DE DIETRICH MCA 45, MCA 65, MCA 90, MCA 115 User Manual

Page 1
Innovens Pro
MCA 45 - 65 - 90 - 115
EN
User Guide
300024828-001-01
Page 2
Contents
1 Introduction ................................................................................................4
1.1 Symbols used .......................................................4
1.3 General ..................................................................5
1.3.1 Manufacturer's liability .............................................5
1.3.2 Installer's liability .....................................................5
1.3.3 User's liability ..........................................................5
1.4 Certifications .........................................................6
2 Safety instructions and recommendations ..............................................7
2.1 Safety instructions ...............................................7
2.2 Recommendations ................................................8
3 Description ..................................................................................................9
3.1 Operating principle ...............................................9
3.1.1 Gas/air setting .........................................................9
3.1.2 Combustion .............................................................9
3.2 Main parts ............................................................10
3.3 DIEMATIC iSystem control panel ......................10
3.3.1 Description of the keys ..........................................10
3.3.2 Description of the display ......................................11
3.3.3 Browsing in the menus ..........................................14
3.4 IniControl control panel .....................................15
3.4.1 Description of the keys ..........................................15
3.4.2 Description of the display ......................................15
4 Operating the appliance - DIEMATIC iSystem .......................................18
4.1 Putting the appliance into operation ................18
4.2 Reading out measured values ...........................18
4.3 Changing the settings ........................................20
4.3.1 Setting the set point temperatures ........................20
4.3.2 Selecting the operating mode ...............................21
4.3.3 Forcing domestic hot water production .................22
4.3.4 Setting the contrast and lighting on the
display ...................................................................22
4.3.5 Setting the time and date ......................................23
4.3.6 Selecting a timer programme ................................23
4.3.7 Customising a timer programme ...........................24
1
28/08/12 - 300024828-001-01
Page 3
Contents
4.3.8 Setting an annual clock .........................................26
4.4 Installation shutdown .........................................29
4.5 Frost protection ..................................................29
5 Operating the appliance - IniControl ......................................................30
5.1 Putting the appliance into operation ................30
5.2 Reading out measured values ...........................30
5.3 Changing the settings ........................................31
5.3.1 Parameter descriptions .........................................31
5.3.2 Modification of the user-level parameters .............32
5.3.3 Setting the manual mode ......................................33
5.3.4 Changing the heating temperature ........................33
5.3.5 Modifying the domestic hot water temperature
setting ....................................................................33
5.4 Installation shutdown .........................................34
5.5 Frost protection ..................................................34
6 Checking and maintenance .....................................................................35
6.1 General instructions ...........................................35
6.1.1 DIEMATIC iSystem control panel ..........................35
6.2 Periodic checks ..................................................35
6.3 Filling the system ...............................................36
6.4 Bleeding the heating system .............................39
6.5 Draining the installation .....................................41
7 Troubleshooting .......................................................................................42
7.1 Anti-hunting ........................................................42
7.2 Messages (Code type Bxx or Mxx) ....................42
7.3 Faults (Code type Lxx or Dxx) ...........................45
7.3.1 DIEMATIC iSystem control panel ..........................45
7.3.2 IniControl control panel .........................................45
7.3.3 List of faults ...........................................................45
2
28/08/12 - 300024828-001-01
Page 4
8 Technical specifications ..........................................................................51
8.1 Technical specifications ....................................51
9 Energy savings .........................................................................................52
9.1 Energy-saving advice .........................................52
9.2 Recommendations ..............................................52
10 Warranty ....................................................................................................53
10.1 General ................................................................53
10.2 Warranty terms ...................................................53
3
28/08/12 - 300024828-001-01
Page 5
MCA 45 - 65 - 90 - 115
1 Introduction
1.1 Symbols used
1. Introduction
In these instructions, various danger levels are employed to draw the user's attention to particular information. In so doing, we wish to safeguard the user's safety, obviate hazards and guarantee correct operation of the appliance.
DANGER
Risk of a dangerous situation causing serious physical injury.
WARNING
Risk of a dangerous situation causing slight physical injury.
1.2 Abbreviations
CAUTION
Risk of material damage.
Signals important information.
¼ Signals a referral to other instructions or other pages in the instructions.
4 3CE: Collective conduit for sealed boiler
4 DHW: Domestic hot water
4 Hi: Lower heating value LHV (Nett)
4 Hs: Higher heating value HHV (Gross)
4 PPS: Polypropylene hardly inflammable
4 PCU: Primary Control Unit - PCB for managing burner operation
4 PSU: Parameter Storage Unit - Parameter storage for PCBs
PCU and SU
4 SCU: Secondary Control Unit - control panel PCB
4 SU: Safety Unit - Safety PCB
4 3WV: 3-way valve
28/08/12 - 300024828-001-01
4
Page 6
1. Introduction
1.3 General
MCA 45 - 65 - 90 - 115
1.3.1. Manufacturer's liability
Our products are manufactured in compliance with the requirements of the various applicable European Directives. They are therefore
delivered with [ marking and all relevant documentation.
In the interest of customers, we are continuously endeavouring to make improvements in product quality. All the specifications stated in this document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the following cases:
4 Failure to abide by the instructions on using the appliance.
4 Faulty or insufficient maintenance of the appliance.
4 Failure to abide by the instructions on installing the appliance.
1.3.2. Installer's liability
The installer is responsible for the installation and inital start up of the appliance. The installer must respect the following instructions:
4 Read and follow the instructions given in the manuals provided
with the appliance.
4 Carry out installation in compliance with the prevailing legislation
and standards.
4 Perform the initial start up and carry out any checks necessary.
4 Explain the installation to the user.
4 If a maintenance is necessary, warn the user of the obligation to
check the appliance and maintain it in good working order.
4 Give all the instruction manuals to the user.
1.3.3. User's liability
To guarantee optimum operation of the appliance, the user must respect the following instructions:
4 Read and follow the instructions given in the manuals provided
with the appliance.
4 Call on qualified professionals to carry out installation and initial
start up.
4 Get your installer to explain your installation to you.
4 Have the required checks and services done.
4 Keep the instruction manuals in good condition close to the
appliance.
5
28/08/12 - 300024828-001-01
Page 7
MCA 45 - 65 - 90 - 115 1. Introduction
This appliance is not intended to be used by persons (including children) whose physcial, sensory or mental capacity is impaired or persons with no experience or knowledge, unless they have the benefit, through the intermediary of a person responsible for their safety, of supervision or prior instructions regarding use of the appliance. Care should be taken to ensure that children do not play with the appliance.
1.4 Certifications
CE identification no
NOx classification
Type of connection
(1) IP20
PIN 0063CL3333
5 (Standards EN)
Chimney: B23
Flue gas outlet: C13 , C33 , C43 , C53 , C63 , C83 , C
93
(1)
, B
23P
(1)
,
28/08/12 - 300024828-001-01
6
Page 8
2. Safety instructions and recommendations MCA 45 - 65 - 90 - 115
2 Safety instructions and
recommendations
2.1 Safety instructions
DANGER
If you smell gas:
1. Do not use a naked flame, do not smoke, do not operate electrical contacts or switches ( doorbell, light, motor, lift, etc..).
2. Shut off the gas supply.
3. Open the windows.
4. Evacuate the premises.
5. Call your fitter.
DANGER
If you smell flue gases:
1. Switch the appliance off.
2. Open the windows.
3. Evacuate the premises.
4. Call your fitter.
WARNING
Depending on the settings of the appliance:
4 The temperature of the flue gas conduits may exceed
60°C.
4 The temperature of the radiators may reach 85°C.
4 The temperature of the domestic hot water may reach
65°C.
CAUTION
Do not neglect to service the appliance: 4 For completely safe and optimum operation, you
must have your boiler regularly serviced by an approved installer.
7
28/08/12 - 300024828-001-01
Page 9
MCA 45 - 65 - 90 - 115 2. Safety instructions and recommendations
2.2 Recommendations
WARNING
Only qualified professionals are authorised to work on the appliance and the installation.
4 Regularly check the water pressure in the installation (minimum
pressure 0,8 bar, recommended pressure between 1,5 and 2,0 bar).
4 Keep the appliance accessible at all times.
4 Never remove or cover labels and rating plates affixed to the
appliance. Labels and rating plates must be legible throughout the entire lifetime of the appliance.
4 The appliance should be on Summer or Antrifreeze mode rather
than switched off to guarantee the following functions:
- Anti blocking of pumps
- Frost protection
28/08/12 - 300024828-001-01
8
Page 10
3. Description MCA 45 - 65 - 90 - 115
3 Description
3.1 Operating principle
3.1.1. Gas/air setting
The casing fitted to the boiler is also used as an air box. Air is sucked in by the fan and gas injected into the venturi by the fan intake. The fan rotation speed is set according to the settings parameters, the thermal energy requirement and the temperatures measured by the temperature sensors. The gas and air are mixed in the venturi. The gas/air ratio ensures that the quantities of gas and air are adjusted to each other. This provides optimum combustion on the entire output range. The gas/air mixture is fed into the burner on top of the exchanger.
3.1.2. Combustion
The burner heats the heating water circulating in the heat exchanger. At a return temperature lower than around 55°C, the flue gases cool down to a temperature lower than the dew point, thus causing the condensation of the water vapour contained in the flue gases in the lower section of the heat exchanger. The heat released during this condensation process (the latent heat or condensing heat) is also transferred to the heating water. The cooled combustion gases are evacuated via the combustion gas outlet flue. The condensation water is evacuated via a siphon.
