DeLonghi AWR-MTD2-XEH, AWR-MTD2-XE-0031, AWR-MTD2-XE-0041, AWR-MTD2-XE-0051, AWR-MTD2-XE-0061 Installation, Operation And Service Manual

...
INSTALLATION - OPERATING - SERVICE MANUAL
Reverse-cycle air/water heat pumps with domestic hot water production, axial-flow fans and water pump assembly.
EN
AWR-MTD2-XE 0011÷0091
2 AWR-MTD2-XE EN 11/2010
U I A
User
Installer
Assistance
Important
Prohibition
Danger voltage
Danger high temperatures
INDEX
U I A
The manufacturer reserves the right to modify the data in this manual without warning.
Eurovent certification program.
The following symbols are used in this publication and inside the unit:
U
I
A
General warnings 3
Waiver of liability 3
Fundamental safety rules 3
Receiving and handling the product 4
Unit identification 5
Description of standard unit 6
Dimensioned drawings 7
Installation 7
Water connections 8
Electrical connections 11
Installer connections 12
Mains power supply connections 15
Installer connections 14
General technical data 32
Operating limits 33
Pump curve 34
Checking and starting up the unit 36
Description of room controller buttons and 38 display
Operation and functions of the room controller 39
Control and operating characteristics 48
System configuration 53
Maintenance and service 59
Peak limiter alarm signals 61
Shutting down for long periods 62
Scheduled maintenance 62
Unscheduled maintenance 63
Disposal 63
List of parameters 64
Installer operations CHECKLIST 66
U I A A
UUI A
I A
I
IU
I A
A
A
I
I
IIA
A
I A
I A
I A
I A
I A
I A
A
A
A
AIU
A
A
A
A
A
A
AIU
AIU
3EN 11/2010 AWR-MTD2-XE
GENERAL WARNINGS
U I A
FUNDAMENTAL SAFETY RULES
U I A
These appliances have been designed to chill and/or
heat water and must be used in applications compatible with their performance characteristics; these appliances are designed for residential or similar applications. Incorrect installation, regulation and maintenance or improper use absolve the manufacturer from all liability, whether contractual or otherwise, for damage to people, animals or things. Only those applications specifically indicated in this list are permitted Read this manual carefully. All work must be carried out by qualified personnel in conformity with legislation in force in the country concerned.
The warranty is void if the above instructions are not respected and if the unit is started up for the first time without the presence of personnel authorised by the Company (where specified in the supply contract) who should draw up a “start-up” report.
The documents supplied with the unit must be con­signed to the owner who should keep them carefully for future consultation in the event of maintenance or service. All repair or maintenance work must be carried out by the Company’s Technical Service or qualified personnel following the instructions in this manual. The air-conditioner must under no circumstances be modified or tampered with as this may create situations of risk. Failure to observe this condition absolves the manufacturer of all liability for resulting damage.
When operating equipment involving the use of electricity and water, a number of fundamental safety rules must be observed, namely:
The unit must not be used by children or by unfit per­sons without suitable supervision. Do not touch the unit with bare feet or with wet or damp parts of the body. Never perform any cleaning operations before having disconnected the unit from the mains power supply. Do not modify safety or control devices without authori­sation and instructions from the manufacturer. Do not pull, detach or twist the electrical cables coming from the unit, even when disconnected from the mains electricity supply. Do not open doors or panels providing access to the internal parts of the unit without first ensuring that the switch QF1 is in the OFF position (see the wiring dia­gram). Do not introduce pointed objects through the air intake and outlet grills. Do not dispose of, abandon or leave within reach of children packaging materials (cardboard, staples, plastic bags, etc.) as they may represent a hazard.
Respect safety distances between the unit and other equipment or structures. Guarantee adequate space for access to the unit for maintenance and/or service opera­tions. Power supply: the cross section of the electrical cables must be adequate for the power of the unit and the pow­er supply voltage must correspond with the value indicat­ed on the respective units. All units must be earthed in conformity with legislation in force in the country con­cerned.
Terminals 6, 7, 9, 10, 11, 12, 13, 21, 22, 23, 24, may be live even after the unit is disconnected. Make sure power is not connected before proceeding. Water connections should be carried out as indicated in the instructions to guarantee correct operation of the unit. Add glycol to the water circuit if the unit is not used during the winter or the circuit is not emptied. Handle the unit with the utmost care (see weight distrib­ution table) to avoid damage.
WAIVER OF LIABILITY
This publication is the sole property of Manufacturer. Any reproduction or disclosure of such is strictly prohibited with­out the written authorisation of Manufacturer. This document has been prepared with maximum care and attention paid to the content shown. Nonetheless, Manufac- turer waives all liability deriving from the use of such docu­ment.
Read this document carefully. All work must be performed, components selected and materials used in complete accor­dance with the legislation in force in material in the country concerned, and considering the operating conditions and intended uses of the system, by qualified personnel.
U I A
4
AWR-MTD2-XE EN 11/2010
Dimensions 0011 0025 0031 0041 0051 0061 0091
Dimension L mm 970 970 970 970 970 1600 1600 Dimension P mm 525 525 525 525 525 610 610 Dimension H mm 1450 1450 1450 1600 1600 1360 1850 Gross weight Kg 165 170 175 190 200 275 360
VISUAL INSPECTION
When the items are consigned by the carrier:
- make sure that the goods delivered correspond to the description on the delivery note, comparing this against the data on the packaging label.
