ROOM CONTROLLER
A
Domestic hot water production not enabled
Press the .
• Domestic hot water production enabled
• The symbol is displayed
Domestic hot water production
Selecting the domestic hot water set point
The domestic hot water temperature is measured by the probe installed inside the DHW storage tank.
x3 sec.
• Press thei + buttons together for 3 seconds
• Turn the knob and select the value of para­meter 012
• Press the knob to confirm • Press the knob to confirm • Turn the knob and select parameter 0023
• Press the knob • Turn the knob to select the domestic hot water set point
• Press the knob to confirm
1 2 3
4 5 6
7 8 9
1 2 3
43EN 11/2010 AWR-MTD2-XE
• Press the button twice until reaching the main display.
• Main display
10 11
OPERATION AND FUNCTIONS OF THE ROOM CONTROLLER
A
44 AWR-MTD2-XE EN 11/2010
Time band 1
Time band 2 Time band 3 Time band 4 Time band 5 Time band 6
Programming the time bands
The room controller can customise on/off times for each zone in the system, based on six time bands. The six time bands are identified by the following symbols, selected by turning the knob:
OPERATION AND FUNCTIONS OF THE ROOM CONTROLLER
A
x5 sec.
• Press the button for 5 seconds
• Turn the knob • Press to confirm
GROUP OF 7 DAYS A Turn the knob B Press the knob to confirm
GROUP OF 5 DAYS A Turn the knob B Press the knob to confirm
GROUP OF 2 DAYS A Turn the knob B Press the knob to confirm
INDIVIDUAL DAY A Turn the knob B Press the knob to confirm
Time band 1
• Press the knob to confirm
Time band 1 start hours A Turn the knob B Press the knob to confirm the
hour value
Time band 1 start minutes A Turn the knob B Press the knob to confirm the
minutes value
Time band 1 room temp. set point A Turn the knob B Press the knob to confirm
The time bands can be programmed by selecting the days in preset groups or for each individual day.
The time bands on systems with multiple zones, each of which is managed by its own room controller (maximum 6), must be programmed on each room controller.
For installations with heap pump connected directly to the system, without storage tanks and secondary pumps, parameter 011D must be set to 0. This means that heat pump operation will be managed based on the time bands.
1 2 3
4 5 6 7
8 9 10 11
A
B
A
B
A
B
A
B
A
B
A
B
A
B
45EN 11/2010 AWR-MTD2-XE
Time band 2
• Press the knob to confirm
Continue as described from step 8 to step 11 to set the hours, minutes and room tem­perature set point for the other time bands
Once the time bands have been set
A Turn the knob and select ESC B Press to confirm
• Press the button twice until reaching the main display.
• Main display
8 + 9 .... 10 .... 11 12 13 14
A
B
Press the button to exit programming mode
Time band program example
Below is an example of a time band program with two temperature levels, Comfort 20°C, Economy 18°C, and OFF.
Time
band 1
Time
band 2
Time
band 3
Time
band 4
Time
band 5
Time
band 6
0
OFF
18°C
20°C
4 8 12 16 20 24
Activating time bands
• Press the button. • The symbol is displayed
• Time band ACTIVE
1 2
Deactivating time bands
• Press the button. • The symbol is no longer displayed
• Time band DEACTIVATED
1 2
Once the time bands have been deacti­vated check that the room set point is at the required value, otherwise turn the knob to select the desired temperature.
46 AWR-MTD2-XE EN 11/2010
ACCESSING THE PROGRAMMING LEVELS
The room controller has a menu structure, divided into levels so as to allow access only to authorised users, as shown below:
Procedure for accessing the menu
x3 sec.
• Main display
• Press the + buttons together for 3 sec­onds
• Turn the knob and select the password (as shown in the table)
1 2 3
OPERATION AND FUNCTIONS OF THE ROOM CONTROLLER
A
Unit ON - ZONE ON
• Press the button for 3 seconds
Unit OFF - ZONE OFF
x3 sec.
1 2 3
Switching OFF
The button disables operation of the pump or the zone valve controlled by the room controller, the heat pump is deactivated using the button, as shown in " Selecting the operating mode".
Level Password Menu description Menu code
User 012 Room unit Mnu00
Installer
022 Zone room terminal address setting Addr
034
System configuration Mnu01 DHW Mnu02 Supplem. sources Mnu03 Cascade/Forced fan Mnu04 Primary and DHW exchanger Mnu06 input / output Mnu09
Authorised technical service Contact Manufacturer
Compressor Mnu05 Source heat exchanger Mnu07 Defrost Mnu08 Alarm log Mnu11 Serial protocol Mnu12
47EN 11/2010 AWR-MTD2-XE
• Press the knob • The parameter value flashes
• Turn the knob to change the parameter val­ue
• Press the knob to confirm
• Press the button twice until reaching the main display
• Main display
7 8 9
4 5 6
10 11
OPERATION AND FUNCTIONS OF THE ROOM CONTROLLER
A
A
B
• Press the knob to confirm A
Turn the knob to select the menu
B Press the knob to confirm
• Turn the knob and select the parameter to be set
Press the button to exit programming mode
48 AWR-MTD2-XE EN 11/2010
CONTROL AND OPERATING CHARACTERISTICS
A
Temperature control
The heating or cooling circuit water temperature is calculat­ed by the controller and depends on the following factors: A) system water set point compensation in heating or cool-
ing (see paragraph)
B) room temperature influence (see paragraph) C) minimum and maximum heating water temperature limit
(see paragraph)
D) room temperature set point
The compensation curves in HEATING are divided into:
• SYSTEM curve: determines the set point for heat pump ope­ration and any high temperature zones. The set point calcu­lated refers to the heat pump return water temperature. The water outlet temperature is usually 5°C higher than the return temperature. This temperature difference may change depending on the flow-rate and the type of system. Make sure that the temperature difference is within the limits required by the manufacturer.
• ZONE curve determines the water outlet temperature in the mixed circuit.
For systems configured with mixed zones, the SYSTEM curve and ZONE curve must be selected.
The system and zone curve work in cascading, the mixed zone curve may therefore not request a higher value than the one supplied by the system curve.
A) System water temperature set point compensation
The water temperature set point in heating or cooling is cal­culated based on the outside temperature trend according to settable curves.
Water set point compensation diagram in HEATING
The compensation curve in heating mode can be modified to allow correct heat pump operation depending on the heat­ing system used (radiant panels, radiators, fan coils).
Example: Selecting heating curve 1.4 with an outside air temperature of -5°C gives a water temperature of +55°C.
A heating curve that is too high gives an excessive outlet temperature, a curve that is too low may mean the desired room temperature is not reached.
The curve can be set separately for each zone, depending on the type of room terminal. The following compensation curves are recommended:
-25 -5
Water set point °C
Outside air temp. °C
2,2
2
1,8
1,6
1,4
1,2
1
0,8
0,6
0,4
0,2
Type of terminal Compensation curve number Radiant panels 0.25÷0.7 Fan coils 0,9÷1,1 Radiators 1,2÷1,5
Description
Enable SYSTEM compensation curve 0= Disabled 1= Enabled SYSTEM compensation curve number
Enable compensation curve zone LT1 0= Disabled 1= Enabled Compensation curve number zone LT1
Enable compensation curve zone LT2 0= Disabled 1= Enabled Compensation curve number zone LT2
Enable compensation curve zone LT3 0= Disabled 1= Enabled Compensation curve number zone LT3
Menu
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Parameter
no.
