In these instructions, various danger levels are employed to draw the
user's attention to particular information. In so doing, we wish to
safeguard the user's safety, obviate hazards and guarantee correct
operation of the appliance.
DANGER
Risk of a dangerous situation causing serious physical
injury.
WARNING
Risk of a dangerous situation causing slight physical
injury.
1.2Abbreviations
CAUTION
Risk of material damage.
Signals important information.
¼ Signals a referral to other instructions or other pages in the
instructions.
4 3CE: Collective conduit for sealed boiler
4 DHW: Domestic hot water
4 Interscenario switch: Home automation switch that can be used
to centralise and control several scenarios
4 Hi: Lower heating value LHV (Nett)
4 Hs: Higher heating value HHV (Gross)
4 IOBL: Carrier current home automation bus
4 PPS: Polypropylene hardly inflammable
4 PCU: Primary Control Unit - PCB for managing burner operation
4 PSU: Parameter Storage Unit - Parameter storage for PCBs
PCU and SU
4 SCU: Secondary Control Unit - control panel PCB
4 SU: Safety Unit - Safety PCB
4 3WV: 3-way valve
31/08/2011 - 300024163-001-B
4
1. Introduction
1.3General
MCA 25/28 BIC
1.3.1.Manufacturer's liability
Our products are manufactured in compliance with the requirements
of the various applicable European Directives. They are therefore
delivered with [ marking and all relevant documentation.
In the interest of customers, we are continuously endeavouring to
make improvements in product quality. All the specifications stated in
this document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the following
cases:
4 Failure to abide by the instructions on using the appliance.
4 Faulty or insufficient maintenance of the appliance.
4 Failure to abide by the instructions on installing the appliance.
1.3.2.Installer's liability
The installer is responsible for the installation and inital start up of the
appliance. The installer must respect the following instructions:
4 Read and follow the instructions given in the manuals provided
with the appliance.
4 Carry out installation in compliance with the prevailing legislation
and standards.
4 Perform the initial start up and carry out any checks necessary.
4 Explain the installation to the user.
4 If a maintenance is necessary, warn the user of the obligation to
check the appliance and maintain it in good working order.
4 Give all the instruction manuals to the user.
1.3.3.User's liability
To guarantee optimum operation of the appliance, the user must
respect the following instructions:
4 Read and follow the instructions given in the manuals provided
with the appliance.
4 Call on qualified professionals to carry out installation and initial
start up.
4 Get your fitter to explain your installation to you.
4 Have the required checks and services done.
4 Keep the instruction manuals in good condition close to the
appliance.
5
31/08/2011 - 300024163-001-B
MCA 25/28 BIC1. Introduction
This appliance is not intended to be used by persons (including
children) whose physcial, sensory or mental capacity is impaired or
persons with no experience or knowledge, unless they have the
benefit, through the intermediary of a person responsible for their
safety, of supervision or prior instructions regarding use of the
appliance. Care should be taken to ensure that children do not play
with the appliance.
1.4Certifications
CE identification no
NOx classification
Type of connection Chimney: B23 , B
PIN 0063BT3444
5 (EN 297 pr A3, EN 656)
Flue gas outlet: C13 , C33, C43, C53, C63, C83 , C
33
93
31/08/2011 - 300024163-001-B
6
2. Safety instructions and recommendationsMCA 25/28 BIC
2Safety instructions and
recommendations
2.1Safety instructions
DANGER
If you smell gas:
1.Do not use a naked flame, do not smoke, do not
operate electrical contacts or switches ( doorbell,
light, motor, lift, etc..).
2.Shut off the gas supply.
3.Open the windows.
4.Evacuate the premises.
5.Call your fitter.
DANGER
If you smell flue gases:
1.Switch the appliance off.
2.Open the windows.
3.Evacuate the premises.
4.Call your fitter.
WARNING
Depending on the settings of the appliance:
4The temperature of the flue gas conduits may exceed
60°C.
4The temperature of the radiators may reach 85°C.
4The temperature of the domestic hot water may reach
65°C.
CAUTION
Do not neglect to service the appliance:
4For completely safe and optimum operation, you
must have your boiler regularly serviced by an
approved installer.
7
31/08/2011 - 300024163-001-B
MCA 25/28 BIC2. Safety instructions and recommendations
2.2Recommendations
WARNING
Only qualified professionals are authorised to work on the
appliance and the installation.
4 Regularly check the water pressure in the installation (minimum
pressure 0,8 bar, recommended pressure between 1,5 and 2,0
bar).
4 Keep the appliance accessible at all times.
4 Never remove or cover labels and rating plates affixed to the
appliance. Labels and rating plates must be legible throughout the
entire lifetime of the appliance.
4 The appliance should be on Summer or Antrifreeze mode rather
than switched off to guarantee the following functions:
- Anti blocking of pumps
- Frost protection
31/08/2011 - 300024163-001-B
8
3. Description
3Description
3.1Operating principle
MCA 25/28 BIC
3.1.1.Gas/air setting
The casing fitted to the boiler is also used as an air box. Air is sucked
in by the fan and gas injected into the venturi by the fan intake. The
fan rotation speed is set according to the settings parameters, the
thermal energy requirement and the temperatures measured by the
temperature sensors. The gas and air are mixed in the venturi. The
gas/air ratio ensures that the quantities of gas and air are adjusted to
each other. This provides optimum combustion on the entire output
range. The gas/air mixture is fed into the burner on top of the
exchanger.
3.1.2.Combustion
The burner heats the heating water circulating in the heat
exchanger. At a return temperature lower than around 55°C, the flue
gases cool down to a temperature lower than the dew point, thus
causing the condensation of the water vapour contained in the flue
gases in the back side of the heat exchanger. The heat released
during this condensation process (the latent heat or condensing heat)
is also transferred to the heating water. The cooled combustion gases
are evacuated via the combustion gas outlet flue. The condensation
water is evacuated via a siphon.
3.1.3.Heating and domestic hot water production
An integrated plate exchanger handles domestic hot water
production. A 3-way valve determines whether the heated water is
fed into the heating system or the plate exchanger. A DHW sensor
signals domestic hot water demands. This signal is transmitted to the
control panel, which then switches the 3-way valve to the hot water
position and trips the heating pump. The 3-way valve is spring-loaded
but only consumes electricity when it switches to another position.
