Notes and Warnings
NOTE: A NOTE indicates important information that helps you make better use of your software.
DANGER: A DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING: A WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or
injury.
A CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury or in property damage incidents.
DANGER: Observe the following instruction to help prevent an imminently hazardous situation which, if not
avoided, will result in death or serious injury:
S This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS
inside the UPS.
S This is Class A Interference Causing Equipment. In a residential environment, this product may cause
radio interference, in which case the user may be required to take additional measures.
Information in this document is subject to change without notice.
E 2011–2013 Dell Inc. All rights reserved.
Reproduction in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden.
Trademarks used in this text: Dell and the DELL logo are trademarks of Dell Inc.; National Electrical Code and NEC are registered
trademarks of National Fire Protection Association, Inc.; Phillips is a registered trademark of Phillips Screw Company.
Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their
products. Dell Inc. disclaims any proprietary interest in trademarks and trade names other than its own.
Typical Alarms and Conditions68.....................................
Silencing the Alarm72..............................................
Table of Contents
|
5
1
Introduction
The Dellt Online Rack uninterruptible power system (UPS) protects your sensitive electronic
equipment from basic power problems such as power failures, power sags, power surges, brownouts, and
line noise.
Power outages can occur when you least expect them and power quality can be erratic. These power
problems have the potential to corrupt critical data, destroy unsaved work sessions, and damage
hardware — causing hours of lost productivity and expensive repairs.
With the Dell Online Rack UPS, you can safely eliminate the effects of power disturbances and guard
the integrity of your equipment. The UPS's flexibility to handle an array of network devices makes it the
perfect choice to protect your LANs, servers, workstations, and other electrical equipment.
Figure 1 shows the Dell Online Rack UPS.
Figure 1. The Dell Online Rack UPS
|
6
Introduction
Providing outstanding performance and reliability, the UPS's unique benefits include:
S Online UPS design with pure sine wave output. The UPS filters and regulates incoming AC power
and provides consistent power to your equipment without draining the battery.
S True online double-conversion technology with high power density, utility frequency
independence, and generator compatibility.
S Selectable High Efficiency mode of operation.
S 4U size that fits any standard 48 cm (19”) rack.
S Start‐on‐battery capability for powering up the UPS even if utility power is not available.
S Maintenance is simplified by allowing the safe replacement of batteries without powering down the
UPS.
S Extended runtime with an optional External Battery Module (EBM).
S Emergency shutdown control through the Remote Emergency Power-off (REPO) ports.
S Two standard communication ports (USB and DB-9 serial port).
S Optional Dell Network Management Card with enhanced communication capabilities for
increased power protection and control.
S Advanced power management with the Dell UPS Management Software for graceful shutdowns
and power monitoring.
S Sequential shutdown and load management through separate receptacle groups called load
segments.
S Firmware that is easily upgradable without a service call.
S Backed by worldwide agency approvals.
Introduction
|
7
Finding Information
CAUTION: The Safety, Environmental, and Regulatory Information document provides important safety and
regulatory information.
What are You Looking For?
S The user's guide for my UPS
S The user's guide for the Dell Network Management
Card
S Dell UPS Management Software
Find It Here
Dell UPS Disc
NOTE: Documentation and software updates can be
found at www.support.dell.com and at
www.dellups.com.
S Specifications
S How to configure UPS settings
S How to troubleshoot and solve problems
S How to install REPO control
S Safety instructions
S Regulatory information
S Recycling information
S Warranty information
S Terms and Conditions (U.S. only)
S End User License Agreement
S Support informationDell Support Website — www.support.dell.com
Dell UPS User's Guide
The user's guide is available on the Dell UPS disc and
on www.support.dell.com.
Safety, Environmental, and Regulatory Information
Dell Warranty and Support Information
NOTE: Select your region or business segment to view
the appropriate support site.
|
8
Introduction
2
Safety Warnings
CAUTION: Before performing the procedures in this document, read and follow the safety instructions and
important regulatory information in your Safety, Environmental, and Regulatory Information document.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the equipment and
save this manual for future reference.
DANGER: Observe the following instruction to help prevent an imminently hazardous situation which, if not
avoided, will result in death or serious injury:
S This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE
PARTS inside the UPS.
WARNING: Observe the following instructions to help prevent a potentially hazardous situation which, if not
avoided, could result in death or injury:
S Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.
S For UPS models with hardwired input, overcurrent protection for the output AC circuit(s) is to be
provided by others.
S For UPS models with hardwired input, suitably rated disconnect switches for the output AC
circuit(s) are to be provided by others.
S Output overcurrent protection and disconnect switch must be provided by others.
S This UPS contains its own energy source (batteries). The output receptacles may carry live voltage
even when the UPS is not connected to an AC supply.
S Do not remove or unplug the input cord when the UPS is turned on. This removes the safety
ground from the UPS and the equipment connected to the UPS.
S To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent
protection with an ampere rating in accordance with the National Electrical Code® (NEC®),
ANSI/NFPA 70 or your local electrical code:
UPS Output Power200V208V230V
3750W—30A25A
4200W30A30A30A
Safety Warnings
|
9
S To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature must not
exceed 40°C (104°F). Do not operate near water or excessive humidity (95% maximum).
S Unpacking the cabinet in a low-temperature environment may cause condensation to occur in and
on the cabinet. Do not install the cabinet until the inside and outside of the cabinet are absolutely
dry (hazard of electric shock).
S If the UPS requires any type of transportation, disconnect the internal UPS batteries before
transporting (see page 59).
CAUTION: Observe the following instructions to help prevent a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury or in property damage incidents:
S For PLUGABLE EQUIPMENT, the power outlet shall be installed near the equipment and shall
be easily accessible.
S Servicing of batteries should be performed or supervised by personnel knowledgeable about
batteries and the required precautions. Keep unauthorized personnel away from batteries.
S Batteries can present a risk of electrical shock or burn from high short-circuit current. The
following precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use
tools with insulated handles; 3) Wear rubber gloves and boots; 4) Do not lay tools or metal parts
on top of batteries; 5) Disconnect the charging source prior to connecting or disconnecting battery
terminals.