9
28/08/12 - 300024828-001-01
Page 11
T002036-B
8
7
4
55
6
2
3
9
11
10
12
13
1
A000866-A
bar
STD
t
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
A
B
C
D
E
F
(
'
MCA 45 - 65 - 90 - 115 3. Description
3.2 Main parts
1
2
3
4
5
6
7
8
9
10
11
12
13
3.3 DIEMATIC iSystem control panel
Flue gas discharge pipe / Air intake
Casing/air box
Heat exchanger (Central heating)
Outlet for measuring combustion gases
Ignition/ionization electrode
Mixer pipe
Combined venturi and gas valve unit
Air intake silencer
Instrument box
Siphon
Box for the control PCBs
Fan
Water flow pipe
3.3.1. Description of the keys
A
B
C
Temperature setting key (heating, DHW, swimming pool)
Operating mode selection key
DHW override key
D
28/08/12 - 300024828-001-01
Key to access the parameters reserved for the installer
10
Page 12
C002705-A
C002704-A
C002703-A
C002702-A
bar
r
STD
(
'
t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
p
b
AUTO
x
c
r
j
L
g
m
bar
STD
t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
p
b
AUTO
x
c
r
j
M
g
m
3. Description MCA 45 - 65 - 90 - 115
E
Keys on which the function varies as and when selections are made
F
Rotary setting button:
4 Turn the rotary button to scroll through the menus or
modify a value
4 Press the rotary button to access the selected menu
or confirm a value modification
3.3.2. Description of the display
Key functions
n
> ( '
?
f
STD
Access to the various menus
Used to scroll through the menus
Used to scroll through the parameters
The symbol is displayed when help is available
Used to display the curve of the parameter selected
Reset of the time programmes
b
Selection of comfort mode or selection of the days to be programmed
v
Selection of reduced mode or deselection of the days to be programmed
j
ESC
Back to the previous level
Back to the previous level without saving the modifications made
t
Flame output level
n
Manual reset
The whole symbol flashes: The burner starts up but the flame is not yet present
Part of the symbol flashes: Output is increasing
Steady symbol: The required output has been reached
11
Part of the symbol flashes: Output is dropping
28/08/12 - 300024828-001-01
Page 13
L000200-A
L000201-A
L000198-A
L000199-A
bar
STD
t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
p
b
AUTO
x
c
r
j
M
g
m
bar
STD
t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
p
b
AUTO
x
c
r
j
M
g
m
bar
STD
t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
p
b
AUTO
x
c
r
j
M
g
m
MCA 45 - 65 - 90 - 115 3. Description
Solar (If connected)
n
u
The solar load pump is running
The top part of the tank is reheated to the tank set point
The entire tank is reheated to the tank set point
The entire tank is reheated to the solar tank set point
The tank is not loaded - Presence of the solar control system
Operating modes
n
p
Summer mode: The heating is off. Domestic hot water continues to be produced
b
WINTER mode: Heating and domestic hot water working
AUTO
x
m
g
m
Operation in automatic mode according to the timer programme
Comfort mode: The symbol is displayed when a DAY override (comfort) is activated
4 Flashing symbol: Temporary override
4 Steady symbol: Permanent override
Reduced mode: The symbol is displayed when a NIGHT override (reduced) is activated
4 Flashing symbol: Temporary override
4 Steady symbol: Permanent override
Holiday mode: The symbol is displayed when a HOLIDAY override (antifreeze) is activated
4 Flashing symbol: Holiday mode programmed
4 Steady symbol: Holiday mode active
Manual mode
28/08/12 - 300024828-001-01
12
Page 14
bar
STD
t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
p
b
AUTO
x
c
r
j
M
g
m
bar
STD
t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
p
b
AUTO
x
c
r
j
M
g
m
bar
STD
t
0 2 4 6 8 10 12 14 16 18 22 2420
C002699-B
p
b
AUTO
x
c
r
j
M
g
m
3. Description MCA 45 - 65 - 90 - 115
System pressure
n
bar
Pressure indicator: The symbol is displayed when a water pressure sensor is connected.
4 Flashing symbol: The water pressure is insufficient.
4 Steady symbol: The water pressure is sufficient.
l
Water pressure level
4 R : 0,9 to 1,1 bar 4 E : 1,2 to 1,5 bar 4 Z : 1,6 to 1,9 bar 4 A : 2,0 to 2,3 bar 4 l : > 2,4 bar
Domestic Hot Water override
n
A bar is displayed when a DHW override is activated:
4 Flashing bar: Temporary override
4 Steady bar: Permanent override
Other information
n
r
The symbol is displayed when domestic hot water production is running.
w
Valve indicator: The symbol is displayed when a 3-way valve is connected.
4 x : 3-way valve opens 4 c : 3-way valve closes
M
The symbol is displayed when the pump is operating.
Name of the circuit for which the parameters are displayed.
13
28/08/12 - 300024828-001-01
Page 15
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
L
g
m
#MEASURES
#CHOICE TIME PROG.
#TIME PROGRAM #SETTING #TIME .DAY
a
C002220-B-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
L
g
m
CURRENT PROG.B
CURRENT PROG.C
P2
P3
a
C002221-C-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
L
g
m
CURRENT PROG.C
"Choice of the timeprogram applied C"
P4
a
C002222-C-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
LUNDI 11:45
C002224-D-04
2x
MCA 45 - 65 - 90 - 115 3. Description
3.3.3. Browsing in the menus
1. To select the desired menu, turn the rotary button.
2. To access the menu, press the rotary button. To go back to the previous display, press the key j.
3. To select the desired parameter, turn the rotary button.
4. To modify the parameter, press the rotary button. To go back to the previous display, press the key j.
5. To modify the parameter, turn the rotary button.
6. To confirm, press the rotary button.
To cancel, press key
h
.
7. To go back to the main display, press key j2 times.
It is possible to use the ( and ' keys instead of the rotary button.
28/08/12 - 300024828-001-01
14
Page 16
-
)
L
m
r
r
ddd
T
y
1 2
SERVICE
°C°Fh barPsi % rpm kW uA x10 l/min
°CSt:
C002968-D
t
h
j
A B
E F
C D
-
)
L
m
r
r
ddd
T
y
1 2
SERVICE
°C°Fh barPsi % rpm kW uA x10 l/min
°CSt:
C003042-B
t
h
j
3. Description MCA 45 - 65 - 90 - 115
3.4 IniControl control panel
3.4.1. Description of the keys
15
A
B
C
D
E
F
3.4.2. Description of the display
Key functions
n
G
t d
[-]
Return button j, Escape G or Manual reset t Heating temperature button d or [-] DHW temperature button r or [+] S [Enter] Key ) [Chimney-sweeping] keys
Press keys A and B simultaneously f [Menu] keys
Press keys C and D simultaneously
Back to the previous level without saving the modifications made
Manual reset
Central heating function: Access to the max. heating temperature parameter.
To reduce a value
28/08/12 - 300024828-001-01
Page 17
-
)
L
m
rrr
d
d
d
T
y
1 2
SERVICE
°C°Fh barPsi % rpm kW uA x10 l/min
°CSt:
M002717-A
t
h
j
-
)
L
m
rrr
ddd
T
y
1 2
SERVICE
°C°Fh barPsi % rpm kW uA x10 l/min
°CSt:
M002718-A
t
h
j
-
)
L
m
r
r
ddd
T
y
1 2
SERVICE
°C°Fh barPsi % rpm kW uA x10 l/min
°CSt:
C003046-B
t
h
j
-
)
L
m
r
r
ddd
T
y
1 2
SERVICE
°C°Fh
barPsi
% rpm kW uA x10 l/min
°CSt:
C003047-C
t
h
j
MCA 45 - 65 - 90 - 115 3. Description
r
[+]
®
Operating modes
n
d
D
r
S
m
DHW function: Access to sanitary hot water temperature parameter.
To increase a value
Access the selected menu or confirm a value modification
State heating pump A
Heating programme deactivated: The heating function is deactivated
State DHW pump
DHW deactivated
Manual mode
Flame output level
n
e r t y
System pressure
n
bar
Low output level 0 - 25 %
Average output level 25 - 50 %
High output level 50 - 75 %
Output level 75 - 100 %
Pressure indicator: The symbol is displayed next to the installation's pressure value. If no water pressure sensor is connected, -.­appears on the display
28/08/12 - 300024828-001-01
16
Page 18
-
)
L
m
r
r
ddd
T
y
1 2
SERVICE
°C°Fh barPsi % rpm kW uA x10 l/min
°CSt:
C003048-B
t
h
j
3. Description MCA 45 - 65 - 90 - 115
Other information
n
"
!
)
-
K
\
a
I
M
a
User menu: Parameters at user level can be changed
Information menu: Reading the various current values
Chimney-sweeping position: Forced full or part load for CO2 measurement
Service menu: Parameters at installer level can be changed
Display with the symbols: $ + K + Z (Maintenance message)
Hour counter menu: Readout of the operating hours, number of successful starts and hours on mains supply
On/Off switch: After 5 lock-outs, the device must be switched off/on again
Outside temperature sensor present
The symbol is displayed when the boiler pump is operating
Defect: Boiler indicates a fault. This is signalled by a P or X code
and a flashing display
17
28/08/12 - 300024828-001-01
Page 19
C002366-B
Français - Deutsch - English ­Italiano - Espanol - Nederlands
- Pycck - Polski - Türk -
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
x
c
r
g
m
ÿ
LANGUE FRANCAIS
C002286-C
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
MCA 45 - 65 - 90 - 115 4. Operating the appliance - DIEMATIC iSystem
4 Operating the appliance - DIEMATIC
iSystem
4.1 Putting the appliance into operation
1. Check the water pressure in the installation shown on the control panel display.
If the water pressure is lower than 0,8 bar, more water should be added. If necessary, top up the water level in the heating system (recommended hydraulic pressure between 1,5 and 2,0 bar).
