Datalogic Scanning DS6400 User Manual

DS6400
Reference Manual
Datalogic Automation S.r.l. Via S. Vitalino 13 40012 - Lippo di Calderara di Reno Bologna - Italy
DS6400 Reference Manual
Ed.: 10/2007
ALL RIGHTS RESERVED Datalogic reserves the right to make modifications or improvements without prior notification.
Datalogic shall not be liable for technical or editorial errors or omissions contained herein, nor for incidental or consequential damages resulting from the use of this material.
Product names mentioned herein are for identification purposes only and may be trademarks and or registered trademarks of their respective companies.
© Datalogic Automation S.r.l. 2003 - 2007
03/10/2007

CONTENTS

REFERENCES ............................................................................................................vi
Reference Documentation........................................................................................... vi
Services and Support .................................................................................................. vi
Patents......................................................................................................................... vi
COMPLIANCE............................................................................................................vii
Electrical Safety...........................................................................................................vii
Laser Safety.................................................................................................................vii
Power Supply..............................................................................................................viii
CE Compliance...........................................................................................................viii
WEEE Compliance .....................................................................................................viii
GENERAL VIEW..........................................................................................................x
GUIDE TO INSTALLATION ...................................................................................... xiii
Point-to-Point Installation............................................................................................xiii
Master/Slave Lonworks Installation ............................................................................xiv
1 INTRODUCTION ..........................................................................................................1
1.1 Product Description ......................................................................................................1
1.2 Model Description.........................................................................................................2
1.3 Oscillating Mirror Models ..............................................................................................3
1.4 Indicators ......................................................................................................................5
1.5 Accessories ..................................................................................................................6
2 INSTALLATION ...........................................................................................................7
2.1 Package Contents ........................................................................................................7
2.2 Mechanical Mounting....................................................................................................8
2.2.1 Mounting the Scanner...................................................................................................8
2.2.2 Mounting the Scanner with Accessories.....................................................................11
2.3 Electrical Connections ................................................................................................13
2.3.1 Main/Aux. Serial Interface and I/O Connector ............................................................15
Main Interface.............................................................................................................16
Auxiliary Interface .......................................................................................................19
Inputs..........................................................................................................................20
Outputs .......................................................................................................................22
2.3.2 Lonworks Connectors.................................................................................................24
Network Termination...................................................................................................25
Lonworks Interface .....................................................................................................26
2.3.3 Ethernet Connector.....................................................................................................28
Ethernet Interface .......................................................................................................29
2.3.4 DeviceNet Connector..................................................................................................30
2.3.5 Profibus Connector.....................................................................................................31
Profibus Interface........................................................................................................31
2.3.6 Power Supply..............................................................................................................32
2.4 User Interface .............................................................................................................32
2.5 Positioning the Scanner..............................................................................................33
2.6 Typical Installations ....................................................................................................35
2.6.1 Standard Installation...................................................................................................35
2.6.2 “45° Skew” Installation................................................................................................35
2.7 Typical Layouts...........................................................................................................36
iii
2.7.1 Point-to-Point..............................................................................................................36
2.7.2 Pass Through .............................................................................................................38
2.7.3 RS232 Master/Slave...................................................................................................39
2.7.4 Multiplexer ..................................................................................................................41
2.7.5 Local Lonworks Network.............................................................................................42
Small Synchronized Network......................................................................................43
Large Synchronized Network...................................................................................... 45
Multidata Network.......................................................................................................46
2.7.6 Fieldbus Network........................................................................................................47
2.8 FLASH™ Dynamic Focus...........................................................................................48
2.8.1 Fixed Mode.................................................................................................................48
2.8.2 Continuous Mode........................................................................................................ 48
2.8.3 Triggered Mode ..........................................................................................................49
2.8.4 D-FLASH™ Mode.......................................................................................................49
2.9 Keypad and Display....................................................................................................50
2.9.1 Internal Net .................................................................................................................50
2.9.2 Test Mode...................................................................................................................51
3 SOFTWARE CONFIGURATION................................................................................52
3.1 Genius™ Installation...................................................................................................52
3.2 Guide to Rapid Configuration .....................................................................................52
3.2.1 Wizard for Quick Reader Setup..................................................................................52
Test Operating Mode..................................................................................................53
On Line Operating Mode ............................................................................................54
Automatic Operating Mode.........................................................................................54
3.2.2 Genius™ Network Setup Through Master..................................................................55
Net-Autoset.................................................................................................................57
Express Network Setup ..............................................................................................57
Network Wizard ..........................................................................................................58
3.2.3 Alternative Slave Address Assignment.......................................................................60
3.3 Advanced Genius™ Configuration .............................................................................60
3.4 Parameter Default Values...........................................................................................61
4 READING FEATURES...............................................................................................65
4.1 Advanced Code Reconstruction (ACR™ 4)................................................................ 65
4.1.1 Tilt Angle for Advanced Code Reconstruction............................................................65
4.2 PackTrack™ ...............................................................................................................66
4.2.1 PackTrack™ Calibration for DS6400..........................................................................68
4.2.2 PackTrack™ Calibration for DS6400 Oscillating Mirror Models .................................70
4.3 Performance ...............................................................................................................70
4.3.1 Reading Conditions ....................................................................................................70
4.4 Reading Diagrams......................................................................................................72
4.4.1 DS6400 Standard Model ............................................................................................73
4.4.2 DS6400 Oscillating Mirror Model ................................................................................ 83
5 MAINTENANCE .........................................................................................................93
5.1 Cleaning......................................................................................................................93
5.2 Automatic Scanner Replacement (ASR) ....................................................................93
5.2.1 ASR Network Configuration........................................................................................93
5.2.2 Scanner Replacement Procedure............................................................................... 94
6 TROUBLESHOOTING ...............................................................................................95
7 TECHNICAL FEATURES........................................................................................... 98
iv
GLOSSARY.............................................................................................................. 100
INDEX.......................................................................................................................103
v