- make sure the packaging and the unit are intact.
If damage or missing components are noted, indicate this on the delivery note. A formal complaint should be sent via fax or registered post to the After Sales Department within eight days from the date of receipt of the items.
HANDLING PACKAGED UNITS
The unit should always be handled by qualified personnel using equipment adequate for the weight of the unit, in com­pliance with the safety standards in force (and subsequent amendments).
Lifting by forklift (1) Insert the forks under the long side of base, opening the forks as fare as possible.
Lifting by crane (2) Use slings with hooks suitable for the weight being lifted. Secure the hook to the lifting bracket fixed to the unit, use always four equal length slings, as shown in the figure, to ensure the weight is balanced.
REMOVING THE PACKAGING
The packaging must be removed by the operator using suit­able protective equipment (gloves, glasses, etc.). Take special care not to damage the unit. Observe the local standards in force as regards disposal of the packaging, using specialist collection or recycling centres.
Do not dispose of packaging materials in the environ­ment or leave them within reach of children as they may represent a hazard.
Envelope A, located in the compressor compartment, con­tains:
• instruction manual;
• warranty certificate;
• CE declaration;
• list of the main components and sub-assemblies fitted on the product
• remote room control unit A5 (must be installed)
• DHW storage water temperature probe BT8
• outside air temperature probe BT11 (must be installed)
• probe BT9 only to be installed when supplementary source is available
Make sure the components listed above are not lost or mis­placed.
The instruction manual is an integral part of the unit and should therefore be read and kept carefully.
STORING THE UNITS
The units must be stored sheltered from direct sunlight, rain, wind or sand. Avoid exposing the units to direct sunlight, as the pressure inside the refrigerant circuit may reach dangerous values and cause the activation of the safety valves, where fitted. The units cannot be stacked.
RECEIVING AND HANDLING THE PRODUCT
I A
H
P
L
Bar code
(compressor side)
A
1
2
5EN 11/2010 AWR-MTD2-XE
RECEIVING AND HANDLING THE PRODUCT
I A
HANDLING UNPACKAGED UNITS
When the packaging has been removed:
• Remove the wooden base.
• Fit the vibration damping feet (accessories).
• Handle the unit using equipment that is suitable for its weight (forklift or crane), in compliance with the safety standards in force (and subsequent amendments).
• Do not drag the unit as the feet may be damaged or break.
Hole Ø22
UNIT IDENTIFICATION
U I A
The heat pump can be identified from:
PACKAGING LABEL
Describes the product identification data
RATING PLATE
Describes the unit technical and performance specifications. Shows the serial number used to uniquely identify the unit. The serial number is also used to identify the unit’s spare parts.
If service is required, the following information must be pro­vided to the service centre: Model, serial number, year of production.
Installation and maintenance operations are much more difficult if the identification plates or anything else need­ed to clearly identify the product are tampered with, removed or missing.
NOMENCLATURE
Packaging label
Rating plate with serial number
AWR MTD2 XE 0011 m s
Power supply voltage: m = 230V/50Hz/1ph t = 400V/3N/50Hz
size
s = peak limiter
Model
6 AWR-MTD2-XE EN 11/2010
DESCRIPTION OF STANDARD UNIT
I A
These air cooled reverse-cycle chillers with axial-flow fans operate with R410A refrigerant fluid and are suitable for out­door installation. The units are CE marked, as established by the EU directives, including the latest amendments, and the corresponding approximated national legislation.
They are factory tested and on site installation is limited to water and electrical connections.
VERSIONS AVAILABLE
AWR-MTD2-XE
Reverse-cycle air/water heat pump with domestic hot water production. Built-in water pump assem­bly without electric heaters.
11
10
15
13
4
20
14
6
8 5
12
3
19
18
17
16
21
9
1
2
7
1 Electrical panel 2 NadiSystem controller 3 System plate heat exchanger 4 Low pressure switch 5 High pressure switch 6 Liquid sight glass (0041 - 0061) 7 Scroll compressor 8 Filter 9 Thermostatic valve 10 Axial-flow fan 11 Airside finned heat exchanger 12 Pump 13 Liquid recipient 14 Expansion vessel 15 Reversing valve 17 Safety valve 18 Air vent valve 19 Pressure gauge 20 Base electric heater 21 Pressure transducer
7EN 11/2010 AWR-MTD2-XE
U I A
DIMENSIONED DRAWINGS
I
600
W1
W2
W4
W3
900
D
B
C
=E
A
=
400
Dimensions 0011 0025 0031 0041 0051 0061 0091
A mm 900 900 900 900 900 1550 1550 B mm 1240 1240 1240 1390 1390 1200 1700 C mm 420 420 420 420 420 450 450 D mm 370 370 370 370 370 497 497 E mm 580 580 580 580 580 1477 1477
Weight distribution 0011 0025 0031 0041 0051 0061 0091
W1 lato rear dx kg 60 62 64 67 71 88 117 W2 lato rear sx kg 17 18 20 23 24 39 54 W3 front sx kg 17 18 18 22 22 36 51 W4 front dx kg 51 52 53 58 63 87 113 tot kg 145 150 155 170 180 250 335
INSTALLATION
I
CHOICE OF INSTALLATION SITE
Before installing the unit, agree with the customer the site where it will be installed, taking the following points into con­sideration:
• check that the support surface is adequate to support the weight of the unit;
• respect safety distances between the unit and other equip­ment or structures so that the fan air intake and outlet are not blocked in any way.