See chapter: "Filling the system", page 36
¼
2. Open the gas valve on the boiler.
3. Turn on the boiler using the on/off switch.
4.2 Reading out measured values
28/08/12 - 300024828-001-01
4. The first time the boiler is powered up, the LANGUAGE menu is displayed. Select the desired language by turning the rotary button.
5. To confirm, press the rotary button. The boiler will begin an automatic venting-programme (which lasts approx. 3 minutes) and will do this every time the power supply is isolated. If there is a problem, the error is displayed on the screen.
The various values measured by the appliance are displayed in the #MEASURES menu.
1. To access user level: Press the > key.
2. Select the menu #MEASURES.
4
Turn the rotary button to scroll through the menus or modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
For a detailed explanation of menu browsing, refer
¼
to the chapter: "Browsing in the menus", page 14.
18
Page 20
4. Operating the appliance - DIEMATIC iSystem MCA 45 - 65 - 90 - 115
User level - Menu #MEASURES
Parameter Description Unit
OUTSIDE TEMP.
ROOMTEMP. A
ROOMTEMP. B
ROOMTEMP. C
(1)
(1)
(1)
BOILER TEMP.
PRESSURE
WATER TEMP.
(1)
INST DWH TEMP.
STOR.TANK.TEMP
DCW TEMPERATURE
SWIMMING P.T.B
SWIMMING P.T.C
OUTLET TEMP. B
OUTLET TEMP. C
SYSTEM TEMP.
T.DHW BOTTOM
TEMP.TANK AUX
DHW A TEMP.
(1)
BACK TEMP
WIND SPEED
POWER
Outside temperature °C
Room temperature of circuit A °C
Room temperature of circuit B °C
Room temperature of circuit C °C
Water temperature in the boiler °C
Water pressure in the installation bar
Water temperature in the DHW tank °C
(1)
Instant hot water temperature °C
(1)
Water temperature in the storage tank °C
Domestic cold water temperature °C
(1)
Water temperature of the swimming pool on circuit B °C
(1)
Water temperature of the swimming pool on circuit C °C
(1)
Temperature of the flow water in circuit B °C
(1)
Temperature of the flow water in circuit C °C
(1)
Temperature of the system flow water if multi-generator °C
Water temperature in the bottom of the DHW tank °C
(1)
Water temperature in the second DHW tank connected to the AUX circuit °C
Water temperature in the second DHW tank connected to circuit A °C
Temperature of the boiler return water °C
Fan rotation speed rpm
Instantaneous boiler output (0%: Burner off or running at minimum output) %
CURRENT (µA) Ionization current µA
NB IMPULS.
Number of burner starts (not restartable) The meter is incremented by 8 every 8 start-ups
RUNTIME
Number of burner operation hours (not restartable)
h
The meter is incremented by 2 every 2 hours
IN 0-10V
(1)
SEQUENCE
CTRL
(1) The parameter is only displayed for the options, circuits or sensors actually connected.
Voltage at input 0-10 V V
Control system sequence
Software control number
19
28/08/12 - 300024828-001-01
Page 21
MODE
C002266-A
MCA 45 - 65 - 90 - 115 4. Operating the appliance - DIEMATIC iSystem
4.3 Changing the settings
4.3.1. Setting the set point temperatures
To set the various heating, DHW and swimming pool temperatures, proceed as follows:
1. Press the C key.
2. To select the desired parameter, turn the rotary button.
3. To modify the parameter, press the rotary button. To go back to the previous display, press the key j.
4. To modify the parameter, turn the rotary button.
5. To confirm, press the rotary button.
To cancel, press key
h
.
Menu C
Parameter Adjustment range Description Factory setting
DAY TEMP. A
NIGHT TEMP. A
DAY TEMP. B
(1)
NIGHT TEMP. B
DAY TEMP. C
(1)
NIGHT TEMP. C
WATER TEMP.
WATER T.NIGHT
(2)
TEMP.TANK AUX
AUX.TANK T.NIGHT
(1)(2)
DHW A TEMP.
A.TANK T.NIGHT
(2)
SWIMMING P.T.B
SWIMMING P.T.C
(1) The parameter is only displayed for the options, circuits or sensors actually connected. (2) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
5 to 30 °C Desired room temperature in comfort periods on circuit A 20 °C
5 to 30 °C Desired room temperature in reduced periods on circuit A 16 °C
5 to 30 °C Desired room temperature in comfort periods on circuit B 20 °C
(1)
5 to 30 °C Desired room temperature in reduced periods on circuit B 16 °C
5 to 30 °C Desired room temperature in comfort periods on circuit C 20 °C
(1)
5 to 30 °C Desired room temperature in reduced periods on circuit C 16 °C
(1)
10 to 80 °C Desired domestic hot water temperature in the DHW circuit 55 °C
(1)
10 to 80 °C Set tank temperature, night programme 10 °C
(1)
10 to 80 °C Desired domestic hot water temperature in the auxiliary circuit 55 °C
10 to 80 °C Set tank temperature, night programme 10 °C
(1)
10 to 80 °C Desired domestic hot water temperature in circuit A 55 °C
(1)
10 to 80 °C Set tank temperature, night programme 10 °C
(1)
5 to 39 °C Desired temperature for swimming pool B 20 °C
(1)
5 to 39 °C Desired temperature for swimming pool C 20 °C
28/08/12 - 300024828-001-01
20
Page 22
MODE
C002267-A
4. Operating the appliance - DIEMATIC iSystem MCA 45 - 65 - 90 - 115
4.3.2. Selecting the operating mode
To select an operating mode, proceed as follows:
1. Press the MODE key.
2. To select the desired parameter, turn the rotary button.
3. To modify the parameter, press the rotary button. To go back to the previous display, press the key j.
4. To modify the parameter, turn the rotary button.
5. To confirm, press the rotary button.
To cancel, press key h.
Menu MODE
Parameter Adjustment range Description Factory setting
AUTOMATIQUE
DAY
NIGHT
HOLIDAYS
SUMMER
MANUEL
FORCE AUTO
(1) The start and end days and the number of days are calculated in relation to each other. (2) The parameter is only displayed if a room sensor is connected.
7/7, xx:xx Comfort mode is forced until the time indicated or all the time (7/7). Present time + 1
7/7, xx:xx Reduced mode is forced until the time indicated or all the time
7/7, 1 to 365 The antifreeze mode is active on all boiler circuits.
(2)
YES / NO An operating mode override is activated on the remote control
The comfort ranges are determined by the timer programme.
(7/7).
Number of days' holiday: xx heating OFF: xx:xx Restarting: xx:xx
The heating is off. Domestic hot water continues to be produced.
The generator operates according to the set point setting. All of the pumps operate. Option of setting the set point by simply turning the rotary button.
(option). To force all circuits to run on AUTOMATIQUE mode, select
YES.
(1)
(1)
(1)
hour
Present time + 1 hour
Present date + 1 day
21
28/08/12 - 300024828-001-01
Page 23
MODE
C002268-A
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
MCA 45 - 65 - 90 - 115 4. Operating the appliance - DIEMATIC iSystem
4.3.3. Forcing domestic hot water production
To force domestic hot water production, proceed as follows:
1. Press the r key.
2. To select the desired parameter, turn the rotary button.
3. To modify the parameter, press the rotary button. To go back to the previous display, press the key j.
4. To modify the parameter, turn the rotary button.
5. To confirm, press the rotary button.
To cancel, press key h.
Menu r
Parameter Description Factory setting
AUTOMATIQUE
COMFORT
The domestic hot water comfort ranges are determined by the timer programme.
Domestic hot water comfort mode is forced until the time indicated or all the time (7/7). Present time + 1 hour
4.3.4. Setting the contrast and lighting on the
display
1. To access user level: Press the > key.
2. Select the menu #SETTING.
4
Turn the rotary button to scroll through the menus or modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
For a detailed explanation of menu browsing, refer
¼
to the chapter: "Browsing in the menus", page 14.
3. Set the following parameters:
User level - Menu #SETTING
Parameter Adjustment range Description Factory setting Customer setting
CONTRAST DISP.
BACK LIGHT COMFORT
ECO
Adjusting the display contrast.
The screen is illuminated continuously in daytime periods.
The screen is illuminated for 2 minutes whenever pressed.
ECO
28/08/12 - 300024828-001-01
22
Page 24
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
4. Operating the appliance - DIEMATIC iSystem
4.3.5. Setting the time and date
1. To access user level: Press the > key.
2. Select the menu #TIME .DAY.
4 Turn the rotary button to scroll through the menus or
modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
For a detailed explanation of menu browsing, refer
¼
to the chapter: "Browsing in the menus", page 14.
3. Set the following parameters:
MCA 45 - 65 - 90 - 115
User level - Menu #TIME .DAYHEURE / JOUR}
(1)
Parameter Adjustment range Description Factory setting Customer setting
HOURS
MINUTE
DAY
DATE
MONTH
YEAR
SUM. TIME: AUTO
0 to 23 Hours setting
0 to 59 Minutes setting
Monday to Sunday Setting the day of the week
1 to 31 Day setting
January to December Month setting
2008 to 2099 Year setting
automatic switch to summer time on the last Sunday
AUTO
in March and back to winter time on the last Sunday in October.