The heating water reheats the domestic water in the plate
exchanger. This water is pumped into the boiler tank to provide a
constant plentiful supply of domestic hot water. In comfort mode, if no
domestic hot water is drawn off, the boiler reheats the plate exchanger
and the boiler tank at regular intervals. Any limescale particles are
kept out of the plate exchanger by a self-cleaning water filter (selfcleans once every 76 hours).
9
31/08/2011 - 300024163-001-B
T001961-D
2
19
18
17
16
15
20
21
22
23
24
25
26
3
4
5
6
7
8
9
10
11
12
1
14 13
27
MCA 25/28 BIC3. Description
3.2Main parts
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Flue gas discharge pipe
Casing/air box
Flue gas measuring point
Mixer pipe
Heating flow hose
Air intake silencer
Box for the control PCBs
Combined venturi and gas valve unit
Flow end hydrobloc
Safety valve outlet pipe
Siphon
Control panel
Tank drainage valve
Expansion vessel (DHW circuit)
Tank hydrobloc
Shunt pump (DHW circuit)
Shunt pump (Heating circuit)
18
19
20
21
22
23
24
25
26
27
Return end hydrobloc
Plate heat exchanger (DHW circuit)
3-way valve
Condensate receiver tank
Fan
Heat exchanger (Heating circuit)
Calorifier tank
Ignition/ionization electrode
Expansion vessel (Heating circuit)
Air intake
31/08/2011 - 300024163-001-B
10
A000866-A
bar
STD
t
02468 10 12 14 16 1822 2420
p
b
AUTO
x
c
r
j
M
g
m
A
B
C
D
E
F
(
'
3. DescriptionMCA 25/28 BIC
3.3Control panel
3.3.1.Description of the keys
A
B
C
D
E
F
Temperature setting key (heating, DHW, swimming pool)
Operating mode selection key
DHW override key
Key to access the parameters reserved for the installer
Keys on which the function varies as and when selections
are made
Rotary setting button:
4Turn the rotary button to scroll through the menus or
modify a value
4Press the rotary button to access the menu selected
or confirm a value modification
11
31/08/2011 - 300024163-001-B
C002705-A
C002704-A
C002703-A
C002702-A
bar
r
STD
(
'
t
0 2 4 6 8 10 12 14 16 1822 2420
C002696-A
p
b
AUTO
x
c
r
j
L
g
m
bar
STD
t
0 2 4 6 8 10 12 14 16 1822 2420
C002701-B
p
b
AUTO
x
c
r
j
M
g
m
MCA 25/28 BIC3. Description
3.3.2.Description of the display
Key functions
n
>
(
'
?
f
STD
b
Access to the various menus
Used to scroll through the menus
Used to scroll through the parameters
The symbol is displayed when help is available
Used to display the curve of the parameter selected
Reset of the time programmes
Selection of comfort mode or selection of the days to be
programmed
v
Selection of reduced mode or deselection of the days to
be programmed
j
ESC
Back to the previous level
Back to the previous level without saving the
modifications made
t
Flame output level
n
Manual reset
The whole symbol flashes: The burner starts up but the
flame is not yet present
Part of the symbol flashes: Output is increasing
Steady symbol: The required output has been reached
Part of the symbol flashes: Output is dropping
31/08/2011 - 300024163-001-B
12
bar
STD
t
0 2 4 6 8 10 12 14 16 1822 2420
C002697-B
p
b
AUTO
x
c
r
j
M
g
m
bar
STD
t
0 2 4 6 8 10 12 14 16 1822 2420
C002698-B
p
b
AUTO
x
c
r
j
M
g
m
bar
STD
t
0 2 4 6 8 10 12 14 16 1822 2420
C002708-A
p
b
AUTO
x
c
r
j
M
g
m
3. DescriptionMCA 25/28 BIC
Operating modes
n
p
b
AUTO
x
m
g
Summer mode: The heating is off. Domestic hot water
continues to be produced
WINTER mode: Heating and domestic hot water working
Operation in automatic mode according to the timer
programme
Comfort mode: The symbol is displayed when a DAY
override (comfort) is activated
4Flashing symbol: Temporary override
4Steady symbol: Permanent override
Reduced mode: The symbol is displayed when a NIGHT
override (reduced) is activated
4Flashing symbol: Temporary override
4Steady symbol: Permanent override
Holiday mode: The symbol is displayed when a HOLIDAY
override (antifreeze) is activated
4Flashing symbol: Holiday mode programmed
4Steady symbol: Holiday mode active
m
System pressure
n
bar
Manual mode
Pressure indicator: The symbol is displayed when a water
pressure sensor is connected.
4Flashing symbol: The quantity of water is insufficient.
4Steady symbol: The quantity of water is sufficient.
l
Water pressure level
4R : 0,9 to 1,1 bar
4E : 1,2 to 1,5 bar
4Z : 1,6 to 1,9 bar
4A : 2,0 to 2,3 bar
4l : > 2,4 bar
13
31/08/2011 - 300024163-001-B
bar
STD
t
0 2 4 6 8 10 12 14 16 1822 2420
C002707-A
p
b
AUTO
x
c
r
j
M
g
m
bar
STD
t
0 2 4 6 8 10 12 14 16 1822 2420
C002699-B
p
b
AUTO
x
c
r
j
M
g
m
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 1822 2420
p
b
AUTO
x
c
r
j
L
g
m
#MEASURES
#CHOICE TIME PROG.
#TIME PROGRAM
#SETTING
#TIME .DAY
a
C002220-B-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 1822 2420
p
b
AUTO
x
c
r
j
L
g
m
CURRENT PROG.B
CURRENT PROG.C
P2
P3
a
C002221-C-04
MCA 25/28 BIC
Domestic Hot Water override
n
A bar is displayed when a DHW override is activated:
4Flashing bar: Temporary override
4Steady bar: Permanent override
Other information
n
3. Description
r
The symbol is displayed when domestic hot water
production is running.
w
Valve indicator: The symbol is displayed when a 3-way
valve is connected.
4x : 3-way valve opens
4c : 3-way valve closes
M
The symbol is displayed when the pump is operating.