0152
0159
0167
0174
0182
0189
015E
012A
Default
0
0,8
0
0,7
0
0,7
0
0,7
UOM
49EN 11/2010 AWR-MTD2-XE
CONTROL AND OPERATING CHARACTERISTICS
A
-2.5
-40
-30
-20
-10
0
10
20
30
40
50
60
2 -1,5 -1 -0,5 0 0,5 1 1,5 2
DT (Room temperature °C - Room set point °C)
System or zone water temperature deviation (°C)
Example referred to compensation curve 1.0
10 % 25 %
50 %
75 % 99 %
Outlet set point with room temp. 20°C
Outside temp. (°C)
20
10
20
30
40
50
60
70
80
90
100
15 10 5 0 -5 -10 -15 -20 -25 -30
Outlet temp. (°C)
Description
MINIMUM set point limit for SYSTEM curve MAXIMUM set point limit for SYSTEM curve
MINIMUM outlet set point limit for compensation curve in zone LT1 MAXIMUM outlet set point limit for compensation curve in zone LT1
MINIMUM outlet set point limit for compensation curve in zone LT2 MAXIMUM outlet set point limit for compensation curve in zone LT2
MINIMUM outlet set point limit for compensation curve in zone LT3 MAXIMUM outlet set point limit for compensation curve in zone LT3
Menu
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Parameter
no.
0165
0166
0180
0181
0195
0196
012F
012G
Default
30
48
23
45
23
45
23
45
UOM
°C
°C
°C
°C
°C
°C
°C
°C
C) System water temperature limits in HEATING
These define the temperature limits (minimum and maxi­mum) that can be requested from the circuit and never exceeded. In the figure the minimum limit is 30°C and the maximum is 40°. Between 30 and 40°C the water temperature will be able to vary based on the trend in outside temperature.
For systems configured with mixed zones, the limits for the SYSTEM curve and ZONE curve must be selected.
B) Room temperature influence in HEATING
The compensation curve determines the heating water tem­perature; this may then be corrected based on the difference between the desired room set point and the actual room tem­perature. The correction made to the water temperature depends on the “Room Authority” coefficient. The higher the value of the Room Authority the higher the correction to the system water temperature, and vice-versa.
This allows the water temperature to adapt quickly to changes in the conditions inside the room.
The function can only be ENABLED if the A5 room controller is positioned in the room and used to measure the reference temperature.
Set authority values for the SYSTEM equal to or greater than those for zones LT1, LT2, LT3.
Enabling room temperature influence on SYSTEM deviates the calculated heat pump return water temperature set point.
Enabling room temperature influence on ZONE LT1, LT2, LT3 deviates the calculated water outlet temperature set point to the system, controlled by the mixing valve.
Description
Enable room temperature influ­ence on SYSTEM 0= Disabled 1= Enabled SYSTEM Room Authority
Enable Room temperature influ­ence on LT1 0= Disabled 1= Enabled LT1 Room Authority
Enable Room temperature influ­ence on LT2 0= Disabled 1= Enabled LT2 Room Authority
Enable Room temperature influ­ence on LT3 0= Disabled 1= Enabled LT3 Room Authority
Menu
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Parameter
no.
0162
0164
0178
0179
0193
0194
012D
012E
Default
0
30
0
30
0
30
0
30
UOM
%
%
%
%
50 AWR-MTD2-XE EN 11/2010
CONTROL AND OPERATING CHARACTERISTIC
A
Description
Enable SYSTEM compensation curve 0= Disabled 1= Enabled Maximum return temperature set point limit in cooling mode (Tm1) Minimum outside temperature corresponding to max.
return
temperature (Te1) Minimum return temperature set point limit in cooling mode (Tm2) Maximum outside temperature correspond­ing to min. return temperature (Te2) Enable compensation curve zone LT1 0= Disabled 1= Enabled Maximum outlet temperature set point limit in cooling mode (Tm1) Minimum outside temperature correspond­ing to max. outlet temperature (Te1) Minimum outlet temperature set point limit in cooling mode (Tm2) Maximum outside temperature correspond­ing to min. outlet temperature (Te2) Enable compensation curve zone LT2 0= Disabled 1= Enabled Maximum outlet temperature set point limit in cooling mode (Tm1) Minimum outside temperature corresponding to max. outlet temperature (Te1) Minimum outlet temperature set point limit in cooling mode (Tm2) Maximum outside temperature correspond­ing to min. outlet temperature (Te2) Enable compensation curve zone LT3 0= Disabled 1= Enabled Maximum outlet temperature set point limit in cooling mode (Tm1) Minimum outside temperature corresponding to max. outlet temperature (Te1) Minimum outlet temperature set point limit in cooling mode (Tm2) Maximum outside temperature correspond­ing to min. outlet temperature (Te2)
Menu
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Parameter
no.
0154
0128
0129
0130
0131
0169
0132
0133
0134
0135
0184
0136
0137
0138
0139
011T
012H
012J
012L
012M
Default
0
25
23
23
36
0
20
23
18
36
0
20
23
18
36
0
20
23
18
36
UOM
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
Description
Enable compensation for room humidity, SYSTEM 0= Disabled 1= Enabled Room relative humidity value to start increasing SYSTEM water return temperature set point Maximum return temperature hys­teresis corresponding to 100% rela­tive humidity Enable compensation for room humidity, ZONE LT1 0= Disabled 1= Enabled Room relative humidity value to start increasing water outlet temperature set point ZONE LT1 Maximum outlet temperature hys­teresis corresponding to 100% rela­tive humidity Enable compensation for room humidity, ZONE LT2 0= Disabled 1= Enabled Room relative humidity value to start increasing water outlet temperature set point ZONE LT2 Maximum outlet temperature hys­teresis corresponding to 100% rela­tive humidity Enable compensation for room humidity, ZONE LT3 0= Disabled 1= Enabled Room relative humidity value to start increasing water outlet temperature set point ZONE LT2 Maximum outlet temperature hys­teresis corresponding to 100% rela­tive humidity
Menu
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Mn01
Parameter
no.
0156
0157
0158
0171
0172
0173
0186
0187
0188
012N
012P
012R
Default
0
70
15
0
70
15
0
70
15
0
70
15
UOM
%
°C
%
°C
%
°C
%
°C
The compensation curves in COOLING are divided into:
• SYSTEM curve: determines the set point for heat pump operation and any high temperature zones. The set point calculated refers to the heat pump return water tempera­ture. The water outlet temperature is usually 5°C lower than the return temperature. This temperature difference may change depending on the flow-rate and the type of system. Make sure that the temperature difference is with­in the limits required by the manufacturer.
• ZONE curve determines the water outlet temperature in the mixed circuit.
For systems configured with mixed zones, the SYSTEM curve and ZONE curve must be selected. The system and zone curve work in cascading, the mixed zone curve may therefore not request a higher value than the one supplied by the system curve.
Water set point compensation diagram in COOLING
The compensation curve in cooling mode can be modified to allow correct heat pump operation depending on the cooling system used (radiant panels, fan coils). Points T1 and T2 correspond to two outside temperature values that respectively identify the maximum and minimum system water temperature.
Te2 Outside temp.Te1
Tm2
Tm1
Water set point
Maximum room humidity compensation
The water temperature set point, calculated based on the compensation curve, can be compensated according to the maximum relative humidity in the room. The water temperature value can increase so as to avoid possible formation of condensate in the radiant cooling sys­tems (underfloor, ceiling, wall, etc.).