MANU
for countries where the time change is done on other dates or is not in use.
(1) According to the configuration
4.3.6. Selecting a timer programme
1. To access user level: Press the > key.
2. Select the menu #CHOICE TIME PROG..
23
4
Turn the rotary button to scroll through the menus or modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
For a detailed explanation of menu browsing, refer
¼
to the chapter: "Browsing in the menus", page 14.
3. To select the desired parameter.
4. Assign the desired timer programme (P1 to P4) to the circuit with the rotary button.
28/08/12 - 300024828-001-01
Page 25
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
L
g
m
PROG P2 C Mo Tu We Th Fr Sa Su "Display of the timeprogram. To continuepush on the button"
a
C002228-B-04
MCA 45 - 65 - 90 - 115
4. Operating the appliance - DIEMATIC iSystem
User level - Menu #CHOICE TIME PROG.
Parameter Adjustment range Description
CURRENT PROG.A
P1 / P2 / P3 / P4 Comfort programme activated
(Circuit A)
CURRENT PROG.B
P1 / P2 / P3 / P4 Comfort programme activated
(Circuit B)
CURRENT PROG.C
P1 / P2 / P3 / P4 Comfort programme activated
(Circuit C)
4.3.7. Customising a timer programme
1. To access user level: Press the > key.
2. Select the menu #TIME PROGRAM.
4 Turn the rotary button to scroll through the menus or
modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
For a detailed explanation of menu browsing, refer
¼
to the chapter: "Browsing in the menus", page 14.
3. To select the desired parameter.
User level - Menu #TIME PROGRAM
Parameter Time schedule Description
TIME PROG.A PROG P2 A
Timer programme for circuit A
PROG P3 A PROG P4 A
TIME PROG.B PROG P2 B
Timer programme for circuit B
PROG P3 B PROG P4 B
TIME PROG.C PROG P2 C
Timer programme for circuit C
PROG P3 C PROG P4 C
TIME PROG.DHW
TIME PROG.AUX
DHW circuit timer programme
Auxiliary circuit timer programme
4. To select a timer programme to be modified.
To select to days for which the timer programme is to be
5. modified: Turn the rotary button to the left until you reach the day desired. To confirm, press the rotary button.
28/08/12 - 300024828-001-01
24
Page 26
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
L
g
m
PROG P2 C Mo Tu
We Th Fr Sa Su
"Select the days to program"
a
C002229-C-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
L
g
m
PROG P2 C Mo Tu
We Th Fr Sa Su
Set the time program.
a
C002230-E-04
06:00
06:00
4. Operating the appliance - DIEMATIC iSystem MCA 45 - 65 - 90 - 115
6.b : Day selection Press key b / v until the symbol b is displayed. Turn the rotary button to the right to select the day(s) desired.
: Cancelling the day selection
v
Press key b / v until the symbol v is displayed. Turn the rotary button to the right to cancel selection of the relevant
day(s).
7. When the days desired for the programme have been selected, press the rotary button to confirm.
To define the timer ranges for the comfort mode and reduced
8. mode: Turn the rotary button to the left until 0:00 is displayed. The first segment of the graphic bar for the timer programme flashes.
9.b : Comfort mode selection Press key b / v until the symbol b is displayed. To select a comfort time range, turn the rotary button to the right.
: Reduced mode selection
v
Press key b / v until the symbol v is displayed. To select a reduced time range, turn the rotary button to the right.
10.When the times for the comfort mode have been selected, press the rotary button to confirm.
User level - Menu #TIME PROGRAM
TIME PROG.A
Day Comfort periods / Filling enabled:
Monday 6:00 to 22:00
Tuesday 6:00 to 22:00
Wednesday 6:00 to 22:00
Thursday 6:00 to 22:00
Friday 6:00 to 22:00
Saturday 6:00 to 22:00
Sunday 6:00 to 22:00
TIME PROG.B
Monday 6:00 to 22:00
Tuesday 6:00 to 22:00
Wednesday 6:00 to 22:00
Thursday 6:00 to 22:00
Friday 6:00 to 22:00
Saturday 6:00 to 22:00
Sunday 6:00 to 22:00
TIME PROG.C
Monday 6:00 to 22:00
Tuesday 6:00 to 22:00
Wednesday 6:00 to 22:00
Thursday 6:00 to 22:00
Friday 6:00 to 22:00
Saturday 6:00 to 22:00
Sunday 6:00 to 22:00
P1 _______________
P2 _______________ P3 _______________ P4 _______________
25
28/08/12 - 300024828-001-01
Page 27
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
MCA 45 - 65 - 90 - 115 4. Operating the appliance - DIEMATIC iSystem
User level - Menu #TIME PROGRAM
TIME PROG.DHW
TIME PROG.AUX
Day Comfort periods / Filling enabled:
P1
P2 _______________ P3 _______________ P4 _______________
_______________
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
4.3.8. Setting an annual clock
28/08/12 - 300024828-001-01
The annual clock is used to programme up to 10 heating stop periods over one year. The circuits selected for this stop are in Antifreeze mode during the period chosen.
1. To access user level: Press the > key.
2. Select the menu #ANNUAL PROG.
4
Turn the rotary button to scroll through the menus or modify a value.
4 Press the rotary button to access the selected menu
or confirm a value modification.
For a detailed explanation of menu browsing, refer
¼
to the chapter: "Browsing in the menus", page 14.
3. To select the desired parameter.
OFF
A
B
A+B
C
A+C
B+C
A+B+C
SU
A+E
B+E
A+B+W
C+E
No stop
circuit A
circuit B
circuit A, B
circuit C
circuit A, C
circuit B, C
circuit A, B, C
DHW circuit
circuit A and DHW
circuit B and DHW
circuit A, B and DHW
circuit C and DHW
26
Page 28
4. Operating the appliance - DIEMATIC iSystem MCA 45 - 65 - 90 - 115
A+C+W
B+C+W
ALL
circuit A, C and DHW
circuit B, C and DHW
circuit A, B, C and DHW
4. Set the start date and the end date of the shutdown selected.
5. To deactivate a shutdown, select the shutdown and set to OFF.
6. To select another shutdown, press the ' button.
Annual programme (Factory setting)
Stop no. Circuit concerned Start date End date
1
2
3
4
5
6
7
8
9
10
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
01-01 01-01
01-01 01-01
01-01 01-01
01-01 01-01
01-01 01-01
01-01 01-01
01-01 01-01
01-01 01-01
01-01 01-01
01-01 01-01
User level - Menu #ANNUAL PROG
STOP N 1:
STOP N 2:
STOP N 3:
BEG.DATE N 01
BEG.MONTH N 01
END DATE N 01
END MONTH N 01
BEG.DATE N 02
BEG.MONTH N 02
END DATE N 02
END MONTH N 02
BEG.DATE N 03
BEG.MONTH N 03
END DATE N 03
END MONTH N 03
For example: Customised programming
Stop no. Circuit concerned Start date End date
1
2
A+C
A+C
01-11 10-11
20-12 02-01
If setting STOP: OFF, the stop is deactivated and the start and end dates are not displayed.