Name of the circuit for which the parameters are
displayed.
3.3.3.Browsing in the menus
1. To select the desired menu, turn the rotary button.
2. To access the menu, press the rotary button.
To go back to the previous display, press the key j.
31/08/2011 - 300024163-001-B
3. To select the desired parameter, turn the rotary button.
4. To modify the parameter, press the rotary button.
To go back to the previous display, press the key j.
14
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 1822 2420
p
b
AUTO
x
c
r
j
L
g
m
CURRENT PROG.C
"Choice of the timeprogram
applied C"
P4
a
C002222-C-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 1618222420
p
b
AUTO
x
c
r
j
M
g
m
LUNDI11:45
C002224-D-04
2x
3. DescriptionMCA 25/28 BIC
5. To modify the parameter, turn the rotary button.
6. To confirm, press the rotary button.
To cancel, press key h.
7. To go back to the main display, press key j2 times.
It is possible to use the ( and ' keys instead of the rotary
button.
15
31/08/2011 - 300024163-001-B
C002366-B
Français - Deutsch - English Italiano - Espanol - Nederlands
- Pycck - Polski - Türk -
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 1822 2420
p
b
x
c
r
g
m
ÿ
LANGUEFRANCAIS
C002286-C
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 1822 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
MCA 25/28 BIC4. Operating the boiler
4Operating the boiler
4.1Commissioning the boiler
1. Check the water pressure in the installation shown on the control
panel display.
If the water pressure is lower than 0,8 bar, more water
should be added. If necessary, top up the water level in the
heating system (recommended hydraulic pressure
between 1,5 and 2,0 bar).
See chapter: "Filling the system", page 27
¼
2. Open the gas valve on the boiler.
3. Turn on the boiler using the on/off switch.
4.2Reading out measured values
31/08/2011 - 300024163-001-B
4. The first time the boiler is powered up, the #LANGUAGE menu is
displayed. Select the desired language by turning the rotary
button.
5. To confirm, press the rotary button.
The boiler will begin an automatic venting-programme (which lasts
approx. 3 minutes) and will do this every time the power supply is
isolated. If there is a problem, the error is displayed on the screen.
The various values measured by the appliance are displayed in the
#MEASURES menu.
1. To access user level: Press the > key.
2. Select the menu #MEASURES.
4
Turn the rotary button to scroll through the menus or
modify a value.
4Press the rotary button to access the menu selected
or confirm a value modification.
For a detailed explanation of menu browsing, refer
¼
to the chapter: "Browsing in the menus", page 14.
16
4. Operating the boilerMCA 25/28 BIC
User level - #MEASURES menu
ParameterDescriptionUnit
OUTSIDE TEMP.
ROOMTEMP. A
ROOMTEMP. B
ROOMTEMP. C
(1)
(1)
(1)
BOILER TEMP.
PRESSURE
WATER TEMP.
(1)
INST DWH TEMP.
STOR.TANK.TEMP
DCW TEMPERATURE
SWIMMING P.T.B
SWIMMING P.T.C
OUTLET TEMP. B
OUTLET TEMP. C
SYSTEM TEMP.
T.DHW BOTTOM
TEMP.TANK AUX
DHW A TEMP.
(1)
Outside temperature°C
Room temperature of circuit A°C
Room temperature of circuit B°C
Room temperature of circuit C°C
Water temperature in the boiler°C
Water pressure in the installationbar
Water temperature in the DHW tank°C
(1)
Instant hot water temperature°C
(1)
Water temperature in the storage tank°C
Domestic cold water temperature°C
(1)
Water temperature of the swimming pool on circuit B°C
(1)
Water temperature of the swimming pool on circuit C°C
(1)
Temperature of the flow water in circuit B°C
(1)
Temperature of the flow water in circuit C°C
(1)
Temperature of the system flow water if multi-generator°C
(1)
Water temperature in the bottom of the DHW tank°C
(1)
Water temperature in the second DHW tank connected to the AUX circuit°C
Water temperature in the second DHW tank connected to circuit A°C
BACK TEMPTemperature of the boiler return water°C
WIND SPEEDFan rotation speedrpm
POWERInstantaneous boiler output (0%: Burner off or running at minimum output) %
CURRENT (µA)Ionization currentµA
NB IMPULS.Number of burner start-ups (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIMENumber of burner operation hours (not restartable)
h
The meter is incremented by 2 every 2 hours
IN 0-10V
(1)
SEQUENCE
CTRLSoftware control number
(1) The parameter is only displayed for the options, circuits or sensors actually connected.
Voltage at input 0-10 VV
Control system sequence
17
31/08/2011 - 300024163-001-B
MODE
C002266-A
MCA 25/28 BIC4. Operating the boiler
4.3Changing the settings
4.3.1.Setting the set point temperatures
To set the various heating, DHW and swimming pool temperatures,
proceed as follows:
1. Press the C key.
2. To select the desired parameter, turn the rotary button.
3. To modify the parameter, press the rotary button.
To go back to the previous display, press the key j.
4. To modify the parameter, turn the rotary button.
5. To confirm, press the rotary button.
To cancel, press key
h
.
Menu C
ParameterAdjustment range DescriptionFactory setting
DAY TEMP. A
NIGHT TEMP. A
DAY TEMP. B
NIGHT TEMP. B
(1)
DAY TEMP. C
NIGHT TEMP. C
(1)
WATER TEMP.
TEMP.TANK AUX
(1)
DHW A TEMP.
SWIMMING P.T.B
(1)
SWIMMING P.T.C
(1)
(1) The parameter is only displayed for the options, circuits or sensors actually connected.