REFERENCES

REFERENCE DOCUMENTATION

The documentation related to the DS6400 management is listed below:
C-BOX100 Installation Manual
INT-30 20 mA Current Loop Interface Board for C-BOX 100
PWR-120 power supply unit
GFC-60 90° deflecting mirror
GFC-600 90° deg. mirror close distance
Document about the Ethernet connectivity
Document about the Profibus connectivity
Help On-Line in PDF format

SERVICES AND SUPPORT

Datalogic provides several services as well as technical support through its website. Log on to www.automation.datalogic.com and click on the including:
PRODUCTS
links indicated for further information
Search through the links to arrive at your product page where you can download specific
Manuals and Software & Utilities including:
- Genius™ a utility program, which allows device configuration using a PC. It provides
RS232 interface configuration.
SERVICES & SUPPORT
-
Datalogic Services - Warranty Extensions and Maintenance Agreements
-
Authorised Repair Centres
CONTACT US
E-mail form and listing of Datalogic Subsidiaries

PATENTS

This product is covered by one or more of the following patents:
U.S. patents: 5,483,051; Re. 36,251; 6,049,406; 5,992,740; 6,347,740B1; 6,629,639B2; 6,394,352B1; 6,742,710B2; 7,161,685B1; 6,688,524B1; 6,443,360 B1; 7,195,162B2.
European patents: 652,530B1; 786,734B1; 789,315B1; 851,376B1; 1,363,228B1; 959,426B9; 1,300,798B1.
Additional patents pending.
vi

COMPLIANCE

ELECTRICAL SAFETY

This product conforms to the applicable requirements contained in the European Standard for electrical safety EN-60950-1 at the date of manufacture.

