DeDietrich AWHP-2 MIT-IN-2 iSystem, MIT-IN-2/E, MIT-IN-2/H Installation And Service Manual

Page 1
Export
HPI EVOLUTION
EN
Air / water heat pump
AWHP-2 MIT-IN-2 iSystem
Installation and Service Manual
Page 2
Declaration of conformity
The device complies with the standard type described in the EG declaration of conformity. It was manufactured and commissioned in accordance with European directives.
The original declaration of conformity is available from the manufacturer.
C004793-A
Page 3
Contents
1 Introduction ................................................................................................6
1.1 Symbols used .......................................................6
1.1.1 Symbols used in the manual ...................................6
1.1.2 Symbols used on the equipment .............................6
1.2 Abbreviations ........................................................7
1.3 Liabilities ...............................................................7
1.3.1 Manufacturer’s liability .............................................7
1.3.2 Installer’s liability .....................................................7
1.4 Homologations ......................................................8
1.4.1 Certifications ...........................................................8
2 Safety instructions and recommendations ..............................................9
2.1 Safety instructions ...............................................9
2.2 Recommendations ................................................9
3 Technical description ..............................................................................11
3.1 General description ............................................11
3.2 Main parts (Indoor module) ...............................11
3.2.1 MIT-IN-2/H ............................................................11
3.2.2 MIT-IN-2/E .............................................................12
3.3 Operating principle .............................................12
3.3.1 General .................................................................12
3.3.2 Skeleton Diagrams ................................................13
3.3.3 Pressure available .................................................14
3.4 Technical specifications ....................................14
3.4.1 Electricity supply ...................................................14
3.4.2 Heat pump .............................................................15
3.4.3 Sensor characteristics ...........................................16
4 Installation ................................................................................................17
4.1 Regulations governing installation ...................17
4.2 Package list .........................................................17
4.2.1 Standard delivery ..................................................17
4.2.2 Accessories ...........................................................18
4.3 Type plate ............................................................19
4.3.1 Outdoor unit ..........................................................19
4.3.2 Indoor module .......................................................19
25/06/2014 - 7616371-001-04
1
Page 4
4.4 Installing the outdoor module ...........................20
4.4.1 Positioning of the appliance ..................................20
4.4.2 Main dimensions ...................................................22
4.4.3 Locating the outside module ................................26
4.5 Installing the indoor module ..............................27
4.5.1 Positioning of the appliance ..................................27
4.5.2 Main dimensions ...................................................27
4.5.3 Assembly of the indoor module ............................28
4.6 Installing the outside sensor .............................29
4.6.1 Choice of the location ............................................29
4.6.2 Connecting the outside sensor ..............................29
4.7 Combination with a DHW tank ...........................30
4.8 Installing the refrigerant piping .........................30
4.8.1 Installing the pipes ................................................30
4.8.2 Water tightness test ..............................................35
4.8.3 Evacuation ............................................................35
4.8.4 Opening the valves ...............................................35
4.8.5 Adding refrigerant ..................................................36
4.9 Hydraulic connections .......................................36
4.9.1 Flushing the system ..............................................36
4.9.2 Connection of the heating circuit ...........................37
4.9.3 Hydraulic connection diagrams .............................37
4.10 Filling the heating system ..................................40
4.10.1 Water treatment in the heating circuit ...................40
4.10.2 Filling the system ..................................................42
4.11 Electrical connections ........................................42
4.11.1 Recommendations ................................................42
4.11.2 Recommended cable cross section ......................43
4.11.3 Accessing the connection terminal blocks ............44
4.11.4 Position of the PCBs .............................................46
4.11.5 Location of the fuse ...............................................47
4.11.6 Connecting the outdoor module ............................47
4.11.7 Connecting the communication cable between the
inside and outside modules ...................................47
4.11.8 Description of the terminal block on the inside
module ..................................................................48
4.11.9 Connecting the mains supply to the inside
module ..................................................................49
4.11.10 Connecting the electrical back-up to the inside
module ..................................................................49
4.11.11 Connecting the hydraulic auxilary on the inside
module ..................................................................51
4.11.12 Connection example for a system with hydraulic back-
up ..........................................................................52
4.11.13 Connection example for a system with electrical back-
up ..........................................................................57
4.11.14 Connection example in cooling mode ...................59
4.11.15 Pool connection .....................................................61
4.11.16 Connecting the options .........................................63
4.11.17 Connecting the "energy metering" option ..............64
4.11.18 Connection in cascade ..........................................67
Contents
25/06/2014 - 7616371-001-04
2
Page 5
4.11.19 Connection example in power cut off EVU ............69
4.12 Electrical principle diagram ...............................71
4.12.1 Legend ..................................................................71
4.12.2 Hydraulic additional heating ..................................73
4.12.3 Electrical back-up ..................................................74
5 Commissioning ........................................................................................75
5.1 Control panel .......................................................75
5.1.1 Description of the keys ..........................................75
5.1.2 Description of the display ......................................76
5.1.3 Access to the various browsing levels ..................79
5.1.4 Browsing in the menus ..........................................80
5.2 Check points before commissioning ................81
5.2.1 Hydraulic connections ...........................................81
5.2.2 Electrical connection .............................................81
5.3 Checklist for commissioning (HP) ....................82
5.4 Putting the appliance into operation ................83
5.5 Checks and adjustments after
commissioning ...................................................84
5.5.1 Displaying the parameters in extended
mode .....................................................................84
5.5.2 Setting the heating pump speed on the heat
pump .....................................................................84
5.5.3 Setting the flow rate threshold ...............................85
5.5.4 Setting the parameters specific to the
installation .............................................................86
5.5.5 Naming the circuits and generators ......................91
5.5.6 Setting the heating curve ......................................92
5.5.7 Setting the speed of the heating pump on the inside
module ..................................................................94
5.6 Reading out measured values ...........................94
5.7 Changing the settings ........................................96
5.7.1 Language selection ...............................................96
5.7.2 Calibrating the sensors .........................................96
5.7.3 Professional settings .............................................98
5.7.4 Configuring the network ......................................109
5.7.5 Return to the factory settings ..............................112
25/06/2014 - 7616371-001-04
3
Page 6
6 Switching off the appliance ...................................................................113
6.1 Installation shutdown .......................................113
6.2 Turning on the antifreeze function ..................113
7 Checking and maintenance ...................................................................114
7.1 General instructions .........................................114
7.2 Maintenance operations to be performed ......114
7.3 Cleaning the 400 µm filter ................................114
7.4 Customising maintenance ...............................115
7.4.1 Maintenance message ........................................115
7.4.2 Contact details of the professional for After Sales
Support ................................................................116
8 Troubleshooting .....................................................................................118
8.1 Anti-hunting ......................................................118
8.2 Messages ...........................................................118
8.3 Message history ................................................120
8.4 Faults (Code type Lxx or Dxx) .........................121
8.4.1 Deletion of sensors from the memory in the
PCB .....................................................................124
8.5 Failure history ...................................................125
8.6 Parameter and input/output check (mode
tests) ..................................................................125
9 Spare parts ..............................................................................................131
9.1 General ..............................................................131
9.2 Spare parts ........................................................132
9.2.1 Outdoor unit 4 and 6 kW .....................................132
9.2.2 Outdoor unit 8 kW ...............................................135
9.2.3 Outdoor unit 11 and 16 kW .................................138
9.2.4 Outdoor unit 22 and 27 kW .................................143
9.2.5 Indoor module .....................................................147
Contents
25/06/2014 - 7616371-001-04
4
Page 7
25/06/2014 - 7616371-001-04
5
Page 8
1 Introduction
1.1 Symbols used
1.1.1. Symbols used in the manual
In these instructions, various danger levels are employed to draw the user’s attention to particular information. In so doing, we wish to safeguard the user’s safety, highlight hazards and guarantee correct operation of the appliance.
DANGER
Risk of a dangerous situation causing serious physical injury.
WARNING
Risk of a dangerous situation causing slight physical injury.
CAUTION
Risk of material damage.
Signals important information.
¼Signals a referral to other instructions or other pages in the instructions.
1.1.2. Symbols used on the equipment
4
Protective earthing
~
Alternating current
Before installing and commissioning the device, read carefully the instruction manuals provided.
Dispose of the used products in an appropriate recovery and recycling structure.
Caution: danger, live parts. Disconnect the mains power prior to any operations.
1 2
M002628-A
1. Introduction
AWHP-2 MIT-IN-2 iSystem
6
25/06/2014 - 7616371-001-04
Page 9
1.2 Abbreviations
4 DHW: Domestic hot water 4 PPS: Polypropylene hardly inflammable 4 PCU: Primary Control Unit - PCB contoller for heat pump operation 4 PSU: Parameter Storage Unit - Parameter storage for PCBs
PCU and SU
4 SCU: Secondary Control Unit - DIEMATIC iSystem control panel
PCB
4 SU: Safety Unit - Safety PCB 4 3WV: 3-way valve 4 EVU: Power supply company 4 AWHP: Outdoor module connected by connection cable to the
indoor module
4 MIT-2: Indoor module fitted with a DIEMATIC iSystem control
panel
4 HP: Heat pump 4 EER: Frigorific efficiency ratio 4 COP: Performance coefficient
4 EER: Frigorific efficiency ratio
1.3 Liabilities
1.3.1. Manufacturer’s liability
Our products are manufactured in compliance with the requirements of the various applicable European Directives. They are therefore
delivered with [ marking and all relevant documentation.
In the interest of customers, we are continuously endeavouring to make improvements in product quality. All the specifications stated in this document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the following cases:
4 Failure to abide by the instructions on using the appliance. 4 Faulty or insufficient maintenance of the appliance. 4 Failure to abide by the instructions on installing the appliance.
1.3.2. Installer’s liability
The installer is responsible for the installation and commissioning of the appliance. The installer must respect the following instructions:
4 Read and follow the instructions given in the manuals provided
with the appliance.
AWHP-2 MIT-IN-2 iSystem
1. Introduction
25/06/2014 - 7616371-001-04
7
Page 10
4 Carry out installation in compliance with the prevailing legislation
and standards.
4 Perform the initial start up and carry out any checks necessary. 4 Explain the installation to the user. 4 If a maintenance is necessary, warn the user of the obligation to
check the appliance and maintain it in good working order.
4 Give all the instruction manuals to the user.
1.4 Homologations
1.4.1. Certifications
This product complies to the requirements to the european directives and following standards:
4 2006/95/EC Low Voltage Directive. Reference Standards:
EN60335-1 / EN60335-2-40.
4 2004/108/EC Electromagnetic Compatibility Directive. Generic
standards: EN1000-6-3 , EN 61000-6-1.
1. Introduction AWHP-2 MIT-IN-2 iSystem
8
25/06/2014 - 7616371-001-04
Page 11
2 Safety instructions and
recommendations
2.1 Safety instructions
DANGER
If smoke is released or in case of refrigerant leak:
1. Do not use a naked flame, do not smoke, do not operate electrical contacts or switches ( doorbell, light, motor, lift, etc..). Contact between refrigerant and a flame may result in emissions of toxic gases.
2. Open the windows.
3. Trace possible leaks and seal them immediately.
WARNING
Before any work, switch off the mains supply to the appliance.
WARNING
Do not touch the refrigeration connection pipes with your bare hands while the appliance is running. Danger of burns or frost injury.
2.2 Recommendations
WARNING
4 Any intervention on the appliance and heating
equipment must be carried out by a qualified engineer.
4 For a proper operating of the boiler, follow carefully
the instructions.
AWHP-2 MIT-IN-2 iSystem 2. Safety instructions and recommendations
25/06/2014 - 7616371-001-04
9
Page 12
Keep this document close to the place where the boiler is installed.
CAUTION
4 Use tools and pipe components especially designed
for use with R410A refrigerant.
4 Install the appliance on a solid, stable structure able
to bear its weight.
4 Use phosphorous-deoxidised copper for pipes
without welds and copper alloy to connect the pipes carrying the refrigerant.
4 Use only R410A gas to fill the pipes with refrigerant. 4 Do not install the appliance in a place where it may
be exposed to steam, sulphuric gas or combustion, an atmosphere with a high salt content, or which may be covered by snow.
4 Ensure correct earthing. 4 Store the refrigeration connection pipes away from
dust and humidity (danger of damage to the compressor) and cover both ends until the expansion process is complete.
4 Do not use a load cylinder.
CAUTION
4 Activate the main switch at least 12 hours before the
appliance starts to function. Using the appliance just after it is switched on may seriously damage the internal parts.
4 When switching off the appliance, wait for at least 5
minutes of post-operation before deactivating the main switch. Danger of breakdown or water leak.
CAUTION
In order to limit the risk of being scalded, the installation of a thermostatic mixing valve on the domestic hot water flow piping is compulsory.
Before carrying out any maintenance work requiring the shutdown of the inside module, also cut the power supply to the outside module to prevent any errors in communication.
2. Safety instructions and recommendations AWHP-2 MIT-IN-2 iSystem
10
25/06/2014 - 7616371-001-04
Page 13
3 Technical description
3.1 General description
The AWHP-2 MIT-IN-2 iSystem heat pump is composed of two elements:
4 The outside unit handles energy production in hot or cold mode. 4 The inside module handles thermal exchange between the R410A
fluid and the hydraulic circuit.
The two units are connected by means of refrigeration and electrical connections.
The system offers the following advantages:
4 The heating circuit is housed in the insulated volume within the
home. There is no danger of the pipes freezing.
4 Thanks to the DC inverter system, the heat pump modulates its
output to adapt to the needs of the home.
4 The control panel uses the outside temperature sensor to adjust
the temperature of the heating circuit according to the outside temperature.
3.2 Main parts (Indoor module)
3.2.1. MIT-IN-2/H
1
Automatic air bleed
2
tank
3
High energy efficient heating pump
4
Plate heat exchanger
5
electrical support
6
Flowmeter
7
Table cover unit
8
Control panel
9
Safety valve
10
Pressure gauge
11
Expansion vessel
M002483-A
2
3
5
4
8
7
6
11
10
9
1
AWHP-2 MIT-IN-2 iSystem 3. Technical description
25/06/2014 - 7616371-001-04
11
Page 14
3.2.2. MIT-IN-2/E
1
Automatic air bleed
2
tank
3
High energy efficient heating pump
4
Plate heat exchanger
5
electrical support
6
Flowmeter
7
Table cover unit
8
Control panel
9
Safety valve
10
Pressure gauge
11
Expansion vessel
12
Automatic air bleed
13
Electric heater
3.3 Operating principle
3.3.1. General
The outside module produces heat or cold (in reversible versions) and transmits it to the heating circuit via the refrigerant in the plate exchanger. The outside module is capable of operating at outside temperatures down to -20°C (-15°C in the case of a 4 kW or 6 kW heat pump).
The DIEMATIC iSystem control panel is used to programme and regulate the heat pump according to the outside temperature.
By activating the pumps and, where necessary, the mixer valve, the regulator handles the regulation of the heating.
Connection of a CDR4 simplified remote control or a CDI4 interactive remote control enables the auto-adaptivity of the gradient and the parallel offset of the heating curve.
The antifreeze function on the installation is active whatever the operating mode. It is triggered as soon as the outdoor temperature reaches the limiting value preset to +3°C.
The installation of a buffer tank is not necessary if the volume of water in the circuit is higher than or equal to 3 litres/kW: Therefore, for a heat pump with an output of less than 11 kW, with a water volume of less than 33 litres, the installation of a buffer tank is necessary.
M002484-A
13
2
3
5
4
8
7
6
11
10
9
1
12
3. Technical description
AWHP-2 MIT-IN-2 iSystem
12
25/06/2014 - 7616371-001-04
Page 15
3.3.2. Skeleton Diagrams
n
MIT-IN-2/H
1
Inside module with hydraulic back-up
2
tank
3
Filter
4
Flowmeter
5
Radiator
6
Plate heat exchanger
7
Outdoor unit
8
Boiler
n
MIT-IN-2/E
1
Inside module with electrical back-up
2
tank
3
Electrical back-up
M002487-E
2
1
3 4
5
8
7
6
M002488-E
2
1
3
4
5 8
6
7
AWHP-2 MIT-IN-2 iSystem 3. Technical description
25/06/2014 - 7616371-001-04
13
Page 16
4
Radiator
5
Plate heat exchanger
6
Filter
7
Flowmeter
8
Outdoor unit
3.3.3. Pressure available
A
Pressure available (mbar)
Z
Water flow rate (m3/h)
1 - 5
Setting the pump
¼To set the speed of the heating pump correctly, refer to chapter: "Setting the speed of the heating pump on the inside module", page 94.