• Follow the instructions shown in the chapter on DIMEN­SIONED DRAWINGS to allow room for maintenance oper­ations.
If installing multiple units the clearances must be doubled.
POSITIONING
• Install the vibration damping feet (accessories).
• Check the unit supports and weights before positioning
• Make sure that the unit is level, adjust the height of the support feet if necessary
• Use the flexible joints supplied for the water connections
• Make sure there is easy access to the water circuit and electrical parts
• For installation, if the site is exposed to strong winds, fix the unit adequately using tie rods if necessary.
• In heating mode the unit produces a significant quantity of condensate, which must be suitably drained. Condensate drainage must not cause problems to objects or people.
• If the outside air temperature is less than 0°C, the conden­sate may freeze; in these case fit a frost protection heater on the drain line.
• Consider the maximum height that may be reached by snow to avoid blocking the air intake or outlet (outdoor installation)
• Unit for outdoor installation
For correct operation of the unit, avoid the following:
• obstacles to air flow, such as leaves that may block the heat exchange coil
• strong winds that stop or reinforce air flow
• sources of heat too close to the unit
• air recirculation between intake and outlet
• poor air change
• stratification of air
8 AWR-MTD2-XE EN 11/2010
WATER CONNECTIONS
I A
Warnings
- The choice and installation of components is the responsi­bility of the installer who should follow good working prac­tice and current legislation.
Before connecting the pipes make sure that these:
- do not contain stones, sand, rust, scale or any foreign objects that may damage the system.
- wash the system with clean water
Water connection dimensions
Components
The following components should be installed for correct installation of the unit:
1. Two pressure gauges with a suitable scale (inlet and out­let);
2. Two vibration damper joints (inlet and outlet).
3. Shut-off valves at the inlet and outlet.
4. A flow switch at the unit outlet on the system circuit (compulsory). The flow switch must be calibrated by the installer to a value equal to 70% of rated flow.
5. Two thermometers (inlet and outlet);
6. An inlet filter (compulsory) as close as possible to the unit and positioned to allow easy access for scheduled maintenance (both on the system circuit and domestic hot water circuit).
7. All the pipes must be insulated with suitable material to prevent the formation of condensate and heat loss. The insulating material must be a vapour barrier. Make sure that the control and shut off devices protrude from the insulation.
8. At the lowest points in the system, install drain valves for easy emptying.
9. At the highest points in the system, install automatic or manual air vent valves.
10. The unit is fitted as standard with an expansion vessel; make sure this is correctly sized for the water content of the system and the expected operating temperature, oth­erwise install an additional expansion vessel.
D
100
B
C
528.5
563.5
A
A = C
D
EB
85
35
328
85
0011-0051
SAFETY VALVE DISCHARGE
UNIT VENT
WATER INLET
WATER OUTLET
SYSTEM FILL G1/2
0061-0091
SYSTEM FILL G1/2
WATER OUTLET
WATER INLET
UNIT VENT
SAFETY VALVE DISCHARGE
OPENING FOR CONDENSATE DRAIN CONNECTION
Dimensions 0011 0025 0031 0041 0051 0061 0091
A mm 61,5 61,5 61,5 61,5 61,5 90,5 90,5 B mm 617 617 617 717,5 717,5 575 770 C mm 57 57 57 57 57 90,5 90,5 D mm 454,5 454,5 454,5 549,5 549,5 120 120 E mm - - - - - 560 551 Water in fittings Ø 1" 1" 1" 1" 1/4 1" 1/4 1" 1/4 1" 1/4 Water out fittings Ø 1" 1" 1" 1" 1/4 1" 1/4 1" 1/4 1" 1/4
9EN 11/2010 AWR-MTD2-XE
11. The connection piping should be supported in such a way as to avoid it weighing on the unit.
Failure to install the flow switches will mean the heat exchangers are not protected in the event of no flow of liquid. The Manufacturer cannot be held liable for any damage to the unit and/or the system following the fail­ure to install these devices or the filter.
The correct operation of the components that help ensure the safety of the appliance and the system should be checked regularly:
• make sure the filters are clean
• check operation of the flow switches installed.
• Make sure that the frost protection heaters on the heat exchanger are powered when the unit is OFF
Water flow to the heat pump must conform to the values shown in the section on “General Technical Data”. The flow of water must be maintained constant during oper­ation. The water content of the unit must be such as to avoid dis­turbing operation of the refrigerant circuits.
Risk of freezing
The unit must be prevented from freezing at outside air tem­peratures around 0°C. The following are recommended:
• use suitable percentages of antifreeze (see “Ethylene gly­col solutions”)
• protect the piping with heating sheaths,
• empty the system, making sure no water remains at the lowest points in the circuit or there are closed valves where water may stagnate.
It is recommended to use non-toxic food grade antifreeze, compliant with the standards in force in the countries where the unit is used, if domestic hot water production is also fea­tured. The antifreeze used must be corrosion inhibited and com­patible with the water circuit components.