S Determine if the battery is inadvertently grounded. If inadvertently grounded, remove the utility
source from the ground. Contact with any part of a grounded battery can result in electrical shock.
The likelihood of such shock can be reduced if such grounds are removed during installation and
maintenance (applicable to equipment and remote battery supplies not having a grounded supply
circuit).
S ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors.
Attempting to alter wiring can cause injury.
S Replace batteries with the same number and type of batteries as originally installed in the UPS.
S Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
S Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and
eyes and may be extremely toxic.
S The UPS may be connected to a maximum of one External Battery Module (EBM).
10
|
Safety Warnings
WARNING: Additional instructions for Rack-Mounted Systems
S Your rack kit has been approved only for the rack cabinet provided. It is your responsibility to
ensure that installation of the equipment into any other rack complies with all applicable
standards. Dell disclaims all liability and warranties with respect to combinations of equipment
with any other rack.
S Before installing your equipment in a rack, install all front and side stabilizers. Failure to install
stabilizers can allow the rack to tip over.
S Always load from the bottom up, and load the heaviest items first.
S Do not overload the AC power supply branch circuit that provides power to the rack.
S Do not stand or step on any components in the rack.
WARNING: Slide/rail mounted equipment is not to be used as a shelf or work space.
Do not add weight to slide/rail mounted equipment.
Safety Warnings
|
11
Operation
This chapter contains information on how to use the UPS, including:
S UPS startup and shutdown
S Control panel and display functions
S Retrieving the Event Log
S Transferring the UPS between modes
S Setting power strategy
S Behavior on overload
S Configuring load segments, battery settings, and automatic restart
UPS Startup and Shutdown
NOTE: The button controls only the UPS output. The button has no effect on equipment connected to
the UPS.
To start up or shut down the UPS, see:
S “Starting the UPS” on page 32
S “Starting the UPS on Battery” on page 33
S “UPS Shutdown” on page 33
4
Starting the UPS
To start the UPS:
1Verify that the UPS power cord is plugged in.
2Switch on utility power where the UPS is connected.
The UPS front panel display illuminates. The Dell startup screen changes to the UPS status
summary screen. The UPS front panel display shows the Standby mode icon .
3Press the button on the UPS front panel.
After the startup is complete, the status icon changes to the appropriate icon based on the UPS
operating mode (see Table 3 on page 37).
|
32
Operation
4On the UPS status summary screen, press the button to check for active alarms or notices.
Resolve any active alarms before continuing. See “Troubleshooting” on page 67.
If there are no active alarms, a “No Active Alarms” message appears.
5Verify that the Normal mode icon appears on the UPS status summary screen, indicating that
the UPS is operating normally and any loads are powered.
Starting the UPS on Battery
NOTE: Before using this feature, the UPS must have been powered by utility power with output enabled at
least once.
NOTE: Utility power cannot be present at startup.
To start the UPS on battery:
1Press the button on the UPS front panel until the UPS beeps.
The UPS front panel display illuminates, and the UPS begins the startup sequence.
The UPS cycles through Standby mode to Battery mode. The Battery mode icon displays on
the UPS status summary screen. The UPS supplies power to your equipment.
NOTE: The UPS does not assume the load if you press the button less than three seconds.
2Press the button to check for active alarms or notices.
Ignore the “UPS on Battery” notice and notices that indicate missing utility power. Resolve other
active alarms before continuing. See “Troubleshooting” on page 67. After correcting the alarms,
restart if necessary.
You can prevent a battery start (requiring utility power at the next startup) by simultaneously pressing
the and buttons for three seconds. Battery start can be disabled. See the Start on Battery setting
on page 44.
UPS Shutdown
To shut down the UPS:
1Press the button on the front panel for three seconds.
The UPS begins to beep. The UPS transfers to Standby mode.
NOTE: Releasing the button before three seconds returns the UPS to its original operating state.
2Switch off utility power where the UPS is connected.
After utility power is removed, the UPS fully shuts down in ten seconds.
|
Operation
33
Control Panel Functions
The UPS has a three-button graphical LCD with dual color backlight. Standard backlight is used to
light up the display with white text and a blue background. When the UPS has a critical alarm, the
backlight changes the text to dark amber and the background to amber. See Figure 23.
Figure 23. Dell Online Rack UPS Control Panel
There are three buttons on the control panel:
SScroll up or back
SSelect
SScroll down or forward
Table 2 describes the functions of the LCD control buttons.
Table 2. Control Button Functions
Control Button
|
34
SequenceFunction
Press for less than one secondScroll back or up to the previous menu.
Press for longer than one
second
Press for less than one secondSelect the menu or option to be changed.
Press for longer than one
second
Press for less than one secondScroll forward or down to the next menu option.
Press both buttons for three
seconds
Press all three buttons for five
seconds
Operation
Return/exit back one menu layer without initiating a command
or changing a setting.
Save the setting being edited.
Temporarily disable the battery startup feature until the next
power cycle. The buzzer emits a one second beep to indicate
that Battery Start has been disabled.
Shortcut for defaulting the language back to English. The
buzzer emits a one second beep to indicate that the setting has
changed to English.
To select an option:
1When scrolling through the settings, the present setting displays for each selection.
2Press the button to select the option.
The current setting for the option flashes when selected.
3Use the or buttons to toggle the available options.
4Set the new option by holding the button again for one second.
The option stops flashing.
Changing the Language
Language selection is controlled through the user settings. See Table 6 page 43 for information on
available languages.
Display Functions
The UPS provides useful information about the UPS itself, load status, events, measurements,
identification, and settings through the front panel display.
Startup Screen
During startup, the Dell logo is the default screen. This startup screen displays for five seconds and then
defaults to the UPS status summary screen.