3.4 Technical specifications
3.4.1. Electricity supply
230 V AC (+/- 10%) - 50 Hz
400 V AC (+ 6%, - 10%) - 50 Hz (depending on the model)
M002627-C
0
100
200
300
400
500
600
700
800
0 0,5 1 1,5 2 2,5 3
1
2
4
3
2
1
5
3. Technical description
AWHP-2 MIT-IN-2 iSystem
14
25/06/2014 - 7616371-001-04
Page 17
3.4.2. Heat pump
Conditions of use:
4 Limit operating temperatures in Hot mode:
- Water: +18 °C / +60 °C
- Outside air:
-15 °C / +35 °C (4, 6 kW)
-20 °C / +35 °C (8, 11, 16, 22, 27 kW)
4 Limit operating temperatures in Cooling mode:
- Water: +7 °C / +25 °C
- Outside air: +15 °C / +40 °C (At less than 18°C, it is necessary
to use the HK24 insulation kit option)
4 Maximum operating pressure: 3 bar
n
Performances in hot mode with outside air temperature at +7°C and outlet water temperature at +35°C (in accordance with EN 14511–2)
AWHP
4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Calorific output - A7/W35 kW 3.72 5.87 8.26 10.56 10.56 14.19 14.19 19.4 24.4 COP hot - A7/W35
4.30 4.18 4.27 4.30 4.30 4.22 4.22 3.94 3.90 Absorbed electrical power - A7/W35 kWe 0.87 1.41 1.93 2.46 2.46 3.36 3.36 4.92 6.25 Nominal amperage - A7/W35 A 4.11 6.57 8.99 11.81 11.81 16.17 16.17 7.75 9.86
n
Performances in hot mode with outside air temperature at +2°C and outlet water temperature at +35°C (in accordance with EN 14511–2)
AWHP
4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Calorific output - A2/W35 kW 3.76 3.87 5.93 10.19 10.19 11.38 11.38 12.10 14.70 COP hot - A2/W35
3.32 3.26 3.20 3.20 3.20 3.27 3.27 3.10 3.10 Absorbed electrical power - A2/W35 kWe 1.13 1.19 1.85 3.19 3.19 3.48 3.48 3.91 4.70 Nominal amperage - A2/W35 A 6.1 6.1 8.2 10.7 6.2 14.6 8.4 9.7 11.8
n
Performances in cold mode with outside air temperature at +35°C and outlet water temperature at +18°C (in accordance with EN 14511–2)
AWHP
4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Cooling output kW 3.84 4.69 7.90 11.16 11.16 14.46 14.46 17.65 22.2 EER
3.80 3.80 3.99 4.68 4.68 4.43 4.43 3.8 3.8
Absorbed electrical power kWe 0.72 1.15 2.0 2.35 2.35 3.65 3.65 4.65 5.84
AWHP-2 MIT-IN-2 iSystem 3. Technical description
25/06/2014 - 7616371-001-04
15
Page 18
n
General values
AWHP 4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
(1)
dB(A) 41.7 41.7 43.2 43.4 43.4 47.4 47.4 51.8 53
Nominal water flow (ΔT = 5K)
m3/h
1.04 1.04 1.47 1.88 1.88 2.67 2.67 3.8 4.6
Manometric height available at nominal flow rate
mbar 618 618 493 393 393 213 213 - -
Nominal air flow rate
m3/h
2100 2100 3000 6000 6000 6000 6000 8400 8400
Power voltage of the outdoor unit
V 230 V~ 230 V~ 230 V~ 230 V~ 400 V3~ 230 V~ 400 V3~ 400 V3~ 400 V3~
Sound output
(2)
dB(A) 63.7 63.7 65.2 65.4 65.4 69.4 69.4 73.8 75
R410A refrigerant kg 2.1 2.1 3.2 4.6 4.6 4.6 4.6 7.1 7.7 refrigerant piping
connection (Liquid­Gas)
inch 1/4-1/2 1/4-1/2 3/8-5/8 3/8-5/8 3/8-5/8 3/8-5/8 3/8-5/8 3/8-3/4 or
3/8-1
1/2-3/4 or 1/2-1
Max pre-loaded length
m 10 10 10 10 10 10 10 30 30
Weight (empty) ­Outside unit
kg 42 42 75 118 118 130 130 135 141
(1) 5 m from the appliance, free field. (2) Test conducted in accordance with the standard NF EN 12102
3.4.3. Sensor characteristics
Outside sensor
Temperature in °C -20 -16 -12 -8 -4 0 4 8 12 16 20 24 Resistance in Ω 2392 2088 1811 1562 1342 1149 984 842 720 616 528 454
DHW sensor Flow sensor
Temperature in °C 0 10 20 25 30 40 50 60 70 80 90 Resistance in Ω 32014 19691 12474 10000 8080 5372 3661 2535 1794 1290 941
3. Technical description AWHP-2 MIT-IN-2 iSystem
16
25/06/2014 - 7616371-001-04
Page 19
4 Installation
4.1 Regulations governing installation
CAUTION
Installation of the appliance must be done by a qualified engineer in accordance with prevailing local and national regulations.
4.2 Package list
4.2.1. Standard delivery
The delivery includes:
4 An outside module (See below) 4 An inside hydraulic module (See below) 4 An outside sensor 4 Refrigerant adapter fitting 4, 6 and 22 kW 4 A mounting rail (screwed to the pallet) 4 The installation and maintenance instructions 4 The user instructions
Combinations possible:
Models
Outdoor unit Indoor module
Description Pack no. Description Pack no.
HPI 4 MR-2
AWHP 4 MR EH336
MIT-IN-2/H 4 - 8 ISYS MIT-IN-2/E 4 - 8 ISYS
EH386 EH389
HPI 6 MR-2
AWHP 6 MR-2 EH380
MIT-IN-2/H 4 - 8 ISYS MIT-IN-2/E 4 - 8 ISYS
EH386 EH389
HPI 8 MR-2
AWHP 8 MR-2 EH381
MIT-IN-2/H 4 - 8 ISYS MIT-IN-2/E 4 - 8 ISYS
EH386 EH389
HPI 11 MR-2
AWHP 11 MR-2 EH382
MIT-IN-2/H 11 - 16 ISYS MIT-IN-2/E 11 - 16 ISYS
EH387 EH390
HPI 11 TR-2
AWHP 11 TR-2 EH383
MIT-IN-2/H 11 - 16 ISYS MIT-IN-2/E 11 - 16 ISYS
EH387 EH390
HPI 16 MR-2
AWHP 16 MR-2 EH384
MIT-IN-2/H 11 - 16 ISYS MIT-IN-2/E 11 - 16 ISYS
EH387 EH390
HPI 16 TR-2
AWHP 16 TR-2 EH385
MIT-IN-2/H 11 - 16 ISYS MIT-IN-2/E 11 - 16 ISYS
EH387 EH390
HPI 22 TR-2
AWHP 22 TR EH225
MIT-IN-2/H 22 - 27 ISYS MIT-IN-2/E 22 - 27 ISYS
EH388 EH391
HPI 27 TR-2
AWHP 27 TR EH226
MIT-IN-2/H 22 - 27 ISYS MIT-IN-2/E 22 - 27 ISYS
EH388 EH391
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
17
Page 20
4.2.2. Accessories
Various options are available depending on the configuration of the installation:
n
Heat pump options
Description package
160 L storage tank EH 60 80 L storage tank EH 85 Wall-hanging kit for outside units 6 - 10 kW EH 95 Condensate receiver tank for wall bracket EH 111 Ground mounting supports for outside units EH 112 Electrical resistor for the condensate receiver tank EH 113 Frigorific ducts with insulation (5/8" - 3/8"); Length: 5 m EH 114 Frigorific ducts with insulation (5/8" - 3/8"); Length: 10 m EH 115 Frigorific ducts with insulation (5/8" - 3/8"); Length: 20 m EH 116 Insulated copper pipe (1/2" - 1/4") 10 m EH 142 1/4" 1/2" - 3/8" 5/8" adapter fittings EH 146 Heat pump hydraulic connection kit - DHW storage tank EH 149 Wall-hanging kit for outside units 11 - 27 kW EH 250 3-way valve module with standard pump EA 63 3-way valve module with electronic pump EA 67 Collector for 2/3 circuits EA140 Wall console EA141 Wall console for hydraulic module EA142 Direct circuit with pump HEE EA143 V3V circuit with HEE pump EA144 Wiring kit for connecting a safety thermostat for underfloor
heating
HA 249
3-way valve kit HK 21 2-circuit kit HK 22 Reversal valve kit HK 23 Insulation kit cold mode HK 24 3-way valve insulation kit HK 25
n
Control system options
Description
package
BUS connection cable (length 12 m) AD134 voice remote monitoring module AD152 Outlet sensor V3V AD199 DHW sensor AD212 Optional PCB for 3-way valve AD249 System sensor AD250 Outside radio-controlled temperature sensor AD251 Radio module AD252 CDR iSystem radio remote control AD284
4. Installation AWHP-2 MIT-IN-2 iSystem
18
25/06/2014 - 7616371-001-04
Page 21
Description package
Interactive radio remote control with LCD display CD12/CD14 AD285 Radio remote control AD253 Interactive remote control AD254 A simplified remote control with room sensor FM52 Condensation detector kit HK 27 Energy metering option HK 29
4.3 Type plate
4.3.1. Outdoor unit
The type plate must be accessible at all times. The type plate identifies the product and provides the following information:
4 Appliance type 4 Manufacturing date (Year - Week) 4 Serial number. 4 Nature of the power supply voltages
4.3.2. Indoor module
1
This data plate is affixed to the inside side panel of the appliance in the factory.
2
When installation has been completed, affix the data plate provided in the instructions bag to the casing of the appliance in a position where it can be seen.
The type plate must be accessible at all times. The type plate identifies the product and provides the following information:
4 Appliance type 4 Manufacturing date (Year - Week) 4 Serial number. 4 Nature of the power supply voltages
MW-M001832-2
M002624-A
Auf ERDGAS H eingestellt für DE: Erdgas E Réglé au gaz naturel H Geregeld voor aardgas H Preset for natural gas H G20 - 20 mbar
8366-4038
1 2
AWHP-2 MIT-IN-2 iSystem
4. Installation
25/06/2014 - 7616371-001-04
19
Page 22
4.4 Installing the outdoor module
4.4.1. Positioning of the appliance
Ensure that the outside module is optimally positioned in relation to neighbours as it is a source of noise.
CAUTION
4 There must be no obstacles hindering the free
circulation of air around the outdoor module (intake and output).
4 No not locate the outside unit close to where people
sleep.
4 Do not locate the unit opposite a wall with windows. 4 Avoid placing it close to a terrace, etc..
Choose a location away from prevailing winds.
C000373-B
Brrrrr....
Brrrrr....
Brrrrr....
Brrrrr....
In some cases, additional precautions are necessary owing to the fact, for example, of too short a distance between you and your neighbours. When installing a noise reduction screen, respect the following recommendations:
4 Locate the noise reduction screen as close as possible to the noise
source whilst allowing for the free circulation of air in the exchanger on the outside unit and maintenance work.
Place the outside unit on a base (concrete base frame, sill, concrete blocks, etc.) with no rigid connection with the building served in order to prevent any transmission of vibrations. Ensure
sufficient above ground elevation (100 to 150 mm) to keep it above water. For regions where heavy snowfalls occur, raise this above ground protection by at least 200 mm compared with the average depth of the covering of snow.
M001448-A
4. Installation
AWHP-2 MIT-IN-2 iSystem
20
25/06/2014 - 7616371-001-04
Page 23
CAUTION
4 If the outside temperatures become negative, take
the necessary precautions to prevent the risk of freezing in the evacuation pipes.
4 Prevent any risk of the condensates freezing in an
area through which they flow.
4 The heating cord keeps the condensates from
freezing: See EH113 leaflet.
n
Distances to be observed
WARNING
To ensure that the heat pump functions correctly, respect the minimum and maximum connection lengths between the heat pump and the indoor module.
A
Outdoor unit
Z
Indoor module
A
Minimum length 5 m Maximum length: 40 m for 4, 6, 8 kW, 75 m for 11, 16 kW, 20 m for 22, 27 kW.
B
Max height difference 10 m For 4, 6, 8 kW Max height difference 30 m For 11, 16, 22, 27 kW
C
Max number of elbows: 15 Respect the minimum curve radii of 100 to 150 mm
¼See chapter: "Installing the pipes", page 30.
M00 1439-A
A
B
2
1
C
MW-M001450-2
G
F
F
G
A
C
B
B
C
E
A
1000
D
M
ax. 500
M
ax. 500
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
21
Page 24
Dimension (mm) 4, 6, 8 kW 11, 16, 22, 27 kW
A
100 150
B
500 1000
C
200 300
D
1000 1500
E
300 500
F
150 250
G
100 200
4.4.2. Main dimensions
n
AWHP 4 and 6 MR-2
A
1/4" flare refrigerant fitting
Z
1/2" flare refrigerant gas fitting
150 500
800
887
300
183
155
365
600
40
10
23
69
18
90
MW-M002199-2
1
2
4. Installation AWHP-2 MIT-IN-2 iSystem
22
25/06/2014 - 7616371-001-04
Page 25
n
AWHP 8 MR-2
A
3/8" flare refrigerant fitting
Z
5/8" flare refrigerant gas fitting
943
950
45
56
53 28
19
23
417
175
330
370
30
443
447
175
65 42
2
(1)
(2)
MW-M001442-2
1
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
23
Page 26
n
AWHP 11 and 16 MR/TR-2
A
3/8" flare refrigerant fitting
Z
5/8" flare refrigerant gas fitting
1350
950
45
56
53 28
19
23
417
175 600
330
370
30
443
447
175
65 42
2
(1)
(2)
1
MW-M001443-2
4. Installation AWHP-2 MIT-IN-2 iSystem
24
25/06/2014 - 7616371-001-04
Page 27
n
AWHP 22 and 27 TR
A
450 mm : 22 kW
424 mm : 27 kW
A
3/8" flare refrigerant fitting (22 kW) 1/2" flare refrigerant fitting (27 kW)
Z
3/4" flare refrigerant gas fitting + adapter 1" (to be brazed)
MW-M002629-1
1338
1050
40
56
26
342
A
225
330
370
417
30
600
225
19
28
60
42
(1)
(2)
2
1
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
25
Page 28
4.4.3. Locating the outside module
CAUTION
Keep the appliance vertical during transport.
n
Installation on the ground
1
Concrete base frame
2
Condensates run-off
3
Install a run-off channel with pebble bed
4 Use the ground installation base kit available as optional
equipment: Package EH112.
4 Install the appliance on a solid, stable structure able to bear its
weight.
n
Condensates discharge
CAUTION
If the outside temperatures become negative, take the necessary precautions to prevent the risk of freezing in the evacuation pipes. Use package EH113 (Electrical resistor for the condensate receiver tank). Prevent any risk of the condensates freezing in an area through which they flow.
>45°
M001456-A
200
1
2
3
M001452-A
4. Installation AWHP-2 MIT-IN-2 iSystem
26
25/06/2014 - 7616371-001-04
Page 29
4.5 Installing the indoor module
4.5.1. Positioning of the appliance
CAUTION
4 Install the appliance in frost-free premises. 4 Fix the appliance to a solid wall capable of bearing
the weight of the appliance when full of water and fully equipped.
4.5.2. Main dimensions
A
3-way valve circuit return (Option) - G1"
Z
3-way valve circuit outlet (Option) - G1"
E
Return direct circuit - G1"
R
Direct circuit flow - G1"
T
Back-up boiler inlet - G1" Only for hydraulic back-up - Version H
Y
Return to the back-up boiler - G1" Only for hydraulic back-up - Version H
U
Gas line 5/8" flare connection: 4, 6, 8, 11, 16 kW 3/4" flare connection: 22, 27 kW (Use 1" braze-on adapter)
I
Liquid line 3/8" flare connection: 4, 6, 8, 11, 16 kW 1/2" flare connection: 22, 27 kW
G
Exterior cylindrical threading, sealed by sheet gasket
T001898-C
600
min.1000
500
min. 250
min. 250
900
M002497-B
122
192
262
332
402
472
542
49 48
900
600
498
1234567
8
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
27
Page 30
4.5.3. Assembly of the indoor module
n
Fitting the mounting rail
1. Drill 2 holes with a Ø of 10 mm.
Additional holes are provided in case one or other of the standard locating holes prevents the correct location of the plugs.