If the relative humidity measured by the A5 room unit A5 exceeds the value set for parameter 0157, 0172, 0187, the water temperature set point increases until reaching the maximum temperature. The maximum water temperature is the set point calculated according to the compensation curve in cooling mode plus the value set for parameter 0158, 0173, 0188.
Enabling room humidity compensation on SYSTEM deviates the calculated heat pump return water temperature set point. Enabling room humidity compensation on ZONE LT1, LT2, LT3 deviates the calculated water outlet temperature set point to the system, controlled by the mixing valve.
100% UR%Value parameter 0157 Value parameter 0172 Value parameter 0187
Room humidity (RH%)
Value: parameter 0158 parameter 0173 parameter 0188
Temperature hysteresis (°C)
51EN 11/2010 AWR-MTD2-XE
CONTROL AND OPERATING CHARACTERISTICS
A
Automatic mode changeover based on outside temperature
In mode, the operating mode (heating / cooling) changes automatically, avoiding the need for the user to change the mode manually. Mode changeover is based on the diagram shown in the fig­ure.
The centre zone A corresponds to an area of inactivity, as the outside climate conditions mean neither heating nor cooling is required.
Description
Automatic mode changeover set point in HEATING Automatic mode changeover dif­ferential in HEATING Automatic mode changeover set point in COOLING Automatic mode changeover dif­ferential in COOLING
Menu
Mn01
Mn01
Mn01
Mn01
Parameter
no.
0106
0107
0108
0109
Default
16
2
24
2
UOM
°C
°C
°C
°C
0106= 16°C
0106+0107=18°C
Heating
ON
OFF
Cooling
0108-0109=24°C
Outside temp.
0108=26°C
A
System pump operation
When reaching the system water set point, the compressor stops and the system pump is activated periodically, so as to minimise energy consumption. Pump operating time can be selected using parameter 0147, while the interval between one sniffing cycle and the next is set using parameter 0148. Intermittent activation of system pump operation can be selected using parameter 0143 (0= system pump always on to, 1=system pump activated at intervals). In systems with fan coils, the time between one sniffing cycle and the next should be reduced in order to avoid cool­ing excessive of the water, and if the system water content is equal to the minimum value shown in the paragraph on "water connections", parameter 0143 should be set to 0.
52 AWR-MTD2-XE EN 11/2010
CONTROL AND OPERATING CHARACTERISTICS
U I A
Heat pump operation with fixed set point
System water set point compensation using the compensa­tion curves can be disabled. To enable fixed set point operation, set parameter 0152=0 and 0154=0 The heat pump will operate based on the fixed return set point defined by parameters 0153 (Heating) and 0155 (cool­ing).
Description
Enable return set point in HEATING 0= Fixed set point in heating ENABLED 1= Fixed set point in heating DISABLED Fixed return water temperature set point in HEATING
Enable return set point in COOLING 0= Fixed set point in cooling ENABLED 1= Fixed set point in cooling DISABLED Fixed return water temperature set point in COOLING
Menu
Mn01
Mn01
Mn01
Mn01
Parameter
no.
0152
0153
0154
0155
Default
0
40
0
12
UOM
-
°C
-
°C
FROST PROTECTION
Frost protection based on system water temperature
The frost protection function is active even if the controller is in standby. To prevent the water freezing and damaging the plate heat exchanger, the microprocessor shuts down the compressor and activates the system heat exchanger heater if the temperature measured by the heat exchanger outlet temperature probe is than +4°C. The frost prevention temperature set point can only be modified by an authorised service centre, and only after verifying that the water circuit contains antifreeze. Tripping of this alarm shuts down the compressor but not the pump, which remains active. To reset normal operation, the water outlet temperature must rise to more than: +7°C on the system side. Reset is automatic.
Frost protection based on inside temperature
Frost protection on the heating circuit is always active, even when the heat pump is off. The heat pump and/or supplementary sources of heat (out­let heater or boiler) are activated if the room temperature falls below the value set for parameter 0140, to prevent the pipes inside the home from freezing.
Outside air T
OFF
ON
Heat pump
0140 Inside temperature
1°C
Description
Inside temperature to enable frost protection
Menu
Mn01
Parameter
no.
0140
Default
14
UOM
°C
Frost protection based on outside air temperature
Frost protection on the heating and domestic hot water cir­cuits based on outside air temperature is always active, even when the heat pump is off. The system and domestic hot water pumps are activated when the outside air temperature falls below the value set for parameter 0141.
Outside air T
OFF
ON
System and DHW circuit water pump
0141 Outside air temperature to enable frost protection
1°C
Description
Outside temperature to enable frost protection
Menu
Mn01
Parameter
no.
0141
Default
4
UOM
°C
53EN 11/2010 AWR-MTD2-XE
SYSTEM CONFIGURATION
U I A
Menu
Parameter
0101
Mixed zone 1 Mixed zone 2 Mixed zone 3
High temperature zone 1 (fan coils /
radiators)
High temperature zone 2 (fan coils /
radiators)
High temperature zone 3 (fan coils /
radiators)
DHW
recircu-
lation
N-EM1
expansion
module
Mn01
0
X 0
Mn01
1
X X 1
Mn01
2
X 1
Mn01
3
X X 1
Mn01
4
X X X2
Mn01
5
X X X 2
Mn01
6
X X X X 2
Mn01
7
X X X X 2
Mn01
8
X X X X X 2
Mn01
9
X X 2
Mn01
10
X X X 2
Mn01
11
X X X X 2
Mn01
12
X X X X X 3
Mn01
13
X X X X X X 3
Mn01
14
X X X X 3
Il controllore della pompa di calore permette la configurazione di 15 differenti tipologie di impianto selezionabili impostando il parametro 0101. La tabella seguente riporta gli impianti configurabili.
Configuration 0 does NOT require additional expansion modules Configurations from 1 to 3 require 1 additional N-EM1 expansion module Configurations from 4 to 11 require 2 additional N-EM1 expansion modules Configurations 12, 13 and 14 require 3 additional N-EM1 expansion modules The water connection and wiring diagrams for configurations from 1 to 14 are shown on the instruction sheet enclosed with the N-EM1 expansion module.
The parameters required for correct system operation can be set on the A5 room controller supplied with the heat pump.
The next few pages are divided into the following sections:
Section 1 WATER CIRCUIT DIAGRAM Section 2 WIRING DIAGRAM Section 3 PARAMETER CONFIGURATION
T
T
ZONA "1"
5
T
T
ZONA "1"
5
T
T
ZONA "1"
5
ZONA "1"
T
T
M
5
ZONA "1"
T
T
M
5
ZONA "1"
T
T
M
5
54 AWR-MTD2-XE EN 11/2010
SYSTEM CONFIGURATION
U I A
Heat pump connection to the system without low-loss header. Make sure the useful pressure head of the circulating pump on the unit is sufficient for the pressure drop in the system. If the minimum system content does not reach val­ues shown in this manual, install an additional storage tank on the heat pump return pipe. No system configurations are required.
Water circuit diagram
T
CONFIGURATION "0"
AWR_MTD2_XE_0000.0
26/01/2011
REV_01
MT
6
7
8
T
T
ZONE "1"
9
T
T
F
N.C.