The display automatically returns to the UPS status summary screen when no button has been pushed
for 15 minutes and no other screen has been locked by a user. When you return to the status summary
screen, press the button for one second to exit back to the menu selections. Selecting UPS Status
from the main menu list enables you to scroll through all of the UPS status menu screens, including the
status summary screen.
|
Operation
35
Screen Locked
To lock a screen, press the button. The current view stays locked and does not automatically return
to the default screen after time-out. When the screen is locked, the image of a key appears on the UPS
status summary screen just to the left of the status icon. See Figure 24.
Pushing any button returns the normal button function, unlocks the screen, and removes the lock
symbol.
Figure 24. A Locked Screen
Only screens that have dynamic, real-time data updates can be locked. Applicable screens include the
status summary screen, measurement screens, active alarms, and the battery status screen.
UPS Status
The UPS status provides separate screens for the following information:
S Status summary, including mode and load
S Notice or alarm status, if any are present
S Battery status, including state and charge level
See Table 3 for examples of the UPS status summary screens. The status icon in the upper right corner
of each status summary screen conveys the UPS status or mode.
Basic operating modes include:
S Normal mode
S High-efficiency mode
S Battery mode
S Bypass mode
S Standby mode
|
36
Operation
Table 3. Status Summary Screens
Status Summary ScreenDescription
UPS Critical Failure
The UPS is in Fault mode. The status icon and background are flashing.
Battery Mode
The status icon and background of the icon are flashing.
An audible alarm (0.5 seconds on/4.5 seconds off) accompanies the switch to
Battery mode.
When the utility power returns, the UPS transfers to Normal mode operation
while the battery recharges.
Bypass Mode
The UPS is operating in Bypass mode through the static bypass switch. The status
icon and background of the icon are flashing. Battery mode is not available.
UPS in Overload Condition
The status icon and background of the icon are flashing.
Bad Battery Detected or Battery Disconnected
The status icon and background of the icon are flashing, along with the outer
shell of the battery symbol at the bottom.
UPS General Alarms Active
The status icon and background of the icon are flashing.
Operation
|
37
Table 3. Status Summary Screens (continued)
Status Summary ScreenDescription
Battery Test Status
The status when the UPS is performing a battery test.
Normal Mode
The UPS is operating in Normal mode from utility power. The UPS monitors and
charges the batteries as needed and provides filtered power protection to your
equipment.
High Efficiency Mode
The UPS is operating in High Efficiency mode.
Converter Mode
The UPS is operating in Converter mode.
Standby Mode
When the UPS is turned off and remains plugged into a power outlet, the UPS is
in Standby mode and utility power supplies the connected equipment. The UPS
is not supporting the load, but is ready to assume the load on command.
The notice and alarm screens are visible only when notices or alarms are active. There is a separate
screen for each active notice or alarm. If there are no active notices or alarms, a “No Active Alarms”
message appears in a single screen between the UPS status summary and the battery status screen. If
there are multiple notices or alarms, scroll through each notice or alarm screen to reach the first battery
status screen.
NOTE: Events are not shown in status summary screens. They appear only in the Event Log.
|
38
Operation
Table 4 describes the available battery status screens. Only one battery status is available at a time.
Table 4. Battery Status Screens
Battery Status Screen
Battery chargingBatteries are charged in constant current mode.
Battery floatingBatteries are charged in constant voltage mode.
Battery restingBatteries are connected but are not being charged or discharged.
Battery dischargingBatteries are discharging.
Battery disconnectedBatteries are unavailable because they are disconnected.
Charger disabledThe battery charger is off. You can enable the Charger setting from the Settings
Description
(This is part of the normal charging cycle.)
menu (see page 46).
Event Log
The Event Log holds up to 50 events. You can scroll through the event screens, beginning with the most
recent event.
NOTE: The date format is dependent on the language selection.
The first row of each event screen contains the date (MM/DD/YYYY) and time (hh:mm:ss) at which the
event occurred. The second row contains the type of event and code. The event description begins on
the third row and may continue to the fourth row. The bottom right corner of the event screen displays
two numbers: an ordering number of the event in the log, followed by the total number of events in the
log.
If there are no events in the log, the event screen displays “No events in log.”
See “Retrieving the Event Log” on page 49.
Operation
|
39
Measurements
The measurements screens provide useful measurement information on:
S Output watts VA, current, power factor, voltage, and frequency
S Input voltage and frequency
S Battery voltage and percentage charged
S Instantaneous Headroom Watts remaining
S Peak Headroom Watts (the remaining watts available to support the load at peak demand,
includes the date and timestamp of the peak demand)
S Peak Consumption Watts (the peak power demand on the UPS, includes the date and timestamp
of the peak demand)
S Present kWh Consumption (the kWh demand on the UPS averaged over the past hour)
S Cumulative kWh Consumption (the total kWh usage, includes the date and timestamp since it
was last reset)
40
|
Operation
Control Screens
Table 5 describes the available control screens.
Table 5. Control Screens
Control Screens
Go to BypassTransfers the UPS system to internal Bypass mode.
Battery TestSchedule Battery Test: yes | Cancel Battery test: no
Reset Error StateReset Alarms: yes | no
Load SegmentsLoad segment 1: on | off
Restore Factory SettingsRestore Factory Settings: yes | no
Description
When the Go to Bypass command is issued, the screen immediately shows the
message for five seconds: Manual Bypass Command. The option then changes to
Go to Normal.
When the Go to Normal command is issued, the screen immediately shows the
message Normal Mode Command Sent for five seconds. The option then changes
to Go to Bypass.
Starts a manual battery test.
See “Testing Batteries” on page 62.
Manually clears any latched alarms, such as bad battery detected or DC Bus
OV/UV.
If a bad battery alarm was also active, reset the battery test status to “Not
Tested.”
Load segment 2: on | off
These on/off commands override automatic load segment on/off controls made by
the Automatic Start Delay and Automatic On Battery Shutdown settings. See
“Configuring Load Segments” on page 50.
Available only in Standby mode.