2. Put the plugs in place.
3. Fix the mounting rail to the wall using the hexagonal head screws provided for this purpose. Set the level using a spirit level.
n
Fixing to the wall
CAUTION
Weight (empty): 74 kg Shipping weight: 112 kg
1. Present the indoor module above the mounting rail until it rests firmly against it.
2. Gently lower the indoor module.
1
2
3
3
M002380-B
458
61
11
558
Ø10
M002381-C
4. Installation AWHP-2 MIT-IN-2 iSystem
28
25/06/2014 - 7616371-001-04
Page 31
4.6 Installing the outside sensor
4.6.1. Choice of the location
It is important to select a place that allows the sensor to measure the outside conditions correctly and effectively.
Advised positions:
4 on one face of the area to be heated, on the north if possible 4 half way up the wall in the room to be heated 4 under the influence of meteorological variations 4 protected from direct sunlight 4 easy to access
A
Recommended position
B
Possible position
H
Inhabited height controlled by the sensor
Z
Inhabited area controlled by the sensor
Positions to be avoided:
4 masked by a building element (balcony, roof, etc.) 4 close to a disruptive heat source (sun, chimney, ventilation grid,
etc.)
4.6.2. Connecting the outside sensor
Mount the sensor using the screws and dowels provided.
8800N001-C
8800N002-C
AWHP-2 MIT-IN-2 iSystem
4. Installation
25/06/2014 - 7616371-001-04
29
Page 32
A
Inserts
Z
Ø4 wood screw
¼For the connection of the outside temperature sensor, refer to the chapter "Electrical Connections".
4.7 Combination with a DHW tank
In order to optimise domestic hot water production, the recommended combinations of heat pumps and DHW tanks are:.
4 MR 6 MR-2 8 MR-2 11 MR-TR 2 16 MR-TR 2 22 TR 27 TR
BLC150 X X X X BLC200
X X X X
BLC300
X X X X
WARNING
An incorrect DHW tank/heat pump combination may adversely affect user comfort.
An incorrect combination may lead to overconsumption subsequent to the repeated tripping of the back-ups.
4.8 Installing the refrigerant piping
4.8.1. Installing the pipes
DANGER
Only a qualified professional may carry out the installation in conformity with in force legislation and standards.
4 Install the frigorific connection pipes between the inside and
outside modules.
4 Respect the minimum curve radii of 100 to 150 mm.
4 Only for 22 - 27 TR models:
If the length of the piping is less than 20 m, it is possible to use annealed pipe for the gas pipe with a diameter of 3/4 without using braze-on adapters. The output in cooling mode may be reduced to 20% depending on the length used.
4 Respect the minimum and maximum lengths. ¼See chapter:
"Positioning of the appliance", page 20. If the frigorific connection between the outside module and the inside module is less than 5 m, the following disruptions may occur:
8800N003-C
2
4. Installation
AWHP-2 MIT-IN-2 iSystem
30
25/06/2014 - 7616371-001-04
Page 33
- Functional disruptions caused by a fluid overload
- Noise pollution caused by the circulation of the refrigerant
In this case, fit a refrigerant connection of at least 5 m by making 1 or 2 horizontal loops, as necessary, in order to limit such annoyance and oil traps. If the refrigeration connection pipes are more than 10 metres long, refrigerant R410A must be added.
Add refrigerant via the refrigerant shut off valve using a safety loader. ¼See chapter: "Adding refrigerant", page 36.
4 Cut the pipes with a pipe cutter and deburr them, point the opening
in the pipe downwards to prevent the introduction of particles.
4 Prevent oil traps.
WARNING
If the pipes are not to be connected immediately, they should be plugged to prevent the infiltration of humidity.
Use a flat spanner to hold the hoses during the various operations.
1. Partially unscrew the 5/8" or 3/4" "gas" nut, depending on the model.
2. A release noise should be heard, which is proof that the exchanger is watertight.
MW-2000076-1
M002395-B
1
M002396-B
OK
Pfffff...
2
AWHP-2 MIT-IN-2 iSystem
4. Installation
25/06/2014 - 7616371-001-04
31
Page 34
3. Unscrew the screws.
CAUTION
Keep the frigorific connection in place on the MIT-IN-2 with a spanner so as not to twist the internal pipe.
4. Remove and discard the gates.
5.
Only for 4 - 6 MR-2 models
Fit the 1/4" to 3/8" and 1/2" to 5/8" adapter fittings (Package EH146). Use the copper gaskets. Use a torque wrench.
¼
See "torque" table (step 9).
Only for the 22 TR model
Fit a 3/8" to 1/2" adapter to the liquid connection. Use the copper gaskets. Use a torque wrench.
¼
See "torque" table (step 9).
CAUTION
Keep the frigorific connection in place on the MIT-IN-2 with a spanner so as not to twist the internal pipe.
6.
Models 8 to 16 MR/TR-2 and 27 TR
Slip the nuts onto the pipes.
Models 4 and 6 MR-2and 22 TR
Slip the nuts provided with the adapters onto the pipes.
7. Bead the pipes.
M002397-C
3
M002498-A
4
M002398-D
4MR - 6MR-2
5
M002399-D
22TR
5
M002207-B
6
7
4. Installation
AWHP-2 MIT-IN-2 iSystem
32
25/06/2014 - 7616371-001-04
Page 35
8.
Models 22 TR and 27 TR
If the length of the piping is less than 20 m, it is possible to use annealed pipe for the gas pipe with a diameter of 3/4 without using braze-on adapters. The output in cooling mode may be reduced to 20% depending on the length used. Using the 1" braze-on gas pipe: Braze the 1" gas pipe on to the braze-on adapter, circulating dehydrated nitrogen inside the pipe to prevent oxidation.
CAUTION
Do not overheat the pipe, protect the insulation and the inside module when brazing.
Use hard solder.
Using the 3/4" crown gas pipe: Slip the nut onto the pipe. Bead the pipes.
9.
A
Only for 4 - 6 MR-2 models
B
Only for 8 - 11 - 16 MR-2 models
C
Only for 22 TR models
D
Only for 27 TR models
Apply refrigerant oil to the beaded parts to facilitate tightening and improve watertightness.Apply refrigerant oil to the beaded parts to facilitate tightening and improve watertightness. Connect the pipes and tighten the nuts with a dynamometric spanner.
CAUTION
Keep the frigorific connection in place on the MIT-IN-2 with a spanner so as not to twist the internal pipe.
External diameter of the pipe (mm-inch)
External diameter of the cone connection (mm)
Torque load (Nm)
6.35 - 1/4 17 14 - 18
9.52 - 3/8 22 34 - 42
12.7 - 1/2 26 49 - 61
15.88 - 5/8 29 69 - 82
19.05 - 3/4
100 - 120
10.Remove the protective side panels from the outdoor module.
M002400-B
8
22TR - 27TR
M002401-G
9
9
A B
9
9
C D
10
10
M002402-A
AWHP-2 MIT-IN-2 iSystem
4. Installation
25/06/2014 - 7616371-001-04
33
Page 36
11.Unscrew the nuts on the shut off valves.
12.Slip the nuts onto the pipes.
13.Bead the pipes. Models 22 and 27 TR (Braze-on 1" fitting): Braze the connecting pipe to the local pipe without oxygen. Braze in a nitrogen atmosphere.
14.Apply refrigerant oil to the beaded parts to facilitate tightening and improve watertightness. Connect the pipes and tighten the nuts with a dynamometric spanner. A Do not use a spanner on this part of the valve, danger of the refrigerant leaking.
B Recommended position of the spanners for tightening the nut.
CAUTION
Tighten the nuts using a dynamometric spanner.
External diameter of the pipe (mm-inch)
External diameter of the cone connection (mm)
Torque load (Nm)
6.35 - 1/4 17 14 - 18
9.52 - 3/8 22 34 - 42
12.7 - 1/2 26 49 - 61
15.88 - 5/8 29 69 - 82
19.05 - 3/4
100 - 120
M002403-A
11
12
13
M002405-A
11
12
13
22TR - 27TR
M002404-A
14
A
B
B
M002406-A
14
A
B
B
22TR - 27TR
4. Installation AWHP-2 MIT-IN-2 iSystem
34
25/06/2014 - 7616371-001-04
Page 37
4.8.2. Water tightness test
1. Check that the shut off valves A and B are closed.
2. Connect the pressure gauge valve and the nitrogen cylinder to the operating connection C on the shut off valve A.
3. Progressively pressurise the refrigerant connection pipes and the indoor module in steps of 5 bar until you reach 35 bar.
4. Check the watertightness of the connections with a "leak detector" spray. If leaks occur, redo and recheck tightness.
5. Release the pressure and release the nitrogen.
4.8.3. Evacuation
1. Check that the shut off valves A and B are closed.
2. Connect the vacuum gauge and the vaccuum pump to the operating connection C and the shut off valve A.
3. Produce a vacuum in the indoor module and the refrigerant connection pipes.
4. Check the pressure according to the recommendations table below:
Outside temperature (°C)
ª
20
10 0 - 10 Pressure to be reached (Pa) 1000 600 250 200 Draw-off evacuation time after reaching the
pressure (h)
1 1 2 3
5. Close the valve between the vacuum gauge/vaccuum pump and the shut off valve A.
6. After shutting off the vaccuum pump, immediately open the valves.
4.8.4. Opening the valves
1. Remove the cap D on the refrigerant off valve A.
2. Open the valve with a hexagonal spanner by turning anti­clockwise until it stops.
3. Put the cap back in place.
4. Remove the cap D on the refrigerant gas shut off valve B.
5. Open the valve with a pair of pliers, turning it anticlockwise by a quarter turn.
6. Put the cap back in place.
7. Disconnect the vacuum gauge and the vaccuum pump. Put the cap back in place.
M002297-A
A
B
C
35 bar
M001470-B
M002297-A
A
B
C
M002499-B
M002295-B
A
B
D
D
AWHP-2 MIT-IN-2 iSystem
4. Installation
25/06/2014 - 7616371-001-04
35
Page 38
8. Tighten the caps with a dynamometric spanner with a torque load of 20 to 25 N·m.
9. Check the watertightness of the connections using a leak detector.
4.8.5. Adding refrigerant
If the refrigeration connection pipes are more than 10 metres long, refrigerant R410A must be added. See table below.
Add refrigerant via the refrigerant shut off valve using a safety loader.
Model (Outdoor unit)
Quantity of refrigerant to be added
11 to 20m21 to 30m31 to 40m41 to
50 m
51 to 60 m
61 to 75 m
4 - 6 kW 0.2 kg 0.4 kg 0.6 kg / / / 8 kW 0.2 kg 0.4 kg 1.0 kg / / / 11-16 kW 0.2 kg 0.4 kg 1.0 kg 1.6 kg 2.2 kg 2.8 kg 22 kW 0.9 kg 1.8 kg 1.8 kg 1.8 kg 2.7 kg 3.6 kg 27 kw 1.2 kg 2.4 kg 2.4 kg 2.4 kg 3.6 kg 4.8 kg
4.9 Hydraulic connections
¼See chapter: "Main dimensions", page 27
4.9.1. Flushing the system
Installation must be carried out in accordance with the prevailing regulations, the codes of practice and the recommendations in these instructions.
Installation must be carried out in accordance with the prevailing regulations, the codes of practice and the recommendations in these instructions.
n
Fitting the appliance to new installations
4 Clean the installation with a universal cleaner to eliminate debris
from the system (copper, hemp, flux).
4 Thoroughly flush the installation until the water runs clear and
shows no impurities.
n
Fitting the appliance to existing installations
4 Remove sludge from the installation. 4 Flush the installation. 4 Clean the installation with a universal cleaner to eliminate debris
from the system (copper, hemp, flux).
4 Thoroughly flush the installation until the water runs clear and
shows no impurities.
4. Installation
AWHP-2 MIT-IN-2 iSystem
36
25/06/2014 - 7616371-001-04
Page 39
4 Prior to connection, rinse the domestic water inlet pipes so as
not to introduce metal or other particles into the DHW coil.
4.9.2. Connection of the heating circuit
1. Connect the heating water return pipe to the heating return connection.
z
: Screw-on connection ∅ 1"
2. Connect the heating water outlet pipe to the heating flow connection.
{
: Screw-on connection ∅ 1"
4 The device is factory-fitted with a safety valve.
CAUTION
4 The heating pipe must be mounted in accordance
with prevailing provisions.
4.9.3. Hydraulic connection diagrams
CAUTION
The maximum volume scheduled for the installation is 215 litres. If this volume is exceeded in relation to the internal expansion vessel, add an external expansion vessel.
M002537-A
1 2
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
37
Page 40
n
Example of connecting a system with MIT-IN-2/H
A
Outdoor unit
Z
Inside module with hydraulic back-up
E
boiler back-up
R
DHW tank
3
3-bar safety valve
4
Pressure gauge
7
Automatic air vent
9
Isolating valve
11a
Automatically regulated electronic pump for direct heating circuit
11b
Pump for heating circuit with mixing valve
16
Closed expansion vessel
17
Drain cock
18
Filling the heating circuit
21
Exterior temperature sensor
22
Boiler temperature sensor
23
Mixing valve outlet temperature sensor
24
DHW calorifier exchanger primary inlet
25
DHW calorifier heat exchanger primary outlet
26
DHW load pump
27
Non-return valve
M003026-C
230V
50Hz
BUS
21
51
230V
50Hz
EA63
9
11b
10
27
9
°C
°C
EA61
65
115
23
52
52
64
64
51
51
EA59
44
9
°C
27
°C
9
11a
2
3
4
1
4. Installation AWHP-2 MIT-IN-2 iSystem
38
25/06/2014 - 7616371-001-04
Page 41
28
Domestic cold water inlet
29
Pressure reducer if supply pressure exceeds 80 % of the safety valve pressure setting
30
Calibrated and sealed safety unit
33
Domestic hot water temperature sensor
34
Primary pump
44
Safety thermostat
50
Disconnector
51
Thermostat valve
52
Differential valve
56
Domestic hot water circulation loop return
57
Domestic hot water outlet
64
Direct heating circuit
65
Heating circuit with mixing valve
89
Heat transfer fluid container
115
Thermostatic distribution valve for each zone
n
Example of connecting a system with MIT-IN-2/E
A
Outdoor unit
Z
Inside module with electrical back-up
E
DHW tank
3
3-bar safety valve
M003027-B
230V
50Hz
230V
50Hz
BUS
21
65
115
23
64
51
44
2
3
1
A
B
A/B
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
39
Page 42
4
Pressure gauge
7
Automatic air vent
9
Isolating valve
11a
Automatically regulated electronic pump for direct heating circuit
11b
Pump for heating circuit with mixing valve
16
Closed expansion vessel
17
Drain cock
18
Filling the heating circuit
21
Exterior temperature sensor
22
Boiler temperature sensor
23
Mixing valve outlet temperature sensor
24
DHW calorifier exchanger primary inlet
25
DHW calorifier heat exchanger primary outlet
26
DHW load pump
27
Non-return valve
28
Domestic cold water inlet
29
Pressure reducer if supply pressure exceeds 80 % of the safety valve pressure setting
30
Calibrated and sealed safety unit
33
Domestic hot water temperature sensor
34
Primary pump
44
Safety thermostat
50
Disconnector
51
Thermostat valve
52
Differential valve
56
Domestic hot water circulation loop return
57
Domestic hot water outlet
64
Direct heating circuit
65
Heating circuit with mixing valve
89
Heat transfer fluid container
115
Thermostatic distribution valve for each zone
4.10 Filling the heating system
4.10.1. Water treatment in the heating circuit
In a number of cases, the heat pump and the central heating system can be filled with normal tap water and no water treatment is necessary.
4. Installation
AWHP-2 MIT-IN-2 iSystem
40
25/06/2014 - 7616371-001-04
Page 43
WARNING
4 Do not add chemical products to the central heating
water without first consulting a water treatment professional. For example: antifreeze, water softeners, products to increase or reduce the pH value, chemical additives and/or inhibitors. Chemical products may cause malfunctions on the heat pump and damage the heat exchanger.