5 to 30 °CDesired room temperature in comfort periods on circuit A20 °C
5 to 30 °CDesired room temperature in reduced periods on circuit A16 °C
(1)
5 to 30 °CDesired room temperature in comfort periods on circuit B20 °C
5 to 30 °CDesired room temperature in reduced periods on circuit B16 °C
(1)
5 to 30 °CDesired room temperature in comfort periods on circuit C20 °C
5 to 30 °CDesired room temperature in reduced periods on circuit C16 °C
(1)
40 to 65 °CDesired domestic hot water temperature in the DHW circuit55 °C
10 to 80 °CDesired domestic hot water temperature in the auxiliary circuit 55 °C
(1)
10 to 80 °CDesired domestic hot water temperature in circuit A55 °C
5 to 39 °CDesired temperature for swimming pool B20 °C
5 to 39 °CDesired temperature for swimming pool C20 °C
31/08/2011 - 300024163-001-B
18
MODE
C002267-A
4. Operating the boilerMCA 25/28 BIC
4.3.2.Selecting the operating mode
To select an operating mode, proceed as follows:
1. Press the MODE key.
2. To select the desired parameter, turn the rotary button.
3. To modify the parameter, press the rotary button.
To go back to the previous display, press the key j.
4. To modify the parameter, turn the rotary button.
5. To confirm, press the rotary button.
To cancel, press key h.
Menu MODE
ParameterAdjustment range DescriptionFactory setting
AUTOMATIQUE
DAY
NIGHT
HOLIDAYS
SUMMER
MANUEL
FORCE AUTO
(1) The start and end days and the number of days are calculated in relation to each other.
7/7, xx:xxComfort mode is forced until the time indicated or all the time (7/7).Present time + 1
7/7, xx:xxReduced mode is forced until the time indicated or all the time (7/7). Present time + 1
7/7, 1 to 365The antifreeze mode is active on all boiler circuits.
YES / NOAn operating mode override is activated on the remote control
The comfort ranges are determined by the timer programme.
Number of days' holiday: xx
heating OFF: xx:xx
Restarting: xx:xx
The heating is off.
Domestic hot water continues to be produced.
The generator operates according to the set point setting. All of the
pumps operate. Option of setting the set point by simply turning the
rotary button.
(option).
To force all circuits to run on AUTOMATIQUE mode, select YES.
(1)
(1)
(1)
hour
hour
Present date + 1
day
19
31/08/2011 - 300024163-001-B
MODE
C002268-A
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 1822 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
MCA 25/28 BIC4. Operating the boiler
4.3.3.Forcing domestic hot water production
To force domestic hot water production, proceed as follows:
1. Press the r key.
2. To select the desired parameter, turn the rotary button.
3. To modify the parameter, press the rotary button.
To go back to the previous display, press the key j.
4. To modify the parameter, turn the rotary button.
5. To confirm, press the rotary button.
To cancel, press key h.
Menu r
ParameterDescriptionFactory setting
AUTOMATIQUE
COMFORT
The domestic hot water comfort ranges are determined by the timer programme.
Domestic hot water comfort mode is forced until the time indicated or all the time (7/7). Present time + 1 hour
4.3.4.Setting the contrast and lighting on the
display
1. To access user level: Press the > key.
2. Select the menu #SETTING.
4
Turn the rotary button to scroll through the menus or
modify a value.
4Press the rotary button to access the menu selected
or confirm a value modification.
For a detailed explanation of menu browsing, refer
¼
to the chapter: "Browsing in the menus", page 14.
3. To set the following parameters:
User level - Menu #SETTING
ParameterAdjustment range DescriptionFactory setting Customer setting
CONTRAST DISP.
BACK LIGHTCOMFORT
ECO
Adjusting the display contrast.
The screen is illuminated continuously in
daytime periods.
The screen is illuminated for 2 minutes
whenever pressed.
ECO
31/08/2011 - 300024163-001-B
20
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 1822 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
bar
1
1
2
2
r
c
STD
(
'
t
v
0 2 4 6 8 10 12 14 16 1822 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
C002219-D-04
4. Operating the boilerMCA 25/28 BIC
4.3.5.Setting the time and date
1. To access user level: Press the > key.
2. Select the menu #TIME .DAY.
4Turn the rotary button to scroll through the menus or
modify a value.
4Press the rotary button to access the menu selected
or confirm a value modification.
For a detailed explanation of menu browsing, refer
Do not switch off the boiler. If the central heating system
is not used for a long period, we recommend activating the
HOLIDAYS mode.
When the heating water temperature in the boiler falls by too much,
the integrated protection system in the boiler starts up. This protection
functions as follows:
4 If the water temperature is lower than 7°C, the heating pump starts
up.
4 If the water temperature is lower than 4°C, the boiler starts up.
4 If the water temperature is higher than 10°C, the boiler shuts down
and the heating pump continues to run for a short time.
4 If the water temperature in the storage tank is less than 7°C, it is
reheated to its set point.
CAUTION
4The anitfreeze protection does not function if the
boiler is switched off.
4The integrated protection system only protects the
boiler, not the installation. To protect the installation,
set the appliance to HOLIDAYS mode.
The HOLIDAYS mode protects:
4 The installation if the outside temperature is lower than 3°C
(factory setting).
4 The room temperature if a remote control is connected and the
room temperature is lower than 6 °C (factory setting).
4 The domestic hot water tank if the tank temperature is lower
than 4 °C (the water is reheated to 10 °C).
31/08/2011 - 300024163-001-B
24
4. Operating the boilerMCA 25/28 BIC
To configure the holidays mode: ¼ See chapter: "Selecting the
operating mode", page 19.
25
31/08/2011 - 300024163-001-B
bar
1
1
2
2
r
c
STD
(
'
t
v
02 4 6 8 10 12 14 16 1822 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
TEMP.: 68°
PCUCOM.FAIL D27
C002302-D-04
T001507-B
MCA 25/28 BIC
5Checking and maintenance
5.1General instructions
The boiler does not require a lot of maintenance. Nevertheless, we
recommend having the boiler inspected and serviced at regular
intervals.
4 Maintenance and cleaning of the boiler must be carried out at least
once a year by a qualified technician.
4 Have the flues swept at least once a year or more, depending on
the regulations in force in your country.
CAUTION
4Maintenance operations must be done by a qualified
engineer.
4We recommend taking out a maintenance contract.
4Only original spare parts must be used.
5. Checking and maintenance
5.2Periodic checks
The boiler displays a message whenever maintenance is necessary.
1. When the message, REVISION, is displayed, press ? to display
the installer's telephone number.
2. Contact the fitter.
3. Have the required checks and services done.
4 Check the water pressure in the installation.
If the water pressure is lower than 0,8 bar, more water
should be added. If necessary, top up the water level in the
heating system (recommended hydraulic pressure
between 1,5 and 2,0 bar).