Restoring the factory settings:
S Returns all user-configurable EEPROM settings to default factory settings
S Resets all pending on/off commands
S Clears the Event Log and resets all time stamps
S Resets the battery test status
S Initiates the Self Diagnostics test
Operation
|
41
Identification
The identification screens display the following UPS information:
S Type and model
S Part number
S Serial number
S UPS firmware
S Network Management Card (NMC) firmware
NOTE: The NMC firmware screen displays only if the NMC is installed. See “Dell Network Management Card“
on page 57.
42
|
Operation
Settings
Only available options are displayed.
User settings are not protected by default. You can enable the password through the User Password
setting.
Table 6 displays the options that can be changed by the user.
English
[Simplified Chinese] [Russian] [Korean]
[Traditional Chinese]
Disabled
If Enabled, the default password is USER.
NOTE: If you enter an incorrect password, the
message “Wrong Password” appears. Press any
button to return to the password screen and retry
the password.
Enabled
NOTE: If you disable audible alarms, it takes effect
instantly and remains disabled, even after a power
cycle. This differs from the mute feature where the
horn is temporarily silenced on any button press,
but turns on again if a new alarm is triggered.
Date: mm/dd/yyyy
Time: hh:mm:ss
NOTE: The date format is dependent on the
language selection.
NOTE: Time is a 24-hour clock.
[Enabled] [Disabled]
If Enabled, control commands are accepted through
the serial port, USB ports, or option card.
If Disabled, configuration and load control
commands are restricted to LCD only.
[Auto-sensing]
01/01/2009
12:00:00
Enabled
Auto-sensing
Operation
|
43
Table 6. Settings (continued)
DescriptionDefault SettingAvailable Settings
Overload Alarm Level[10%] [20%] [30%]...[100%]
100%
If 100%, the UPS issues an Output Overload alarm
at load > 100%.
NOTE: Output Overload Level 1 by default is set to
100% and is configurable from 10% to 100% in 10%
increments through the LCD setting menu. This
allows customers to be alerted before the UPS has
reached its rated capacity limits.
Power Strategy[Normal] [High Efficiency] [Converter]
Automatic on Battery Shutdown[Off] [0s] [1s] [2s]...[32767s]
Off
See “Configuring Load Segments” on page 50.
Start on Battery[Enabled] [Disabled]
NOTE: Battery start is disabled from the factory and
Enabled
remains disabled until the UPS has been powered
from utility and enters Standby mode. After the
UPS has been started once from utility, the Start on
Battery feature is automatically enabled. After this is
set by the user, it remains set.
If ±3.0 Hz, on inverter operation the inverter tries to
synchronize with the Bypass when the Bypass
frequency is not more than 3 Hz from the nominal
output frequency; otherwise, the inverter goes to
nominal frequency. On Bypass mode, the sync
window is always ±3 Hz.
NOTE: In Sync Disabled state, if the Bypass
operation is allowed, the UPS synchronizes only
when it is operating on Bypass mode.
-15% of nominal
+10% of nominal
Always
±3.0 Hz
Operation
|
45
Table 6. Settings (continued)
DescriptionDefault SettingAvailable Settings
Unsynchronized Transfers[Enabled] [Disabled]
If Enabled, unsynchronized transfers to the Bypass
are allowed.
If Disabled, unsynchronized transfers to the Bypass
are not allowed.
NOTE: The Qualify Bypass setting may overrule the
Unsynchronized Transfers setting.
External Battery Module (EBM)[0] [1]
See “Configuring the UPS for an EBM” on page 53.
Charger[Enabled] [Disabled]
If Enabled, batteries charge normally.
If Disabled, the battery charger is off.
Battery Charge % to Restart[0 %] [10%] [20%] [30%]...[100%]
When enabled, automatic restart is made when the
battery charge state reaches the selected level. If set
to 0, the feature is disabled.
The number after “Total events” shows how
many events are currently stored in the log.
Press the button for one second to reset
the event count to zero and clear the log.
[+4], [+5]
The LCD Contrast is adjustable and the valid range
is from -5 to +5. This range covers the maximum
adjustment for contrasting the background with the
text in the visual display of the control panel.
Transferring the UPS Between Modes
Transferring between modes includes:
S Transferring from Normal to Bypass mode
S Transferring from Bypass to Normal mode
No
—
[+0]
Transferring from Normal to Bypass Mode
To transfer from Normal to Bypass mode:
1Press the button for one second to go to the main menu selection and scroll down to the
Control menu using the button.
2Press the button to enter the Control menu.
3Select Go to Bypass.
The text on the screen changes to Manual Bypass Command Sent. The Bypass mode icon
flashes, indicating Bypass mode.
Operation
|
47
Transferring from Bypass to Normal Mode
To transfer from Bypass to Normal mode:
1Press the button for one second to go to the main menu selection and scroll down to the
Control menu using the button.
2Press the button to enter the Control menu.
3Select Go to Normal.
The text on the screen changes to Normal Command Sent. The Normal mode icon flashes,
indicating Normal mode.
Setting Power Strategy
On the High Efficiency setting, the UPS operates normally on Bypass, transfers to inverter in < 10 ms
when utility power fails, and transfers back to Bypass in one minute after utility power returns. The
Bypass mode status icon box appears on the UPS status summary screen when the UPS transfers to
Bypass.
NOTE: High Efficiency operation is available after one minute of stable power.
To set the power strategy:
1Press the button for one second to go to the main menu selection and scroll down to the
Settings menu using the button.
2Press the button to enter the Settings menu.
3Use the button to scroll to Power Strategy and press the button.
The current setting for the option flashes when selected.
4Select High Efficiency, Normal, or Converter using the and buttons.
The default is High Efficiency.
5Press the button to confirm.
|
48
Operation
Retrieving the Event Log
To retrieve the Event Log through the display:
1Press the button for one second to go to the main menu selection and scroll down to the
Event Log menu using the button.
2Press the button to enter the Event Log list.
3Scroll through the listed events, notices, and alarms using either the button or the button.
4To return to the main menu, press the button for one second. The Event Log displays.
5Press the button. The UPS status screen displays.
Behavior on Overload
See Table 7 for an explanation of how the UPS responds to an overload condition.