LASER SAFETY

The following information is provided to comply with the rules imposed by international authorities and refers to the correct use of the DS6400 reader.
Standard Regulations
This scanner utilizes a low-power laser diode. Although staring directly at the laser beam momentarily causes no known biological damage, avoid staring at the beam as one would with any very strong light source, such as the sun.
Avoid that the laser beam hits the eye of an observer, even through reflective surfaces such as mirrors, etc.
This product conforms to the applicable requirements of both EN60825-1 and CDRH 21 CFR1040 at the date of manufacture. The reader is classified as a Class 2 laser product according to EN60825-1 regulations and as a Class II laser product according to CDRH regulations.
Disconnect the power supply when opening the device during maintenance or installation to avoid exposure to hazardous laser light.
There is a safety device which allows the laser to be switched on only if the motor is rotating above the threshold for its correct scanning speed.
Use of controls or adjustments or performance of procedures other than those specified herein may result in exposure to hazardous visible laser light.
WARNING
The laser light is visible to the human eye and is emitted from the window on the head of the reader (Figure A, 7).
Warning labels indicating exposure to laser light and the device classification are applied onto the head of the reader (Figure A, 1, 3):
LASER RADIATION IS EMITTED FROM THIS APERTURE
AVOID EXPOSURE
AVOID EXPOSURE – LASER LIGHT
IS EMITTED FROM THIS APERTURE
Laser Safety Label for Oscillating Mirror and Standard Models
CAUTION-CLASS 3B
LASER LIGHT WHEN OPEN
AVOID EXPOSURE
TO BEAM
LASER LIGHT – DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
MAX. OUTPUT RADIATION 1 m W
EMITTED WAVE LENGTH 630 ~ 680 nm
EN60825-1:2001
Warning and Device Class Label
vii
The identification label is applied onto the bottom part of the scanner (Figure A, 2):
DATALOGIC S.p.A. Via Candini, 2 40012 LIPPO DI CALDERARA DI RENO (BO) ITALY MANUFACTURED VOLT Amp. JANUARY 2002 15-30 DC 1.5-0.7 MODEL No.
SERIAL No.
This product conforms to the applicable requirements of 21CFR 1040 at the date of manufacture.
Device Identification Label
N2468
The laser diode used in this device is classified as a Class 3B laser product according to EN60825-1 regulations and as a Class IIIb laser product according to CDRH regulations. Any violation of the optic parts in particular can cause radiation up to the maximum level of the laser diode (35 mW at 630~680 nm).

POWER SUPPLY

- This product is intended to be installed by Qualified Personnel only.
- All DS6400 Models:
This device is intended to be supplied by a UL Listed Power Unit marked “Class 2” or LPS power source which supplies power directly to the scanner via the 25/26-pin connector.

CE COMPLIANCE

Warning:
This is a Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.

WEEE COMPLIANCE

ENGLISH
Information for the user in accordance with the European Commission Directive 2002/96/EC
t the end of its useful life, the prA
separately from urban waste.
Disposin
or consu
g of the product according to this Directive:
avoids potentially negative conse quences to the environment and human health which o be caused by incorrect disposal
enables the recovery of materials to obtain a significant savings of energy and resources.
or more detailed information about disposal, contact the supplier that providedF
lt the dedicated section at the website www.automation.datalogic.com.
oduct marked with the crossed out wheeled wastebin must be disposed of
therwise could
you with the product in question
viii
ITALIANO
Informazione degli utenti ai sensi della Direttiva Europea 2002/96/EC
L’apparecchiatura che riporta il simbolo del bidone barrato deve essere smaltita, alla fine della sua vita utile, separatamente dai rifiuti urbani.
Smaltire l’apparecchiatura in conformità alla presente Direttiva consente di:
evitare possibili conseguenze negative per l’ambiente e per la salute umana che potrebbero invece essere causati dall’errato smaltimento dello stesso;
recuperare materiali di cui è composto al fine di ottenere un importante risparmio di energia e di risorse.
Per maggiori dettagli sulle modalità di smaltimento, contattare il Fornitore dal quale è stata acquistata l’apparecchiatura o consultare la sezione dedicata sul sito www.automation.datalogic.com.
DEUTSCH
Benutzerinformation bezüglich Richtlinie 2002/96/EC der europäischen Kommission
Am Ende des Gerätelebenszyklus darf das Produkt nicht über den städtischen Hausmüll entsorgt werden. Eine entsprechende Mülltrennung ist erforderlich.
Beseitigung des Produkts entsprechend der Richtlinie:
verhindert negative Auswirkungen für die Umwelt und die Gesundheit der Menschen
ermöglicht die Wiederverwendung der Materialien und spart somit Energie und Resourcen
Weitere Informationen zu dieser Richtlinie erhalten Sie von Ihrem Lieferanten, über den Sie das Produkt erworben haben, oder besuchen Sie unsere Homepage unter www.automation.datalogic.com.
FRANÇAIS
Information aux utilisateurs concernant la Directive Européenne 2002/96/EC
Au terme de sa vie utile, le produit qui porte le symbole d'un caisson à ordures barré ne doit pas être éliminé avec les déchets urbains.
Éliminer ce produit selon cette Directive permet de:
éviter les retombées négatives pour l'environnement et la santé dérivant d'une élimination incorrecte
récupérer les matériaux dans le but d'une économie importante en termes d'énergie et de ressources
Pour obtenir des informations complémentaires concernant l'élimination, veuillez contacter le fournisseur auprès duquel vous avez acheté le produit ou consulter la section consacrée au site Web www.automation.datalogic.com.
ESPAÑOL
Información para el usuario de accuerdo con la Directiva Europea 2002/96/CE
Al final de su vida útil, el producto marcado con un simbolo de contenedor de bassura móvil tachado no debe eliminarse junto a los desechos urbanos.
Eliminar este producto de accuerdo con la Directiva permite de:
evitar posibles consecuencias negativas para el medio ambiente y la salud derivadas de una eliminación inadecuada
recuperar los materiales obteniendo así un ahorro importante de energía y recursos
Para obtener una información más detallada sobre la eliminación, por favor, póngase en contacto con el proveedor donde lo compró o consultar la sección dedicada en el Web site www.automation.datalogic.com.
ix