4 Do not use hydrochloric acid-based cleaning or
descaling products.
CAUTION
4 Check the compatibility of the product with the
materials used in the installation.
4 Check the compatibility of the product with stainless
steel and copper.
4 Respect the manufacturer’s instructions (use, dose,
etc.) to obviate any hazards (corporal, material, environmental).
4 An uncleaned installation or an installation using
water of unsuitable quality may bring about the cancellation of the warranty.
4 Flush the central heating installation with at least 3x
the volume of the central heating installation.
4 Flush the DHW pipes with at least 20 times the volume
of the pipes.
For an optimum functioning of the boiler, the water of the installation must comply with following characteristics:
Output ≤ 70 kW
Acidity (pH)
7.5 - 9 Conductivity at 25°C µS/cm 10 to 500 Chlorides mg/l < 50 Other components mg/l < 1 Hardness of the water of the installation °f 7- 15
°dH 4- 8.5
If a water treatment is necessary, De Dietrich Thermique recommends the following manufacturers:
4 Cillit 4 Climalife 4 Fernox 4 Permo 4 Sentinel
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
41
Page 44
4.10.2. Filling the system
CAUTION
Do not use glycol. The heat pump components are not designed to be used with glycol. The use of glycol in the heating circuit invalidates the warranty.
4 Fill the installation until a pressure of 1.5 to 2 bars is reached.
Water pressure display: See chapter: ¼ "Reading out measured values", page 94.
4 Check for any water leaks. 4 Completely vent any air in the inside module and the installation
for optimum running.
4.11 Electrical connections
4.11.1. Recommendations
WARNING
4 Only qualified professionals may carry out electrical
connections, always with the power off.
4 Earth the appliance before making any electrical
connections.
Make the electrical connections of the appliance according to:
4 The instructions of the prevailing standards, 4 The instructions on the circuit diagrams provided with the
appliance,
4 The manufacturer’s instructions.
The earthing shall comply with local standards.
CAUTION
4 Separate the sensor cables from the 230/400 V
circuit cables.
4 The installation must be fitted with a circuit breaker
disconnecting switch.
4 Three phase models must always be fitted with
neutral.
Power the appliance via a circuit which includes a remote omnipolar switch with a gap of more than 3 mm.
4 Single phase models: 230 V AC (+6%/-10%) 50 Hz 4 Three phase models: 400 V AC (+6%/-10%) 50 Hz
4. Installation
AWHP-2 MIT-IN-2 iSystem
42
25/06/2014 - 7616371-001-04
Page 45
When making electrical connections to the mains, respect the following polarities:
4 Brown wire: Live 4 Blue wire: Neutral 4 Green/yellow wire: Earth
WARNING
Secure the cable with the cable clamp provided. Be careful that you do not invert the wires.
4.11.2. Recommended cable cross section
The electrical characteristics of the mains power supply available must correspond to the values given on the rating plate.
The cable will be carefully chosen according to the following information:
4 Maximum intensity of the outdoor module. See table below. 4 Distance of the appliance from the original power supply. 4 Upstream protection. 4 Neutral operating conditions.
Appliance
AWHP MIT-IN-2 4 MR 6 MR-2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Outdoor unit Absorbed
electrical power
kW 1.50 1.50 2.10 2.59 2.59 4.03 4.03 5.6 6.9
Nominal amperage
A 6.8 6.8 9.34 11.2 3.98 17.7 5.99 13.9 17.2
Maximal amperage
A 13 13 19 28 13 29 13 19 21
Type
(1)
1 ~ 1 ~ 1 ~ 1 ~ 3 ~ 1 ~ 3 ~ 3 ~ 3 ~
Power supply
S-C
(2)
3 x 2.5 3 x 2.5 3 x 4 3 x 6 5 x 2.5 3 x 10 5 x 2.5 5 x 4 5 x 6
Curve D DJ
(3)
16 A 16 A 25 A 32 A 16 A 40 A 16 A 25 A 32 A
Indoor module Power supply
S-C
(2)
3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5
Curve C DJ
(3)
10 A 10 A 10 A 10 A 10 A 10 A 10 A 10 A 10 A
Cable BUS
(4)
S-C
(2)
3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5
(1) 1 ~ : Single phase, 3 ~ : Three-phase (2) Cable cross section (mm²) (3) Circuit breaker (4) Connection cable between outdoor and indoor module
n
Connecting the electrical back-up
Type
S-C
(1)
Curve C DJ
(2)
Single phase 3 x 6 32 A Three-phase 5 x 4 25 A
(1) Cable cross section (mm²) (2) Circuit breaker
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
43
Page 46
4.11.3. Accessing the connection terminal blocks
n
Outdoor unit
Only for 4, 6 kW models
1. Unscrew the holding screws.
2. Remove the protection cap.
Only for 8, 11, 16, 22, 27 kw models
1. Unscrew the holding screws.
2. Remove the protection cap.
CAUTION
Secure the cables with cable clamps to obviate any contact with the centre of the protective cover or the gas valve.
n
Indoor module
To access the connection terminal blocks, proceed as follows:
1. Unscrew the 2 screws under the front panel by a quarter turn.
MW-2000052-1
MW-2000055-1
M002382-B
1
2
4. Installation AWHP-2 MIT-IN-2 iSystem
44
25/06/2014 - 7616371-001-04
Page 47
2. Remove the front panel.
3. Open the holding clips located on the sides.
4. Tilt the control panel forwards.
5. Lift the clip located in front of the control panel.
6. Lift the control panel cover.
7. Unclip the PCB cover.
M002383-B
3
3
4
M002491-A
5
5
6
M002492-A
7
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
45
Page 48
4.11.4. Position of the PCBs
On/off
OT BL S ECS
BUS
A B 0VS EXT
2
4
3
1
TS + B AB
0-10V
S AMB C
4 3 2 1 2 1
+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA -
S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
TS + C AUXC
SCU
PCU
M002490-B
PCU
SCU
A
Do not connect anything to the terminal block.
Z
Optional PCB (Package AD249)
E
The BL inlet must always be connected to a dry contact (potential-free).
R
Do not connect anything to the terminal block.
4. Installation AWHP-2 MIT-IN-2 iSystem
46
25/06/2014 - 7616371-001-04
Page 49
4.11.5. Location of the fuse
A
F1 6,3 AT fuse 250 V AC
Z
Spare fuse
4.11.6. Connecting the outdoor module
M001478-B
N
L
L N S1 S2 S3
L1 L2 L3 N
L2L1 L3 N S1 S2 S3
1 2
A
Single phase power supply
Z
Three-phase power supply
4.11.7. Connecting the communication cable between the inside and outside modules
Communication cable liaison: 3 x 1.5 mm
2
Cable to be supplied by the installer.
M002494-B
PCU
1
2
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
47
Page 50
WARNING
Be careful that you do not invert the wires.
1 Connect to terminals S2, S3 and *. 2 Connect to terminals S2, S3 and *. (Outdoor unit)
4.11.8. Description of the terminal block on the inside module
n
Inside module with hydraulic back-up
A
Bus for communication with the outside module
M002407-B
L N S1 S2 S3
S2 S3
S2S3
1
2
S2 S3
M002410-B
1
S2 S3
4. Installation AWHP-2 MIT-IN-2 iSystem
48
25/06/2014 - 7616371-001-04
Page 51
n
Inside module with electrical back-up
A
Ouput configuration of electric back-ups
Z
Auxiliary electrical power supply
E
Bus for communication with the outside module
4.11.9. Connecting the mains supply to the inside module
A
L (Live: Brown)
Z
N (Neutral: Blue)
E * (Earth: Green/yellow wire)
X1
Power connector
CAUTION
The earth conductor must be longer than the live and neutral conductors.
CAUTION
Use the cable clamps provided in the instructions bag.
4.11.10. Connecting the electrical back-up to the inside module
M002408-D
S2 S3
BUS<>HPBUS<>HP
L1 L2 L3 N L N
1 2
C3
Configuration
C2 C1 L1
Alim appoint électriqueAlim appoint électrique
L2 L3 CN
S2 S3
BUS<>HPBUS<>HP
C3
Configuration
C2 C1 L1
Alim appoint électriqueAlim appoint électrique
L2 L3 CN
A
Three-phase power supply: 400 V AC
M002409-B
C3
Configuration
C2 C1 L1
Alim appoint électriqueAlim appoint électrique
L2 L3 CN
1 2 3
S2 S3
M002489-C
1
2 3
PCU
X1
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
49
Page 52
Z
Single phase power supply: 230 V AC
CAUTION
The earth conductor must be longer than the live and neutral conductors.
n
Fitting the jumpers and bridges
M002393-E
S2 S3
BUS<>HPBUS<>HP
1 2
C3
Configuration
C2 C1 L1
Alim appoint électriqueAlim appoint électrique
L2 L3 CN
S2 S3
BUS<>HPBUS<>HP
C3
Configuration
C2 C1 L1
Alim appoint électriqueAlim appoint électrique
L2 L3 CN
* *
A
Three-phase
Z
Single phase
*
For the various options for setting the bridge, see the paragraph below, "Setting the output".
CAUTION
Check that the clips are correctly connected to the tab as poor contact may lead to the connection overheating.
n
Output control
¼For setting the BACKUP TYPE parameter, see: "Professional settings", page 98
Type
BACKUP TYPE setting
Back-up Output Bridge
Single phase
/E2
Stage 1 2 kW between C2 and
C1
Stage 2 4 kW Stage 1 + 2 6 kW
/E1
Stage 1 2 kW
4. Installation AWHP-2 MIT-IN-2 iSystem
50
25/06/2014 - 7616371-001-04
Page 53
Type BACKUP TYPE
setting
Back-up Output Bridge
Three-phase
/E2
Stage 1 4 kW between C3 and
C2
Stage 2 8 kW Stage 1 + 2 12 kW Stage 1 8 kW between C2 and
C1
Stage 2 4 kW Stage 1 + 2 12 kW Stage 1 4 kW Remove bridge Stage 2 4 kW Stage 1 + 2 8 kW
/E1
Stage 1 8 kW between C2 and
C1
4 kW Remove bridge
4.11.11. Connecting the hydraulic auxilary on the inside module
WARNING
Respect the polarity of the terminals: Live (P), neutral (N), and earth (*).
A
Back-up pump
Z
Burner (Volt free contact)
M002423-B
LN 21
1
2
PCU
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
51
Page 54
4.11.12. Connection example for a system with hydraulic back-up
n
Boiler fitted with a control panel with a TAM and/or I.TEL input
M003032-C
BUS
EA63
°C
°C
EA61
EA59
°C
°C
13
14
On/off
OT BL S ECS
BUS
A B 0V
S EXT
TS + B AB
0-10V
S AMB C
4 3 2 1 2 1
+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA -
S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
SCU
PCU
1 2
3
8
9
E.TEL
TAM /
K
5 6
7
4
10
12
N L
NL
11
A
Not used: Do not connect anything to the terminal block.
Z
CAUTION
Do not connect anything to the DHW pump outlet.
E
Connect the outside temperature sensor.
R
Connect the heating pump (Circuit A).
T
Connect the 3-way valve motor (Circuit B).
Y
Connect the heating pump (Circuit B).
4. Installation AWHP-2 MIT-IN-2 iSystem
52
25/06/2014 - 7616371-001-04
Page 55
U
Connect a safety thermostat if the heating circuit is for underfloor heating: Remove the bridge. Connect the wires from the safety thermostat to the connector.
I
Not used: Do not connect anything to the terminal block.
O
Connect the BUS cable between the outside module and the terminal block on the inside module.
P
Connect the outlet sensor (Circuit B).
a
Connect the heating pump and the K relays to the AL1 connector on the PCU PCB.
z
Connect the boiler’s room thermostat to the AL2 connector on the PCU PCB.
e
Inside module with hydraulic back-up
r
Outdoor unit
Settings to be made on the inside module for this type of installation
Parameters Access Settings to be made See chapter
INSTALLATION
Installer level
#SYSTEM menu
EXTENDED
¼ "Displaying the parameters in extended mode", page 84
O.PUMP A
(1)
Installer level
#SYSTEM menu
CH.PUMP A
¼ "Setting the parameters specific to the installation", page 86
CIRC.A
(1)
Installer level
#SYSTEM menu
DIRECT
¼ "Setting the parameters specific to the installation", page 86
PUMP MIT/MHR
Installer level
#SYSTEM menu
CIRC.A
¼ "Setting the parameters specific to the installation", page 86
CIRC.B
(1)
Installer level
#SYSTEM menu
3WV
¼ "Setting the parameters specific to the installation", page 86
CIRC.CURVE A
Installer level #SECONDARY INSTAL.P menu
1.5
¼ "Professional settings", page 98
CIRC.CURVE B
Installer level #SECONDARY INSTAL.P menu
0.7
¼ "Professional settings", page 98
HP BUS
Installer level
#PRIMARY INSTAL.P menu
TOR
¼ "Professional settings", page 98
BACKUP TYPE
Installer level
#PRIMARY INSTAL.P menu
/H
¼ "Professional settings", page 98
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
Setting the back-up boiler
The setting of the back-up boiler depends on its type of control panel.
4 Diematic 3
Set the following installer settings on the boiler control panel:
- I.TEL: THERM A
- HCZP D / HCZP N: same value as the parameter HEAP
MAX: on the Diematic iSystem control panel on the MIT.
- CIRC.CURVE A: 0.0
- OUT.ANTIFREEZE: -8 °C
Access to parameters:
- Press the - key for 5 seconds.
- Press the ( key 2 times.
- Use key to select the desired parameter.
AWHP-2 MIT-IN-2 iSystem
4. Installation
25/06/2014 - 7616371-001-04
53
Page 56
4 SVmatic
Heating temperature setting = HEAP MAX:.
4 B control panel
Set the boiler thermostat to the same value as HEAP MAX:.
4 Other
Heating temperature setting = HEAP MAX:.
Operating principle
4 No back-up requested:
The boiler continues to provide DHW. Contacts AL1 and AL2 are both open.
4 Back-up requested:
The AL2 contact closes. The AL1 outlet is powered up: If the boiler is in domestic hot water mode, the back-up pump is not tripped as the K relay is open. The back-up pump is tripped when the domestic hot water load pump stops.
4. Installation AWHP-2 MIT-IN-2 iSystem
54
25/06/2014 - 7616371-001-04
Page 57
n
Boiler fitted with a control panel without TAM input (Modulating room thermostat)
M003033-B
BUS
EA63
°C
°C
EA61
EA59
°C
°C
13
14
On/off
OT BL S ECS
BUS
A B 0V
S EXT
TS + B AB
0-10V
S AMB C
4 3 2 1 2 1
+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA -
S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
SCU
PCU
1 2
3
8
9
5 6
7
4
10
N L
NL
11
CS
12
A
Not used: Do not connect anything to the terminal block.
Z
CAUTION
Do not connect anything to the DHW pump outlet.
E
Connect the outside temperature sensor.
R
Connect the heating pump (Circuit A).
T
Connect the 3-way valve motor (Circuit B).
Y
Connect the heating pump (Circuit B).
U
Connect a safety thermostat if the heating circuit is for underfloor heating: Remove the bridge. Connect the wires from the safety thermostat to the connector.
I
Not used: Do not connect anything to the terminal block.
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
55
Page 58
O
Connect the BUS cable between the outside module and the terminal block on the inside module.
P
Connect the outlet AD 199 sensor (Circuit B).
a
Connect the heating pump and the K relays to the AL1 connector on the PCU PCB.
z
Connect the boiler’s inlet CS to the AL2 connector on the PCU PCB.
e
Inside module with electrical back-up
r
Outdoor unit
Settings to be made on the inside module for this type of installation
Parameters Access Settings to be made See chapter
INSTALLATION
Installer level
#SYSTEM menu
EXTENDED
¼ "Displaying the parameters in extended mode", page 84
O.PUMP A
(1)
Installer level
#SYSTEM menu
CH.PUMP A
¼ "Setting the parameters specific to the installation", page 86
CIRC.A
(1)
Installer level
#SYSTEM menu
DIRECT
¼ "Setting the parameters specific to the installation", page 86
PUMP MIT/MHR
Installer level
#SYSTEM menu
CIRC.A
¼ "Setting the parameters specific to the installation", page 86
CIRC.B
(1)
Installer level
#SYSTEM menu
3WV
¼ "Setting the parameters specific to the installation", page 86
CIRC.CURVE A
Installer level #SECONDARY INSTAL.P menu
1.5
¼ "Professional settings", page 98
CIRC.CURVE B
Installer level #SECONDARY INSTAL.P menu
0.7
¼ "Professional settings", page 98
HP BUS
Installer level
#PRIMARY INSTAL.P menu
TOR
¼ "Professional settings", page 98
BACKUP TYPE
Installer level
#PRIMARY INSTAL.P menu
/H
¼ "Professional settings", page 98
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
Setting the back-up boiler
4 Switch the boiler control system to 24h/24 comfort mode. 4 Heating temperature setting = HEAP MAX:.
Operating principle
4 In DHW production:
The relay K closes the contact CS to enable the burner to start up.