1
5
D
T
2
3
4
ACS
1
4
2
3
5
6
T
F
MT
7
8
9
APPLIANCES
PRESSURE GAUGE
THERMOMETER
FLOW SWITCH
VIBRATION DAMPER JOINT
SHUT-OFF VALVE
SAFETY VALVE WITH
PIPED DISCHARGE
CHECK VALVE
THERMOSTATIC MIXER
VENT VALVE
MEMBRANE EXPANSION
VESSEL
KEY TO THE SYMBOLS
DRAIN VALVE
CALIBRATING VALVE
HEAT PUMP OUTLET
HEAT PUMP RETURN
DOMESTIC HOT WATER
DOMESTIC COLD WATER
ELECTRICAL CONNECTIONS
INDICATES ACCESSORIES
(*) INSTALL A STORAGE TANK ON THE HEAT PUMP RETURN
IF THE SYSTEM WATER CONTENT IS LESS THAN THE VALUE DESCRIBED
IN THE TECHNICAL BULLETIN.
MEDIUM TEMPERATURE REVERSE-CYCLE UNIT, MODEL AWR MTD2 XE
RUBBER VIBRATION DAMPER KIT FOR FLOOR-STANDING
INSTALLATION
OUTSIDE AIR TEMPERATURE PROBE
(SUPPLIED AS STANDARD WITH THE HEAT PUMP)
REMOVABLE METAL MESH FILTER (1"1/4, 1"1/2 OR 2")
1”1/4 THREE-WAY SELECTOR VALVE FOR DHW PRODUCTION
DHW STORAGE TANK, MODEL HWC 300 OR HWC 500
STORAGE TANK FOR HEATED AND CHILLED WATER,
MODEL BT35, BT100 OR BT200 (*)
ELECTRIC HEATER KIT, 1-2-3 kW
ROOM UNIT (SUPPLIED AS STANDARD WITH THE HEAT PUMP)
N.B.: Typical water circuit diagram.
OUTSIDE INSIDE
LOW-LOSS
HEADER
SELF-CLEANING
FILTER
FROM WATER
MAINS
AUTOMATIC FILL
ASSEMBLY
“Y” FILTER
Water circuit diagram (not a working drawing)
55EN 11/2010 AWR-MTD2-XE
SYSTEM CONFIGURATION
U I A
Parameter configuration
Description Menu
Parameter
no.
Default
Write
set value
UOM
SYSTEM compensation curves in heating mode
Enable SYSTEM compensation curve
0= Disabled
1= Enabled
Mn01 0152 0 -
SYSTEM compensation curve number Mn01 0159 1 -
Enable room temperature influence on SYSTEM
0= Disabled
1= Enabled
Mn01 0163 0 -
SYSTEM Room Authority Mn01 0164 30 %
MINIMUM return set point limit for SYSTEM curve Mn01 0165 30 °C
MAXIMUM return set point limit for SYSTEM curve Mn01 0166 48 °C
SYSTEM compensation curves in cooling mode
Enable SYSTEM compensation curve
0= Disabled
1= Enabled
Mn01 0154 0 -
Maximum return temperature set point limit in cooling mode (Tm1) Mn01 0128 25 °C
Minimum outside temperature corresponding to max. return
temperature (Te1)
Mn01 0129 23 °C
Minimum return temperature set point limit in cooling mode (Tm2) Mn01 0130 23 °C
Maximum outside temperature corresponding to min. return
temperature (Te2)
Mn01 0131 36 °C
56 AWR-MTD2-XE EN 11/2010
SYSTEM CONFIGURATION
U I A
System number 0
Water circuit diagram
T
CONFIGURATION "0"
AWR_MTD2_XE_0000.1
26/01/2011
REV_01
MT
6
7
8
ZONE "1"
9
T
T
F
N.C.
1
5
D
T
2
3
4
ACS
T
T
1
4
2
3
5
6
T
F
MT
7
8
9
MEDIUM TEMPERATURE REVERSE-CYCLE UNIT, MODEL AWR MTD2 XE
HEAT PUMP OUTLET
HEAT PUMP RETURN
DOMESTIC HOT WATER
DOMESTIC COLD WATER
ELECTRICAL CONNECTIONS
INDICATES ACCESSORIES
RUBBER VIBRATION DAMPER KIT FOR FLOOR-STANDING
INSTALLATION
OUTSIDE AIR TEMPERATURE PROBE
(SUPPLIED AS STANDARD WITH THE HEAT PUMP)
REMOVABLE METAL MESH FILTER (1"1/4, 1"1/2 OR 2")
1”1/4 THREE-WAY SELECTOR VALVE FOR DHW PRODUCTION
DHW STORAGE TANK, MODEL HWC 300 OR HWC 500
ELECTRIC HEATER KIT, 1-2-3 kW
STORAGE TANK FOR HEATED AND CHILLED WATER,
MODEL BT35, BT100 OR BT200 (*)
HOT WATER RECIRCULATION
9 ROOM UNIT (SUPPLIED AS STANDARD WITH THE HEAT PUMP)
APPLIANCES
KEY TO THE SYMBOLS
PRESSURE GAUGE
THERMOMETER
FLOW SWITCH
VIBRATION DAMPER JOINT
SHUT-OFF VALVE
“Y” FILTER
SAFETY VALVE WITH
PIPED DISCHARGE
CHECK VALVE
THERMOSTATIC MIXER
VENT VALVE
MEMBRANE EXPANSION
VESSEL
DRAIN VALVE
CALIBRATING VALVE
N.B.: Typical water circuit diagram.
OUTSIDE INSIDE
LOW-LOSS
HEADER
SELF-CLEANING
FILTER
FROM WATER
MAINS
AUTOMATIC FILL
ASSEMBLY
Water circuit diagram (not a working drawing)
57EN 11/2010 AWR-MTD2-XE
SYSTEM CONFIGURATION
U I A
System number 0
Wiring diagram
CONFIGURATION "0"
AWR_MTD_XE_0000.1
26/01/2011
REV_01
6
7
8
ZONE "1"
9
1
5
D
T
3
1
3
567
8
9
NL
TxRx- TxRx+
GND
GND
24V
AC
230V
50 Hz
N 11 21 31
N 1 2 T1 T2U
230V
50 Hz
10 11 2145 46 9 41 42 51 52 5322 54 55
KM4BT11 YV5 BT8 A5
GND
TxRx+
TxRx-
GND
24
VAC
12 13
1
2
HL1
230V
50 Hz
L
SELECTOR VALVE
TERMINAL BLOCK
Brown
Black
Blue
Red
Green
Yellow/Green
Ausiliary
contact
Marrone
Nero
Blu
INSTALLER TERMINAL BLOCK
(CONTACTS USED)
OUTSIDE INSIDE
OUTSIDE AIR PROBE
TERMINAL BLOCK
ELECTRIC HEATER PANEL
TERMINAL BLOCK
ELECTRIC HEATER
TERMINAL BLOCK
PUMP TERMINAL BLOCK
ROOM CONTROLLER
TERMINAL BLOCK
APPLIANCES
MEDIUM TEMPERATURE REVERSE-CYCLE UNIT, MODEL AWR MTD2 XE
OUTSIDE AIR TEMPERATURE PROBE
(SUPPLIED AS STANDARD WITH THE HEAT PUMP)
1”1/4 THREE-WAY SELECTOR VALVE FOR DHW PRODUCTION
DHW STORAGE TANK, MODEL HWC 300 OR HWC 500
ELECTRIC HEATER KIT, 1-2-3 kW
STORAGE TANK FOR HEATED AND CHILLED WATER,
MODEL BT35, BT100 OR BT200 (*)
ROOM UNIT (SUPPLIED AS STANDARD WITH THE HEAT PUMP)
58 AWR-MTD2-XE EN 11/2010
SYSTEM CONFIGURATION
U I A
System number 0
Parameter configuration
Description Menu
Parameter
no.