GENERAL VIEW

DS6400
7
6
1
2
3
4
5
x
Figure A - DS6400
1
Laser Safety Label Identification Label
2
Warning and Device Class Label
3
Service Cap
4
5
Connector Panel Display and Keypad Panel
6
Laser Beam Output Window
7
DS6400
2
1
Figure B - DS6400 Oscillating Mirror Version
5
Programming Keypad
1
Laser Safety Label
1
Laser Beam Output Window
2
3
4
Figure C - Display and Keypad Panel
2
Power On LED
4
1
2
TX Data LED
3
Phase On LED
LCD Display
5
xi
1
3
2
Figure D - Connector Panel for Master/Slave Models
1
Lonworks 9-pin maole connector
2
nnector Main/Aux. Interface 25-pin D-Sub male c
3
Lonworks 9-pin female connector
1
2
3
Figure E – Connector Panel for Ethernet Models
Main/Aux. Interface 26-pin D-Sub male connector
1
RJ45 modular connector for Ethernet Interface
2
3
Lonworks 9-pin female connector
1
2
3
Figure F – Connector Panel for DeviceNet Models
Main/Aux. Interface 26-pin D-Sub male connector
1
DeviceNet 5-pin male connector
2
3
Lonworks 9-pin female connector
1
3
2
Figure G – Connector Panel for Profibus Models
Main/Aux. Interface 26-pin D-Sub male connector
1
xii
Profibus 9-pin female connector (white)
2
3
Lonworks 9-pin female connector

GUIDE TO INSTALLATION

POINT-TO-POINT INSTALLATION

The following can be used as a checklist to verify all the steps necessary to complete installation of the DS6400 scanner.
1) Read all information in the section “Safety Precautions” at the beginning of this manual.
2) Correctly mount the scanner using the bracket provided according to the information in par. 2.2.2 and position it at the correct reading distance according to your model as shown in par. 2.5 and par. 4.4.
3) Make electrical connections to your DS6400 scanner by:
a) Connecting the DS6400 scanner to the C-BOX 100 by means of one of the cables
provided as accessory (see par. 1.5).
b) Providing correct and complete system cabling through the C-BOX 100 according to
the signals (trigger, inputs, outputs) necessary for the layout of your application.
Layout: Point-to-Point, Pass Through, RS232 Master/Slave, Lonworks, Fieldbus.
See sub-paragraphs under 2.7 for reference.
Cabling: Power, Main Serial Interface – RS232, RS485 Half Duplex, RS485 Full
Duplex, 20 mA Current Loop, Auxiliary Interface, Inputs, Outputs, etc -. For further details, see all sub-paragraphs under par. 2.3.
4) Configure the DS6400 scanner by installing and running the Genius™ configuration program from the CD-ROM provided. The main steps are:
Select the codes to be read
Set-up the communication parameters
When PackTrack™ is required, set the PS Offset and Position parameters
Define data formatting parameters
Fine tuning of the scanner position for barcode reading can be
NOTE
accomplished in Genius™.
by performing a test through the SPY configuration tool
5) Exit the configuration program and run your application.
he installation is now complete.
T
xiii