Description Factory
setting
Selection of the circuit stopped
Setting start date of the stop 01 1-31
Setting start month of the stop 01 1-12
Setting end date of the stop 01 1-31
Setting end month of the stop 01 1-12
Selection of the circuit stopped
Setting start date of the stop 01 1-31
Setting start month of the stop 01 1-12
Setting end date of the stop 01 1-31
Setting end month of the stop 01 1-12
Selection of the circuit stopped
Setting start date of the stop 01 1-31
Setting start month of the stop 01 1-12
Setting end date of the stop 01 1-31
Setting end month of the stop 01 1-12
OFF
OFF
OFF
Adjustment range
OFF, A, B, A+B, C, A+C, B+C, A+B+C, SU, A+E, B+E, A+B+W, C+E, A+C+W, B +C+W, ALL
OFF, A, B, A+B, C, A+C, B+C, A+B+C, SU, A+E, B+E, A+B+W, C+E, A+C+W, B +C+W, ALL
OFF, A, B, A+B, C, A+C, B+C, A+B+C, SU, A+E, B+E, A+B+W, C+E, A+C+W, B +C+W, ALL
27
28/08/12 - 300024828-001-01
Page 29
MCA 45 - 65 - 90 - 115 4. Operating the appliance - DIEMATIC iSystem
User level - Menu #ANNUAL PROG
STOP N 4:
STOP N 5:
STOP N 6:
STOP N 7:
STOP N 8:
STOP N 9:
STOP N 10:
BEG.DATE N 04
BEG.MONTH N 04
END DATE N 04
END MONTH N 04
BEG.DATE N 05
BEG.MONTH N 05
END DATE N 05
END MONTH N 05
BEG.DATE N 06
BEG.MONTH N 06
END DATE N 06
END MONTH N 06
BEG.DATE N 07
BEG.MONTH N 07
END DATE N 07
END MONTH N 07
BEG.DATE N 08
BEG.MONTH N 08
END DATE N 08
END MONTH N 08
BEG.DATE N 09
BEG.MONTH N 09
END DATE N 09
END MONTH N 09
BEG.DATE N 10
BEG.MONTH N 10
END DATE N 10
END MONTH N 10
Description Factory
setting
Selection of the circuit stopped
Setting start date of the stop 01 1-31
Setting start month of the stop 01 1-12
Setting end date of the stop 01 1-31
Setting end month of the stop 01 1-12
Selection of the circuit stopped
Setting start date of the stop 01 1-31
Setting start month of the stop 01 1-12
Setting end date of the stop 01 1-31
Setting end month of the stop 01 1-12
Selection of the circuit stopped
Setting start date of the stop 01 1-31
Setting start month of the stop 01 1-12
Setting end date of the stop 01 1-31
Setting end month of the stop 01 1-12
Selection of the circuit stopped
Setting start date of the stop 01 1-31
Setting start month of the stop 01 1-12
Setting end date of the stop 01 1-31
Setting end month of the stop 01 1-12
Selection of the circuit stopped
Setting start date of the stop 01 1-31
Setting start month of the stop 01 1-12
Setting end date of the stop 01 1-31
Setting end month of the stop 01 1-12
Selection of the circuit stopped
Setting start date of the stop 01 1-31
Setting start month of the stop 01 1-12
Setting end date of the stop 01 1-31
Setting end month of the stop 01 1-12
Selection of the circuit stopped
Setting start date of the stop 01 1-31
Setting start month of the stop 01 1-12
Setting end date of the stop 01 1-31
Setting end month of the stop 01 1-12
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Adjustment range
OFF, A, B, A+B, C, A+C, B+C, A+B+C, SU, A+E, B+E, A+B+W, C+E, A+C+W, B +C+W, ALL
OFF, A, B, A+B, C, A+C, B+C, A+B+C, SU, A+E, B+E, A+B+W, C+E, A+C+W, B +C+W, ALL
OFF, A, B, A+B, C, A+C, B+C, A+B+C, SU, A+E, B+E, A+B+W, C+E, A+C+W, B +C+W, ALL
OFF, A, B, A+B, C, A+C, B+C, A+B+C, SU, A+E, B+E, A+B+W, C+E, A+C+W, B +C+W, ALL
OFF, A, B, A+B, C, A+C, B+C, A+B+C, SU, A+E, B+E, A+B+W, C+E, A+C+W, B +C+W, ALL
OFF, A, B, A+B, C, A+C, B+C, A+B+C, SU, A+E, B+E, A+B+W, C+E, A+C+W, B +C+W, ALL
OFF, A, B, A+B, C, A+C, B+C, A+B+C, SU, A+E, B+E, A+B+W, C+E, A+C+W, B +C+W, ALL
28/08/12 - 300024828-001-01
28
Page 30
4. Operating the appliance - DIEMATIC iSystem MCA 45 - 65 - 90 - 115
4.4 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance. If the central heating system is not used for a long period, we recommend activating the HOLIDAYS mode (to ensure the anti-grip of the heating pump).
4.5 Frost protection
CAUTION
4 The antifreeze protection does not function if the
appliance is switched off.
4 The integrated protection system only protects the
boiler, not the installation. To protect the installation, set the appliance to HOLIDAYS mode.
The HOLIDAYS mode protects:
4 The installation if the outside temperature is lower than 3°C
(factory setting).
4 The room temperature if a remote control is connected and the
room temperature is lower than 6 °C (factory setting).
4 The domestic hot water tank if the tank temperature is lower
than 4 °C (the water is reheated to 10 °C).
To configure the holidays mode: ¼ See chapter: "Selecting the operating mode", page 21.
29
28/08/12 - 300024828-001-01
Page 31
MCA 45 - 65 - 90 - 115
5. Operating the appliance - IniControl
5 Operating the appliance - IniControl
5.1 Putting the appliance into operation
1. Check the water pressure in the installation shown on the control panel display.
If the water pressure is lower than 0,8 bar, more water should be added. If necessary, top up the water level in the heating system (recommended hydraulic pressure between 1,5 and 2,0 bar).
See chapter: "Filling the system", page 36
¼
2. Open the gas valve on the boiler.
3. Switch on the boiler.
4. The start-up cycle begins and cannot be interrupted. During the start-up cycle, the display shows the following information:
fK[xx pK[xx
The version numbers are displayed alternately.
5. A vent cycle of a duration of around 3 minutes is carried out automatically.
6. In addition to 0, in STAND-BY the display normally shows the
water pressure and the symbols d,
: Software version
: Parameter version
5tH
and r.
5.2 Reading out measured values
The following current values can be read off the information menu Q:
4 5t = State. 4 5v = Sub-status. 4 t1 = Supply temperature (°C). 4 t" = Return temperature (°C). 4 t3 = Calorifier temperature (°C). 4 t4 = Outside temperature (°C). 4 t5 = Solar boiler temperature (°C). 4 5p = Internal set point (°C). 4 fl = Ionization current (µA). 4 Mf = Fan speed in rpm. 4 pr = Water pressure (bar). 4 p; = Supplied relative heat output (%).
28/08/12 - 300024828-001-01
30
Page 32
)
r
d
bar
C003049-A
t
h
j
h
j
4x
2x
5. Operating the appliance - IniControl MCA 45 - 65 - 90 - 115
The current values can be read as follows:
1. Press the two f keys simultaneously. The symbol Q flashes.
2. Confirm using key S.
is displayed, alternating with the
5t
current status 3 (for example).
3. Press the [+] key.
sub-status
(for example).
30
4. Press the [+] key.
flow temperature
is displayed, alternating with the current
5v
is displayed, alternating with the current
t1
°C (for example).
60
5. Press the [+] key successively to scroll down the various parameters.
t", t3, t4, t5
6. Press the [+] key.
set point
°C (for example).
88
7. Press the [+] key.
ionization current
8. Press the [+] key.
fan rotation speed
9. Press the [+] key.
water pressure
#0
is displayed, alternating with the internal
5p
is displayed, alternating with the current
fl
µA (for example).
70
is displayed, alternating with the current
Mf
3000
pr
rpm (for example).
is displayed, alternating with the current
bar (for example). If no water pressure sensor
.
is connected, [-.-] appears on the display.
10.Press the [+] key.
modulation percentage
11.Press the [+] key. The readout cycle starts again with
is displayed, alternating with the current
p;
% (for example).
78
5t
.
12.Press the j key 2 times to return to the current operating mode.
5.3 Changing the settings
Description Adjustment range Factory setting
Maximum outlet temperature 20 to 90 °C 80 80 80 80
Domestic hot water temperature: T
Heating / DHW mode Do not modify 1 1 1 1
ECO mode Do not modify 2 2 2 2
Anticipation resistance Do not modify 0 0 0 0
Parameter
p1 p2
p3 p4 p5
31
5.3.1. Parameter descriptions
SET
40 to 65 °C 60 60 60 60
MCA
45 65 90 115
28/08/12 - 300024828-001-01
Page 33
)
r
d
bar
C003050-A
t
h
j
h
j
1x
2x
MCA 45 - 65 - 90 - 115 5. Operating the appliance - IniControl
Parameter Description Adjustment range Factory setting
MCA
45 65 90 115
p6 p7
p8
Display screen Do not modify 2 2 2 2
Post-circulation of the boiler pump connected to the PCU 1 to 98 minutes
99 minutes = continuous
Brightness of display lighting Do not modify 1 1 1 1
3 3 3 3
5.3.2. Modification of the user-level parameters
Parameters p1 to p8 can be modified by the user in order to meet central heating and DHW comfort needs.
CAUTION
Modification of the factory settings may be detrimental to the functioning of the appliance.
1. Press the two keys f simultaneously and then key [+] until the symbol W flashes on the menu bar.
2. Select the users menu using the key S.
flashing.
1
3. Press the S key a second time. The value 80°C appears and flashes (for example).
4. Change the value by pressing the [-] or [+] key. In this example using key [-] to
5. Confirm the value with the S key.
60
°C.
p[1
flashing.
6. Press the j key 2 times to return to the current operating mode.
is displayed with
p[1
is displayed with
1
The parameters
4
same way as
p1
p2
to
are changed in the
p8
. After step 2, use the [+] key to
move to the required parameter.
4 The parameters
temperature) and
(the maximum heating water
p1
(the maximum drinking water
p2
temperature) can also be modified using the quick selection menu.
28/08/12 - 300024828-001-01
32
Page 34
)
m
r
d
bar
C003051-A
t
h
j
h
j
2x
2x
bar
d
C003052-A
1x
5. Operating the appliance - IniControl
MCA 45 - 65 - 90 - 115
5.3.3. Setting the manual mode
In some cases it may be necessary to switch the boiler to manual operation, For example, if the controller has not yet been connected. The boiler can be switched to automatic or manual operation under the symbol m. To do this, proceed as follows:
1. Press the two keys f simultaneously and then key [+] until the symbol m flashes on the menu bar.
2. Press the S key:
or
The text
sensor is connected). The flow temperature is determined by the internal heating curve.
or
The value of the minimum flow temperature.
3. Press the [-] or [+] key to increase this value temporarily in manual operation.
4. Confirm the value with the S key. The boiler is now set to manual operation.
5. Press the j key 2 times to return to the current operating mode.
with the current water pressure (only if an outside
Zv
5.3.4. Changing the heating temperature
If using an outside temperature sensor, the heating flow temperature is adjusted automatically.
In summer, it is possible to reduce the heating flow temperature whilst maintaining comfort. To do this, proceed as follows:
1. Press the d key 1 times.
2. The symbol d and the current temperature are displayed (the temperature flashes, e.g.
85
°C).
3. Change the value by pressing the [-] or [+] key. In this example using key [-] to
60
°C.