Default
Write
set value
UOM
System type (table 1) Mn01 0101 0 0* -
SYSTEM compensation curves in heating mode
Enable SYSTEM compensation curve
0= Disabled
1= Enabled
Mn01 0152 0 -
SYSTEM compensation curve number Mn01 0159 1 -
Enable room temperature influence on SYSTEM
0= Disabled
1= Enabled
Mn01 0163 0 -
SYSTEM Room Authority Mn01 0164 30 %
MINIMUM return set point limit for SYSTEM curve Mn01 0165 30 °C
MAXIMUM return set point limit for SYSTEM curve Mn01 0166 48 °C
SYSTEM compensation curves in cooling mode
Enable SYSTEM compensation curve
0= Disabled
1= Enabled
Mn01 0154 0 -
Maximum return temperature set point limit in cooling mode (Tm1) Mn01 0128 25 °C
Minimum outside temperature corresponding to max. return
temperature (Te1)
Mn01 0129 23 °C
Minimum return temperature set point limit in cooling mode (Tm2) Mn01 0130 23 °C
Maximum outside temperature corresponding to min. return
temperature (Te2)
Mn01 0131 36 °C
Contact HL1 configuration, secondary circuit pump
Enable contact HL1 HIGH TEMPERATURE ZONE The contact closes and the pump or motor-driven shut-off valve is activated)
Mn01 015A 0 3*
* obligatory values for the present configuration
59EN 11/2010 AWR-MTD2-XE
REGOLAZIONE IMPIANTO E CARATTERISTICHE DI FUNZIONAMENTO
U I A
MAINTENANCE AND SERVICE
A
Alarm signals
When an alarm is activated, the symbol comes one.
Displaying alarms
x3 sec.
• Press the and buttons for 3 sec­onds
• Turn the knob
• Display the alarm codes
• Press the knob to confirm
• Resolve the problem and then reset the alarms using the procedure described in “Resetting alarms”
1 2 3
Resetting alarms
Alarm log
The alarm log can only be displayed using the service key­pad. Contact an authorised service centre.
The room controller can display the most recently activated alarm code from Mn11:
- parameter 1100 = no. of alarms saved in the log (visible only with service keypad)
- parameter 1101= code of last alarm activated
- parameter 1102= alarm activation hour
- parameter 1103= alarm activation minutes
- parameter 1104= alarm activation day
- parameter 1105= alarm activation month
- parameter 1106= alarm activation year
x3 sec.
• Press the and buttons for 3 sec­onds
• Turn the knob
• Select
• Press the knob to confirm
• Alarms reset
1 2 3
60 AWR-MTD2-XE EN 11/2010
MAINTENANCE AND SERVICE
A
ALARM TABLE
Alarm code Cause Solution
A001 BT1 System heat exchanger water inlet temperature probe Probe faulty or disconnected A002 BT2 System heat exchanger water outlet temperature probe Probe faulty or disconnected A003 BT8 DHW storage temperature probe Probe faulty or disconnected A004 BT7 Outside air temperature probe for unit management Probe faulty or disconnected A005 BT9 Storage tank temperature probe Probe faulty or disconnected A006 BT11 Outside air temperature probe Probe faulty or disconnected A007 BP1 High pressure transducer Transducer faulty or disconnected
A013 F1 High pressure switch
Check connection Check refrigerant circuit pressure
A014 High pressure measured by transducer BP1
A019 Difference between low and high pressure in refrigerant circuit too low
Check refrigerant circuit pressure Check refrigerant charge
A022 Operation outside of limits
Make sure outside air temperature and water tempera­ture set point are inside the specified operating limits
A023 Source differential pressure switch/flow switch activated
Make sure the filter is clean Make sure the system is filled with water Check water flow-rate
A025 Differential pressure switch / system flow switch F3 activated
Make sure filters are clean Check water flow
Check for air in the system A030 Compressor operating hours reached Scheduled maintenance A033 System pump operating hours reached Scheduled maintenance A034 Domestic hot water pump operating hours reached Scheduled maintenance A035 Mixed zone pump operating hours reached Scheduled maintenance A036 Fan operating hours reached Scheduled maintenance A038 System heat exchanger frost prevention alarm Scheduled maintenance A041 DHW storage temperature too high A042 Inside frost prevention alarm
A045 Outside air temperature probe
Check connections
Faulty probes, replace terminal A047
Thermostatic valve driver Contact service centre
A048 A049 A050 A051 A052 A053 A054 Legionella prevention alarm
A055 Temperature probe N-THC n.1
Check connections
Probe faulty or disconnected
A056 Address setting error on remote terminal supplied with the unit
Check connections
Check address
A057 Address setting error on expansion module 2
Check connections
Check address, must be 1 A058 Temperature probe in low temperature zone LT2, expansion 2 Probe faulty or disconnected
A063 Address setting error on expansion module 3
Check connections
Check address, must be 2 A064 Temperature probe in low temperature zone LT3, expansion 3 Probe faulty or disconnected A075 Water temperature too high in mixed circuit, expansion module 1 A077 Water temperature too high in mixed circuit, expansion module 2 A094 End defrost due to maximum time
A095 Temperature probe N-THC n.2
Check connections
Probe faulty or disconnected
A096 Address setting error on zone remote terminal
Check connections
Check address
A097 Temperature probe N-THC n.3
Check connections
Probe faulty or disconnected
A098 Address setting error on zone remote terminal
Check connections
Check address
A099 Temperature probe N-THC n.4
Check connections
Probe faulty or disconnected
A100 Address setting error on zone remote terminal
Check connections
Check address
A101 Temperature probe N-THC n.5
Check connections
Probe faulty or disconnected
A102 Address setting error on zone remote terminal
Check connections
Check address
A103 Address setting error on expansion module 1
Check connections
Check address, must be 1 A104 Low temperature zone LT1 temperature probe, expansion 1 Probe faulty or disconnected
A109 Low pressure alarm from low pressure switch
Check connection
Check refrigerant circuit pressure
A114 Solar/pool module address setting error
Check connections
Check address A115 Solar/pool module general alarm A116 Master unit not connected, cascade control A117 Slave unit not connected, cascade control A120 Water temperature too high in mixed circuit, expansion module, expansion module 3
A121 Temperature probe N-THC n.6
Check connections
Probe faulty or disconnected
A122 Address setting error on zone LT3 remote terminal
Check connections
Check address
61EN 11/2010 AWR-MTD2-XE
MAINTENANCE AND SERVICE
A
ALARM TABLE
The heat pumps can be fitted with a single-phase or three-phase peak limiter to reduce compressor start-up current.