Ethylene glycol solutions
Water and ethylene glycol solutions used as a heat carrier in the place of water reduce the performance of the unit. Multiply the performance figures by the values given in the following table.
The heat pumps must be fitted with a filling/top-up sys­tem connected to the return line and a drain valve in the lowest part of the system. Systems containing antifreeze or covered by specific legislation must be fitted with low-loss headers.
cPf
cQ
cdp
0 1 1 1
12%
0,985
1,02 1,07
20% 0,98 1,04 1,11
28% 0,974 1,075
1,18
35% 0,97
1,11
1,22
40%
0,965
1,14 1,24
0 -5 -10 -15 -20 -25
Freezing point (°C)
Percentage of ethylene glycol by weight
cPf: cooling capacity correction factor cQ: flow rate correction factor cdp: pressure drop correction factor
Fouling factors
The performance data given refer to conditions with clean evaporator plates (fouling factor = 1). For different fouling factors, multiply the figures in the perfor­mance tables by the coefficient given in the following table.
f1: capacity correction factor fk1: compressor power input correction factor fx1: total power input correction factor
4,4 x 10
-5
0,86 x 10
-4
1,72 x10
-4
­0,96 0,93
­0,99 0,98
­0,99 0,98
Fouling factors
(m2°C/W) f1
Evaporator
fk1 fx1
Water quality
The water used in the system and domestic hot water cir­cuits must comply with the following characteristics:
PH 6-8 Electrical conductivity less than 200 mV/cm (25°C) Chlorine ions less than 50 ppm Sulphuric acid ions less than 50 ppm Total iron less than 0.3 ppm Alkalinity M less than 50 ppm Total hardness less than 50 ppm Sulphur ions none Ammonia ions none Silicon ions less than 30 ppm
WATER CONNECTIONS
I A
10 AWR-MTD2-XE EN 11/2010
WATER CONNECTIONS
I A
Water content in the system
Size 0011 0025 0031 0041 0051 0061 0091
Minimum water content l 24 31,5 40 46 65 74 110
Expansion vessel size
Size 0011 0025 0031 0041 0051 0061 0091
Expansion vessel l 2222244
Safety valve calibration
Size 0011 0025 0031 0041 0051 0061 0091
Safety valve bars 6666666
Factory connections Installer connections
1
2
12
12
13
14
14
UTILITY RETURN
UTILITY OUTLET
9
8
7
16
3
11
T
6
15
16
T
6
F
5
4
2
10
1
1
9
Utility water circuit connection diagram
1 Pressure gauge 2 Vibration damper joint 3 Shut off valve 4 Calibrating valve
5 Flow switch 6 Thermometer 7 Pump 8 Safety valve
9 Expansion vessel 10 Wire mesh filter 11 Unit fill/drain valve 12 Temperature sensor
13 Differential pressure switch 14 Drain / chemical washing valve 15 System vent
Condensate drain
In heating mode the unit produces a significant quantity of condensate, which must be suitably drained. Proceed as follows:
• Connect the unit condensate drain
• Make sure the drain hose has a incline of at least 2 cm/m, without obstructions or choking.
• Connect the condensate drain hose to a rainwater drain. Do not connect to the sewage system as odours may be sucked up if the water in the drain trap evaporates.
• After connecting, check correct drainage of the conden­sate by pouring water into the pan.
• If necessary, suitably insulate the condensate drain hose.
• Condensate drainage must not cause problems to objects or people.
• If the outside air temperature is less than 0°C, the conden­sate may freeze.
The unit comes with frost protection for the condensate col­lection basin inside the unit. Use hot wires on the condensate drain hose downstream of the unit to protect against frost.
FILLING THE SYSTEM
- Before starting to fill, place the unit mains switch QF1 in the OFF position.
- Before filling, check that the system drain valve is closed.
- Open all system and terminal air vents.
- Open system shut off valves.
- Start filling by slowly opening the system water fill valve out­side the unit.
- When water begins to leak out of the terminal air vent valves,
close them and continue filling until the pressure gauge indi­cates a pressure of 1.5 bar.
The system must be filled to a pressure of between 1 and 2 bars. It is recommended that this operation be repeated after the unit has been operating for a number of hours. The pressure in the system should be checked regularly and if it drops below 1 bar, the water content should be topped-up. Check the tightness of the joints.
ON
OFF
11EN 11/2010 AWR-MTD2-XE
ELECTRICAL CONNECTIONS
I A
The heat pumps must be installed downstream of a main switch (QF1, see wiring diagram), as required by the stan­dards in force in the country where the unit is installed. Con­nection to the mains power supply and the connection of the flow switch to the corresponding terminals must be per­formed by authorised personnel in compliance with the stan­dards in force.
For all electrical work, refer to the electrical wiring diagrams in this manual. It is also recommended to check that:
- The characteristics of the mains electricity supply are ade­quate for the power ratings indicated in the electrical spec­ifications below, also bearing in mind the possible use of other equipment at the same time.
Power to the unit must be turned on only after installa­tion work (plumbing and electrical) has been completed. All electrical connections must be carried out by quali­fied personnel in accordance with legislation in force in the country concerned Respect instructions for connecting phase, neutral and earth conductors.. The power line should be fitted upstream with a suitable device to protect against short-circuits and leakage to earth, isolating the installation from other equipment.