MASTER/SLAVE LONWORKS INSTALLATION

The following can be used as a checklist to verify all the steps necessary to complete installation of the DS6400 scanner in a Master/Slave Lonworks network.
1) Read all information in the section “Safety Precautions” at the beginning of this manual.
2) Correctly mount the scanner using the bracket provided according to the information in par. 2.2.2 and position it at the correct reading distance according to your model as shown in par. 4.4.
3) Make electrical connections to your DS6400 scanner by: a) Connecting the DS6400
Master scanner to the C-BOX 100 by means of one of the
cables provided as accessory (see par. 1.5).
b) Correctly inserting the BTK-6000 terminator in the DS6400 Master reader according
to the information given under “Local Lonworks Network” in par. 2.3.2 and par. 2.7.5.
c) Completing the system wiring adding as much slave scanners as required by your
system layout (refer to par. 2.7).
d) Correctly inserting the BTK-6000 terminator in the last DS6400 Slave reader of the
network according to the information given under “Local Lonworks Network” in par.
2.3.2 and par. 2.7.5.
4) Install and run the Genius™ configuration program from the CD-ROM provided. Configure the Local Lonworks Network using one of the procedures given below:
a) Configure the entire network through the Master as described in par. b) Configure the Master as described in par. 3.2.2 and locally define each slave scanner
address as described in par. 3.2.3.
c) Define each scanner, master and slaves (with their addresses), by using the scanner
keypad according to the information given in par. 2.9.1.
5) Configure the Master scanner through the Genius™ program. The main steps are:
Select the codes to be read
Set-up the communication parameters
When PackTrack™ is required, perform PackTrack™ calibration, see par. 4.2.1
Define data formatting parameters
6) Configure each Slave scanner through the Master scanner using Genius™. The main steps are:
Select the codes to be read
When PackTrack™ is required, perform PackTrack™ calibration, see par. 4.2.1
Fine tuning of the scanner position for barcode reading can be accomplished by performing a test through the SPY configuration tool
NOTE
in Genius™.
7) Send the configuration to the Master.
xiv
8) Optionally, perform the ASR Network Configuration procedure for system backup purposes (see par. 5.2.1).
9) Exit the configuration program and run your application.
The installation is now complete.
xv
xvi