Table 7. Behavior on Overload
Overload
Severity
Level 1Load 100% to
Level 2Load 102% to
Level 3Load > 110% Transfer to Bypass immediately
Load LevelOn Utility Power
Overload alarm only and
101%
110%
support load indefinitely
Transfer to Bypass after
12 seconds (±1 sec)
If Bypass is not available,
transfer to Fault mode after
12 seconds (±1 sec)
If Bypass is not available,
transfer to Fault mode in
300 ms to 1 sec
On Bypass/High
Efficiency Mode
Overload alarm only
and support load
indefinitely
Transfer to Fault mode
in 2 minutes (±1 sec)
Transfer to Fault mode
in 300 ms to 1 sec
On Battery
Overload alarm only,
support load until low
battery shutdown level
is reached
Transfer to Fault mode
after 12 seconds
(±1 sec) or until low
battery shutdown level
is reached
Transfer to Fault mode
in 300 ms to 1 sec
Operation
|
49
Configuring Load Segments
Load segments are sets of receptacles that can be controlled by the Dell UPS Management Software,
the Dell Network Management Card, or through the LCD display, providing an orderly shutdown and
startup of your equipment. For example, during a power outage, you can keep key pieces of equipment
running while you turn off other equipment. This feature allows you to save battery power.
Each Dell Online Rack model has two configurable load segments. See “Identifying the UPS Rear
Panels” on page 15 for the load segment locations.
To control the load segments with power management software, see your power management software
manual for details (refer to the Software CD or www.dell.com for the latest information).
Controlling Load Segments Through the Display
To control the load segments through the display:
1Press the button for one second to go to the main menu selection and scroll down to the
Control menu using the button.
2Press the button to enter the Control menu.
3Use the button to scroll to Load Segments.
4Press the button.
The current setting for the option flashes when selected.
5Select the desired load segment using the and buttons.
6Set the desired load segment ON or OFF using the button.
7Press the button to confirm.
8Set the other load segment if applicable.
|
50
Operation
Configuring Automatic Start Delay
You can configure the load segment to turn on automatically after the utility power returns, if it was
shut down by:
S The button
S An external command with auto-restart option
S Battery under voltage state
S Automatic on battery shutdown command
You can specify the restart delay time for each load segment: select zero seconds (0s is the default) to
restart immediately, select 1–32767 seconds to delay for the specified time, or select Off.
To set the restart delay times for each load segment:
1Press the button for one second to go to the main menu selection and scroll down to the
Settings menu using the button.
2Press the button to enter the Settings menu.
3Use the button to scroll to the Automatic Start Delay option and press the button.
The current setting for the option flashes when selected.
4Set the restart delay for one load segment using the and buttons.
5Press the button to confirm.
6Set the restart delay for the other load segment if applicable.
7Press the button to confirm.
NOTE: Load segment On/Off commands issued through the Control menu override the user settings for load
segments.
NOTE: A single load segment delay applies to both outlets. However, there is an additional built-in one-second
delay between closing segment 1 and 2. The delay is always present when an On command is issued for both
segments at the same time.
Operation
|
51
Configuring Automatic on Battery Shutdown
If set to Off (default), the load segment turns off only when commanded manually by the button,
an external command, or through the display (Control > Load Segments).
If set to zero seconds (0s), the load segment turns off automatically when the UPS on Battery state
activates.
If you select a value, the load segment turns off automatically after the selected delay while the UPS
operates on battery, but the shutdown is cancelled if the utility returns before the delay has expired.
To set the shutdown times for each load segment:
1Press the button for one second to go to the main menu selection and scroll down to the
Settings menu using the button.
2Press the button to enter the Settings menu.
3Use the button to scroll to the Automatic on Battery Shutdown option and press the button.
The options display and the current settings flash when selected.
4Set the shutdown delay for one load segment using the and buttons.
5Press the button to confirm.
6Set the shutdown delay for the other load segment if applicable.
7Press the button to confirm.
52
|
Operation
Configuring Battery Settings
Configure the UPS settings for an installed EBM, including whether to run automatic battery tests and
automatic restart configuration.
Configuring the UPS for an EBM
If the UPS is not configured for the EBM, the UPS reports less battery time remaining on the UPS front
panel and to any remote software. You may receive a shutdown warning prematurely. To ensure
maximum battery runtime when using power management software, configure the UPS for the EBM:
1Press the button for one second to go to the main menu selection and scroll down to the
Settings menu using the button.
2Press the button to enter the Settings menu.
3Use the button to scroll to the External Battery Module option and press the button.
The battery number value begins to flash.
4Set the battery number value using the and buttons.
Configuration
UPS only (internal batteries)0 (default)
UPS + 1 EBM1
NOTE: Runtime is automatically adjusted based on present load levels and whether an EBM is configured.
5Press the button to confirm.
Setting
Operation
|
53
Running Automatic Battery Tests
The automatic discharge test, enabled by default, runs during the transition from Float to Rest mode.
After the test completes, the charge cycle restarts to completely charge the batteries and then continues
to Rest mode normally. The automatic test runs approximately once every three months and does not
run again until after three more Float to Rest mode transitions. If a manual battery test is requested,
the automatic battery test timer is reset so it will not run for the next three months.
For an automatic battery test to run:
S The Automatic Battery Tests setting must be enabled for the automatic battery tests to run. (See
the following section, “Configuring Automatic Battery Tests.”)
S The batteries must be fully charged.
S The UPS must be in Normal mode or High Efficiency mode with no active alarms.
S The load must be higher than 10%.
Configuring Automatic Battery Tests
To configure the automatic battery tests:
1Press the button for one second to go to the main menu selection and scroll down to the
Settings menu using the button.
2Press the button to enter the Settings menu.
3Use the button to scroll to the Automatic Battery Tests option and press the button.
The option begins to flash.
4Select whether to enable or disable the automatic battery test using the and buttons.
5Press the button to confirm.
Configuring Automatic Restart
The UPS automatically restarts if the utility power returns after the output was shut off due to depleted
batteries, a shutdown input signal, or automatic shutdown command.