4. To confirm, press the S key.
It also possible to modify this setting using the parameter
.
p1
5.3.5. Modifying the domestic hot water
temperature setting
33
It may be that a lower domestic hot water temperature will be sufficient for your needs. Reduce this temperature and save energy. To do this, proceed as follows:
28/08/12 - 300024828-001-01
Page 35
C003053-A
r
1x
MCA 45 - 65 - 90 - 115 5. Operating the appliance - IniControl
1. Press the r key 1 times.
2. The symbol r and the current temperature are displayed (the temperature flashes, e.g.
60
°C).
3. Change the value by pressing the [-] or [+] key. In this example using key [-] to
55
°C.
4. To confirm, press the S key.
5.4 Installation shutdown
CAUTION
Do not switch off the boiler.
If the central heating system is not used for a long period, we recommend proceeeding as follows:
4 Press key d until OFF is displayed. 4 Press key r until OFF is displayed.
5.5 Frost protection
When the heating water temperature in the boiler is too low, the integrated boiler protection system starts up. This protection functions as follows:
4 If the water temperature is lower than 7°C, the heating pump starts
up.
4 If the water temperature is lower than 4°C, the boiler starts up.
4 If the water temperature is higher than 10°C, the boiler shuts down
and the circulation pump continues to run for a short time.
4 If the water temperature in the storage tank is less than 4°C, it is
reheated to its set point.
28/08/12 - 300024828-001-01
34
Page 36
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
TEMP. : 68°
PCU COM.FAIL D27
C002302-D-04
6. Checking and maintenance MCA 45 - 65 - 90 - 115
6 Checking and maintenance
6.1 General instructions
The boiler does not require a lot of maintenance. Nevertheless, we recommend having the boiler inspected and serviced at regular intervals.
4 Maintenance and cleaning of the boiler must be carried out at least
once a year by a qualified technician.
4 Have the flues swept at least once a year or more, depending on
the regulations in force in your country.
CAUTION
4 Maintenance operations must be done by a qualified
engineer.
4 We recommend taking out a maintenance contract.
4 Only original spare parts must be used.
4 Make certain that the flues and chimneys are
connected, in good condition and not blocked.
6.2 Periodic checks
6.1.1. DIEMATIC iSystem control panel
The boiler displays a message whenever maintenance is necessary.
1. When the message, REVISION, is displayed, press ? to display the installer's telephone number.
2. Contact the fitter.
3. Have the required checks and services done.
4 Check the water pressure in the installation.
If the water pressure is lower than 0,8 bar, more water should be added. If necessary, top up the water level in the heating system (recommended hydraulic pressure between 1,5 and 2,0 bar).
¼ See chapter: "Filling the system", page 36.
35
28/08/12 - 300024828-001-01
Page 37
T001507-B
1
2
3
4
T000181-B
1
2
3
4
T000181-B
T000182-A
T000185-A
MCA 45 - 65 - 90 - 115
6.3 Filling the system
6. Checking and maintenance
4 Carry out a visual check for the presence of any water leaks.
4 Open and close the radiator valves several times a year (this
prevents the valves from seizing up).
4 Clean the outside of the boiler using a damp cloth and a light
detergent.
CAUTION
Only a qualified professional is authorised to clean the inside of the boiler.
1. Check the water pressure in the installation shown on the control panel display.
If the water pressure is lower than 0,8 bar, more water should be added. If necessary, top up the water level in the heating system (recommended hydraulic pressure between 1,5 and 2,0 bar).
2. Open the valves on all radiators connected to the heating system.
3. Set the room thermostat to as low a temperature as possible.
4. Wait until the temperature drops below 40°C and the radiators seem cold before filling the central heating system.
28/08/12 - 300024828-001-01
36
Page 38
T000845-A
T000846-A
T000847-A
T000848-A
6. Checking and maintenance MCA 45 - 65 - 90 - 115
5. To fill with water, use a filling tube with two tap connections, a rag and a bleed key.
6. Connect the filling tube to a (cold) water tap.
7. Eliminate the air from the filling tube. Slowly fill the tube with water. Hold the end of the tube up, above a bucket. Turn off the tap as soon as water runs out of the pipe.
8. Unscrew the plug from the filling/draw-off valve.
The filling/draw-off valve is not necessarily located next to the boiler.
37
28/08/12 - 300024828-001-01
Page 39
T000849-A
T000850-A
T000853-A
MCA 45 - 65 - 90 - 115 6. Checking and maintenance
9. Attach the tube to the filling/draw-off valve. Firmly tighten the nut on the filling tube.
10.Open the filling/draw-off valve on the heating system.
11.Open the running water tap.
12.Check the water pressure in the installation shown on the control panel display.
13.Close the water tap when the water pressure reaches 2 bar.
14.Close the filling/draw-off valve on the heating system.Leave the tube on the filling/draw-off valve until the air is purged from the installation.
When water is added, air gets into the heating system. Degas the installation. After the air has been vented, the water pressure can drop below the required level. Check the water pressure in the installation shown on the control panel display. If the water pressure is lower than 0,8 bar, more water should be added.
15.After filling the installation, switch the boiler on.
Filling and bleeding the installation 2 times a year should be sufficient to obtain an adequate hydraulic pressure. If it is often necessary to top up the installation with water, contact your fitter.
28/08/12 - 300024828-001-01
38
Page 40
1
2
3
4
T000181-B
T000184-A
T000185-A
T000854-A
3
1
4
5
2
6. Checking and maintenance MCA 45 - 65 - 90 - 115
6.4 Bleeding the heating system
It is essential that you bleed any air in the calorifier, the conduits or the taps to prevent the annoying noises likely to be produced during heating or when tapping water. To do this, proceed as follows:
1. Open the valves on all radiators connected to the heating system.
2. Set the heating set point to as high a temperature as possible.
3. Wait until the radiators are hot.
4. Switch the boiler off.
5. Wait around 10 minutes until the radiators are cold.
6. Bleed the radiators. Start with the lower floors.
39
28/08/12 - 300024828-001-01
Page 41
T000217-A
T000218-A
MCA 45 - 65 - 90 - 115 6. Checking and maintenance
7. Open the bleed connection using the bleed key provided whilst keeping a rag pressed against the connection.
8. Wait until water comes out of the bleed valve and then close the bleed connection.
CAUTION
The water may still be hot.
9. Switch on the boiler. A vent cycle of a duration of around 3 minutes is carried out automatically.
10.After venting, check whether the pressure in the installation is still sufficient.
If the water pressure is lower than 0,8 bar, more water should be added. If necessary, top up the water level in the heating system (recommended hydraulic pressure between 1,5 and 2,0 bar).
See chapter: "Filling the system", page 36
¼
11.Set the heating set point.
28/08/12 - 300024828-001-01
40
Page 42
1
2
3
4
T000181-B
T000185-A
T000858-A
6. Checking and maintenance MCA 45 - 65 - 90 - 115
6.5 Draining the installation
It may become necessary to empty the water from the heating system when the radiators have to be replaced, should there be a major water leak or a risk of frost. To do this, proceed as follows:
1. Open the valves on all radiators connected to the heating system.
2. Switch off the boiler electrical power supply.
3. Wait around 10 minutes until the radiators are cold.
4. Connect an evacuation hose to the plug located at the lowest level. Place the end of the hose in a discharge sump or in a place where the water discharged from the valve can not do any damage.
5. Open the filling/draw-off valve on the heating system. Vent the heating installation.
WARNING
The water may still be hot.
6. When no more water comes out of the drainage plug, close the drainage valve.
41
28/08/12 - 300024828-001-01
Page 43
MCA 45 - 65 - 90 - 115 7. Troubleshooting
7 Troubleshooting
7.1 Anti-hunting
This display only concerns boilers with the DIEMATIC iSystem control panel.
When the boiler is in Anti-short-cycle operating mode, the symbol ? flashes.
1. Press the "?" key. The message Operation assured when the restart temperature will be reached is displayed.
This message is not an error message but an item of information.
7.2 Messages (Code type Bxx or Mxx)
In the case of failure, the control panel displays a message and a corresponding code.
1. Make a note of the code displayed. The code is important for the correct and rapid diagnosis of the type of failure and for any technical assistance that may be needed.
2. Switch the boiler off and switch back on. The boiler starts up again automatically when the reason for the blocking has been removed.
3. If the code is displayed again, correct the problem by following the instructions in the table below:
Depending on the control panel, the message display is different:
4 DIEMATIC iSystem control panel: The code and the
4 IniControl control panel: Only the code is displayed.
message are displayed.
28/08/12 - 300024828-001-01
42
Page 44
7. Troubleshooting MCA 45 - 65 - 90 - 115
Code Messages Description Checking / solution
B00 BL.CRC.PSU
The PSU PCB is incorrectly configured
Parameter error on the PSU PCB
4 Contact the professional who takes care of maintenance of
the appliance
B01 BL.MAX BOILER
B02 BL.HEATING
SPEED
Maximum flow temperature exceeded
The increase in flow temperature has exceeded its maximum limit
The water flow in the installation is insufficient
4 Check the circulation (direction, pump, valves)
The water flow in the installation is insufficient
4 Check the circulation (direction, pump, valves)
4 Check the water pressure
Sensor error
4 Contact the professional who takes care of maintenance of
the appliance
B07 BL.DT OUTL RET.
Maximum difference between the flow and return temperature exceeded
The water flow in the installation is insufficient
4 Check the circulation (direction, pump, valves)
4 Check the water pressure
Sensor error
4 Contact the professional who takes care of maintenance of
the appliance
B08 BL.RL OPEN
The RL inlet on the PCU PCB terminal block is open
Parameter error
4 Contact the professional who takes care of maintenance of
the appliance
Bad connection
B09 BL.INV. L/N
B10
BL.BL INPUT
B11
OPEN
B13 BL. PCU COM
BL.COM PCU-D4
B14 BL.WATER MIS.