INTRODUCTION

1
1 INTRODUCTION
1.1 PRODUCT DESCRIPTION
The DS6400 is a high performance laser scanner in a complete range of industrial bar code readers offering an innovative and modular solution in terms of reading performance, connectivity and maintenance, in addition to a completely new hardware and software platform.
The DS6400 has been specifically designed for simple installation, easy use and flexibility. An innovative mechanical design together with the Datalogic patent pending Step-a-Head feature make it possible to rotate the reader head and the decoder base independently from each other. Step-a-Head
TM
enables the DS6400 to always be installed in the ideal position, by modifying the orientation of the connector panel while leaving the laser window in the desired position. The need for space is minimized and installation is easier.
The DS6400 has an innovative linear motor designed to control the focus position of the scanner via software. This dynamic system, called FLASH
TM,
is able to move the focus position rail to rail, from the minimum position to the maximum position, in less than 10 msec. In typical applications, where a DOF <1 meter is required, the focus position is adjusted in 4 msec.
The DS6400 can read all most popular bar codes even in the most difficult conditions, thanks to a new generation decoder with Intel Xscale CPU and code reconstruction technology (ACR™ 4).
This reader is also offered in a model with an integrated SW programmable oscillating mirror.
Great attention has been given to built-in connectivity for all market standards. Lonworks, Profibus, DeviceNet and Ethernet bus have been integrated in dedicated versions of the decoder base.
Some of the main features of DS6400 are listed below:
scanning speed up to 1200 scans/sec;
2 serial communication interfaces
reading all popular codes;
supply voltage from 15 to 30 Vdc;
electrical connection through connectors;
high speed Lonworks connectivity for Master/Slave layout;
built-in connectivity for Profibus, DeviceNet and Ethernet;
programmable in 5 different operating modes to suit the most various barcode reading
system requirements;
light source: solid state laser diode; the light emitted has a wavelength between
630~680nm.
IP64 protection class of the enclosure (not yet available for Ethernet models).
Manufacturing is the traditional industry for Auto-ID applications, with a market becoming mature, standardized reading solutions and a tough competition. Manufacturing has been the target industry since the very beginning of the new 6000 family with the DS6300. The DS6400 makes possible to enlarge the market applications including Transportation & Logistics industry, making wider the Business Opportunities scenario.
TM
1
1
Feature
Modular solution with separated head and base and Step-A-
TM
Head
feature
Benefit
Possibility to select the combination of head and
base that best fits the needs of the application;
Great scalability of the offer;
Down time cost reduction, since the decoder base
DS6400
works even if the head has been removed;
Easy maintenance. In case of replacement of the
head, all the configuration parameters are stored in the base, and the scanner is automatically configured;
Reading on pallets or big objects
Easy installation with the minimum room needed.
DS6400 with FLASH
TM
dynamic focusing system.
where a large reading distance / wide reading field are needed
Reading parcels on conveyors DS6400 implements the Packtrack
TM
functionality which leads to an increase of the plant production as a result of the augmented system throughput.
Master working as a multiplexer on a high speed Lonworks bus
Great competitiveness of the offer, since the cost
of an external multiplexer is saved;
High data transfer on a industrial, reliable bus
running at 1,2 Mbit/sec.
GENIUSTM Configurator SW Reduced learning time, with an easy wizard
approach;
Multilanguage platform;
All the configuration parameters stored into the
scanner;
Not dependent on the Physical interface.
1.2 MODEL DESCRIPTION
The DS6400 scanner is available in versions that differ in regard to the following characteristics:
Optical Model (Head)
2
Decoder Model (Base)
DS6400 - 10X - 0YY
Decoder Model (Base)
Optical Model (Head)
0 = Standard 5 = Oscillating Mirror
10 = Master/Slave 11 = Profibus 12 = Ethernet 15 = Devicenet
INTRODUCTION
1
1.3 OSCILLATING MIRROR MODELS
Oscillating mirror models are used when coverage of a large reading area is required, mainly in picket fence applications. The DS6400 scanner mounts a dedicated optic head with integrated oscillating mirror driven by a linear motor. The speed, the precision, the repeatability, and the reliability of this driving technology assure high level performance.
The new oscillating mirror is completely software controlled and software programmable. The Genius™ software tool allows adjusting the linear motor speed (oscillating frequency) and the upper and lower limits of the oscillation by defining the top and bottom line limit angles.
When the oscillating mirror is programmed to read barcode labels at very small angles, position the reader to assure at least 10° for the Skew angle (see par. 2.4). This angle refers to the most inclined or external laser line, so that all other laser lines assure more than 10° Skew. This avoids the direct reflection of the laser light emitted by the reader.
1 0
°
Figure 1 – Oscillating Mirror Skew Angle
Otherwise, the scanner can be mounted at an angle of inclination of 17.5° in order to attain symmetrical deflection ranges.
1
7
.
5
°
°
5
.
7
0
1
Figure 2 - Oscillating Mirror Reading Position
In the above case, the zone where the scan line is perpendicular to the reflecting surface corresponds to a neutral zone at the center of the reading field.
3
1
DS6400
The mirror can be deflected up to 40°. Oscillation with respect to the output window median axis is asymmetrical ( see figure below).
3
40°
7
.
5
°
-
2.
5
°
Figure 3 - Oscillating Mirror Maximum Aperture and Asymmetry
By configuring the oscillating speed up to the maximum value of 19 Hz, raster emulation can
e performed for reading fast moving objects. b
Hz Max. Aperture
0-5 40°
6-10 30° 11-15 20° 16-19 10°
By limiting the raster width to the minimum necessary, the number of
NOTE
scans on the reading surface is increased.
Oscillating angles are selected in software where the minimum and maximum angles
orrespond to –2.c 5° and +37.5°.
he scanner can be tilted in order for the 17.5° software setting to correspond with the 0°
T horizontal plane.
4
+37.5°
+17.5°
-2.5°
Figure 4 - Oscillating Mirror Extreme Angle Positions
INTRODUCTION
These models provide higher scanning speed (1200 scans/sec) compared to standard models and the reading performance is not adversely effected by the oscillating mirror.
The following example represents the selection of an angle of +10° for the bottom line and an angle of +20° for the top line (see figure below).
1
+37.5°
+27.5°
+17.5°
Figure 5 - Oscillating Mode
Refer to par. 2.2.1 for deta
ils about oscillating mirror mounting.
1.4 INDICATORS
T dec se
he DS6400 oder ba provides an LCD display for system messages and configuration
menus. The three keys present on the side of the display allow configuration menu
avigation (Figure C, 1).
n
he three LED indicators have the following functions:
T
POWE PHASE ON TX DATA
R ON
(red) Indicates the reader is turned on (Figure C, 4) (yellow) Indicates the presence sensor is turned on (Figure C, 3). (green) Indicates the main serial interface is operating correctly during
data transmission (Figure C, 2).
5
1
DS6400
1.5 ACCESSORIES
The following accessories are available on request for DS6400:
Name Description Part Number
CAB-6001 cable to C-BOX100 1 m 93A051190 CAB-6002 cable to C-BOX100 2 m 93A051200 CAB-6005 cable to C-BOX100 5 m 93A051210 CAB-6010 cable to C-BOX100 10 m 93A051271 CAB-6011 cable to C-BOX100 1 m (DS6400 Fieldbus version) 93A051221 CAB-6012 cable to C-BOX100 2 m (DS6400 Fieldbus version) 93A051222 CAB-6015 cable to C-BOX100 5 m (DS6400 Fieldbus version) 93A051223 CAB-6101 cable master/slave 1 m 93A051220 CAB-6102 cable master/slave 2 m CAB-6105 cable master/slave 5 m 93A051240 CAB-6112 cable master/slave no power 2 m 93A051224 CAB-6115 cable master/slave no power 5 m 93A051225 CAB-6305 Power cable Fam 6k 5 m 93ACC1768 CAB-6310 Power cable Fam 6k 10 m 93ACC1752 C-BOX 100
passive connection box 93ACC1510 INT-30 20 m.A. C.L. interface board for C-BOX 100 93A151022 PWR-120 power unit 110/230 V AC 24 V 93ACC1530 BTK-6000 terminator kit (5 pcs) PG6002 PG6001
single unit power supply (US) 93ACC1718
single unit power supply (UK) 93ACC1719 PG6000 single unit power supply (EU) 93ACC1720 FBK-6000 fast bracket kit (2 pcs) 93ACC1721 GFC-60 90° mirror 93A201100 GFC-600 90° deg. mirror close distance 93A201102 US-60 mounting bracket kit (5 pcs) for multisided stations 890001020 PH-1 Photocell kit – PNP 93ACC1791 MEP-543 Photocell kit - NPN 93ACC1728 OEK-2 Optical encoder (10 m cable + spring) 93ACC1770 OEK-1 Optical encoder kit + 10 m cable 93ACC1600
93A051230
93ACC1710
6