¼ See chapter: "Filling the system", page 27.
31/08/2011 - 300024163-001-B
4 Carry out a visual check for the presence of any water leaks.
26
1
2
3
4
T000181-B
1
2
3
4
T000181-B
T000185-A
T001620-A
5. Checking and maintenanceMCA 25/28 BIC
4 Open and close the radiator valves several times a year (this
prevents the valves from seizing up).
4 Clean the outside of the boiler using a damp cloth and a light
detergent.
CAUTION
Only a qualified professional is authorised to clean the
inside of the boiler.
5.3Filling the system
1. Check the water pressure in the installation shown on the control
panel display.
If the water pressure is lower than 0,8 bar, more water
should be added. If necessary, top up the water level in the
heating system (recommended hydraulic pressure
between 1,5 and 2,0 bar).
2. Open the valves on all radiators connected to the heating system.
3. Set the heating set point to as low a temperature as possible.
4. Wait until the temperature drops below 40°C and the radiators
seem cold before filling the central heating system.
5. Open the cold water inlet and heating outlet valves.
27
31/08/2011 - 300024163-001-B
T001618-A
1
2
T001619-A
2
1
2 bar
1
2
3
4
T000181-B
T000184-A
MCA 25/28 BIC
5. Checking and maintenance
6. Open the disconnector valves.
7. Close the disconnector valves when the manometer indicates a
pressure of 2 bar.
When water is added, air gets into the heating system.
Degas the installation. After the air has been vented, the
water pressure can drop below the required level. Check
the water pressure in the heating system. If the water
pressure is lower than 0,8 bar, more water should be
added.
8. After filling the installation, switch the boiler on.
5.4Bleeding the heating system
It is essential that you bleed any air in the calorifier, the conduits or
the taps to prevent the annoying noises likely to be produced during
heating or when tapping water. To do this, proceed as follows:
1. Open the valves on all radiators connected to the heating system.
2. Set the heating set point to as high a temperature as possible.
3. Wait until the radiators are hot.
Filling and bleeding the installation 2 times a year should
be sufficient to obtain an adequate hydraulic pressure. If it
is often necessary to top up the installation with water,
contact your fitter.
31/08/2011 - 300024163-001-B
4. Switch the boiler off.
28
T000185-A
T000854-A
3
1
4
5
2
T000217-A
5. Checking and maintenanceMCA 25/28 BIC
5. Wait around 10 minutes until the radiators are cold.
6. Bleed the radiators. Start with the lower floors.
7. Open the bleed connection using the bleed key provided whilst
keeping a rag pressed against the connection.
29
31/08/2011 - 300024163-001-B
T000218-A
1
2
3
4
T000181-B
T000185-A
MCA 25/28 BIC
5. Checking and maintenance
8. Wait until water comes out of the bleed valve and then close the
bleed connection.
CAUTION
The water may still be hot.
9. Switch on the boiler. A vent cycle of a duration of around 3 minutes
is carried out automatically.
10.After venting, check whether the pressure in the installation is still
sufficient.
If the water pressure is lower than 0,8 bar, more water
should be added. If necessary, top up the water level in the
heating system (recommended hydraulic pressure
between 1,5 and 2,0 bar).
See chapter: "Filling the system", page 27
¼
11.Set the heating set point.
5.5Draining the installation
It may become necessary to empty the water from the heating system
when the radiators have to be replaced, should there be a major water
leak or a risk of frost. To do this, proceed as follows:
1. Open the valves on all radiators connected to the heating system.
2. Switch off the boiler electrical power supply.
3. Wait around 10 minutes until the radiators are cold.
31/08/2011 - 300024163-001-B
30
T000858-A
5. Checking and maintenanceMCA 25/28 BIC
4. Connect an evacuation hose to the plug located at the lowest
level. Place the end of the hose in a discharge sump or in a place
where the water discharged from the valve can not do any
damage.
5. Open the filling/draw-off valve on the heating system. Vent the
heating installation.
WARNING
The water may still be hot.
6. When no more water comes out of the drainage plug, close the
drainage valve.
31
31/08/2011 - 300024163-001-B
MCA 25/28 BIC6. Troubleshooting
6Troubleshooting
6.1Anti-hunting
When the boiler is in Anti-short-cycle operating mode, the symbol ?
flashes.
1. Press the "?" key.
The message Operation assured when the restart temperaturewill be reached is displayed. When the restart temperature is
reached, operation will be guaranteed.
This message is not an error message but an item of
information.
6.2Messages (Code type Bxx or Mxx)
In the case of failure, the control panel displays a message and a
corresponding code.
1. Make a note of the code displayed.
The code is important for the correct and rapid diagnosis of the
type of failure and for any technical assistance that may be
needed.
2. Switch the boiler off and switch back on.
The boiler starts up again automatically when the reason for the
blocking has been removed.
3. If the code is displayed again, correct the problem by following the
instructions in the table below:
Code
MessagesDescriptionChecking / solution
B00BL.PSU ERROR
B01BL.MAX BOILER
B02BL.HEATING
SPEED
The PSU PCB is incorrectly
configured
Maximum flow temperature
exceeded
The increase in flow temperature
has exceeded its maximum limit
Parameter error on the PSU PCB
4Contact the professional who takes care of maintenance of
The water flow in the installation is insufficient
4Check the circulation (direction, pump, valves)
The water flow in the installation is insufficient
4Check the circulation (direction, pump, valves)
4Check the water pressure
Sensor error
the appliance
B07BL.DT OUTL RET.