B15 BL.GAS PRESS
B16
BL.BAD SU
4 Contact the professional who takes care of maintenance of
the appliance
4 Contact the professional who takes care of maintenance of the appliance
The BL inlet on the PCU PCB terminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care of maintenance of
the appliance
Parameter error
4 Contact the professional who takes care of maintenance of
the appliance
Bad connection
4 Contact the professional who takes care of maintenance of
the appliance
Communication error with the SCU PCB
Bad connection
4 Contact the professional who takes care of maintenance of
the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care of maintenance of
the appliance
The water pressure is lower than 0,8 bar
Not enough water in the circuit
4 Top up the installation with water
Gas pressure too low Incorrect setting of the gas pressure switch on the SCU PCB
4 Check that the gas valve is fully opened
4 Contact the professional who takes care of maintenance of
the appliance
The SU PCB is not recognised Wrong SU PCB for this boiler
B17 BL.PCU ERROR
43
The parameters saved on the PCU PCB are impaired
4 Contact the professional who takes care of maintenance of
the appliance
Parameter error on the PCU PCB
4 Contact the professional who takes care of maintenance of
the appliance
28/08/12 - 300024828-001-01
Page 45
MCA 45 - 65 - 90 - 115 7. Troubleshooting
Code Messages Description Checking / solution
B18 BL.BAD PSU
B19 BL.NO CONFIG
B21 BL. COM SU
B22 BL.FLAME LOS
B25
BL.SU ERROR
B26 BL.DHW. S.
B27 BL.DHW INST
M04 REVISION
The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care of maintenance of
the appliance
The boiler has not been configured
Communication error between the PCU and SU PCBs
No flame during operation No ionization current
Internal error on the SU PCB
The DHW tank sensor is disconnected or short circuited
The sensor on the plate exchanger outlet is disconnected or short circuited
A service is required The date programmed for the service has been reached
The PSU PCB has been changed
4 Contact the professional who takes care of maintenance of
the appliance
Bad connection
4 Contact the professional who takes care of maintenance of
the appliance
4 Check that the gas valve is fully opened
4 Contact the professional who takes care of maintenance of
the appliance
4 Contact the professional who takes care of maintenance of
the appliance
4 Contact the professional who takes care of maintenance of
the appliance
4 Contact the professional who takes care of maintenance of
the appliance
M05 REVISION A
M06
REVISION B
M07 REVISION C
M20 DISGAS
FL.DRY.B XX DAYS
FL.DRY.C XX DAYS
FL.DRY.B+C XX DAYS
M23 CHANGE OUTSI.S
STOP N XX
4 If the symbol ? flashes, press key ?. The installer's contact
details are displayed.
4 Contact the professional who takes care of maintenance of
the appliance
An A, B or C service is required The date programmed for the service has been reached
4 If the symbol ? flashes, press key ?. The installer's contact
details are displayed.
4 Contact the professional who takes care of maintenance of
the appliance
A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes Floor drying is active XX DAYS = Number of days' floor
drying remaining.
The outside temperature sensor is defective.
The shutdown is active XX = Number of the active shutdown
Floor drying is underway. Heating on the circuits not concerned is shut down.
4 Contact the professional who takes care of maintenance of
the appliance
Change the outside radio temperature sensor.
A shutdown is underway. The circuits selected for this stop are in Antifreeze mode during the period chosen.
28/08/12 - 300024828-001-01
44
Page 46
bar
1
1
2
2
r
c
STD
(
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
TEMP. : 68°
PCU. COM. FAIL. D27
C002604-B-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 18 22 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
TEMP. : 68°
PCU COM.FAIL D27
C002302-D-04
7. Troubleshooting
7.3 Faults (Code type Lxx or Dxx)
In the event of operational failure, the control panel flashes and displays an error message and a corresponding code.
7.3.1. DIEMATIC iSystem control panel
1. Make a note of the code displayed. The code is important for the correct and rapid diagnosis of the type of failure and for any technical assistance that may be needed.
2. Press the t key. If the code is displayed again, switch off the boiler and then switch it back on.
MCA 45 - 65 - 90 - 115
Depending on the control panel, the message display is different:
4 DIEMATIC iSystem control panel: The code and the
message are displayed.
4 IniControl control panel: Only the code is displayed.
3. Press the ? key. Follow the instructions displayed to solve the problem.
4. Consult the meaning of the codes in the table below:
7.3.2. IniControl control panel
1. Make a note of the code displayed. The code is important for the correct and rapid diagnosis of the type of failure and for any technical assistance that may be needed.
2. Press the t key. If the code is displayed again, switch off the boiler and then switch it back on.
7.3.3. List of faults
45
28/08/12 - 300024828-001-01
Page 47
MCA 45 - 65 - 90 - 115 7. Troubleshooting
Code Faults Cause
of the fault
L00 PSU FAIL
L01 PSU PARAM FAIL
L02 DEF.OUTLET S.
L03 DEF.OUTLET S.
L04 DEF.OUTLET S.
PCU PSU PCB not connected Bad connection
PCU The safety parameters are incorrect Bad connection
PCU The boiler flow sensor has short-
PCU The boiler flow sensor is on an open
PCU Boiler temp too low Bad connection
Description Checking / solution
PSU PCB faulty
4 Contact the professional who takes care of
maintenance of the appliance
PSU PCB faulty
4 Contact the professional who takes care of
maintenance of the appliance
Bad connection
circuited
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
Bad connection
circuit
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
No water circulation
L05 STB OUTLET
L06 BACK S.FAILURE
L07 BACK S.FAILURE
L08 BACK S.FAILURE
4 Vent the air in the heating system
4 Check the circulation (direction, pump,
valves)
4 Check the water pressure
PCU Boiler temperature too high Bad connection
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump,
valves)
4 Check the water pressure
PCU The return temperature sensor has
short-circuited
Bad connection Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
PCU The return temperature sensor is on
an open circuit
Bad connection Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
PCU Return temperature too low Bad connection
Sensor fault
28/08/12 - 300024828-001-01
4 Contact the professional who takes care of
maintenance of the appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump,
valves)
4 Check the water pressure
46
Page 48
7. Troubleshooting MCA 45 - 65 - 90 - 115
Code Faults Cause
of the fault
L09 STB BACK
L10 DEP-RET>MAX
L11 RET-DEP>MAX
PCU Return temperature too high Bad connection
PCU Difference between the flow and
PCU Difference between the flow and
Description Checking / solution
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump,
valves)
4 Check the water pressure
Bad connection
return temperatures insufficient
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump,
valves)
4 Check the water pressure
Bad connection
return temperatures too great
Sensor fault
L12 STB OPEN
L14 BURNER FAILURE
4 Contact the professional who takes care of
maintenance of the appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump,
valves)
4 Check the water pressure
PCU Maximum boiler temperature
exceeded (STB thermostat maximum)
Bad connection Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump,
valves)
4 Check the water pressure
PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care of
maintenance of the appliance
Ignition arc, but no flame formation
4 Check that the gas valve is fully opened
4 Contact the professional who takes care of
maintenance of the appliance
Presence of the flame but insufficient ionization (<3 µA)
47
4 Check that the gas valve is fully opened
4 Contact the professional who takes care of
maintenance of the appliance
28/08/12 - 300024828-001-01
Page 49
MCA 45 - 65 - 90 - 115 7. Troubleshooting
Code Faults Cause
of the fault
L16 PARASIT FLAME
L17 VALVE FAIL
L34 FAN FAILURE
L35 BACK>BOIL FAIL
PCU Detection of a parasite flame Ionization current present when there should not
PCU Problem on the gas valve Bad connection
PCU The fan is not running at the right
PCU Flow and return reversed Bad connection
Description Checking / solution
be a flame Ignition transformer defective Gas valve defective The burner remains very hot: CO2 too high
4 Contact the professional who takes care of
maintenance of the appliance
SU PCB faulty
4 Contact the professional who takes care of
maintenance of the appliance
Bad connection
speed
Fan defective
4 Contact the professional who takes care of
maintenance of the appliance
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
Water circulation direction reversed
L36 I-CURRENT FAIL
L37
SU COM.FAIL
L38 PCU COM.FAIL
L39 BL OPEN FAIL
L40 TEST.HRU.FAIL
L250 DEF.WATER MIS.
4 Check the circulation (direction, pump,
valves)
PCU The flame went out more than 5
times in 24 hours while the burner was operating
No ionization current
4 Check that the gas valve is fully opened
4 Contact the professional who takes care of
maintenance of the appliance
PCU Communication failure with the SU
PCB
Bad connection
4 Contact the professional who takes care of
maintenance of the appliance
PCU Communication failure between the
PCU and SCU PCBs
Bad connection SCU PCB not connected or faulty
4 Contact the professional who takes care of
maintenance of the appliance
PCU The BL inlet opened for a short time Bad connection
External cause Parameter incorrectly set
4 Contact the professional who takes care of
maintenance of the appliance
PCU HRU/URC unit test error Bad connection
External cause Parameter incorrectly set
4 Contact the professional who takes care of
maintenance of the appliance
PCU The water pressure is too low Hydraulic circuit incorrectly vented
Water leak Measurement error
L251
MANOMETRE FAIL
28/08/12 - 300024828-001-01
4 Top up with more water if necessary
4 Reset the boiler
PCU Fault on the water pressure sensor Wiring problem
The manometer is defective Sensor pcb defective
4 Contact the professional who takes care of
maintenance of the appliance
48
Page 50
7. Troubleshooting MCA 45 - 65 - 90 - 115
Code Faults Cause
of the fault
D03
OUTL S.B FAIL.