4 In auxiliary heater mode:
The MIT-2 module controls input CS on the boiler and the back­up pump. When back-up is requested, the boiler continues to handle DHW priority. After the back-up is shut down, the back-up pump continues to run during the timed period BACKUP PUMP DEL. which can be adjusted in the #HEAT PUMP menu.
4. Installation
AWHP-2 MIT-IN-2 iSystem
56
25/06/2014 - 7616371-001-04
Page 59
4.11.13. Connection example for a system with electrical back-up
M003034-B
BUS
13
14
On/off
OT BL S ECS
BUS
A B 0V
S EXT
TS + B AB
0-10V
S AMB C
4 3 2 1 2 1
+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA -
S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
SCU
PCU
1 2
3
9
12
5 6
8
7
4
3 4
10
11
A
B
A/B
A
Not used: Do not connect anything to the terminal block.
Z
CAUTION
Do not connect anything to the DHW pump outlet as the reversal valve is connected to the PCU PCB in the boiler.
E
Connect the outside temperature sensor.
R
Connect the 3-way valve motor (circuit B) and the circuit B flow sensor.
T
Connect the heating pump (Circuit B).
Y
Connect a safety thermostat if the heating circuit is for underfloor heating: Remove the bridge. Connect the wires from the safety thermostat to the connector.
U
Connect the DHW sensor.
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
57
Page 60
I
Connect the DHW tank anode.
CAUTION
4 If the tank is fitted with a Titan Active
System® impressed current anode, connect the anode to the inlet (+ TA on the anode, - on the tank).
4 If the tank is not fitted with an impressed
current anode, put the simulation connector in place (delivered with the DHW sensor - package AD212).
O
Not used: Do not connect anything to the terminal block.
P
Connect the motor on the DHW reversal valve.
a
Connect the domestic hot water looping pump to the M outlet.
z
Connect the BUS cable between the outside module and the terminal block on the inside module.
¼ "Connecting the communication cable between the inside and outside modules", page 47.
e
Inside module with electrical back-up
r
Outdoor unit
Settings to be made for this type of installation
Parameters Access Settings to be made See chapter
INSTALLATION
Installer level
#SYSTEM menu
EXTENDED
¼ "Displaying the parameters in extended mode", page 84
O.PUMP A
(1)
Installer level
#SYSTEM menu
DHW LOOP
¼ "Setting the parameters specific to the installation", page 86
CIRC.A
(1)
Installer level
#SYSTEM menu
DIRECT
¼ "Setting the parameters specific to the installation", page 86
PUMP MIT/MHR
Installer level
#SYSTEM menu
CIRC.A
¼ "Setting the parameters specific to the installation", page 86
CIRC.B
(1)
Installer level
#SYSTEM menu
3WV
¼ "Setting the parameters specific to the installation", page 86
CIRC.CURVE A
Installer level #SECONDARY INSTAL.P menu
1.5
¼ "Professional settings", page 98
CIRC.CURVE B
Installer level #SECONDARY INSTAL.P menu
0.7
¼ "Professional settings", page 98
HP BUS
Installer level
#PRIMARY INSTAL.P menu
TOR
¼ "Professional settings", page 98
BACKUP TYPE
Installer level
#PRIMARY INSTAL.P menu
/E1 (Stage 1) /E2 (Stage 2)
¼ "Professional settings", page 98
DHW TYPE
Installer level
#PRIMARY INSTAL.P menu
SECONDARY
¼ "Professional settings", page 98
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
4. Installation AWHP-2 MIT-IN-2 iSystem
58
25/06/2014 - 7616371-001-04
Page 61
4.11.14. Connection example in cooling mode
M003035-B
BUS
15
16
On/off
OT BL S ECS
BUS
A B 0V
S EXT
TS + B AB
0-10V
S AMB C
4 3 2 1 2 1
+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA -
S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
SCU
PCU
1 2
3
9
12
5 6
8
7
4
3 4
10 13 14
11
A
B
A/B
K
230V 50Hz
230V / 400V
50Hz
A
Not used: Do not connect anything to the terminal block.
Z
CAUTION
Do not connect anything to the DHW pump outlet as the reversal valve is connected to the PCU PCB in the boiler.
E
Connect the outside temperature sensor.
R
Connect the 3-way valve motor (circuit B) and the circuit B flow sensor.
T
Connect the heating pump (Circuit B).
Y
Connect a safety thermostat if the heating circuit is for underfloor heating: Remove the bridge. Connect the wires from the safety thermostat to the connector.
U
Connect the DHW sensor.
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
59
Page 62
I
Connect the DHW tank anode.
CAUTION
4 If the tank is fitted with a Titan Active
System® impressed current anode, connect the anode to the inlet (+ TA on the anode, - on the tank).
4 If the tank is not fitted with an impressed
current anode, put the simulation connector in place (delivered with the DHW sensor - package AD212).
O
Not used: Do not connect anything to the terminal block.
P
Connect the motor on the DHW reversal valve.
a
Connect the domestic hot water looping pump to the MA outlet.
z
Connect the BUS cable between the outside module and the terminal block on the inside module.
¼ "Connecting the communication cable between the inside and outside modules", page 47.
e
Connect the relay command on the tank heating resistor to the ELEC ECS terminal block.
r
Connect the condensation detector (Option).
The condensation detector shuts down cooling if there is a risk of condensation.
CAUTION
We strongly advise installing the cold mode insulation kit to prevent any risk of condensation in the inside module.
t
Inside module with electrical back-up
y
Outdoor unit
Settings to be made for this type of installation
Parameters Access Settings to be made See chapter
INSTALLATION
Installer level
#SYSTEM menu
EXTENDED
¼ "Displaying the parameters in extended mode", page 84
O.PUMP A
(1)
Installer level
#SYSTEM menu
DHW LOOP
¼ "Setting the parameters specific to the installation", page 86
CIRC.A
(1)
Installer level
#SYSTEM menu
FAN CONVECTOR
¼ "Setting the parameters specific to the installation", page 86
PUMP MIT/MHR
Installer level
#SYSTEM menu
CIRC.A
¼ "Setting the parameters specific to the installation", page 86
CIRC.B
(1)
Installer level
#SYSTEM menu
3WV
¼ "Setting the parameters specific to the installation", page 86
COOLING
Installer level
#PRIMARY INSTAL.P menu
YES+DHW
¼ "Professional settings", page 98
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
4. Installation AWHP-2 MIT-IN-2 iSystem
60
25/06/2014 - 7616371-001-04
Page 63
Settings to be made for this type of installation
Parameters Access Settings to be made See chapter
DHW BACKUP
Installer level
#PRIMARY INSTAL.P menu
MIT/D.COOL
¼ "Professional settings", page 98
DHW TYPE
Installer level
#PRIMARY INSTAL.P menu
SECONDARY
¼ "Professional settings", page 98
MINI COOLING A
Installer level #SECONDARY INSTAL.P menu
7 °C
¼ "Professional settings", page 98
MINI COOLING B
Installer level #SECONDARY INSTAL.P menu
10 °C
¼ "Professional settings", page 98
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
4.11.15. Pool connection
M002712-B
On/off
OT BL S ECS
BUS
A B 0V
S EXT
PCU
6
1
3
5
2
TS + B AB
0-10V
S AMB C
4 3 2 1 2 1
+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA -
S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
SCU
4
A
Connect the secondary swimming pool pump.
Z
Connect the swimming pool sensor.
E
Plate heat exchanger.
R
Pool heating cut-off control
When the parameter I.TEL is on 0/1 B, the swimming pool is no longer heated when the contact is open (factory setting), only the antifreeze continues to be active. The contact direction can still be adjusted by the parameter CT.TEL.
T
Connect the primary swimming pool pump.
Y
Do not connect anything to the terminal block.
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
61
Page 64
Settings to be made for this type of installation
Parameters Access Settings to be made See
INSTALLATION
Installer level Menu #SYSTEM
EXTENDED
¼ "Displaying the parameters in extended mode", page 84
CIRC.B
Installer level Menu #SYSTEM
SWIM.P.
¼ "Setting the parameters specific to the installation", page 86
If I.TEL is used
I.TEL
Installer level Menu #SYSTEM
0/1 B
MAX. CIRC. B
Installer level Menu #SECONDARY
LIMITS
Set the value of MAX.CIRC.B to the temperature corresponding to the needs of the exchanger
¼ "Professional settings", page 98
n
Controlling the pool circuit
The control system can be used to manage a swimming pool circuit in both cases:
Case 1: The control system regulates the primary circuit (boiler/ exchanger) and the secondary circuit (exchanger/pool).
4 Connect the primary circuit pump (boiler/exchanger) to the MB
outlet on the connection terminal block. The temperature MAX.
CIRC. B is then guaranteed during comfort periods on programme B in summer and winter alike.
4 Connect the swimming pool sensor (package AD212) to the S
DEP B inlet on the connection terminal block.
4 Set the set point of the pool sensor using key C in the range 5 -
39°C.
Case 2: The pool has already a regulation system that is to be kept. The control system only regulates the primary circuit (boiler/exchanger).
4 Connect the primary circuit pump (boiler/exchanger) to the MB
outlet on the connection terminal block. The temperature MAX. CIRC. B is then guaranteed during comfort periods on programme B in summer and winter alike.
The swimming pool must also be connected to circuit C by adding the additional 3-way valve option. With optional package AD249:
4 Make the connection to the terminal blocks marked
C.
4 Set the parameters for circuit C.
n
Hourly programming of the secondary circuit pump
The secondary pump operates during programme B comfort periods in summer and winter alike.
n
Stopping
To prepare your pool for winter, consult your pool specialist.
4. Installation
AWHP-2 MIT-IN-2 iSystem
62
25/06/2014 - 7616371-001-04
Page 65
4.11.16. Connecting the options
M002713-B
V
PRG
TELCOM 2
ALP
AL2
AL1
3
2
1
SET
#09
V
8
7
65
4321
On/off
OT BL S ECS
BUS
A B 0V
S EXT
PCU
9
7
1
5
TS + B AB
0-10V
S AMB C
4 3 2 1 2 1
+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA -
S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
TS + C AUXC
SCU
3
4
2
8
6
MODE
r
x
0 2 4 6 8 10 12 14 16 18 22 2420
c
MODE
r
x
0 2 4 6 8 10 12 14 16 18 22 2420
c
A
Do not connect anything to the terminal block.
Z
Connect the load pump of the second tank.
E
Second domestic hot water tank
R
Connect the DHW sensor of the second tank.
T
Alarm indicator
Y
Connect the TELCOM remote vocal monitoring module (depending on its availability in your country).
U
Connecting the BUS cascade, VM
I
Connect the remote control (Package AD254/FM52).
O
Do not connect anything to the terminal block.
Settings to be made for this type of installation
Parameters Access Settings to be made See chapter
INSTALLATION
Installer level
#SYSTEM menu
EXTENDED
¼ "Displaying the parameters in extended mode", page 84
O.PUMP A
(1)
Installer level
#SYSTEM menu
FAILURE
¼ "Setting the parameters specific to the installation", page 86
If second tank connected:
S.AUX
(1)
Installer level
#SYSTEM menu
DHW
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
63
Page 66
4.11.17. Connecting the "energy metering" option
n
Operating principle
The "energy metering" option provides data on electrical energy consumption and thermal energy production by the outside module, the inside module and the back-ups, according to the chosen configuration (heating, DHW, etc.). The restored values are memorised for two years and can be viewed on the control panel display.
n
Specifications of the energy meters
Electrical energy meter:
4 Opto-insulated pulse output. 4 Minimum admissible voltage: 27 V 4 Minimum admissible intensity: 20 mA 4 Minimum pulse time: 25 ms 4 Maximum frequency: 20 Hz 4 Pulse weight: Between 1 and 1000 Wh.
Thermal energy meter (Optional):
4 Opto-insulated pulse output. 4 Minimum admissible voltage: 27 V 4 Minimum admissible intensity: 3 mA 4 Minimum pulse time: 5 ms 4 Maximum frequency: 100 Hz 4 Pulse weight: Between 10 and 1000 Wh.
If the thermal energy meter is connected, the pulses are added at the thermal energy value calculated by the sensors and the flowmeter.
4. Installation AWHP-2 MIT-IN-2 iSystem
64
25/06/2014 - 7616371-001-04
Page 67
n
Adjustment
M003006-B
1 2
3
4
230Vac 50Hz 230Vac/400Vac 50Hz
Ele2
THERM
Ele1
A
Electricity meter (to meter the electrical energy consumed by the outside module).
Z
Electricity meter (to meter the electrical energy consumed by the inside module (without electric back-ups)).
E
Output sensor - PT100.
R
Return sensor - PT100.
The second electricity meter is not compulsory but can be used to tally the energy absorbed by the inside module (PCBs, circulating pumps, 3-way valves, etc.). The thermal energy is calculated thanks to the two sensors connected to the PCB and the flowmeter in the inside module.
¼Refer to the instructions delivered with the option (HK29).
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
65
Page 68
CAUTION
Do not install meters for the electric back-ups. The power input when setting the parameters is used to automaticaly calculate the consumed and restored energy.
Settings to be made for this type of installation
Parameters Access Settings to be made See chapter
INSTALLATION
Installer level
#SYSTEM menu
EXTENDED
¼ "Displaying the parameters in extended mode", page 84
FLOWM.LOC.
(1)
Installer level Menu #ENERGY
COUNTERS
PCU 194
¼ "Professional settings", page 98
GLYCOL
(1)
Installer level Menu #ENERGY
COUNTERS
0%
ELEC.PUL.VAL.1
(1)
Installer level Menu #ENERGY
COUNTERS
According to the specifications of the electricity meter
ELEC.PUL.VAL.2
(1)
Installer level Menu #ENERGY
COUNTERS
According to the specifications of the electricity meter
BACKUP 1
(1)
Installer level Menu #ENERGY
COUNTERS
According to the stage 1 output configuraton on the electrical back-ups
¼ "Connecting the electrical back-up to the inside module", page 49
BACKUP 2
(1)
Installer level Menu #ENERGY
COUNTERS
According to the stage 2 output configuraton on the electrical back-ups
¼ "Connecting the electrical back-up to the inside module", page 49
DHW RESISTOR
(1)
Installer level Menu #ENERGY
COUNTERS
According to the electrical resistor output of the DHW tank
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
Examples of settings: Metering the energy of the heat pump only: Set parameters BACKUP 1 and BACKUP 2 to 0. Set parameter DHW RESISTOR to 0. Metering the energy of the heat pump and the back-ups: Set parameters BACKUP 1 and BACKUP 2 according to the output
configuration of the stages of the electrical back-ups (¼ "Connecting the electrical back-up to the inside module", page 49). Set parameter DHW RESISTOR according to the electrical output of the DHW tank.
4. Installation
AWHP-2 MIT-IN-2 iSystem
66
25/06/2014 - 7616371-001-04
Page 69
4.11.18. Connection in cascade
BUS
230V ou 400V 50Hz
EH 114
BUS
BUS
230V ou 400V 50Hz
EH 114
M003036-B
1
8
8
2
3
4
5
6
7
°C °C °C °C
4
°C °C °C °C
A
Master inside module
Z
Slave inside module
E
Reversal valve (Package HK23)
R
Connect the DHW sensor (Package AD212)
T
BUS cable
Y
Low loss header
U
Cascade outlet sensor Connect the sensor to the S SYST terminal block on the master appliance.
I
Outdoor unit
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
67
Page 70
CAUTION
The "cooling" function is impossible with a connection in cascade.