31/08/2011 - 300024163-001-B
Maximum difference between the
flow and return temperature
exceeded
4Contact the professional who takes care of maintenance of
the appliance
The water flow in the installation is insufficient
4Check the circulation (direction, pump, valves)
4Check the water pressure
Sensor error
4Contact the professional who takes care of maintenance of
the appliance
32
6. TroubleshootingMCA 25/28 BIC
Code MessagesDescriptionChecking / solution
B08BL.RL OPEN
The RL inlet on the PCU PCB
terminal block is open
Parameter error
4Contact the professional who takes care of maintenance of
the appliance
Bad connection
4Contact the professional who takes care of maintenance of
the appliance
B09BL.INV. L/N
B10
BL.BL INPUT
B11
OPEN
4Contact the professional who takes care of maintenance of the appliance
The BL inlet on the PCU PCB
terminal block is open
The contact connected to the BL inlet is open
4Contact the professional who takes care of maintenance of
the appliance
Parameter error
4Contact the professional who takes care of maintenance of
the appliance
Bad connection
4Contact the professional who takes care of maintenance of
the appliance
B13BL. PCU COM
Communication error with the
SCU PCB
Bad connection
4Contact the professional who takes care of maintenance of
the appliance
SCU PCB not installed in the boiler
B14BL.WATER MIS.
B15BL.GAS PRESS
B16
BL.BAD SU
B17BL.PCU ERROR
B18BL.BAD PSU
B19BL.NO CONFIG
B21BL. COM SU
B22BL.FLAME LOS
4Contact the professional who takes care of maintenance of
the appliance
The water pressure is lower than
0,8 bar
Not enough water in the circuit
4Top up the installation with water
Gas pressure too lowIncorrect setting of the gas pressure switch on the SCU PCB
4Check that the gas valve is fully opened
4Contact the professional who takes care of maintenance of
the appliance
The SU PCB is not recognisedWrong SU PCB for this boiler
4Contact the professional who takes care of maintenance of
the appliance
The parameters saved on the
PCU PCB are impaired
Parameter error on the PCU PCB
4Contact the professional who takes care of maintenance of
the appliance
The PSU PCB is not recognisedWrong PSU PCB for this boiler
4Contact the professional who takes care of maintenance of
the appliance
The boiler has not been
configured
The PSU PCB has been changed
4Contact the professional who takes care of maintenance of
the appliance
Communication error between
the PCU and SU PCBs
Bad connection
4Contact the professional who takes care of maintenance of
the appliance
No flame during operationNo ionization current
B25
33
BL.SU ERROR
Internal error on the SU PCB
4Check that the gas valve is fully opened
4Contact the professional who takes care of maintenance of
the appliance
4Contact the professional who takes care of maintenance of
the appliance
31/08/2011 - 300024163-001-B
bar
1
1
2
2
r
c
STD
(
t
v
0 2 4 6 8 10 12 14 16 1822 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
TEMP. : 68°
PCU. COM. FAIL. D27
C002604-B-04
bar
1
1
2
2
r
c
STD
(
'
t
v
02 4 6 8 10 12 14 16 1822 2420
p
b
AUTO
x
c
r
j
M
g
m
SUNDAY 11:45
TEMP.: 68°
PCUCOM.FAIL D27
C002302-D-04
MCA 25/28 BIC
Code MessagesDescriptionChecking / solution
M04REVISION
A service is requiredThe date programmed for the service has been reached
4If the symbol ? flashes, press key ?. The installer's contact
details are displayed.
4Contact the professional who takes care of maintenance of
the appliance
M05REVISION A
M06
REVISION B
M07REVISION C
An A, B or C service is requiredThe date programmed for the service has been reached
4If the symbol ? flashes, press key ?. The installer's contact
details are displayed.
4Contact the professional who takes care of maintenance of
the appliance
M20DISGAS
A boiler vent cycle is underwaySwitching the boiler on
4Wait 3 minutes
FL.DRY.B XX
DAYS
FL.DRY.C XX
DAYS
Floor drying is active
XX DAYS = Number of days' floor
drying remaining.
Floor drying is underway. Heating on the circuits not concerned
is shut down.
4Contact the professional who takes care of maintenance of
the appliance
FL.DRY.B+C XX
DAYS
M23CHANGE OUTSI.S
The outside temperature sensor
Change the outside radio temperature sensor.
is defective.
STOP N XX
The shutdown is active
XX = Number of the active
A shutdown is underway. The circuits selected for this stop are
in Antifreeze mode during the period chosen.
shutdown
6. Troubleshooting
6.3Faults (Code type Lxx or Dxx)
In the event of operational failure, the control panel flashes and
displays an error message and a corresponding code.
1. Make a note of the code displayed.
The code is important for the correct and rapid diagnosis of the
type of failure and for any technical assistance that may be
needed.
2. Press the t key. If the code is displayed again, switch off the boiler
and then switch it back on.
3. Press the ? key. Follow the instructions displayed to solve the
problem.
4. Consult the meaning of the codes in the table below:
31/08/2011 - 300024163-001-B
34
6. TroubleshootingMCA 25/28 BIC
Code FaultsCause
of the
fault
L00PSU FAIL
L01PSU PARAM FAIL
L02DEF.OUTLET S.
L03DEF.OUTLET S.
L04DEF.OUTLET S.