Voltage must be within a tolerance of ±10% of the rated power supply voltage for the unit (for three phase units, the unbalance between the phases must not exceed 3%). If these parameters are not respected, contact the elec­tricity supply company. For electrical connections, use double insulation cable in conformity with legislation in force in the country con­cerned..
A thermal overload switch and a lockable mains dis­connect switch, in compliance with the CEI-EN stan­dards (contact opening of at least 3mm), with ade­quate switching and residual current protection capacity based on the electrical data table shown below, must be installed as near as possible to the appliance.
An efficient earth connection is obligatory. The manufacturer cannot be held liable for any damage caused by the failure to correctly earth the unit. In the case of three phase units, ensure the phases are connected correctly.
Do not use water pipes to earth the unit.
Electrical data at maximum conditions allowed (full load)
F.L.I. Maximum power input F.L.A. Maximum current input L.R.A. Start-up current
Maximum values for sizing the protection switches and power supply cables.
Size
Power
supply
Maximum values Fuses
(5x20T 250V)
Heater
Power consumption without heater
Total power consumption
L.R.A.
[A]
FU1 FU5 FU6
(V-Ph-Hz) P MAX [kW] I MAX [A] P MAX TOT [kW] I MAX TOT [A] F.L.I. [kW] F.L.A. [A] [A] [A] [A]
0011ms 230-1N-50 - - - - 2,82 13,5 27 1,6 4 1,25 0025ms 230-1N-50 - - - - 3,56 16,7 30 1,6 4 1,25 0031ms 230-1N-50 - - - - 5,11 23,6 45 1,6 4 1,25 0041ms 230-1N-50 - - - - 6,15 30,1 45 1,6 4 1,25
0031t 400-3N-50 - - - - 4,76 10,0 48 1,6 4 1,25 0041t 400-3N-50 - - - - 6,38 12,4 64 1,6 4 1,25 0051t 400-3N-50 - - - - 6,43 12,7 64 1,6 4 1,25 0061t 400-3N-50 - - - - 7,77 14,8 75 1,6 4 1,25 0091t 400-3N-50 - - - - 10,86 24,6 111 2 4 1,25
12
AWR-MTD2-XE EN 11/2010
INSTALLER CONNECTIONS
I A
PE
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55
C90051683E_00
A4
A2
FU3
C1
A1
C2
C3
A3
QS1
QM1
KA1
KA1
KA6
KA7
KA15
FU1
FU5
FU6
A7
TC1
INSTALLER TERMINAL BLOCK
Power supply
13EN 11/2010 AWR-MTD2-XE
MAINS POWER SUPPLY CONNECTIONS
I A
AWR MTD2 XE heat pump terminal block
Installer connections
UVWN
400V - 3N ~50Hz
U N
PE
230V - 1Ph - 50Hz
QS1
QS1
• Before connecting the unit to the power supply, makes sure that switch QF1 is open, suitably padlocked and marked.
• Remove the inspection panel by unscrewing the screws.
• Use cable gland A for the main electrical power cable and cable gland B for other external cables to be connected by the installer.
• Identify the terminals used for electrical connections on the layout drawing shown in this manual.
• Make the connections as shown in the wiring diagram pro­vided in this manual.
• The figures show the power supply connection terminals for 230V and 400V.
• Replace the covers on the electrical panel and the closing panel.
• Make sure that all the covers removed to make the electri­cal connections have been replaced before powering up the unit.
• Position the main switch QF1 (outside the unit) in the “ON” position.
• Once the remote terminal has been switched on, “OFF” and “init” are displayed.
• The room unit is ready to use after a few seconds, when “init” is shown and the clock is displayed
A
B
* Compliant with standards in force in the place where the unit is installed
Power supply 230V 400V Number of power wires 2 + PE 4 + PE Power wire size* 6 mmq 6 mmq
14 AWR-MTD2-XE EN 11/2010
Outside air probe (BT11) connection
The outside air probe allows the system water temperature set point to be compensated during heating or cooling opera­tion.
Installation instructions
The outside air probe must be installed:
• outside of the home
• not in direct sunlight, away from flue gas discharges, air outlets, or doors and windows.
• on a perimeter wall facing north/north-west
• at a minimum height of 2.5 metres above the ground or at most half way up the house.
H
H
2
/
1
N
N-W
m 5,2nim
Mounting method:
• Open the cover of the sensor.
• Attach a probe to the wall and the correct position as described above.
• For the electrical connections see “Connection diagram”.
• Re-place the cover of the sensor.
INSTALLER CONNECTIONS
I A
12
45 46
BT11
TECHNICAL DATA
Sensing element NTC 10Kohm ± 1% (25°C) Degree of protection IP65 Perm. ambient / carriage temperatur
e -50°C...+100°C Measuring range -50°C...+100°C Materials PA 15% GK, Colour RAL 9010
15EN 11/2010 AWR-MTD2-XE
A5 room controller connection
Installation instructions
The room controller must be installed in the best reference position for temperature control. Position the room controller as follows:
• around 1.5 metres from the floor, in a part of the room that allows the sensor to accurately measure the room temper­ature;
• away from cold air flows, sunlight or other sources of heat.