Peak limiter single-phase
The LED on the peak limiter identifies different operating or alarm conditions based on the sequence of flashes:
• 2 flashes every 5 sec.: line voltage present, correct operation
• LED on for 5 sec. and LED off for 5 sec.: peak limiter faulty
• quick flashes for 10 sec.: line voltage out-of-range
PEAK LIMITER ALARM SIGNALS
A
Alarm code Cause Solution
A124 Humidity probe N-THC n.1
Check connections Probe faulty or disconnected
A125 Humidity probe N-THC n.2
Check connections Probe faulty or disconnected
A126 Humidity probe N-THC n.3
Check connections Probe faulty or disconnected
A127 Humidity probe N-THC n.4
Check connections Probe faulty or disconnected
A128 Humidity probe N-THC n.5
Check connections Probe faulty or disconnected
A129 Humidity probe N-THC n.6
Check connections Probe faulty or disconnected
62 AWR-MTD2-XE EN 11/2010
MAINTENANCE AND SERVICE
A
SYSTEM emergency operation
If the heat pump is not working correctly or the compressor has shut down, emergency operation can be activated. Emergency operation involves heating the water using the electric heaters available on the system (outlet, storage tank). The compressor remains off.
To enable manual operation of system heaters, set parame­ter 0620 = 1 (manual)
DOMESTIC HOT WATER emergency operation
If the heat pump is not working correctly or the compressor has shut down, emergency operation can be activated. Emergency operation involves heating the domestic hot water using the electric heater inside the storage tank.
To enable manual operation of DHW storage heaters, set parameter 0202 = 1
Description
Electric heater operating mode 0 = heat pump only 1 = electric heater only 2 = heat pump + electric heater
Menu
Mn02
Parameter
no.
0202
Valore da
impostare
1
UOM
SCHEDULED MAINTENANCE
A
Never perform any cleaning operations before having
disconnected the unit from the mains power supply. Make sure power is not connected before proceeding. Control maintenance is fundamental to maintain the efficien­cy of the unit both in terms of operation and energy con­sumption. The Technical Service maintenance plan must be observed, with an annual service which includes the following opera­tions and checks:
- Filling of the water circuit;
- Presence of air bubbles in the water circuit;
- Efficiency of safety devices;
- Power supply voltage;
- Electrical power input;
- Tightness of electrical and water connections;
- Condition of the compressor contactor;
- Efficiency of the plate heat exchanger resistor;
- Verification of operating pressure, superheating and sub­cooling
- Efficiency of the compressor heater
- Cleaning of the finned coil every three months
- Cleaning of the fan grills
- Cleaning of condensate drain pan.
- Cleaning of water filters.
- Checking the ventilation openings on the base are free of leaves, bushes or anything else that may obstruct air flow.
For units installed near the sea, the intervals between main­tenance should be halved.
SHUTTING DOWN FOR LONG PERIODS
A
After deactivating the heat pump:
- Disconnect the unit from the power supply.
- Make sure the remote keypad is in the “OFF” position.
- Place QF1 in the OFF position (see wiring diagram).
- Deactivate the indoor terminal units by placing the switch of each unit in the “OFF” position.
- Close the water valves.
If the outside temperature may fall below zero; there is the risk of freezing. The water circuit MUST BE EMPTIED AND CLOSED (if draining after operation in heat pump mode, beware that
the water may be hot), or antifreeze must be added in the proportion recommended by the manufacturer. It is recommended to use non-toxic food grade antifreeze, compliant with the standards in force in the countries where the unit is used, if domestic hot water production is also featured. If the mains switch is turned to “off” for more than four hours, after turning it on and before reactivating the unit, leave the power on but the unit deactivated for at least two hours to preheat the oil in the compressor sump.
Description
Type of outlet electric heater oper­ation 0 = Supplementary 1 = Replacement Enable manual heater operation
Menu
Mn01
Mn06
Parameter
no.
010G
0620
Default
1
1
UOM
Set the parameters following the sequence described in the table
63EN 11/2010 AWR-MTD2-XE
UNSCHEDULED MAINTENANCE
A
Never perform any cleaning operations before having
disconnected the unit from the mains power supply. Make sure power is not connected before proceeding.
CHEMICAL WASHING
It is recommended to chemically flush the plate heat exchanger after every 3 years of operation. To perform this operation, contact a specialist technician.
REFRIGERANT GAS CHARGE
The chillers are filled with R410A refrigerant gas and tested in the factory. In normal conditions, there should be no need for the Tech­nical Service to intervene to check the refrigerant gas. However, over time, small leaks may develop at the joints leading to loss of refrigerant and draining of the circuit, causing the unit to function poorly. In this case, the leaks of refrigerant must be identified and repaired and the refrigerant circuit recharged. Proceed as follows:
- Empty and dry the entire refrigerant circuit using a vacuum pump connected to the low and high pressure tap until the vacuometer reads about 10 Pa. Wait a couple of minutes and check that this value does not rise to more than 50 Pa.
- Connect the refrigerant gas cylinder or a filling cylinder to the low pressure line pressure gauge connection
- Charge the quantity of refrigerant indicated on the unit’s rating plate.
- Always check the superheating and subcooling values, which should be between 5 and 10°C and 4 and 8°C.
- After a couple of hours operation, check that the liquid indicator indicates a dry circuit (dry-green).
In the event of partial leaks, the circuit must be com­pletely emptied before being recharged. The R410A refrigerant must only be charged in the liq­uid state. Operating conditions other than rated conditions may produce considerably different values. Tightness testing or identification of leaks must only be carried out using R410A refrigerant gas, checking with a suitable leak detector. The refrigerant circuit must not be charged with a refrigerant other than that indicated on the rating plate and in this manual. The use of a different refrigerant may cause serious damage to the compressor.
Oxygen, acetylene or other flammable or poisonous gas­es must never be used in the refrigerant circuit as they may cause explosion or poisoning. Oils other than those indicated must not be used. The use of different oil may cause serious damage to the compressor.