PCUPSU PCB not connectedBad connection
PCUThe safety parameters are incorrect Bad connection
PCUThe boiler flow sensor has short-
PCUThe boiler flow sensor is on an open
PCUBoiler temp too lowBad connection
DescriptionChecking / solution
PSU PCB faulty
4Contact the professional who takes care of
maintenance of the appliance
PSU PCB faulty
4Contact the professional who takes care of
maintenance of the appliance
Bad connection
circuited
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
Bad connection
circuit
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
No water circulation
L05STB OUTLET
L06BACK S.FAILURE
L07BACK S.FAILURE
L08BACK S.FAILURE
4Vent the air in the heating system
4Check the circulation (direction, pump,
valves)
4Check the water pressure
PCUBoiler temperature too highBad connection
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump,
valves)
4Check the water pressure
PCUThe return temperature sensor has
short-circuited
Bad connection
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
PCUThe return temperature sensor is on
an open circuit
Bad connection
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
PCUReturn temperature too lowBad connection
Sensor fault
35
4Contact the professional who takes care of
maintenance of the appliance
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump,
valves)
4Check the water pressure
31/08/2011 - 300024163-001-B
MCA 25/28 BIC6. Troubleshooting
Code FaultsCause
of the
fault
L09STB BACK
L10DEP-RET<MIN
L11DEP-RET>MAX
PCUReturn temperature too highBad connection
PCUDifference between the flow and
PCUDifference between the flow and
DescriptionChecking / solution
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump,
valves)
4Check the water pressure
Bad connection
return temperatures insufficient
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump,
valves)
4Check the water pressure
Bad connection
return temperatures too great
Sensor fault
L12STB OPEN
L14BURNER FAILURE
4Contact the professional who takes care of
maintenance of the appliance
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump,
valves)
4Check the water pressure
PCUMaximum boiler temperature
exceeded (STB thermostat
maximum)
Bad connection
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
No water circulation
4Vent the air in the heating system
4Check the circulation (direction, pump,
valves)
4Check the water pressure
PCU5 burner start-up failuresNo ignition
4Contact the professional who takes care of
maintenance of the appliance
Presence of the ignition arc but no flame formation
4Check that the gas valve is fully opened
4Contact the professional who takes care of
maintenance of the appliance
Presence of the flame but insufficient ionization
(<3 µA)
31/08/2011 - 300024163-001-B
4Check that the gas valve is fully opened
4Contact the professional who takes care of
maintenance of the appliance
36
6. TroubleshootingMCA 25/28 BIC
Code FaultsCause
of the
fault
L16PARASIT FLAME
L17VALVE FAIL
L34FAN FAILURE
L35BACK>BOIL FAIL
PCUDetection of a parasite flameIonization current present when there should not
PCUProblem on the gas valveBad connection
PCUThe fan is not running at the right
PCUFlow and return reversedBad connection
DescriptionChecking / solution
be a flame
Ignition transformer defective
Gas valve defective
The burner remains very hot: CO2 too high
4Contact the professional who takes care of
maintenance of the appliance
SU PCB faulty
4Contact the professional who takes care of
maintenance of the appliance
Bad connection
speed
Fan defective
4Contact the professional who takes care of
maintenance of the appliance
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
Water circulation direction reversed
L36I-CURRENT FAIL
L37
SU COM.FAIL
L38PCU COM.FAIL
L39BL OPEN FAIL
L40TEST.HRU.FAIL
L250 DEF.WATER MIS.
4Check the circulation (direction, pump,
valves)
PCUThe flame went out more than 5
times in 24 hours while the burner
was operating
No ionization current
4Check that the gas valve is fully opened
4Contact the professional who takes care of
maintenance of the appliance
PCUCommunication failure with the SU
PCB
Bad connection
4Contact the professional who takes care of
maintenance of the appliance
PCUCommunication failure between the
PCU and SCU PCBs
Bad connection
SCU PCB not connected or faulty
4Contact the professional who takes care of
maintenance of the appliance
PCUThe BL inlet opened for a short time Bad connection
External cause
Parameter incorrectly set
4Contact the professional who takes care of
maintenance of the appliance
PCUHRU/URC unit test errorBad connection
External cause
Parameter incorrectly set
4Contact the professional who takes care of
maintenance of the appliance
PCUThe water pressure is too lowHydraulic circuit incorrectly vented
Water leak
Measurement error
L251
MANOMETRE FAIL
37
4Top up with more water if necessary
4Reset the boiler
PCUFault on the water pressure sensor Wiring problem
The manometer is defective
Sensor pcb defective
4Contact the professional who takes care of
maintenance of the appliance
31/08/2011 - 300024163-001-B
MCA 25/28 BIC6. Troubleshooting
Code FaultsCause
of the
fault
D03
OUTL S.B FAIL.
D04
OUTL S.C FAIL.
D05OUTSI.S.FAIL.
D07AUX.SENS.FAIL.
D09DHW S.FAILURE
D11
ROOM S.A FAIL.
D12
ROOM S.B FAIL.
D13
ROOM S.C FAIL.
D14MC COM.FAIL
SCUCircuit B flow sensor fault
SCUOutside temperature sensor fault
SCUAuxiliary sensor faultBad connection
SCUDomestic hot water sensor fault
SCUA room temperature sensor fault
SCUCommunication failure between the
DescriptionChecking / solution
Bad connection
Circuit C flow sensor fault
Remarks:
The circuit pump is running.
The 3-way valve motor on the circuit
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
is no longer powered and can be
adjusted manually.
Bad connection
Remarks:
The boiler operates on BOILERMAX temperature.
The valve setting is no longer
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
ensured but monitoring the
maximum temperature of the circuit
after the valve is ensured.
Valves may be manually operated.
Reheating the domestic hot water
remains ensured.
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
Bad connection
Remarks:
Heating of domestic hot water is no
longer ensured.
The load pump operates.
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
The load temperature of the dhw
tank is the same as the boiler.
Bad connection
B room temperature sensor fault
C room temperature sensor fault
Note:
The circuit concerned operates
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
without any influence from the room
sensor.
Bad connection
SCU PCB and the boiler radio
module
4Check the link and the connectors
Boiler module failure
D15ST.TANK S.FAIL
D16
SWIM.P.B. S.FAIL
D16
SWIM.P.C. S.FAIL
D17DHW 2 S.FAIL
31/08/2011 - 300024163-001-B
4Change the boiler module
SCUStorage tank sensor fault
Note:
The hot water storage tank
reheating operation is no longer
assured.
SCUSwimming pool sensor fault circuit
B
Swimming pool sensor fault circuit
C
Note:
Bad connection
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
Bad connection
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
Swimming pool reheating is always
done during the circuit's comfort
period.
SCUSensor fault tank 2Bad connection
Sensor fault
4Contact the professional who takes care of
maintenance of the appliance
38
6. TroubleshootingMCA 25/28 BIC
Code FaultsCause
of the
fault
D27PCU COM. FAIL
D29IOBL.3WV B DEF
D30IOBL.3WV C DEF
D31COM.IOBL FAIL.
D325 RESET:ON/OFF
D37
TA-S SHORT-CIR
SCUCommunication failure between the SCU and PCU PCBs
SCUCommunication failure between the
SCUCommunication failure between the
SCUThe IOBL function is no longer
SCU5 resets done in less than an hour
SCUThe Titan Active System® is short-circuited
DescriptionChecking / solution
4Contact the professional who takes care of maintenance of the appliance
The V3V module is switched off
SCU PCB and the V3V module
The V3V module and the SCU PCB are not
connected to the same live terminal
The V3V module has been removed
4Contact the professional who takes care of
maintenance of the appliance
The V3V module is switched off
SCU PCB and the V3V module
The V3V module and the SCU PCB are not
connected to the same live terminal
The V3V module has been removed
4Contact the professional who takes care of
maintenance of the appliance
Problem on the SCU PCB
active
4Contact the professional who takes care of
maintenance of the appliance
4Switch the boiler off and switch back on
4If the boiler does not start after several resets (5 attempts possible), contact your
heating engineer and inform him of the error message displayed
D38TA-S DISCONNEC
4Contact the professional who takes care of maintenance of the appliance
Remarks:
Domestic hot water production has stopped but can nonetheless be restarted using key
r.