• leave enough space above the room controller to allow assembly and removal where necessary.
• If the room controller is removed from its base, it discon­nects from the power supply and consequently is no longer operating.
min. 10 cm
Installation procedure
Assembly
• Separate the front from the rear of the terminal using a screwdriver r (1)
• Disconnect the 4-pin connector from the front part (2)
• Remove the cover A1, unscrewing the screw A2 (3).
• Fix the controller support to the wall using the holes A3 (4). Support hole size and spacing in figure (5).
• Make the electrical connections as shown in the figure (6), also see the wiring diagram.
A2
A1
A3
A3
E
131
83,5
86
51
52 53 54 55
TxRx -
TxRx +
GND
24 VAC
GND
A5 room controller terminal block Installer terminal block
Number of wires 5 shielded Power supply wire size 0.5 mm
2
Maximum distance 500 m
1
3
6
4 5
2
INSTALLER CONNECTIONS
I A
16 AWR-MTD2-XE EN 11/2010
INSTALLER CONNECTIONS
I A
YV5 3-way valve for domestic hot water production
The 3-way valve installed outside of the unit deviates the flow of hot water produced by the unit to the DHW storage tank. During domestic hot water production, the cooling/heating demand is not satisfied. Wire the three-way valve supplied as an accessory by Man­ufacturer following the instructions shown in the figure.
The valve is also fitted with a limit switch. The limit switch contact is either closed or open based on the position of the valve. Limit switch (red and green wires): Auxiliary contact closed = Valve open Auxiliary contact open = Valve closed
If not supplied by Manufacturer, the 3-way valve for domes­tic hot water production should have the following character­istics:
• Voltage 230V AC, 50/60 Hz
• Opening/closing time 10s.
• Delta P 500 kPa
• Fluid temperature 0°C to 90°C Use three-way valves with pressure drop below 20 kPa. For further details see the chapter “Operating characteris­tics”.
If three-way valves with a travel time greater than 10 sec­onds are used, modify the setting of parameter 0231
• Close the cover A1 and secure it with the screw A2
• Plug in the 4-pin connector, figure (7)
• Replace the terminal, starting with the lower tabs, applying a hinge movement. Make sure that the electrical wires are inside to ensure correct fastening (click on).
• Dimensions of A5 room controller figure (8).
68
8 28
143
Wall
7
8
9 12 13
YV5
Yellow/Green
Red
Blue Green
Black
Brown
Auxiliary contact
INSTALLER CONNECTIONS
I A
43 44
6 7
230V / 400V
BT9
N
1
Description
Three-way valve travel time for domestic hot water production
Menu
Mn02
Parameter
no.
0231
Default
12
Value to be set
Set the travel time
for valves not supplied by the heat pump manufacturer
UOM
sec.
Optional connection
KM2 System outlet electric heater
An electric heater installed at the outlet can be activated as a supplementary heater for the system.
Solution 1
System with heat pump and electric heater with storage tank. Position probe BT9 in the storage tank.
17EN 11/2010 AWR-MTD2-XE
INSTALLER CONNECTIONS
I A
B) SUPPLEMENTARY: the electric heater operates in sup-
plementary heating mode, together with the compressor, to satisfy the heating load.
Supplementary heating for low outside air temperature
The electric heater is enabled only when the outside tem­perature is less than the value of parameter 0304, figure 3. To enable supplementary heating for low outside air temper­ature set parameter 0303 = 1 and 010G = 0
Electric heater operation reflects the trend in water outlet temperature, as shown on the graph in figure 4.
Description
Activation electrical heater 0 = Electrical Heater not enabled 1 = Electrical Heater enabled Type of outlet electric heater oper­ation 0 = Supplementary 1 = Replacement Enable boiler 0 = Boiler not enabled 1 = Boiler enabled Activation with low outside air temperature 0 = Function not enabled 1 = Function enabled Outside air temperature to enable elec­tric heater Minimum outside air temperature for heat pump operation (make sure the value set is the same as shown in the table) Electric heater delay time (allows the heat pump to reach steady operation and thus avoid activating the heater when not needed) Integration time to activate outlet elec­tric heaters
Menu
Mn01
Mn03
Mn03
Mn03
Mn03
Mn03
Mn06
Mn06
Parameter
no
0300
010G
0301
0303
0304
0311
0616
0617
Value to be
set
1*
0
0*
1
Example
-5°C
-15
60
600
UOM
°C
°C
min.
°C*sec
Outlet electric heater control
A) REPLACEMENT: The electric heater is enabled when
the outside temperature is less than the value of parameter 0304 and the compressor is off, figure 3. To enable heater activation in REPLACEMENT mode set parameter 0303 = 1 and 010G = 1.
Electric heater operation reflects the trend in water outlet temperature, as shown on the graph in figure 4.
If the heat pump shuts down due to an alarm, the electric heater is activated automatically regardless of the outside air temperature. In REPLACEMENT mode the electric heater activation delay time is ignored, and the device is activated immediate­ly if necessary.
Outlet electric heater operating parameters in REPLACE­MENT mode
Outlet electric heater operating parameters in SUPPLE­MENTARY mode for OUTSIDE AIR TEMP.