INSTALLATION

2 INSTALLATION
To install the system follow the given procedure:
Select the mounting location for DS6400;
Mount the DS6400 scanner;
Position the scanner with respect of the barcode;
Proceed with system electrical connection;
Install the Genius™ program on the PC and configure the scanner;
Set the Flash™ dynamic focus by means of the Genius™ software tool.
When installing several scanners, take care to position them correctly so
that no laser beam enters the reading window perpendicularly and at the
same level of the output beam of the other scanners. This condition could
occur more frequently for side mounted applications. If these precautions
are not followed, it may occur that the laser of the blinded scanner starts
WARNING
blinking due to an internal circuit which temporarily turns the laser off
when detecting a power anomaly. To resolve this problem, it is sufficient
to slightly change the inclination and position of one of the two scanners
involved.
2
Refer to the Reference Documentation for details on connecting
NOTE
DS6400 reader to other devices in the system (i.e. C-BOX 100, etc ).
2.1 PACKAGE CONTENTS
Verify that the DS6400 reader and all the parts suppl intact when opening the packaging; the list of parts inc
DS6400 reader
Installation Quick Reference +
DS6400 configuration CD-ROM
Mounting bracket and screws
barcode test chart
your
ied with the equipment are present and
ludes:
Figure 6 - DS6400 Package Contents
7
2
DS6400
2.2 MECHANICAL MOUNTING