The tank is no longer protected.
If a tank without Titan Active System® is connected to the boiler,check that the TAS
simulation connector (delivered with package AD212) is fitted to the sensor card.
SCUThe Titan Active System® is on an open circuit
4Contact the professional who takes care of maintenance of the appliance
Remarks:
Domestic hot water production has stopped but can nonetheless be restarted using key
r.
The tank is no longer protected.
If a tank without Titan Active System® is connected to the boiler,check that the TAS
simulation connector (delivered with package AD212) is fitted to the sensor card.
39
31/08/2011 - 300024163-001-B
MCA 25/28 BIC7. Technical specifications
7Technical specifications
7.1Technical specifications
Boiler type
General
Flow rate settingAdjustable
Nominal output (Pn)
Heating System (80/60 °C)
Nominal output (Pn)
DHW System
Data on the gases and combustion gases
Gas consumption - Natural gas H (G20) minimum-maximum
Gas consumption - Propane G31minimum-maximum
NOx-Emission per year (n =1)
Mass flue gas flow rateminimum-maximum kg/h8,9 - 49,3
Flue gas temperatureminimum-maximum °C30 - 85
Maximum counter pressure
Characteristics of the heating circuit
Water content
Water operating pressure (PMS)maximumkPa (bar) 300 (3,0)
4 Keep the room in which the boiler is installed well ventilated.
4 Do not block ventilation outlets.
4 Do not cover the radiators. Do not hang curtains in front of the
radiators.
4 Install reflective panels behind the radiators to prevent heat
losses.
4 Insulate the pipes in rooms that are not heated (cellars and lofts).
4 Close the radiators in rooms not in use.
4 Do not run hot (or cold) water pointlessly.
4 Install a water-saving shower head to save up to 40 % energy.
4 Take showers rather than baths. A bath consumes twice as much
water and energy.
8.2Recommendations
The remote control is available in the following versions:
4 Wire
4 Radio
The setting of the control panel and/or of the remote control has a
considerable influence on energy consumption.
A few tips:
4 In the room in which the room thermostat is installed, it's advised
not to use thermostatic valve radiators. If a thermostatic valve is
used the valve must be fully opened.
4 Completely closing and opening thermostatic valve radiators
causes undesirable temperature fluctuations. Open and close
thermostatic valves in small steps.
4 Lower the temperature to around 20°C. This reduces heating costs
and energy consumption.
4 Lower the temperature when you air the rooms.
4 When setting a time schedule , bear days when you are absent
and holidays in mind.
41
31/08/2011 - 300024163-001-B
MCA 25/28 BIC
9Warranty
9.1General
9.2Warranty terms
9. Warranty
You have just purchased one of our appliances and we thank you for
the trust you have placed in our products.
Please note that your appliance will provide good service for a longer
period of time if it is regularly checked and maintained.
Your fitter and our customer support network are at your disposal at
all times.
The following provisions are not exclusive of the buyer being able
benefit from the legal provisions applicable regarding hidden defects
in the buyer's country.
Starting from the purchase date shown on the original fitter's invoice,
your appliance has a contractual guarantee against any
manufacturing defect.
The length of the guarantee is mentioned in the price catalogue.
The manufacturer is not liable for any improper use of the appliance
or failure to maintain or install the unit correctly (the user shall take
care to ensure that the system is installed by a qualified engineer).
In particular, the manufacturer shall not be held responsible for any
damage, loss or injury caused by installations which do not comply
with the following:
4 applicable local laws and regulations,
4 specific requirements relating to the installation, such as national
and/or local regulations,
4 the manufacturer's instructions, in particular those relating to the
regular maintenance of the unit,
4 the rules of the profession.
The warranty is limited to the exchange or repair of such parts as have
been recognised to be faulty by our technical department and does
not cover labour, travel and carriage costs.
The warranty shall not apply to the replacement or repair of parts
damaged by normal wear and tear, negligence, repairs by unqualified
parties, faulty or insufficient monitoring and maintenance, faulty
power supply or the use of unsuitable fuel.
31/08/2011 - 300024163-001-B
Sub-assemblies such as motors, pumps, electric valves etc. are
guaranteed only if they have never been dismantled.
The legislation laid down by european directive 99/44/EEC,
transposed by legislative decree No. 24 of 2 February 2002 published
in O.J. No. 57 of 8 March 2002, continues to apply.
42
DE DIETRICH THERMIQUE S.A.S.
www.dedietrich-thermique.fr
FR
Direction des Ventes France
57, rue de la Gare
F- 67580 MERTZWILLER
+33 (0)3 88 80 27 00
+33 (0)3 88 80 27 99
DE DIETRICH REMEHA GmbH
www.dedietrich-remeha.de
VAN MARCKE
www.vanmarcke.be
WALTER MEIER (Klima Schweiz) AG
www.waltermeier.com
DE
BE
CH
NEUBERG S.A.
www.dedietrich-heating.com
LU
DE DIETRICH
RU
Rheiner Strasse 151
D- 48282 EMSDETTEN
+49 (0)25 72 / 23-5
+49 (0)25 72 / 23-102
info@dedietrich.de
Weggevoerdenlaan 5
B- 8500 KORTRIJK
+32 (0)56/23 75 11
Bahnstrasse 24
CH-8603 SCHWERZENBACH
+41 (0) 44 806 44 24
+41 (0) 44 806 44 25
39 rue Jacques Stas
L- 2010 LUXEMBOURG
+352 (0)2 401 401
ch.klima@waltermeier.com
DE DIETRICH
www.dedietrich-heating.com
CN
Room 512, Tower A, Kelun Building
12A Guanghua Rd, Chaoyang District