Settings to be made for this type of installation: master module
Parameters Access Settings to be made See chapter
INSTALLATION
Installer level Menu #SYSTEM
EXTENDED
¼ "Displaying the parameters in extended mode", page 84
CASCADE
(1)
Installer level Menu #NETWORK
ON
¼ "Configuring the network", page 109
MASTER CONTROLER
(1)
Installer level Menu #NETWORK
ON
SYSTEM NETWORK
(1)
Installer level Menu #NETWORK
Enlist generators or VMs in cascade mode.
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
Settings to be made for this type of installation: slave module
Parameters Access Settings to be made See chapter
INSTALLATION
Installer level Menu #SYSTEM
EXTENDED
¼ "Displaying the parameters in extended mode", page 84
CASCADE
(1)
Installer level Menu #NETWORK
ON
¼ "Configuring the network", page 109
MASTER CONTROLER
(1)
Installer level Menu #NETWORK
OFF
SLAVE NUMBER
(1)
Installer level Menu #NETWORK
2, 3, ...
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
4. Installation AWHP-2 MIT-IN-2 iSystem
68
25/06/2014 - 7616371-001-04
Page 71
4.11.19. Connection example in power cut off EVU
M003037-B
BUS
13
14
15
On/off
OT BL S ECS
BUS
A B 0V
S EXT
TS + B AB
0-10V
S AMB C
4 3 2 1 2 1
+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA -
S ECS S EXT S DEP C
2 12 12 12 1 2 1
S DEP B
2 1
SCU
EVU
PCU
1 2
3
9
12
5 6
8
7
4
3 4
10
11
A
B
A/B
A
B
A/B
A
Not used: Do not connect anything to the terminal block.
Z
CAUTION
Do not connect anything to the DHW pump outlet as the reversal valve is connected to the PCU PCB in the boiler.
E
Connect the outside temperature sensor.
R
Connect the 3-way valve motor (circuit B) and the circuit B flow sensor.
T
Connect the heating pump (Circuit B).
Y
Connect a safety thermostat if the heating circuit is for underfloor heating: Remove the bridge. Connect the wires from the safety thermostat to the connector.
U
Connect the DHW sensor (Package AD212).
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
69
Page 72
I
Connect the DHW tank anode.
CAUTION
4 If the tank is fitted with a Titan Active
System® impressed current anode, connect the anode to the inlet (+ TA on the anode, - on the tank).
4 If the tank is not fitted with an impressed
current anode, put the simulation connector in place (delivered with the DHW sensor - package AD212).
O
Not used: Do not connect anything to the terminal block.
P
Connect the motor on the DHW reversal valve.
a
Connect the EVU contact to the 1-2 terminals on the TEL connector.
z
Connect the BUS cable between the outside module and the terminal block on the inside module.
¼ "Connecting the communication cable between the inside and outside modules", page 47.
e
Inside module with electrical back-up
r
Outdoor unit
t
Buffer tank
Settings to be made for this type of installation
Parameters Access Settings to be made See chapter
INSTALLATION
Installer level
#SYSTEM menu
EXTENDED
¼ "Displaying the parameters in extended mode", page 84
CIRC.A
(1)
Installer level
#SYSTEM menu
DIRECT
¼ "Setting the parameters specific to the installation", page 86
PUMP MIT/MHR
Installer level
#SYSTEM menu
CIRC.A
¼ "Setting the parameters specific to the installation", page 86
CIRC.B
(1)
Installer level
#SYSTEM menu
3WV
¼ "Setting the parameters specific to the installation", page 86
CT.TEL
Installer level
#SYSTEM menu
CLOSE
¼ "Setting the parameters specific to the installation", page 86
I.TEL
Installer level
#SYSTEM menu
0/1 EVU
¼ "Setting the parameters specific to the installation", page 86
DHW TYPE
Installer level
#PRIMARY INSTAL.P menu
SECONDARY
¼ "Professional settings", page 98
BACKUP TYPE
Installer level
#PRIMARY INSTAL.P menu
/E1: Stage 1 /E2: Stage 2
¼ "Professional settings", page 98
HP BUS
Installer level
#PRIMARY INSTAL.P menu
TOR
¼ "Professional settings", page 98
CIRC.CURVE A
Installer level
#SECONDARY INSTAL.P
menu
0.7
¼ "Professional settings", page 98
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
4. Installation AWHP-2 MIT-IN-2 iSystem
70
25/06/2014 - 7616371-001-04
Page 73
Settings to be made for this type of installation
Parameters Access Settings to be made See chapter
CIRC.CURVE B
Installer level
#SECONDARY INSTAL.P
menu
0.7
¼ "Professional settings", page 98
OFFSET EVU
Installer level
#SECONDARY INSTAL.P
menu
7 °C
¼ "Professional settings", page 98
EVU TIMER PROG.
User level Menu #TIME PROGRAM
Set the timer programme according to the power cut off hours EVU.
¼Refer to the user instructions.
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
4.12 Electrical principle diagram
4.12.1. Legend
0-10 V
Input
M A, B
Baffle, Circuit A, B
AL1 M, AL2
Hydraulic additional heating
C1, C2, C3
Homologation
CN21
Cooling sensor
CN20
Heating sensor
CN2A
HP setpoint
CNX2
Machine fault
CNX4
Defrosting
CNX3
Compressor - ON
ECS
Electrical back-up - Domestic hot water
F6.3AT
6.3A fuse
HMI
Display
J-
PCB connector
L
Live
L1, L2, L3, D3, N
Auxiliary electrical power supply
N
Neutral
PCU
Primary control unit
Res
Resistance
RL.
Relay
S2, S3
bus
SONDE ECS
Domestic hot water sensor
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
71
Page 74
SONDE SYST
System sensor
SONDE AMB A, B, C
Room sensor A, B, C
SONDE DEP B, C
Outlet sensor B, C
SONDE EXT
Outside sensor
TA
Titan Active System
TB6, TB142
Terminal block interface board
TS
Safety thermostat
V3V
3-way valve
X-
PCB connector - PCU
X25
HP pump
X28
Outlet sensor
X29
Flowmeter
X30
Pressure gauge
XA
Through-feed terminal unit
SCU
DIEMATIC iSystem control panel PCB
ZG
General switch
<
DHW circuit reversal valve
4. Installation AWHP-2 MIT-IN-2 iSystem
72
25/06/2014 - 7616371-001-04
Page 75
4.12.2. Hydraulic additional heating
SENSOR
FTC LIQUID PIPE
TARGET TEMPERATURE
SENSOR FTC
SWITCHS
1
2
34 8
7 5
6
OFF
ON
SW1
1
2
34
87 56
OFF
ON
SW2
12
34
87 56
OFF
ON
SW3
SW6
1
2
INTERFACE BOARD
FUSE
T3.15AL 250V
FLOW TEMP
PROBE
CH PUMP
X2
FLOWMETER
HP PUMP
N
X1
X33
1
2
3
1
3 2
F6.3AT
V3V
J10
J5
HYDRAULIC B
ACKUP
PWM
DRIVING
PWM
DRIVING
*
* : 230V AC Main power supply
HMI
PRINCIPLE DIAGRAM INVERTER HYDRAULIC
L N T
S2
S3 1
5 7
9
TB142
11 13
2 4 6 8
10 12 14
3
3
CNX3
1
1
2CN 21
XA
1
2CN 20
°C
+
-
X27
2
1 2
2
3
2
1
3
LN
Main Input
X3
PCU-194
2
3
3 2 1
1
3
2
N L
0V
5V
S
1
L
N
PE
2
q°C
1
2
OT BL S EXT S ECS
X11
1
2
3
4
5
6
X12
5
4
X28
1
5V
S0V
X29
X8
X25
3 1
X30
2
Mano.
1 2
ZG
3 4
X23
2 3
1
S1
6
1
5 3
X31
4
7
2
9 10 8
11
1
CNX2
3
CNX4
1
3
CN2A
0V
5V
1
PE
L
L'
Condens.sensor
+-34
LN
X21
1 2
X34
2
1
TB6
0V
B
A
BUS
T
J7
2
J7
1
RL-V3VALIM
SCU D4
3
123412
0-10 V
LNLN 12LN
12
SONDE
ECS
B
°C
1
J2
1
2
3
4
5
6
SENSOR
EXT
°C
12
SENSOR
AMB A
SENSOR
DEP C
°C
12 12
SENSOR
DEP B
°C
12
SENSOR
AMB C
SENSOR
AMB B
121212
SONDE
SYST
12 -+
T.A
N
RL-PA
RL-ECSRL-V3VOF
J6
RL-PB
3
S2 S3
ECSECS AL2
N21L
°C
°C
AWHP-2 MIT-IN-2 iSystem 4. Installation
25/06/2014 - 7616371-001-04
73
Page 76
4.12.3. Electrical back-up
SENSOR FTC LIQUID PIPE
TARGET TEMPERATURE
SENSOR FTC
Détail of switchs
1
2
34 8
7 5
6
OFF
ON
SW1
1
2
34
87 56
OFF
ON
SW2
12
34
87 56
OFF
ON
SW3
SW6
1
2
INTERFACE BOARD
FUSE
T3.15AL 250V
FLOW TEMP
PROBE
CH PUMP
X2
FLOWMETER
HP PUMP
N
X1
X33
1
2
3
1
3 2
F6.3AT
V3V
J10
J5
Res
XA
TS
PWM
DRIVING
PWM
DRIVING
C1
C2 C3
*
* : 230V AC Main power supply
Heating resistor power supply
HMI
PRINCIPLE DIAGRAM INVERTER ELECTRIC
L N T
S2
S3 1
5 7
9
TB142
11 13
2 4 6 8
10 12 14
3
RL1
11
14
A2
A1
RL1
RL3
11
14
A2
A1
RL2
11
14
A2
A1
RL3
3
CNX3
1
1
2CN 21
q°C
XA
1
2CN 20
q°C
+
-
X27
2 1
2
2
3
2
1
3
LN
Main Input
X3
PCU-194
2
3
3
2
1
1
3
2
N L
0V
5V
S
1
L
N
PE
2
q°C
1
2
OT BL S EXT S ECS
X11
1
2
3
4
5
6
X12
5
4
X28
1
5V
S0V
X29
X8
X25
3
1
X30
2
Mano.
1 2
ZG
3 4
X23
2 3
1
S1
6
1
5 3
X31
4
7
2
9 10 8
11
1
CNX2
3
CNX4
1
3
CN2A
0V
5V
1
PE
L
L'
Condens.sensor
+-34
LN
ECS
X21
1 2
X34
2
1
TB6
X24
1 2
X32_B
2 3
0V
B
A
BUS
12
RL2
B3 B2
A2
B1
A1
T
J7
2
J7
1
RL-V3VALIM
SCU D4
3
123412
0-10 V
LNLN 12LN
12
SONDE
ECS
B
°C
1
J2
1
2
3
4
5
6
SONDE
EXT
q°C
12
SONDE
AMB A
SONDE
DEP C
q°C
12 12
SONDE
DEP B
q°C
12
SONDE
AMB C
SONDE
AMB B
121212
SONDE
SYST
12 -+
T.A
N
RL-PA
RL-ECSRL-V3VOF
J6
RL-PB
3
L1
L2
L3
N
C
S2 S3
°C
A3
4. Installation AWHP-2 MIT-IN-2 iSystem
74
25/06/2014 - 7616371-001-04
Page 77
5 Commissioning
5.1 Control panel
5.1.1. Description of the keys
A
Temperature setting key (heating, DHW, swimming pool)
B
Operating mode selection key
C
DHW override key
D
Key to access the parameters reserved for the installer
E
Keys on which the function varies as and when selections are made
¼See: "Key functions", page 76
F
Rotary setting button:
4 Turn the rotary button to scroll through the menus or
modify a value
4 Press the rotary button to access the selected menu
or confirm a value modification
M002616-A
bar
STD
0 2 4 6 8 10 12 14 16 18 22 2420
b
v
AUTO
g
A
B
C
D
E
F
w
1
1 2
AWHP-2 MIT-IN-2 iSystem 5. Commissioning
25/06/2014 - 7616371-001-04
75
Page 78
5.1.2. Description of the display
n
Key functions
>
Access to the various menus
(
Used to scroll through the menus
Used to scroll through the parameters
?
The symbol is displayed when help is available
f
Used to display the curve of the parameter selected
STD
Reset of the time programmes
b
Selection of comfort mode or selection of the days to be programmed
v
Selection of reduced mode or deselection of the days to be programmed
j
Back to the previous level
ESC
Back to the previous level without saving the modifications made
t
Manual reset
n
Solar (If connected)
u
The solar load pump is running
L000200-A
The top part of the tank is reheated to the tank set point
L000201-A
The entire tank is reheated to the tank set point
L000198-A
The entire tank is reheated to the solar tank set point
L000199-A
The tank is not loaded - Presence of the solar control system
n
Operating modes
p
Summer mode: Cooling is possible. Domestic hot water continues to be produced.
b
WINTER mode: Heating and domestic hot water working.
w + p
Forced cooling mode.
w
Cooling mode: Heating according to the time programme.
bar
r
STD
(
'
t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
p
b
AUTO
x
c
r
j
L
g
m
bar
STD
t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
p
b
AUTO
x
c
r
j
M
g
m
bar
1
1
2
c
STD
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
M002620-A
p
b
w
AUTO
x
c
r
j
M
g
m
5. Commissioning AWHP-2 MIT-IN-2 iSystem
76
25/06/2014 - 7616371-001-04
Page 79
AUTO
Operation in automatic mode according to the timer programme.
x
Comfort mode: The symbol is displayed when a DAY override (comfort) is activated.
4 Flashing symbol: Temporary override 4 Steady symbol: Permanent override
m
Reduced mode: The symbol is displayed when a NIGHT override (reduced) is activated.
4 Flashing symbol: Temporary override 4 Steady symbol: Permanent override
g
Holiday mode: The symbol is displayed when a HOLIDAY override (antifreeze) is activated.
4 Flashing symbol: Holiday mode programmed 4 Steady symbol: Holiday mode active
m
Manual mode
n
System pressure
bar
Pressure indicator: The symbol is displayed when a water pressure sensor is connected.
4 Flashing symbol: The water pressure is insufficient. 4 Steady symbol: The water pressure is sufficient.
l
Water pressure level
4 R: 0,9 to 1,1 bar 4 E: 1,2 to 1,5 bar 4 Z: 1,6 to 1,9 bar 4 A: 2,0 to 2,3 bar 4 l: > 2,4 bar
n
Domestic Hot Water override
A bar is displayed when a DHW override is activated:
4 Flashing bar: Temporary override 4 Steady bar: Permanent override
bar
STD
t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
p
b
AUTO
x
c
r
j
M
g
m
bar
STD
t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
p
b
AUTO
x
c
r
j
M
g
m
bar
STD
t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
p
b
AUTO
x
c
r
j
M
g
m
AWHP-2 MIT-IN-2 iSystem 5. Commissioning
25/06/2014 - 7616371-001-04
77
Page 80
n
Electrical back-up
G
The symbol 1 or 2 lights up, depending on whether stage 1 or 2 on the electrical back-up is commanded.
n
Hydraulic additional heating
y
4 Steady symbol: The burner and the heating pump on
the back-up boiler are commanded.
4 Flashing symbol: The heating pump on the back-up
boiler is commanded.
n
Status of the compressor
v
4 Steady symbol: The compressor is running. 4 Flashing symbol: The heat pump is required but the
compressor is off.
n
Other information
r
The symbol is displayed when domestic hot water production is running.
w
Valve indicator: The symbol is displayed when a 3-way valve is connected.
4 x: 3-way valve opens 4 c: 3-way valve closes
M
The symbol is displayed when the pump is operating.
Name of the circuit for which the parameters are displayed.
bar
1
1
2
c
STD
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
M002630-A
p
b
w
AUTO
x
c
r
j
M
g
m
bar
1
1
2
c
STD
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
M002632-A
p
b
w
AUTO
x
c
r
j
M
g
m
bar
1
1
2
c
STD
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
M002631-A
p
b
w
AUTO
x
c
r
j
M
g
m
bar
STD
t
0 2 4 6 8 10 12 14 16 18 22 2420
C002699-B
p
b
AUTO
x
c
r
j
M
g
m
5. Commissioning AWHP-2 MIT-IN-2 iSystem
78
25/06/2014 - 7616371-001-04
Page 81
5.1.3. Access to the various browsing levels
n
User level
The information and settings in the User level can be accessed by everyone.
1. Press the > key.
n
Installer level
The information and settings in the Installer level can be accessed by experienced people.