You can set the load segment for the amount of time to delay the restart when utility power returns,
using the Automatic Start Delay setting. You can also configure UPS restart to depend on the battery
charge level, using the Battery Charge % to Restart setting.
|
54
Operation
5
Additional UPS Features
This chapter describes:
S Communication ports (RS-232 and USB)
S Dell Network Management Card
S Dell UPS Management Software
RS-232 and USB Communication Ports
To establish communication between the UPS and a computer, connect your computer to one of the
UPS communication ports using an appropriate communication cable (RS-232 cable not supplied). See
“Identifying the UPS Rear Panels” on page 15 for the communication port locations.
When the communication cable is installed, power management software can exchange data with the
UPS. The software polls the UPS for detailed information on the status of the power environment. If a
power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the
equipment.
The cable pins for the RS-232 communication port are identified in Figure 25, and the pin functions
are described in Table 8.
879
Figure 25. RS-232 Communication Port (DB-9 Connector)
3
16245
|
Additional UPS Features
55
Table 8. RS-232 Communication Port Pin Assignment
PinSignal NameFunctionDirection from the UPS
1Unused—
2TxTransmit to external deviceOut
3RxReceive from external deviceIn
4Unused—
5GNDSignal common (tied to chassis)—
6Unused—
7Unused—
8Unused—
9Unused—
*Unused pins must be left free on all models.
56
|
Additional UPS Features
Dell Network Management Card (Optional)
The Dell Online Rack UPS has one available communication bay, which supports the optional Dell
Network Management Card. See Figure 26 for the location of the communication bay.
It is not necessary to shut down the UPS before installing a communication card.
1Remove the slot cover secured by two screws. Retain the screws.
2Insert the communication card into the slot.
3Secure the card with both screws.
Figure 26. Dell Network Management Card
For details on disabling control commands from the Dell Network Management Card, see the Control
Commands from Serial Port setting on page 43.
Refer to the Dell Network Management Card User's Guide for more information.
The LAN card transfer rate is 10/100 Mbps.
|
Additional UPS Features
57
Dell UPS Management Software
Each Dell Online Rack UPS ships with Dell UPS Management Software.
Dell UPS Management Software provides up-to-date graphics of UPS power and system data and power
flow. It also gives you a complete record of critical power events, and it notifies you of important UPS or
power information. If there is a power outage and the Dell Online Rack UPS battery power becomes
low, the software can automatically shut down your computer system to protect your data before the
UPS shutdown occurs.
For details on disabling control commands from the software, see the user setting for Control
Commands from Serial Port setting on page 43.
58
|
Additional UPS Features
6
UPS Maintenance
This chapter explains how to:
S Care for the UPS and batteries
S Transport the UPS
S Store the UPS and batteries
S Test the batteries
S Update the UPS firmware
UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS clean and dust‐free. If the
atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For full battery life,
keep the UPS at an ambient temperature of 25°C (77°F).
NOTE: The batteries in the UPS are rated for a 3–5 year service life. The length of service life varies, depending
on the frequency of usage and ambient temperature. Batteries used beyond expected service life will often
have severely reduced runtimes. Replace batteries at least every 5 years to keep units running at peak
efficiency.
Transporting the UPS
NOTE: The internal UPS batteries MUST be disconnected before transportation.
CAUTION: The following procedure should be performed or supervised by personnel knowledgeable about
batteries and the required precautions. Keep unauthorized personnel away from batteries.
If the UPS requires any type of transportation, the batteries must be disconnected (but not removed)
before the unit is transported:
1Verify that the UPS is off and unplugged.
2Place the UPS on a flat, stable surface with the front of the cabinet facing you.
|
UPS Maintenance
59
3Remove the UPS front cover (see Figure 27).
Figure 27. Removing the UPS Front Cover
4Disconnect the internal battery connectors (see Figure 28).
Figure 28. Disconnecting the Internal Battery Connector
|
60
UPS Maintenance
5Replace the UPS front cover (see Figure 29).
Figure 29. Replacing the UPS Front Cover
Storing the UPS and Batteries
If you store the UPS for a long period, recharge the battery every 6 months by plugging the UPS into a
power outlet. The batteries charge to 90% capacity in approximately 4 hours. However, it is
recommended that the batteries charge for 48 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date has passed and the batteries
were never recharged, do not use the UPS. Contact your service representative.
When to Replace Batteries
When the status summary screen displays the UPS fault icon with the “Service Battery” alarm and the
audible alarm sounds continuously, the batteries may need replacing. Contact your service
representative to order new batteries.
NOTE: With the user-replaceable battery feature, UPS batteries can be replaced easily without turning the
UPS off or disconnecting the load.
|
UPS Maintenance
61
Testing Batteries
For a battery test to run:
S The batteries must be fully charged.
S The UPS must be in Normal mode or High Efficiency mode with no active alarms.
S The load must be higher than 10%.
To test batteries:
1Plug the UPS into a power outlet for at least 48 hours to charge the batteries.
2Press the button for one second to go to the main menu selection and scroll down to the
Control menu using the button.
3Press the button to enter the Control menu.
4Use the button to scroll to the Battery Test option.
5Press the button to start the battery test.
During the battery test, the UPS transfers to Battery mode and discharges the batteries for 25% of
the original expected runtime. The front panel displays “Battery test running” and the percentage
of the test completed. The results display on the UPS front panel when complete.
Updating the UPS Firmware
To keep the UPS firmware updated with the latest improvements and benefits, visit www.dell.com for
updates. You can download the latest firmware version and the instructions for installing it.
|
62
UPS Maintenance
Specifications
This chapter provides the following specifications:
ChargingApproximately 4 hours to 90% usable capacity at nominal line and no
supplementary power supply load
MonitoringAdvanced monitoring for earlier failure detection and warning
Battery Runtimes*3750W internal batteries: 5 minutes at full load/21 minutes at half load
4200W internal batteries: 5 minutes at full load/16 minutes at half load
3750W with one EBM attached: 14 minutes at full load/43 minutes at half load
4200W with one EBM attached: 11 minutes at full load/35 minutes at half load
*Battery runtimes are approximate and vary depending on the load configuration and battery charge.