Description
Activation electrical heater 0 = Electrical Heater not enabled
1 = Electrical Heater enabled Type of outlet electric heater oper­ation 0 = Supplementary 1 = Replacement Enable boiler 0 = Boiler not enabled 1 = Boiler enabled Activation with low outside air temperature 0 = Function not enabled 1 = Function enabled Outside air temperature to enable elec­tric heater Integration time to activate outlet elec­tric heaters
Menu
Mn03
Mn01
Mn03
Mn03
Mn03
Mn06
Parameter
no
0300
010G
0301
0303
0304
0617
Value to be
set
1*
1
0*
1
Example
-5°C 600
UOM
°C
°C*sec
43 446 7
230V / 400V
BT9
N
Solution 2
System with heat pump and outlet electric heater WITHOUT storage tank. Position probe BT9 on the system outlet pipe.
2
Set the parameters following the sequence described in the table
Set the parameters following the sequence described in the table
18 AWR-MTD2-XE EN 11/2010
INSTALLER CONNECTIONS
I A
Supplementary heating always enabled
Supplementary heating with the electric heater is enabled for all outside air temperatures. To enable heating at all times set parameter 0303 = 0 and 010G = 0
Electric heater operation reflects the trend in water outlet temperature, as shown on the graph in figure 4.
Once the heater is enabled, supplementary heating is activated when the integra­tion time set for parameter 0617 is reached and the delay time 0616 has elapsed. The delay time is ignored when the unit is first started.
Example: Value 0617 = 600°C*sec Outlet temperature set point= 50°C Actual temperature = 40°C
(50 – 40) x 60 sec = 600°Csec. ----> Electric heater ON
Low values of 0617 mean frequent activation of the heater. Too high values of 0617 mean long delays in activating the heater
Description
Activation electrical heater 0 = Electrical Heater not enabled 1 = Electrical Heater enabled Type of outlet electric heater oper­ation 0 = Supplementary 1 = Replacement Enable boiler 0 = Boiler not enabled 1 = Boiler enabled Activation with low outside air temperature 0 = Function not enabled 1 = Function enabled Minimum outside air temperature for heat pump operation (make sure the value set is the same as shown in the table) Electric heater delay time (allows the heat pump to reach steady operation and thus avoid activating the heater when not needed) Integration time to activate outlet electric heaters
Menu
Mn03
Mn01
Mn03
Mn03
Mn03
Mn06
Mn06
Parameter
no
0300
010G
0301
0303
0311
0616
0617
Value to be
set
1*
0
0*
0
-15
60
600
UOM
°C
min.
°C*sec
3 4
Outlet electric heater operating parameters in SUPPLE­MENTARY mode when always ENABLED
Outside air T
OFF
Enabled
Outlet heater
0304 Outside temperature to enable outlet heaters
3°C
OFF
ON
ON
OFF
Compressor
Heater
Electric heater activation delay time 0616
Integration time 0617
System water control set point
Actual water temperature
System HP control hysteresis
Set the parameters following the sequence described in the table
19EN 11/2010 AWR-MTD2-XE
INSTALLER CONNECTIONS
U I A
Boiler control
A) REPLACEMENT: the boiler is only enabled if the outside
air temperature is less than the value of parameter 0307 and the compressor is off, figure 3. To enable boiler activation in REPLACEMENT mode set parameter 0306=1 and 010H = 1
Boiler operation reflects the trend in water temperature, as shown on the graph in figure 4.
If the heat pump shuts down due to an alarm the boiler is activated automatically regardless of the outside air temper­ature. In REPLACEMENT mode the activation delay time is ignored, and the boiler is activated immediately if necessary.
Description
Enable electric heater 0 = Heater not enabled 1 = Heater enabled Activation Boiler 0 = Boiler not enabled 1 = Boiler enabled Type of boiler operation 0 = Supplementary 1 = Replacemen Activation with low outside air temperature 0 = Function not enabled 1 = Function enabled Outside air temperature to enable boiler Integration time to activate boiler
Menu
Mn03
Mn03
Mn01
Mn03
Mn03
Mn06
Parameter
no.
0300
0301
010H
0306
0307
0619
Value to be
set
0
1
1
1
Example
-5°C 600
UOM
°C
°C*sec
B) SUPPLEMENTARY: the boiler operates in supplemen­tary heating mode, together with the compressor, to satisfy the heating load.
Supplementary heating for low outside air temperature The boiler is enabled only when the outside air temperature is less than the value of parameter 0307, figure 3. To enable the supplementary heating for outside air temper­ature set parameter 0306 = 1 and 010H = 0
Boiler operation reflects the trend in water temperature, as shown on the graph in figure 4.
Description
Enable electric heater 0 = Heater not enabled 1 = Heater enabled Activation Boiler 0 = Boiler not enabled 1 = Boiler enabled Type of boiler operation 0 = Supplementary 1 = Replacemen Activation with low outside air temperature 0 = Function not enabled 1 = Function enabled Outside air temperature to enable boiler Minimum outside air temperature for heat pump operation (make sure the value set is the same as shown in the table) Boiler activation delay time (allows the heat pump to reach steady operation and thus avoid activat­ing the boiler when not needed) Integration time to activate boiler
Menu
Mn03
Mn03
Mn01
Mn03
Mn03
Mn03
Mn06
Mn06
Parameter
no.