1. Press the > key.
2. Press the - key.
It is also possible to access the installer level by pressing only the - key for around 5 seconds.
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
TEMP.: 68°
C002271-F-04
AWHP-2 MIT-IN-2 iSystem 5. Commissioning
25/06/2014 - 7616371-001-04
79
Page 82
n
After Sales level
The After Sales Service information and settings can be accessed by the professional providing the After Sales Service.
1. Press the > key.
2. Press key - for around 5 seconds.
It is also possible to access the After Sales level by pressing only the - key for around 10 seconds.
5.1.4. Browsing in the menus
1. To select the desired menu, turn the rotary button.
2. To access the menu, press the rotary button.
To go back to the previous display, press the key j.
3. To select the desired parameter, turn the rotary button.
4. To modify the parameter, press the rotary button.
To go back to the previous display, press the key j.
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
5
"
TEMP.: 68°
C002235-F-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
L
g
m
#MEASURES
#CHOICE TIME PROG.
#TIME PROGRAM #SETTING #TIME .DAY
a
C002220-B-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
L
g
m
CURRENT PROG.B
CURRENT PROG.C
P2
P3
a
C002221-C-04
5. Commissioning
AWHP-2 MIT-IN-2 iSystem
80
25/06/2014 - 7616371-001-04
Page 83
5. To modify the parameter, turn the rotary button.
6. To confirm, press the rotary button.
To cancel, press key h.
7. To go back to the main display, press key j2 times.
It is possible to use the ( and ’ keys instead of the rotary button.
5.2 Check points before commissioning
5.2.1. Hydraulic connections
4 Hoses correctly connected to the heat pump. 4 Fill the installation with water and check hydraulic tightness. 4 Vent the installation with the on/off cycles. Be sure to open all
valves on the heating circuit and the thermostatic valves on the radiators.
4 After venting, check that the filters are not clogged. Clean the
filters.
4 Raise the pressure to 1.5 / 2 bar.
5.2.2. Electrical connection
Check the electrical connections, particularly the earth:
4 HP: Mains supply connected 4 Indoor module: Mains supply connected. 4 depending on the version: Connecting the electrical back-up. 4 HP modules interconnected by BUS cable.
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
L
g
m
CURRENT PROG.C
"Choice of the timeprogram applied C"
P4
a
C002222-C-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
LUNDI 11:45
C002224-D-04
2x
AWHP-2 MIT-IN-2 iSystem
5. Commissioning
25/06/2014 - 7616371-001-04
81
Page 84
5.3 Checklist for commissioning (HP)
4 Range:
4 Models:
4 Soft version:
Checklist before commissioning:
OK
OK
Position of the outside unit, distance from the wall
Other functions
Circulation direction of the hydraulic fluids
Cooling
Tightness of the refrigerant fittings
Mixing valve
Pressure during vacuum tapping before filling
Electric OK
Checks after start-up
After 1 hour’s running
OK
Circuit breaker presence (curve C) recommended
Verification of tightness
Tighten the terminals
Vent any air in the heating circuit using the appliance’s air vent
Separation of the power and low voltage cables
Check the water pressure
EAC power cut off (blockage by the electricity supplier)? u ON u OFF
Start-up of the heating circulating pumps
Mounting and position of the outside temperature sensor
No error on regulator
Mounting and position of the room sensor
Compressor starts
Presence and connection of the underfloor heating thermostat
Heat transfer to the heating circuits Additional heating function
Heating mode checks OK
Cleanliness of the filter Flow rate in the primary circuit Δ T heating (between 5 and 15°C)
Instruct the user on how the product operates
Setting the primary pump speed
Notes:
Setting the secondary pump speed Setting the temperature: 55 or 60°C Setting the minimum flow rate
Remarks:
5. Commissioning AWHP-2 MIT-IN-2 iSystem
82
25/06/2014 - 7616371-001-04
Page 85
5.4 Putting the appliance into operation
1. Make a note of the output and type shown on the outside module’s nameplate.
2. Switch on the power by throwing the on/off switch on the inside module.
3. The first time the boiler is powered up, the LANGUAGE menu is displayed. Select the desired language by turning the rotary button.
4. To confirm, press the rotary button.
5. The parameter TYPE displays. According to the values noted on the outside module’s nameplate, select the type of thermodynamic unit by turning the rotary button.
Outside module output
Indoor module TYPE
From 4 to 16 kW
MIT-IN-2/E
MIT AWHP E HT FR
MIT-IN-2/H
MIT AWHP H HT FR
22 and 27 kW
MIT-IN-2/E
MIT AWHP E FR
MIT-IN-2/H
MIT AWHP H FR
Error during the start-up procedure:
4 No information is shown on the display:
- Check the mains supply voltage.
- Check the fuse (¼See chapter: "Location of the fuse", page
47).
- Check the connection of the power cable to the connector on
the PCU PCB (See chapter: ¼ "Connecting the mains supply to the inside module", page 49).
4 If there is a problem, the error is displayed on the screen.
¼See chapter: "Messages", page 118.
MW-M001832-2
C002366-B
Français - Deutsch - English ­Italiano - Espanol - Nederlands
- Pycck - Polski - Türk -
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
x
c
r
g
m
ÿ
LANGUE FRANCAIS
C002286-C
AWHP-2 MIT-IN-2 iSystem
5. Commissioning
25/06/2014 - 7616371-001-04
83
Page 86
5.5 Checks and adjustments after commissioning
5.5.1. Displaying the parameters in extended
mode
The display mode on the control panel is set as standard in such a way as only to show the conventional parameters. It is possible to switch to extended mode by proceeding as follows:
1. Access the installer level: Press key - for around 5 seconds.
2. Select the menu #SYSTEM.
4 Turn the rotary button to scroll through the menus or
modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 80
3. Set parameter INSTALLATION to EXTENDED.
Installer level - Menu #SYSTEM
Parameter Adjustment range Description Factory setting Customer setting
INSTALLATION TRADITIONAL
Displays the parameters of a conventional installation
TRADITIONAL
EXTENDED
Displays all parameters
Regardless of what is done to the keys, the regulator switches back to TRADITIONAL mode after 30 minutes.
5.5.2. Setting the heating pump speed on the heat
pump
The setting is used to select the speed of the primary pump located between the condenser and the tank, according to the output of the outside module; it is important to guarantee correct running of the heat pump.
1. Access the installer level: Press key - for around 5 seconds.
2. Select the menu #PRIMARY LIMITS:
4
Turn the rotary button to scroll through the menus or modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 80.
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
5
"
TEMP.: 68°
C002235-F-04
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
5
"
TEMP.: 68°
C002235-F-04
5. Commissioning AWHP-2 MIT-IN-2 iSystem
84
25/06/2014 - 7616371-001-04
Page 87
Installer level - Menu #PRIMARY LIMITS
Parameter Adjustment range Description Factory setting Customer setting MHR.PUMP SPEED
(1)
1 - 5 Speed of the heat pump heating pump 3
4 1: 4, 6 kW 4 2: 8, 11 kW 4 4: 16 kW 4 5: 22, 27 kW
(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED
5.5.3. Setting the flow rate threshold
Setting the flow rate threshold is used to select the threshold below which the heat pump goes into safety shutdown. The flow rate threshold must be chosen according to the type of outside module (See table below).
1. Access the installer level: Press key - for around 5 seconds.
2. Select the menu #PRIMARY INSTAL.P:
4 Turn the rotary button to scroll through the menus or
modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 80.
Installer level - Menu #PRIMARY INSTAL.P
(1)
Parameter Adjustment range Description Factory setting Customer setting
MIN.MES.FLOW.
OFF / 5 - 60 Flow rate limit below which a message is
displayed indicating that the flow rate is low.
¼See chapter: "Messages", page
118.
25 l/mim.
MIN.STOP.FLOW.
OFF / 5 - 60 Flow rate limit below which the heat pump goes
into default. After 4 successive defaults, the system must be
reset.
17 l/mim.
(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED
Type of group MIN.MES.FLOW. MIN.STOP.FLOW.
l/min l/min 4, 6 kW 12 8 8 kW 16 13 11 kW 19 13 16 kW 28 19 22, 27 kW 35 30
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
5
"
TEMP.: 68°
C002235-F-04
AWHP-2 MIT-IN-2 iSystem 5. Commissioning
25/06/2014 - 7616371-001-04
85
Page 88
CAUTION
Check the water flow rate in the system, which must be higher by at least 4 to 5 l/min than the MIN.MES.FLOW. value. Check the parameter FLOWMETER.
¼See chapter: "Reading out measured values", page
94. If the flow rate is too low, clean the filter upstream of the
plate heat exchanger. ¼See chapter: "Cleaning the 400 µm filter", page
114.
5.5.4. Setting the parameters specific to the installation
1. Access the installer level: Press key - for around 5 seconds.
2. Select the menu #SYSTEM.
4 Turn the rotary button to scroll through the menus or
modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 80
3. Set the following parameters according to the connections made
to the PCBs:
Installer level - Menu #SYSTEM
Parameter Adjustment range Description Factory setting Customer
setting
CIRC.A
(1) (2)
DIRECT
Use as a direct heating circuit (Radiator). Cooling is not possible.
DIRECT
HEATING FL.
Use as direct circuit on underfloor heating. Cooling is possible.
PROGRAM.
Use as an independent programmable outlet.
H.TEMP
Enables operation of circuit A in summer despite manual or automatic summer shutdown.
FAN CONVECTOR
Use as fan coil unit circuit. Cooling is possible.
DHW
Connection of a second domestic hot water tank.
DHW ELEC
Used to control the electrical resistor according to the timer programme on circuit A in summer mode.
DISAB.
No data for circuit A is displayed.
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED (2) If the pump incorporated in the boiler is used for circuit A (parameter CIRC.A set to DIRECT), the O.PUMP A outlet is free (3) The parameter is only displayed if the parameter O.PUMP A is set to CIRC.AUX or the 3-way valve PCB option is connected (4) The parameter is only displayed if a sensor is connected to the S.SYST inlet
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
5
"
TEMP.: 68°
C002235-F-04
5. Commissioning AWHP-2 MIT-IN-2 iSystem
86
25/06/2014 - 7616371-001-04
Page 89
Installer level - Menu #SYSTEM
Parameter Adjustment range Description Factory setting Customer
setting
O.PUMP A
(1) (2)
CH.PUMP A
Heating pump circuit A: The PUMP A outlet is used to control the pump on circuit A.
CH.PUMP A
CIRC.AUX
Used to resume the functions of the S.AUX parameter without adding the PCB + sensor option (Package AD249).
DHW LOOP
Used to control the domestic hot water looping pump according to the DHW timer programme and force its operation during an override.
PRIMARY PUMP
The outlet PUMP A is active if a heating demand is present on the secondary pump.
FAILURE
The outlet PUMP A is active if an fault is detected.
DEF.CASC
The Pump A outlet is active if a fault is present in the cascade.
VM P
The Pump A outlet is active if the VM pump is active.
COLD
The Pump A outlet is active in cold running.
PUMP MIT/MHR ALL
Runs if a circuit is required.
ALL
CIRC.A
Runs if A is required.
CIRC.B
(1)
3WV
Connecting a circuit with 3-way valve (For example: Underfloor heating).
3WV
SWIM.P.
Using the circuit for pool management.
FAN CONVECTOR
Use as fan coil unit circuit.
CIRC.C
(1)
3WV
Connecting a circuit with 3-way valve (For example: Underfloor heating).
3WV
SWIM.P.
Using the circuit for pool management.
FAN CONVECTOR
Use as fan coil unit circuit.
P.DHW
(1)
PUMP
Not used.
RV
RV
Not used.
S.AUX
(1) (3)
DHW LOOP
Use as a domestic loop pump.
DHW LOOP
PROGRAM.
Use as an independent programmable outlet.
PRIMARY PUMP
The outlet AUX PUMP is active if a heating demand is present on the secondary pump.
DHW
Use of primary circuit of second DHW tank.
FAILURE
The outlet AUX PUMP is active if a fault is detected.
DHW ELEC
Used to control the electrical resistor according to the timer programme on circuit AUX in summer mode.
COLD
The AUX Pump outlet is active in cold running.
VM P
The AUX Pump outlet is active if the VM pump is active.
DEF.CASC
The AUX Pump outlet is active if a fault is present in the cascade.
I.SYST
(1) (4)
SYSTEM
The inlet sensor is used to connect the common flow sensor of a cascade system.
SYSTEM
BUFFER TANK
Hot water storage tank affected to heating only.
DHW STRAT
Using the DHW tank with 2 sensors (top and bottom).
ST.TANK+DHW
Hot water storage tank affected to heating and domestic hot water.
DISAB.
Not used.
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED (2) If the pump incorporated in the boiler is used for circuit A (parameter CIRC.A set to DIRECT), the O.PUMP A outlet is free (3) The parameter is only displayed if the parameter O.PUMP A is set to CIRC.AUX or the 3-way valve PCB option is connected (4) The parameter is only displayed if a sensor is connected to the S.SYST inlet
AWHP-2 MIT-IN-2 iSystem 5. Commissioning
25/06/2014 - 7616371-001-04
87
Page 90
Installer level - Menu #SYSTEM
Parameter Adjustment range Description Factory setting Customer
setting
O.TEL
(1)
FAILURE
The telephone outlet is closed in the event of failure.
FAILURE
REVISION
The telephone outlet is closed in the event of revision display.
DEF+REV
The telephone outlet is closed in the event of failure or revision display.
CT.TEL
(1)
CLOSE
See table below.
CLOSE
Open
I.TEL
(1)
ANTIFR
Boiler anti-freeze activation.
ANTIFR
0/1 A
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuit A.
0/1 B
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuit B.
0/1 A+B
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuits A+B
0/1 C
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuit C.
0/1 A+C
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuits A+C
0/1 B+C
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuits B+C
0/1 A+B+C
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuits A+B+C
0/1 DHW
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuit ECS.
I.TEL
(1)
0/1 A+DHW
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuits A+ECS
ANTIFR
0/1 B+DHW
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuits B+ECS
0/1 A+B+DHW
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuits A+B+ECS
0/1 C+DHW
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuits C+ECS
0/1 A+C+DHW
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuits A+C+ECS
0/1 B+C+DHW
ON or OFF contact: I.TEL: can be used as an antifreeze activation inlet on circuits B+C+ECS
0/1 AUX
ON or OFF contact: I.TEL can be used as an antifreeze activation inlet on circuit AUX (S.AUX if the AD 249 option is connected or the parameter O.PUMP A is set to CIRC.AUX). When I.TEL is not activated, the auxiliary circuit (AUX) follows the maximum temperature of the inside module (parameter MAX MIT).
0/1 EVU
ON or OFF contact: Enables you to use I.TEL as an EVU power cut off inlet.
IN 0-10V
Enables use of I.TEL as the input for a 0–10 V command.
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED (2) If the pump incorporated in the boiler is used for circuit A (parameter CIRC.A set to DIRECT), the O.PUMP A outlet is free (3) The parameter is only displayed if the parameter O.PUMP A is set to CIRC.AUX or the 3-way valve PCB option is connected (4) The parameter is only displayed if a sensor is connected to the S.SYST inlet
5. Commissioning AWHP-2 MIT-IN-2 iSystem
88
25/06/2014 - 7616371-001-04
Page 91
Influence of the parameter setting CT.TEL on the I.TEL contact
CT.TEL I.TEL I.TEL contact closed I.TEL contact open
CLOSE ANTIFR
The antifreeze mode is active on all circuits. The heating system is off.
The mode selected on the inside module is active.
0/1 A
The mode selected on the circuit is active. The antifreeze mode is active on the circuit
concerned.
0/1 B
The mode selected on the circuit is active. The antifreeze mode is active on the circuit
concerned.
0/1 C
The mode selected on the circuit is active. The antifreeze mode is active on the circuit
concerned.
0/1 DHW
The mode selected on the DHW circuit is active. The antifreeze mode is active for the DHW circuit.
0/1 AUX
4 The MAUX outlet on the connection terminal
block is active.
4 The device operates with a set point temperature
equal to MAX MIT.
4 The MAUX outlet on the connection terminal
block is not active.
4 The device operates with a set point temperature
dependent on the outside temperature.
0/1 EVU
No EVU power cut off The heat pump and back-ups are cut off. The buffer
tank meets the heating needs.
Open ANTIFR
The mode selected on the inside module is active. The antifreeze mode is active on all circuits.