Input
Filter
Charger
Figure 30. Online UPS Block Diagram
|
66
Specifications
Bypass
AC/DC
Boost
DC/DC
Battery
DC/AC
Inverter
Output
Filter
8
Troubleshooting
The Dell Online Rack UPS is designed for durable, automatic operation and issues alarms to alert you
whenever potential operating problems occur. Usually the alarms shown by the control panel do not
mean that the output power is affected. Instead, they are preventive alarms intended to alert the user.
Active alarms and active notices are accompanied by an audible buzzer.
Accessing Alarms and Conditions
The control panel provides troubleshooting information from two main menus:
S UPS Status menu: access to all active alarms
S Event Log menu: access to the most recent 50 events, which may include active and closed alarms
UPS Status Menu
From the UPS Status menu, you can access the following screens for troubleshooting information:
S Status summary screen: The status summary screen provides information on both mode and load.
When there is a critical alarm, the status summary screen changes from its normal white text on a
blue background to dark amber text on an amber background.
S Notice or alarm screens: A separate screen appears for each active notice or alarm. If there are no
active alarms or notices, the display reads “No Active Alarms.”
S Battery status screen: The battery status screen indicates the battery charge mode, the percent the
battery is charged, and the runtime with the present load level.
NOTE: When an alarm is active, the control panel automatically displays an active alarm screen unless the
screen lock is enabled by the user.
To access troubleshooting information using the UPS Status menu:
1Press the button for one second to go to the main menu selection.
2Press the button to access the UPS Status menu.
3Press the button to access the UPS status summary screen.
The UPS status summary screen provides load information. The status icon indicates the UPS
operating mode (see Table 3 on page 37).
4Use the button to scroll through the active notice and active alarm screens.
5After scrolling through all alarms, press the button to access the Battery Status screen.
Troubleshooting
|
67
Event Log Menu
From the Event Log menu, you can access the last 50 events, which includes events, notices, and
alarms, arranged from newest to oldest.
Events are silent conditions that are recorded in the Event Log as status information, such as “Clock Set
Done.” Events do not require a response.
Notices and alarms are records of when events occurred and, if applicable, when they were cleared.
S Notices, including active notices, are recorded in the Event Log. Active notices, such as “UPS on
Battery,” are announced by an intermittent beep. Notices do not normally require a response.
S Alarms, including active alarms, are recorded in the Event Log. Active alarms are announced by an
intermittent beep. Examples are “Output Overload” and “Heatsink Overtemperature.” Active
alarms require a response.
The Main Status Menu displays by default. To access troubleshooting information using the Event Log
menu:
1Press the button for one second to go to the main menu selection and scroll down to the
Event Log menu using the button.
2Click the button to enter the Event Log list.
3Scroll through the listed events, notices, and alarms using the or button.
Typical Alarms and Conditions
Table 15 describes typical alarms and conditions.
Table 15. Typical Alarms and Conditions
Alarm or Condition
The UPS does not provide or
indicate the expected backup
time.
Power is not available at the
UPS output receptacles.
The UPS does not start.
(The LCD is off.)
The UPS operates normally,
but some or all of the
protected equipment is not
on.
|
68
Troubleshooting
Possible CauseAction
The batteries need charging or
service.
The UPS is in Standby mode.Supply power to the connected equipment by
Power is not connected.Check the power connections. Also ensure
The equipment is not
connected correctly to the UPS.
Apply utility power for 48 hours to charge the
batteries. If the condition persists, contact
your service representative.
pressing the On/Off button until the front
panel displays the UPS status summary screen.
that the battery is plugged in.
Verify that the equipment is plugged into the
UPS receptacles. Also verify that the load
segment is on.
Table 15. Typical Alarms and Conditions (continued)
Alarm or ConditionActionPossible Cause
Battery test did not run or
was interrupted.
One of the conditions listed in
“Running Automatic Battery
Tests” on page 54 was not
present.
The UPS does not transfer to
Bypass mode.
The bypass utility does not
qualify.
Bypass mode is disabled.Check that the Bypass settings are configured
UPS on Bypass
(Notice 169)
The UPS is operating from
Bypass mode.
Continuous Alarm
On Manual Bypass
(Notice 143)
Intermittent Alarm
UPS on Battery
(Notice 168)
UPS was manually commanded
to transfer to Bypass mode and
will remain in bypass until
commanded.
A utility failure has occurred
and the UPS is in Battery mode.
Intermittent Alarm
Battery Disconnected
(Alarm 199)
Continuous Alarm
The UPS does not recognize
the internal batteries.
Battery voltage is lower than the
batteries disconnected level
defined for this UPS. This may
be due to a blown fuse,
intermittent battery
connection, or battery cable
being disconnected.
Low Battery Warning
(Alarm 56)
Continuous Alarm
Battery time remaining or
battery capacity is lower than
the battery low warning level
defined for this UPS.
Resolve the condition, then restart the test.
Check the bypass utility. The UPS is receiving
bypass utility power that may be unstable or in
brownout conditions.
correctly. See “Settings” on page 43.
The equipment transferred to bypass utility
power. Battery mode is not available and your
equipment is not protected; however, the
utility power continues to be passively filtered
by the UPS. Check for one of the following
alarms: overtemperature, overload, or UPS
failure.
None.
The UPS is powering the equipment with
battery power. Prepare your equipment for
shutdown.
If the condition persists, contact your service
representative.
Verify that all batteries are properly
connected. If the condition persists, contact
your service representative.
This warning is approximate. The actual time to
shutdown may vary depending on the UPS load
and presence of an External Battery Module
(EBM).
Troubleshooting
|
69
Table 15. Typical Alarms and Conditions (continued)
Alarm or ConditionActionPossible Cause
Shutdown Imminent
(Alarm 55)
Continuous Alarm
Communication to external
devices stops because the UPS
has entered a state where it may
abruptly stop operating without
further notice unless utility
returns.