0300
0301
010H
0306
0307
0311
0618
0619
Value to be
set
0
1
0
1
Example
-5°C
-15
60
600
UOM
°C
°C
min.
°C*sec
Boiler operating parameters in REPLACEMENT mode
Boiler operating parameters in SUPPLEMENTARY mode for outside temperature
Boiler
43 44
BT9
67
BT9
Boiler
43 4467
1
2
Set the parameters following the sequence described in the table
Set the parameters following the sequence described in the table
KM2 Boiler
A boiler can be used as a supplementary or replacement heat source for the system.
Solution 1
System with heat pump and boiler with storage tank.
Solution 2
System with heat pump and boiler without storage tank.
20 AWR-MTD2-XE EN 11/2010
INSTALLER CONNECTIONS
U I A
Supplementary heating always enabled
Supplementary heating by boiler is enabled for all outside air temperatures. To enable heating at all times set parameter 0306 = 0 and 010H = 0
Boiler operation reflects the trend in water temperature, as shown on the graph in figure 4.
Description
Enable electric heater 0 = Heater not enabled 1 = Heater enabled Activation Boiler 0 = Boiler not enabled 1 = Boiler enabled Type of boiler operation 0 = Supplementary 1 = Replacement Activation with low outside air temperature 0 = Function not enabled 1 = Function enabled Outside air temperature to enable boiler Minimum outside air temperature for heat pump operation (make sure the value set is the same as shown in the table) Boiler activation delay time (allows the heat pump to reach steady operation and thus avoid activat­ing the boiler when not needed) Integration time to activate boiler
Menu
Mn03
Mn03
Mn01
Mn03
Mn03
Mn03
Mn06
Mn06
Parameter
no.
0300
0301
010H
0306
0307
0311
0618
0619
Value to be
set
0
1
0
0
Example
-5°C
-15
60
600
UOM
°C
°C
min.
°C*sec
3 4
Boiler operating parameters in SUPPLEMENTARY mode when always ENABLED
Once the boiler has been enabled, supplementary heating is activated when the integration time set for parameter 0619 is reached and the delay time 0618 has elapsed. The delay time is ignored when the unit is first started.
Example: Value 0619 = 600°C*sec Outlet temperature set point= 50°C Actual temperature = 40°C
(50 – 40) x 60 sec = 600°Csec. ----> Boiler ON
Low values of 0619 mean frequent activation of the boiler. Too high values of 0619 mean long delays in activating the boiler
Outside air T
OFF
Enabled
Boiler
0304 Outside temperature to enable boiler
3°C
OFF
ON
ON
OFF
Compressor
Boiler
Boiler activation delay time 0618
Integration time 0619
System outlet temperature set point
Actual water temperature
System HP control hysteresis
Set the parameters following the sequence described in the table
ON
OFF
ON
OFF
Heater
Compressor
0023
0209
t
21EN 11/2010 AWR-MTD2-XE
INSTALLER CONNECTIONS
U I A
Description
Domestic hot water heating 0 = heat pump only 1 = electric heater only 2 = heat pump + electric heater Legionella prevention function with: 0 = heat pump only 1 = electric heater only 2 = heat pump + electric heater Domestic hot water temperature set point for Legionella prevention Legionella prevention cycle day MONDAY (0=no; 1=yes) Legionella prevention cycle day TUESDAY (0=no; 1=yes) Legionella prevention cycle day WEDNESDAY (0=no; 1=yes) Legionella prevention cycle day THURSDAY (0=no; 1=yes) Legionella prevention cycle day FRIDAY (0=no; 1=yes) Legionella prevention cycle day SATURDAY (0=no; 1=yes) Legionella prevention cycle day SUNDAY (0=no; 1=yes) Legionella prevention cycle time
Enable Legionella prevention function 0 = Not enabled 1 = Enabled Maximum Legionella prevention function duration
Menu
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Mn02
Parameter
no.
0202
0223
0211
0213
0214
0215
0216
0218
0219
0220
0221
0222
0225
Value to be
set
2
1
Example
65°C
0
0
Example 1
0
0
0
0
02
1
20
UOM
°C
h
min.
KM4 DHW storage electric heater
An electric heater can be managed for heating the DHW storage.
DHW storage electric heater control
The electric heater is activated to reach a temperature value that the heat pump on its own is not able to reach.
Example: Domestic hot water temperature produced with heat pump 0023 = 55°C Domestic hot water temperature produced with electric heater 0209 = 65°C. The electric heater works so as to increase the DHW stor­age temperature from 55°C to 65°C, figure 1
Legionella prevention function with electric heater
The Legionella prevention function ensures the elimination of the Legionella bacteria that reside in domestic water stor­age tanks. The temperature and duration of the Legionella prevention cycles are typically:
• 2 minutes > 70°C
• 4 minutes > 65°C
• 60 minutes > 60°C
To enable the Legionella prevention function, set 0222=1
Description
Electric heater operating mode 0 = Heat pump only 1 = Electric heater only 2 = Heat pump + Electric heater
Domestic hot water temperature set point with heat pump Domestic hot water temperature set point with heater
Menu
Mn02
Mn00
Mn02
Parameter
no.
0202
0023
0209
Value to be
set
2
Example
55
Example
65
UOM
°C
°C
1
Domestic hot water electric heater
NU
10 11
Loading...
+ 49 hidden pages