DISPOSAL
A
The unit must be disposed of according to the legislation
in force in the country concerned
64 AWR-MTD2-XE EN 11/2010
LIST OF PARAMETERS
U I A
Description Menu Parameter no. UOM
Enable domestic hot water set point: 0 = Economy, 1 = Comfort Mn00 0015
Domestic hot water Economy set point Mn00 0022 °C
Domestic hot water Comfort set point Mn00 0023 °C
User password Mn00 0036
Enable remote contact: 0= remote contact enabled, 1= remote contact disabled (selection from keypad only) Mn01 0100
Automatic mode changeover set point in HEATING Mn01 0106 °C
Automatic mode changeover differential in HEATING Mn01 0107 °C
Automatic mode changeover set point in COOLING Mn01 0108 °C
Automatic mode changeover differential in COOLING Mn01 0109 °C
Type of outlet heater operation: 0 = Supplementary , 1 = Replacement Mn01 010G
Type of boiler operation: 0 = Supplementary , 1 = Replacement Mn01 010H
Maximum return set point limit in cooling mode (Tm1) Mn01 0128 °C
Outside minimum temperature corresponding to max. return temperature (Te1) Mn01 0129 °C
Enable compensation for room humidity, ZONE LT3: 0= Disabled , 1= Enabled Mn01 012N
Room relative humidity value to start increasing water outlet temperature set point, ZONE LT3 Mn01 012P %
Maximum outlet temperature hysteresis corresponding to 100% relative humidity Mn01 012R °C
Minimum return set point limit in cooling mode (Tm2) Mn01 0130 °C
Maximum outside temperature corresponding to min. return temperature (Te2) Mn01 0131 °C
Maximum outlet temperature set point limit in cooling mode (Tm1) Mn01 0132 °C
Minimum outside temperature corresponding to max. outlet temperature (Te1) Mn01 0133 °C
Minimum outlet temperature set point limit in cooling mode (Tm2) Mn01 0134 °C
Maximum outside temperature corresponding to min. outlet temperature (Te2) Mn01 0135 °C
Maximum outlet temperature set point limit in cooling mode (Tm1) Mn01 0136 °C
Minimum outside temperature corresponding to max. outlet temperature (Te1) Mn01 0137 °C
Minimum outlet temperature set point limit in cooling mode (Tm2) Mn01 0138 °C
Maximum outside temperature corresponding to min. outlet temperature (Te2) Mn01 0139 °C
Inside temperature to enable frost protection Mn01 0140 °C
Outside air temperature for frost protection Mn01 0141 °C
Enable SYSTEM compensation curve 0= Disabled 1= Enabled Mn01 0152
Fixed return water temperature set point in HEATING Mn01 0153 °C
Enable SYSTEM compensation curve: 0= Disabled, 1= Enabled Mn01 0154
Fixed return water temperature set point in COOLING Mn01 0155 °C
Enable compensation for room humidity, SYSTEM: 0= Disabled , 1= Enabled Mn01 0156
Room relative humidity value to start increasing SYSTEM return water set point Mn01 0157 %
Maximum return temperature hysteresis corresponding to 100% relative humidity Mn01 0158 °C
SYSTEM compensation curve number Mn01 0159
Enable contact as: 0= Alarm signal, 1= Dehumidifier, 3= Secondary circuit pump Mn01 015A
Enable compensation curve for zone LT3 0= Disabled 1= Enabled Mn01 015E
Enable room temperature influence on SYSTEM 0= Disabled 1= Enabled Mn01 0163
SYSTEM Room Authority Mn01 0164 %
Minimum set point limit for SYSTEM curve Mn01 0165 °C
Maximum set point limit for SYSTEM curve Mn01 0166 °C
Enable compensation curve for zone LT1 0= Disabled 1= Enabled Mn01 0167
Enable compensation curve for zone LT1: 0= Disabled, 1= Enabled Mn01 0169
Enable compensation for room humidity, ZONE LT1: 0= Disabled , 1= Enabled Mn01 0171
Room relative humidity value to start increasing water outlet temperature set point, ZONE LT1 Mn01 0172 %
Maximum outlet temperature hysteresis corresponding to 100% relative humidity Mn01 0173 °C
Zone LT1 compensation curve number Mn01 0174
Enable room temperature influence on LT1 0= Disabled 1= Enabled Mn01 0178
LT1 Room Authority Mn01 0179 %
MINIMUM outlet set point limit for compensation curve in zone LT1 Mn01 0180 °C
MAXIMUM outlet set point limit for compensation curve in zone LT1 Mn01 0181 °C
Enable compensation curve for zone LT2 0= Disabled 1= Enabled Mn01 0182
Enable compensation curve for zone LT2: 0= Disabled, 1= Enabled Mn01 0184
Enable compensation for room humidity, ZONE LT2: 0= Disabled , 1= Enabled Mn01 0186
Room relative humidity value to start increasing water outlet temperature set point, ZONE LT2 Mn01 0187 %
Maximum outlet temperature hysteresis corresponding to 100% relative humidity Mn01 0188 °C
Zone LT2 compensation curve number Mn01 0189
Enable room temperature influence on LT2 0= Disabled 1= Enabled Mn01 0193
LT2 Room Authority Mn01 0194 %
MINIMUM outlet set point limit for compensation curve in zone LT2 Mn01 0195 °C
MAXIMUM outlet set point limit for compensation curve in zone LT2 Mn01 0196 °C
Electric heater operating mode: 0 = heat pump only, 1 = electric heater only, 2 = heat pump + electric heater Mn02 0202
Domestic hot water set point with heater Mn02 0209 °C
65EN 11/2010 AWR-MTD2-XE
LIST OF PARAMETERS
U I A
Description Menu Parameter no. UOM
Domestic hot water temperature set point for Legionella prevention Mn02 0211 °C
Legionella prevention cycle day MONDAY (0=no 1=yes) Mn02 0213
Legionella prevention cycle day TUESDAY (0=no 1=yes) Mn02 0214
Legionella prevention cycle day WEDNESDAY (0=no 1=yes) Mn02 0215
Legionella prevention cycle day THURSDAY (0=no 1=yes) Mn02 0216
Legionella prevention cycle day FRIDAY (0=no 1=yes) Mn02 0218
Legionella prevention cycle day SATURDAY (0=no 1=yes) Mn02 0219
Legionella prevention cycle day SUNDAY (0=no 1=yes) Mn02 0220
Legionella prevention cycle time Mn02 0221 h
Enable Legionella prevention function 0 = Not enabled 1 = Enabled Mn02 0222
Legionella prevention function with: 0 = heat pump only 1 = electric heater only 2 = heat pump + electric heater Mn02 0223
Maximum Legionella prevention function duration Mn02 0225 min.
Enable electric heater: 0 = Heater not enabled, 1 = Heater enabled Mn03 0300
Enable boiler: 0 = Boiler not enabled, 1 = Boiler enabled Mn03 0301
Activation for low outside air temperature: 0 = Function not enabled, 1 = Function enabled Mn03 0303
Outside air temperature to enable electric heater Mn03 0304 °C
Activation for low outside air temperature: 0 = Function not enabled, 1 = Function enabled Mn03 0306
Outside air temperature to enable boiler Mn03 0307 °C
Minimum outside air temperature for heat pump operation (make sure the value shown in the table is set)
Mn03 0311 °C
Electric heater activation delay time (allows the heat pump to reach steady operation and thus avoid activating the heater when not needed)
Mn06 0616 min.
Integration time to activate outlet electric heaters Mn06 0617 °C*sec
Boiler activation delay time (allows the heat pump to reach steady operation and thus avoid activating the boiler when not needed)
Mn06 0618 min.
Integration time to activate boiler Mn06 0619 °C*sec
Enable manual heater operation Mn06 0620
Relationship between plant and ambient: 0 = Unit work on ambient request, 1 = Unit work indipendent Mn01 011D
Installer password Mn01 011G
Enable compensation curve for LT3 in HEATING 0= Disabled (fixed set point operation) 1= Enabled Mn01 011R
Enable compensation curve for zone LT3: 0= Disabled, 1= Enabled Mn01 011T
Fixed water outlet temperature set point for LT3 in HEATING Mn01 011U °C
Zone LT3 compensation curve number Mn01 012A
Enable room temperature influence on LT3 0= Disabled 1= Enabled Mn01 012D
LT3 Room Authority Mn01 012E %
MINIMUM outlet set point limit for compensation curve in zone LT3 Mn01 012F °C
MAXIMUM outlet set point limit for compensation curve in zone LT3 Mn01 012G °C
Maximum outlet temperature set point limit in cooling mode (Tm1) Mn01 012H °C
Minimum outside temperature corresponding to max. outlet temperature (Te1) Mn01 012J °C
Minimum outlet set point limit in cooling mode (Tm2) Mn01 012L °C
Minimum outside temperature corresponding to min. outlet temperature (Te2) Mn01 012M °C
Activation of system pump operation at intervals: 0= system pump always on, 1=system pump operation at intervals Mn01 0143
System pump operating time in sniffing mode Mn01 0147
System pump off time between one sniffing cycle and the next Mn01 0148
Enable contact as: 0 =Reduced electricity rate, 1=Stop operation due to excess power consumption Mn01 015D
Enable compensation curve for LT1 in HEATING 0= Disabled (fixed set point operation) 1= Enabled Mn01 0168
Fixed water outlet temperature set point for LT1 in HEATING Mn01 0170 °C
Enable compensation curve for LT2 in HEATING 0= Disabled (fixed set point operation) 1= Enabled Mn01 0183
Fixed water outlet temperature set point for LT2 in HEATING Mn01 0185 °C
Minimum heat pump operating time for system Mn02 0226
Maximum heat pump operating time to reach domestic hot water set point Mn02 0227
Three-way valve travel time for domestic hot water production Mn02 0231 sec.