The heating system is off.
0/1 A
The antifreeze mode is active on the circuit concerned.
The mode selected on the circuit is active.
0/1 B
The antifreeze mode is active on the circuit concerned.
The mode selected on the circuit is active.
0/1 C
The antifreeze mode is active on the circuit concerned.
The mode selected on the circuit is active.
0/1 DHW
The antifreeze mode is active for the DHW circuit. The mode selected on the DHW circuit is active.
0/1 AUX
4 The MAUX outlet on the connection terminal
block is not active.
4 The device operates with a set point temperature
dependent on the outside temperature.
4 The MAUX outlet on the connection terminal
block is active.
4 The device operates with a set point temperature
equal to MAX MIT.
0/1 EVU
The heat pump and back-ups are cut off. The buffer tank meets the heating needs.
No EVU power cut off
AWHP-2 MIT-IN-2 iSystem 5. Commissioning
25/06/2014 - 7616371-001-04
89
Page 92
n
Power cut off (EVU)
A
Circulator
Z
EVU power cut off timer program
E
Compressor
R
Outside temperature
T
Temperature set point
Y
Temperature OFFSET EVU (0 to 20 K)
A
Phase A (¼See below)
B
Phase B (¼See below)
C
Phase C (¼See below)
EVU
EVU function
Phase A
Normal operation according to the DHW and ECO / COMFORT timer programme.
Phase B
Start-up of the EVU timer programme. The set point temperature on the inside module is increased by the value shown in the OFFSET EVU parameter as long as the EVU timer programme is active and the EVU signal is absent (the EVU contact is closed). Domestic hot water production can only be handled if the tank has an electrical resistor.
Phase C
Presence of the EVU signal (the EVU contact is open). The outside module, the back-ups and the heating pumps on the inside module are powered down. The secondary pumps continue to run as long as the circuits concerned are required. No DHW production enabled.
M002702-A
1
2
3
4
5
6
A B
EVU
C A
5. Commissioning AWHP-2 MIT-IN-2 iSystem
90
25/06/2014 - 7616371-001-04
Page 93
5.5.5. Naming the circuits and generators
1. Access the installer level: Press key - for around 5 seconds.
2. Select the menu #NAMES OF THE CIRCUITS.
4 Turn the rotary button to scroll through the menus or
modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 80
3. Select the circuit or generator you wish to rename.
Installer level - Menu #NAMES OF THE CIRCUITS
Parameter Description Name given by the customer
CIRC.A
Circuit A
CIRC.B
Circuit B
CIRC.C
Circuit C
CIRC.AUX
Auxiliary circuit
CIRC.DHW
Domestic hot water circuit
GENE
Generator
4. Turn the rotary button to choose the first character from the list.
To confirm, press the rotary button.
5. Then press again to enter a second character or turn the rotary
button to leave an empty space.
6. Choose the other characters in the same way. The input zone may
contain up to 6 characters.
To move from one character to another, turn the rotary button. To exit without modifications, press key h.
7. To confirm the name, press the rotary button and then turn the
button slightly anti-clockwise. When the symbol U appears, press the rotary button. The name is confirmed.
If the name reaches 6 characters, it is automatically confirmed when the last character is confirmed.
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
5
"
TEMP.: 68°
C002235-F-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
L
g
m
CIRC.B I
"Personalize the nameof this circuit B"
a
E F G H
.
. .
C002344-E-04
I
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
L
g
m
CIRC.B FLOOR1
"Personalize the nameof this circuit B"
a
X Y Z
. . .
C002345-D-04
AWHP-2 MIT-IN-2 iSystem 5. Commissioning
25/06/2014 - 7616371-001-04
91
Page 94
5.5.6. Setting the heating curve
1. Access the installer level: Press key - for around 5 seconds.
2. Select the menu #SECONDARY INSTAL.PAL}.
4 Turn the rotary button to scroll through the menus or
modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 80.
3. Select the parameter CIRC.CURVE ...
4. To modify the value directly, turn the rotary button.
To modify the value by displaying the curve, press key f.
5. To modify the curve, turn the rotary button.
6. To confirm, press the rotary button.
To cancel, press key h.
0.7 = Heating curve set.
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
5
"
TEMP.: 68°
C002235-F-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
BUILD.INERTIA
CIRC.CURVE B
CIRC.CURVE C
SCREED DRYING
3
2.0
0.7 No
a
C002316-E-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
CIRC.CURVE B
"Slope of the heatcurve of the circuit B"
2.0
C002317-D-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
75 64
50
020 -15
C002318-B-04
0,7
0.7
5. Commissioning AWHP-2 MIT-IN-2 iSystem
92
25/06/2014 - 7616371-001-04
Page 95
n
Heating curve without BCT
A
Maximum temperature of the circuit
Z
Water temperature in the circuit for an outside temperature of 0°C
E
DAY set point on the circuit
R
Outside temperature for which the maximum water temperature in the circuit is reached
T
Value of the heating curve Select the parameter CIRC.CURVE ..
When you modify the heating curve, Z and R are recalculated and repositioned automatically.
n
Heating curve with BCT
The BCT (Base heat Curve Temperature) parameter allows a minimum operating temperature to be imposed on the heating circuit (this temperature may be constant if the circuit gradient is nil).
A
Maximum temperature of the circuit
Z
Water temperature in the circuit for an outside temperature of 0°C
E
DAY set point on the circuit
R
Outside temperature for which the maximum water temperature in the circuit is reached
T
Value of the heating curve Select the parameter CIRC.CURVE ..
x
Value set to the parameter HCZP D
When you modify the heating curve, Z and R are recalculated and repositioned automatically.
20 0 -16
50
75
1.5
C002319-B
1
2
3
4
5
20 0 -15
64
50
75
0.7
C002320-B
1
2
X
3
4
5
AWHP-2 MIT-IN-2 iSystem 5. Commissioning
25/06/2014 - 7616371-001-04
93
Page 96
5.5.7. Setting the speed of the heating pump on the inside module
The setting is used to select the speed of heating pump A, located on the secondary tank circuit. The speed must be selected in such a way as to have a temperature differential between the flow and the return of 5 to 10 K when running at nominal output.
1. Access the installer level: Press key - for around 5 seconds.
2. Select the menu #PRIMARY LIMITS:
4 Turn the rotary button to scroll through the menus or
modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 80.
Installer level - Menu #PRIMARY LIMITS
Parameter Adjustment range Description Factory setting Customer setting PERCENT PUMP MIT
(1)
1 - 5 Inside module pump speed 3
(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED
CAUTION
The integrated filter must be cleaned after one hour’s operation on commissioning.
¼ "Cleaning the 400 µm filter", page 114.
5.6 Reading out measured values
The various values measured by the appliance are displayed in the #MEASURES menu.
1. To access user level: Press the > key.
2. Select the menu #MEASURES.
4
Turn the rotary button to scroll through the menus or modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 80.
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
5
"
TEMP.: 68°
C002235-F-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
5. Commissioning AWHP-2 MIT-IN-2 iSystem
94
25/06/2014 - 7616371-001-04
Page 97
User level - Menu #MEASURES
Parameter Description Unit
OUTSIDE TEMP.
Outside temperature °C
ROOMTEMP.A
(1)
Room temperature of circuit A °C
ROOMTEMP.B
(1)
Room temperature of circuit B °C
ROOMTEMP.C
(1)
Room temperature of circuit C °C
MIT TEMP.
Inside module flow sensor measurement °C
PRESSURE
Water pressure in the installation bar (MPa)
WATER TEMP.
(1)
Water temperature in the DHW tank °C
STOR.TANK.TEMP
(1)
Water temperature in the storage tank °C
SWIMMING P.T.B
(1)
Water temperature of the swimming pool on circuit B °C
SWIMMING P.T.C
(1)
Water temperature of the swimming pool on circuit C °C
OUTLET TEMP.B
(1)
Temperature of the flow water in circuit B °C
OUTLET TEMP.C
(1)
Temperature of the flow water in circuit C °C
TEMP.SYSTEM
(1)
Temperature of the system flow water if multi-generator °C
T.DHW BOTTOM
(1)
Water temperature in the bottom of the DHW tank °C
TEMP.TANK AUX
(1)
Water temperature in the second DHW tank connected to the AUX circuit °C
DHW A TEMP.
(1)
Water temperature in the second DHW tank connected to circuit A °C
TEMP.SOL.TANK
(1)
Temperature of the hot water produced by solar power (TS) °C
SOLAR.COLL.T.
(1)
Solar panel temperature (TC) °C
SOLA.ENERGY
(1)
Solar energy accumulated in the tank kWh
FLOWMETER
Plate exchanger flow rate l/min
NB IMPULS.COMP
Number of heat pump start-ups
RUNTIME HP
Number of hours’ operation of the heat pump compressor h
IN 0-10V
(1)
Voltage at input 0-10 V V
SEQUENCE
Control system sequence
CTRL Software control number (SCU)
DT INSTALLATION
Installation temperature delta K
ELEC.ENERGY
(1)
Total electrical energy consumed kWh
ELEC.ENERG.Y1
(1)
Total electrical energy consumed in the previous year kWh
ELEC.ENERG.Y2
(1)
Total electrical energy consumed two years ago kWh
THERM.ENERGY
(1)
Total thermal energy yield kWh
THERM.ENERG.Y1
(1)
Total thermal energy yield in the previous year kWh
THERM.ENERG.Y2
(1)
Total thermal energy yield two years ago kWh
(1) The parameter is only displayed for the options, circuits or sensors actually connected.
AWHP-2 MIT-IN-2 iSystem 5. Commissioning
25/06/2014 - 7616371-001-04
95
Page 98
5.7 Changing the settings
The heat pump control panel is set for the most common heating installations. With these settings, practically all heating systems operate correctly. The user or installer can optimise the parameters according to own preferences.
¼For the user settings, refer to the user instructions.
5.7.1. Language selection
1. Access the installer level: Press key - for around 5 seconds.
2. Select the menu #LANGUAGE.
4 Turn the rotary button to scroll through the menus or
modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 80
Installer level - Menu #LANGUAGE
Adjustment range Description
FRANCAIS Display in French DEUTSCH Display in German ENGLISH Display in English ITALIANO Display in Italian ESPANOL Display in Spanish NEDERLANDS Display in Dutch POLSKI Display in Polish PУCCKИЙ Display in Russian TÜRK Display in Turkish
5.7.2. Calibrating the sensors
1. To access user level: Press the > key.
2. Select the menu #SETTING.
4
Turn the rotary button to scroll through the menus or modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 80
3. Set the following parameters:
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
5
"
TEMP.: 68°
C002235-F-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
5. Commissioning
AWHP-2 MIT-IN-2 iSystem
96
25/06/2014 - 7616371-001-04
Page 99
User level - Menu #SETTING
Parameter Adjustment
range
Description Factory setting Customer
setting
SUM/WIN 15 to 30 °C Used to set the outside temperature above
which heating will be shut down.
4 The heating pumps are shut down. 4 The heat pump only starts up for
domestic hot water needs.
4 In this case the letter E and symbol p
are displayed.
22 °C
NO
Heating is never shut down automatically
CALIBR.OUT
Outside sensor calibration: Used to correct the outside temperature
Outside temperature
CALIBR.ROOM A
(1)
Calibration of the room sensor on circuit A Make this setting 2 hours after switching on, when the room temperature has stabilised
Room temperature of circuit A
OFFSET ROOM A
(2)
-5.0 to +5.0 °C Room offset on circuit A: Is used to set a room offset Make this setting 2 hours after switching on, when the room temperature has stabilised
0.0
ANTIFR.ROOM A 0.5 to 20 °C Room temperature antifreeze activation on
circuit A
6 °C
CALIBR.ROOM B
(1)
(3)
Calibration of the room sensor on circuit B Make this setting 2 hours after switching on, when the room temperature has stabilised
Room temperature of circuit B
OFFSET ROOM B
(2)
(3)
-5.0 to +5.0 °C Room offset on circuit B: Is used to set a room offset Make this setting 2 hours after switching on, when the room temperature has stabilised
0.0
ANTIFR.ROOM B
(3)
0.5 to 20 °C Room temperature at which the antifreeze mode is activated on circuit B
6 °C
CALIBR.ROOM C
(1)
(3)
Calibration of the room sensor on circuit C Make this setting 2 hours after switching on, when the room temperature has stabilised
Room temperature of circuit C
OFFSET ROOM C
(2)
(3)
-5.0 to +5.0 °C Room offset on circuit C: Is used to set a room offset Make this setting 2 hours after switching on, when the room temperature has stabilised
0.0
ANTIFR.ROOM C
(3)
0.5 to 20 °C Room temperature antifreeze activation on circuit C
6 °C
COST HIGH TARIFF
(4)
€ 0.01 to € 2.50 Cost of peak time electrical energy. 0.13
COST HIGH TARIFF
(4)
€ 0.01 to € 2.50 Cost of off-peak electrical energy. The tariff
is only factored in if parameter E. BL is set to HP/HC and the contact on the BL input is closed.
¼ "Professional settings", page 98
0.09
COST GAS.OIL
(4)
€ 0.01 to € 2.50 Cost of fossil energy (oil or gas). (Price per
litre or m3 )
0.90
(1) The parameter is only displayed if a room sensor is connected to the circuit concerned (2) The parameter is only displayed if no room sensor is connected to the circuit concerned or the sensor has no influence (3) The parameter is only displayed if the circuit concerned is actually connected (4) The parameter is only displayed if HYBRID ENABLED is set to COST
AWHP-2 MIT-IN-2 iSystem 5. Commissioning
25/06/2014 - 7616371-001-04
97
Page 100
5.7.3. Professional settings
1. Access the installer level: Press key - for around 5 seconds.
2. Set the following parameters:
4 Turn the rotary button to scroll through the menus or
modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 80.
Installer level - Menu #PRIMARY LIMITS
Parameter Adjustment range Description Factory setting Customer setting
MAX MIT
20 to 79 °C Maximum temperature of the MIT 4 to 16 kW: 65 °C
22 and 27 kW: 60 °C
MAX HP
(1)
20 to 79 °C Maximum heat pump temperature 4 to 16 kW: 65 °C
22 and 27 kW: 60 °C
PERCENT PUMP MIT
(1)
¼See chapter: "Setting the speed of the heating pump on the inside module", page 94
MHR.PUMP SPEED
(1)
¼See chapter: "Setting the heating pump speed on the heat pump", page 84
STOP HP:
(1)
-20 to +5 °C Heat pump shutdown temperature -15 °C
TEMP MIN DEFR.
(1)
25 to 40 °C Minimum defrosting temperature 25 °C
BIVALENCE.TEMP
(1)
-10 to +20 °C Temperature at the bivalence point 10 °C
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED
Installer level - Menu #SECONDARY LIMITS
Parameter Adjustment range Description Factory setting
MAX.CIRC.A
30 to 95 °C Maximum temperature (Circuit A)
¼ "MAX.CIRC...", page 105
75 °C
MAX.CIRC.B
20 to 95 °C Maximum temperature (Circuit B)
¼ "MAX.CIRC...", page 105
50 °C
MAX.CIRC.C
20 to 95 °C Maximum temperature (Circuit C)
¼ "MAX.CIRC...", page 105
50 °C
OUT.ANTIFREEZE
OFF, -8 to +10 °C Outside temperature at which the installation’s antifreeze protection
is activated. Below this temperature the pumps are permanently on and the minimum temperatures for each circuit are respected. When NIGHT :STOP is set, the reduced temperature is maintained in each circuit (Menu #SECONDARY INSTAL.P).
OFF: Antifreeze protection is not activated
+3 °C
HCZP D A
(1) (2)
OFF, 20 to 90 °C Curve base temperature in Daytime mode (Circuit A)
OFF
HCZP N A
(1) (2)
OFF, 20 to 90 °C Curve base temperature in Nighttime mode (Circuit A)
OFF
HCZP D B
(1) (2)
OFF, 20 to 90 °C Curve base temperature in Daytime mode (Circuit B)
OFF
HCZP N B
(1) (2)
OFF, 20 to 90 °C Curve base temperature in Nighttime mode (Circuit B)
OFF
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED (2) The parameter can be set to the heating curve by pressing key f.
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
5
"
TEMP.: 68°
C002235-F-04
5. Commissioning AWHP-2 MIT-IN-2 iSystem
98
25/06/2014 - 7616371-001-04
Loading...