D04
OUTL S.C FAIL.
D05 OUTSI.S.FAIL.
D07 SYST.SENS.FAIL.
D09 DHW S.FAILURE
D11
ROOM S.A FAIL.
D12
ROOM S.B FAIL.
D13
ROOM S.C FAIL.
D14 MC COM.FAIL
SCU Circuit B flow sensor fault
SCU Outside temperature sensor fault
SCU System sensor fault Bad connection
SCU Domestic hot water sensor fault
SCU A room temperature sensor fault
SCU Communication failure between the
Description Checking / solution
Bad connection
Circuit C flow sensor fault Remarks:
The circuit pump is running. The 3-way valve motor on the circuit
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
is no longer powered and can be adjusted manually.
Bad connection
Remarks: The boiler operates on BOILER MAX temperature. The valve setting is no longer
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
ensured but monitoring the maximum temperature of the circuit after the valve is ensured. Valves may be manually operated. Reheating the domestic hot water remains ensured.
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
Bad connection
Remarks: Heating of domestic hot water is no longer ensured. The load pump operates.
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
The load temperature of the dhw tank is the same as the boiler.
Bad connection B room temperature sensor fault C room temperature sensor fault
Note: The circuit concerned operates
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
without any influence from the room sensor.
Bad connection SCU PCB and the boiler radio module
4 Check the link and the connectors
Boiler module failure
D15 ST.TANK S.FAIL
D16
SWIM.P.B. S.FAIL
D16
SWIM.P.C. S.FAIL
D17 DHW 2 S.FAIL
D27 PCU COM. FAIL
49
4 Change the boiler module
SCU Storage tank sensor fault
Note: The hot water storage tank reheating operation is no longer assured.
SCU Swimming pool sensor fault circuit B
Swimming pool sensor fault circuit C Note:
Pool reheating is independent of its temperature.
Bad connection
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
Bad connection
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
SCU Sensor fault tank 2 Bad connection
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the appliance
28/08/12 - 300024828-001-01
Page 51
MCA 45 - 65 - 90 - 115 7. Troubleshooting
Code Faults Cause
of the fault
D32 5 RESET:ON/OFF
D37
TA-S SHORT-CIR
D38 TA-S DISCONNEC
D99 DEF.BAD PCU
SCU 5 resets done in less than an hour
SCU The Titan Active System® is short-circuited
SCU The Titan Active System® is on an open circuit
SCU The SCU software version does not recognise the PCU connected
Description Checking / solution
4 Switch the boiler off and switch back on
4 If the boiler does not start after several resets (5 attempts possible), contact your
heating engineer and inform him of the error message displayed
4 Contact the professional who takes care of maintenance of the appliance
Remarks: Domestic hot water production has stopped but can nonetheless be restarted using key r. The tank is no longer protected. If a tank without Titan Active System® is connected to the boiler,check that the TAS simulation connector (delivered with package AD212) is fitted to the sensor card.
4 Contact the professional who takes care of maintenance of the appliance
Remarks: Domestic hot water production has stopped but can nonetheless be restarted using key r. The tank is no longer protected. If a tank without Titan Active System® is connected to the boiler,check that the TAS simulation connector (delivered with package AD212) is fitted to the sensor card.
4 Contact the professional who takes care of maintenance of the appliance
28/08/12 - 300024828-001-01
50
Page 52
8. Technical specifications MCA 45 - 65 - 90 - 115
8 Technical specifications
8.1 Technical specifications
Boiler type
General
Flow rate setting Adjustable
Nominal output (Pn) Heating System (80/60 °C)
Nominal output (Pn) Heating System (50/30 °C)
Data on the gases and combustion gases
Gas consumption G20 (Natural gas H) minimum-maximum
Gas consumption G31 (Propane) minimum-maximum
NOx-Emission per year (EN 483)
Mass flue gas flow rate minimum-maximum Kg/h 14 - 69 21 - 104 28 - 138 36 - 178
Flue gas temperature minimum-maximum °C 30 - 67 30 - 68 30 - 68 30 - 72
Maximum counter pressure
Characteristics of the heating circuit
Water content
Water operating pressure minimum kPa (bar) 80 (0,8) 80 (0,8) 80 (0,8) 80 (0,8)
Water operating pressure (PMS) maximum kPa (bar) 400 (4,0) 400 (4,0) 400 (4,0) 400 (4,0)
Water temperature maximum °C 110 110 110 110
Operating temperature maximum °C 90 90 90 90
Electrical characteristics
Power supply voltage
Power consumption - Full load maximum W 68 88 125 199
Power consumption - Part load maximum W 18 23 20 45
Power consumption - Standby maximum W 5 6 4 7
Electrical protection index
Other characteristics
Weight (empty) Total kg 53 60 67 68
Acoustic level at 1 metre
minimum-maximum kW 8,0 - 40,0 12,0 - 61,0 14,1 - 84,2 16,6 - 107,0
Factory setting kW 40,0 61,0 84,2 107,0
minimum-maximum kW 8,9 - 43,0 13,3 - 65,0 15,8 - 89,5 18,4 - 114,0
Factory setting kW 43,0 65,0 89,5 114,0
m3/h
m3/h
mg/kWh 37 32 45 46
Pa 150 100 160 220
l 5,5 6,5 7,5 7,5
V/Hz 230/50 230/50 230/50 230/50
IP X4D X4D X4D X4D
dBA 45 45 52 51
MCA 45 MCA 65 MCA 90 MCA 115
Modulating, Start/Stop, 0 - 10 V
0,9 - 4,4 1,3 - 6,6 1,5 - 9,1 1,8 - 11,7
0,3 - 1,7 0,5 - 2,5 0,6 - 3,5 0,6 - 4,7
51
28/08/12 - 300024828-001-01
Page 53
MCA 45 - 65 - 90 - 115
9 Energy savings
9.1 Energy-saving advice
9. Energy savings
4 Keep the room in which the boiler is installed well ventilated.
4 Do not block ventilation outlets.
4 Do not cover the radiators. Do not hang curtains in front of the
radiators.
4 Install reflective panels behind the radiators to prevent heat
losses.
4 Insulate the pipes in rooms that are not heated (cellars and lofts).
4 Close the radiators in rooms not in use.
4 Do not run hot (or cold) water pointlessly.
4 Install a water-saving shower head to save up to 40 % energy.
4 Take showers rather than baths. A bath consumes twice as much
water and energy.
9.2 Recommendations
The remote control is available in the following versions:
4 Wire
4 Radio
The setting of the control panel and/or of the remote control has a considerable influence on energy consumption.
A few tips:
4 In the room in which the room thermostat is installed, it's advised
not to use thermostatic valve radiators. If a thermostatic valve is used the valve must be fully opened.
4 Completely closing and opening thermostatic valve radiators
causes undesirable temperature fluctuations. Open and close thermostatic valves in small steps.
4 Lower the temperature to around 20°C. This reduces heating costs
and energy consumption.
4 Lower the temperature when you air the rooms.
4 When setting a time schedule , bear days when you are absent
and holidays in mind.
28/08/12 - 300024828-001-01
52
Page 54
10. Warranty
10 Warranty
10.1 General
10.2 Warranty terms
MCA 45 - 65 - 90 - 115
You have just purchased one of our appliances and we thank you for the trust you have placed in our products.
Please note that your appliance will provide good service for a longer period of time if it is regularly checked and maintained.
Your fitter and our customer support network are at your disposal at all times.
The following provisions are not exclusive of the buyer being able benefit from the legal provisions applicable regarding hidden defects in the buyer's country.
Starting from the purchase date shown on the original fitter's invoice, your appliance has a contractual guarantee against any manufacturing defect.
The length of the guarantee is mentioned in the price catalogue. The manufacturer is not liable for any improper use of the appliance or failure to maintain or install the unit correctly (the user shall take care to ensure that the system is installed by a qualified engineer).
In particular, the manufacturer shall not be held responsible for any damage, loss or injury caused by installations which do not comply with the following:
4 applicable local laws and regulations,
4 specific requirements relating to the installation, such as national
and/or local regulations,
4 the manufacturer's instructions, in particular those relating to the
regular maintenance of the unit,
4 the rules of the profession.
The warranty is limited to the exchange or repair of such parts as have been recognised to be faulty by our technical department and does not cover labour, travel and carriage costs.
The warranty shall not apply to the replacement or repair of parts damaged by normal wear and tear, negligence, repairs by unqualified parties, faulty or insufficient monitoring and maintenance, faulty power supply or the use of unsuitable fuel.
53
Sub-assemblies such as motors, pumps, electric valves etc. are guaranteed only if they have never been dismantled.
The legislation laid down by european directive 99/44/EEC, transposed by legislative decree No. 24 of 2 February 2002 published in O.J. No. 57 of 8 March 2002, continues to apply.
28/08/12 - 300024828-001-01
Page 55
MCA 45 - 65 - 90 - 115 10. Warranty
28/08/12 - 300024828-001-01
54
Page 56
© Copyright
300024828- 001- 01
DEDIETRICH THERMIQUE 57,ruedelaGareF-67580MERTZWILLER-BP 30
All technical and technological information contained in these technical instructions, as well as any drawings and technical descriptions supplied, remain our property and shall not be multiplied without our prior consent in writing.
28/08/12
Loading...