BT1 Heat exchanger water inlet temperature probe Mn09 0900 °C
BT2 Heat exchanger water outlet temperature probe Mn09 0901 °C
BT8 Domestic hot water probe Mn09 0902 °C
BT7 Unit control air temperature probe Mn09 0903 °C
BT9 Storage tank probe Mn09 0904 °C
BT11 Outside air temperature probe for set point management Mn09 0905 °C
BP1 Condenser/evaporator control pressure transducer Mn09 0906 bar
66 AWR-MTD2-XE EN 11/2010
INSTALLER OPERATIONS CHECKLIST
U I A
Installer: __________________________________________ Designer: _______________________________________
Type of application:___________________________________________________________________________________
Street ___________________________________________________________________________ number _____________
City/town __________________________ Postcode/ZIP code _____________ Province/State _________________________
Unit model installed ________________________________________ Serial number _________________________________
Is there a system design? YES NO If YES, has the system been developed completely in accordance with the design? YES NO
Installation date: ____________________________________
Systems included:
• Winter heating AT (radiators)
• Winter heating MT (fan coil)
• Winter heating BT (radiant panels)
• Summer cooling
• DHW production
• Solar thermal installed
❑❑
❑❑
Heating system circuit
Mark the type of system installed and describe the components in the corresponding tables
Storage tank
Additional
expansion vessel
Volume [l]
Type/model
Secondary pump
Installed?
Type/model
Domestic hot water circuit
Storage tank
with coil
Volume [l]
Type/model
Coil water volume [l]
Coil heat exchange area [m2]
Storage
cylinder
Expansion
vessel
Hot water set point: __________ °C
Cold water set point: __________ °C
Domestic hot water set point: __________ °C
HEAT
PUMP
HEAT
PUMP
HEAT
PUMP
HEAT
PUMP
HEAT
PUMP
67EN 11/2010 AWR-MTD2-XE
INSTALLER OPERATIONS CHECKLIST
U I A
CONCERNING UNIT INSTALLATION OPERATIONS AND SETUP FOR COMMISSIONING,
HAVE THE FOLLOWING CHECKS BEEN COMPLETED?
Components installed (as described in the paragraph on "Water circuit connections") YES NO
• Two pressure gauges with a suitable scale are installed on the inlet and outlet
❑❑
• Shut-off valves are installed on the heating system circuit and domestic hot water circuit inlet and outlet ❑❑
• Two thermometers are installed, on the inlet and outlet ❑❑
• All pipes are insulated with suitable vapour barrier material to prevent formation of condensate and heat loss, ❑❑ with control and shut-off devices protruding from the insulation
• Drain valves are installed at the lowest points in the system
❑❑
• Automatic or manual air vent valves are installed at the highest points in the system ❑❑
• An additional expansion vessel is installed on the system if the standard vessel is insufficient ❑❑
• Vibration damper joints are installed on the inlet and outlet water pipes ❑❑
• A low-loss header is installed if the water content is insufficient ❑❑
• Vibration damper supports are installed on the unit ❑❑
• The domestic hot water production system is installed ❑❑
• The safety valve is installed and suitably sized ❑❑
• The domestic hot water expansion vessel is installed and suitably sized ❑❑
Checks (as described in the paragraph on "Checking and starting up the unit")
• Two pressure gauges with a suitable scale are installed on the inlet and outlet
• The unit is positioned as described in the chapter on "Positioning" in this manual
• The filter is installed on the system return/inlet as close as possible to the unit and in a position that is easy to access for maintenance. REQUIRED component, this must be installed before water circulates through the heat
exchanger otherwise the warranty will be void
• The filter is installed on the domestic hot water return/inlet as close as possible to the unit and in a position that is easy to access for maintenance. REQUIRED component, this must be installed before water circulates through the heat exchanger otherwise the warranty will be void
• (Water-to-water units only) The filter is installed on the source return/inlet as close as possible to the unit and in a position that is easy to access for maintenance. REQUIRED component, this must be installed before water circulates through the heat exchanger otherwise the warranty will be void
• The flow switch is installed on the unit's outlet to the heating system circuit and is electrically connected.
REQUIRED component, this must be installed before water circulates through the heat exchanger otherwise the warranty will be void
• (Water-to-water units only) The flow switch is installed unit's outlet to the source circuit and is electrically connected. REQUIRED component, this must be installed before water circulates through the heat exchanger
otherwise the warranty will be void
CHECKED
68 AWR-MTD2-XE EN 11/2010
INSTALLER OPERATIONS CHECKLIST
U I A
Checks (as described in the paragraph on "Checking and starting up the unit")
• The connection pipes are suitably supported so that these do not weigh on the appliance
• Correct sizing of the expansion vessel has been verified according to the system water content and the expected operating temperature
• The position of the outside air temperature probe complies with the information provided in the installation manual
• The position of the room controllers installed complies with the information provided in the installation manual
• The position of the DHW storage tank probe complies with the information provided in the installation manual
• (Units with heat recovery only) The non-return valve is fitted on the domestic hot water circuit
• All safety conditions have been respected
• The unit is fixed to the surface it rests on
• Water connections have been carried out as indicated in the installation manual
• All water connections are tight
• All electrical connections are tight
• Make sure the water circuit has been washed and drained
• There is no air in the system (vent if necessary)
• The valves on the water circuit are open
• Electrical connections have been carried out correctly
• Voltage is within a tolerance of 10% of the rated voltage for the unit
• Unbalance between phases is less than 2%, for three-phase units
• Maintenance clearances comply with the specifications in the Installation manual under the section on POSITIONING
• Power supply electrical complies with the data on the rating plate and specified in the Installation manual under the section on MAINS POWER SUPPLY CONNECTION
• The system water content complies with the specifications in the Installation manual under the section on WATER CONNECTIONS
• Suitable water flow-rate for operation of the entire unit is guaranteed as specified in the Installation manual under the section on WATER CONNECTIONS
• (Air-to-water units only) The system has been protected with antifreeze, respecting the quantities shown in the Installation manual under the section on WATER CONNECTIONS
• The DHW storage tank has been fitted with an electric heater for Legionella prevention
CHECKED
It is hereby declared that the site and access to the site where the unit to be operated or serviced is installed has been made safely accessible in compliance with all safety standards specified by Italian law 81/08 in force. A supervisor must be present on site to inform workers of residual risks in the workplace.
WARNING:
Failure to complete commissioning due to causes not attributable to the unit will require a second visit, to be charged to the cus­tomer directly by the local service centre.
Installer's signature ___________________________________________________ Date ________________________
Sede Legale: Via L.Seitz, 47 - 31100 Treviso Sede Amm.va: Via Sarson, 57/S - 36061 Bassano del Grappa (VI) - Italia
COD. C01001823E_01
Loading...