Battery Test Failed
(Alarm 191)
A weak battery string was
detected during the last battery
test.
Intermittent Alarm
Service Battery
(Alarm 149)
A faulted battery string has
been detected and as a result,
the charger is disabled.
Continuous Alarm
Utility Not Present
(Alarm 59)
Utility level has fallen below the
Utility Not Present threshold
(typically <25 to 50V).
Intermittent Alarm
Bypass Not Available
(Alarm 105)
Input AC Over Voltage
(Alarm 6)
Utility is outside of the bypass
limits defined in the UPS.
Utility voltage exceeds the
maximum operating range.
Intermittent Alarm
Input AC Under Voltage
(Alarm 7)
Utility voltage is below the
minimum operating range.
Intermittent Alarm
Input Under/Over Frequency
(Alarm 8)
The utility frequency is out of
usable frequency range.
Intermittent Alarm
Site Wiring Problem
(Alarm 194)
An alarm triggers when the
difference between ground and
neutral voltage is >15V.
Continuous Alarm
Remote Emergency Power
Off
(Alarm 12)
Continuous Alarm
The external contacts in the
rear of the UPS are configured
for REPO operation and they
have been activated.
The alarm is issued when the battery time
remaining reaches zero. All connected devices
should have already shut down gracefully.
This is a warning notice. Dell recommends
that you replace the batteries soon.
Contact your service representative.
Transfer to battery if supporting load. Power
down if not supporting load.
Check the bypass settings. See “Settings” on
page 43.
The UPS transfers to Battery mode if
supporting load.
The UPS transfers to Battery mode if
supporting load.
The UPS transfers to Battery mode if
supporting load.
Have a qualified electrician correct the wiring
problem. If the UPS is not wired with a
neutral wire, Site Fault should be disabled in
the Settings menu (see page 43).
The UPS de-energizes the load and enters
Standby mode. See “Installing Remote
Emergency Power-off” on page 26 for more
information.
70
|
Troubleshooting
Table 15. Typical Alarms and Conditions (continued)
Alarm or ConditionActionPossible Cause
Output Overload
(Alarm 25)
Continuous Alarm
Output Overload Level 2
(Alarm 159)
The load level is at or has
exceeded the configurable
threshold limit for a Level 1
Overload condition.
The load level is >101% and
<110% of the UPS rating.
Continuous Alarm
Output Overload Level 3
(Alarm 162)
The load is >110% of the UPS
rating.
Continuous Alarm
Battery DC Over Voltage
(Alarm 68)
Battery voltage levels have
exceeded the maximum
allowable limits.
Continuous Alarm
Charger Failure
(Alarm 34)
A battery charger fault has been
detected.
Continuous Alarm
Inverter AC Over Voltage
(Alarm 0)
The UPS has detected
abnormally high inverter
voltage levels.
Continuous Alarm
Inverter AC Under Voltage
(Alarm 1)
The UPS has detected
abnormally low inverter voltage
levels.
Continuous Alarm
Rectifier Input Over Current
(Alarm 26)
The UPS has detected that
rectifier input current limits
have been exceeded.
Continuous Alarm
Inverter Output Over
Current
(Alarm 27)
The UPS has detected that the
inverter output current limits
have been exceeded.
Continuous Alarm
The UPS can support the load indefinitely at
this load level.
The alarm clears when the load drops below
5% of the set point.
Remove some of the equipment from the
UPS. The UPS continues to operate, but
transfers to Fault mode in two minutes.
The alarm clears when the load drops below
5% of the set point.
Remove some of the equipment from the
UPS. The UPS continues to operate, but
transfers to Fault mode in 300 ms to one
second.
The alarm clears when the load drops below
5% of the set point.
The UPS turns off the charger until the next
power recycle. Contact your service
representative.
The UPS turns off the charger until the next
power recycle. Contact your service
representative.
The UPS transfers to Bypass mode if
supporting the load.
The UPS transfers to Bypass mode if
supporting the load.
The UPS transfers to Bypass mode if
supporting the load.
The UPS transfers to Bypass mode if
supporting the load.
Troubleshooting
|
71
Table 15. Typical Alarms and Conditions (continued)
Alarm or ConditionActionPossible Cause
DC Link Over Voltage
(Alarm 28)
Continuous Alarm
DC Link Under Voltage
(Alarm 29)
Continuous Alarm
Rectifier Fault
(Alarm 30)
Continuous Alarm
Inverter Fault
(Alarm 31)
Continuous Alarm
Fatal EEPROM Fault
(Alarm 53)
Continuous Alarm
Output Short Circuit
(Alarm 58)
Continuous Alarm
Fan Failure
(Alarm 193)
Continuous Alarm
The link or rail voltage has
exceeded its upper threshold
limit.
The link or rail voltage has
dropped below its lower
threshold limit.
The UPS has detected a fault in
the rectifier circuit while
attempting recovery from
Bypass mode or Converter
mode.
The UPS has detected a fault in
the inverter circuit while
attempting a recovery from
Bypass mode or Converter
mode.
There is EEPROM data
corruption due to a failed
device or incorrect flash
upgrade.
The UPS has detected an
abnormally low impedance
placed on its output and
considers it a short circuit.
The UPS has detected that one
or more fans are not
functioning properly.
The UPS transfers to Bypass mode if
supporting the load.
The UPS transfers to Bypass mode if
supporting the load.
Contact your service representative.
Contact your service representative.
Contact your service representative.
If the UPS is in Normal mode, the UPS
transfers to Bypass mode if available,
otherwise, the UPS shuts down after five line
cycles.
If the UPS is in Battery mode, the UPS shuts
down after five line cycles.
This is an alarm only. Contact your service
representative immediately and remove the
load.
Silencing the Alarm
Press any button on the control panel to silence the alarm. Check the alarm condition and perform the
applicable action to resolve the condition. If any new alarm becomes active, the audible alarm resumes,
overriding the previously silenced alarm.
|
72
Troubleshooting