2.2.1 Mounting the Scanner

The DS6400 reader can be positioned and installed in the best way possible as a result of the Step-a-Head™ feature. Thanks to the separation between Head and Base, you can modify the orientation of the decoder base, and therefore display-keypad and connector panels, while keeping the optic head in the correct reading position. The reading head and the decoder base can be rotated independently from each other allowing the installation even in the most critical locations.
Head Screws
Fixing Screw (4)
Figure 7 - Step-A-Head™ Feature
To rotate the head follow the given procedure:
. detach the head from the base by unscrewing the four fixing screws;
1
. rotate the head in the desired position;
2
loosen but don't remove the two screws on top of the head;
3.
4. affix the head onto the base carefully aligning the four fixing screws and progressively tightening them about half-way;
5. completely tighten the two screws on top of the head;
6. completely tighten the four fixing screws.
8
INSTALLATION
2
The following diagrams give the overall dimensions of the reader standard model, oscillating mirror model and mounting brackets. They may be used for their installation. Refer to par.
2.4 for correct positioning of the scanner with respect to the code passage zone.
16.5
0.65 85
3.34
60
2.36
30
1.18
76
2.99
30
1.18
74
2.85
99
3.90
mm
113
4.45
110
4.33
inch
Figure 8 - DS6400 Overall Dimensions
42
1.65
10
0.4
18
0.71 N°2
25
0.98
82
3.22 50
20
0.78
1.96
2
°
2
°
N
N
1
.
6
4
1
.
Ø
0
Ø
1.96
2.83 100
3.93
.
8
0
22
0.86
S
50
T
O
1.96
L
S
T
S
O
4
L
°
S
N
4
5
°
.
N
4
8
1
.
0
==
50
72
5 .
==
S
T
O
L
S
2
°
S
T
N
O
L
S
2
°
N
3
3
5
.
8
3
Ø
3
.
0
Ø
82
3.22
35
1.37
1
4
2
.
6
9
6
106°
73.2
2.88
36
1.41
mm
inch
4
0.15
130
5.12
Figure 9 – ST-237 Mounting Bracket Overall Dimensions
9
2
30
60
DS6400
1.18
2.36
104.5
110.3
85
3.35
2.50
63.5
4.11
69
2.72 56
2.20
102
4.34
4.01
180
7.08
114
4.48
16.5
0.65
99
3.90
113
4.45
mm
inch
Figure 10 - DS6400 Oscillating Mirror Model Overall Dimensions
42
1.65
130
82
5.11
3.22
25
50
0.98
1.96
18
20
1
0.7
0.78
10
0.4
Ø4.1
0.16
22
0.86
35
4
0.15
50
1.96
1.37
10
R1
R5
0.43 14
0.55
0.55
36
1111
0.43 14
1.41
75
2.95
mm inch
50
1.96 72
2.83 100
3.93
R36
R22
5
.
8
Ø
Figure 11 – ST-210 Mounting Bracket Overall Dimensions
INSTALLATION
2

2.2.2 Mounting the Scanner with Accessories

The following a
our network layout:
y
ST-237 mounting bracket;
-
- ST-210 mounting bracke
FBK-6000 fast bracket.
The ST-237 is a 106° mounting bracket to be mounted on the reader as displayed in the image below:
ccessories allow installing the DS6400 reader in the most suitable position for
t;
-
Figure 12 – Mounting the ST-237 Mounting Bracket
The ST-210 is a 90° mounting bracket to be mounted on the reader as displayed in the image below:
Figure 13 – Mounting the ST-210 Mounting Bracket
11
2
DS6400
The FBK-6000 is a fast bracket kit allowing a quick and easy mounting of the scanner on either the ST-210 or the ST-237 brackets.
First, it is necessary to fix the FBK-6000 to the DS6400 scanner by means of the mounting screws:
Figure 14 – Mounting the FBK-6000 on the Scanner
Then, attach the assembly to the mounting bracket by slipping the hook into the bracket hole. Finally, fix it by means of the 2 fixing screws:
12
Figure 15 – Mounting the Assembly on the Bracket
INSTALLATION
2.3 ELECTRICAL CONNECTIONS
All the connectors available for each scanner model are the following:
Scanner Model Connector
Master/Slave 25-pin male serial interface and I/O connector
9-pin male Lonworks connector* 9-pin female Lonworks connector
Ethernet 26-pin male serial interface and I/O connector
9-pin female Lonworks connector RJ45 modular connector
DeviceNet 26-pin male serial interface and I/O connector
9-pin female Lonworks connector 5-pin male connector
Profibus 26-pin male serial interface and I/O connector
9-pin female Lonworks connector 9-pin female Profibus connector
2
CAUTION
* Do not connect an RS232 port to the 9-pin Lonworks Connector. This may damage your Laptop PC.
13
2
DS6400
The table below gives the pinout of the C-BOX 100 terminal block connectors. Use this pinout when the DS6400 reader is connected in a network by means of the C-BOX 100:
C-BOX 100 Terminal Block Connectors
Power
1, 3, 5 VS 2, 4, 6 GND
7, 8 EARTH GROUND
20, 40 Reserved
Inputs
27 EXT TRIG/PS A (polarity insensitive) for PS 28 EXT TRIG/PS B (polarity insensitive) for PS 29 IN 2/ENC A (polarity insensitive) for Encoder
30 IN 2/ENC B (polarity insensitive) for Encoder 31, 33 IN 3A (polarity insensitive) 32, 34 IN 4A (polarity insensitive)
36 IN 3B/IN 4B Reference (polarity insensitive)
Outputs
21 OUT 1+
22 OUT 1-
23 OUT 2+
24 OUT 2-
25 OUT 3A (polarity insensitive)
26 OUT 3B (polarity insensitive)
Auxiliary Interface
35 TX AUX
37 RX AUX 38, 39 GND
Main Interface
Pin RS232
RS485
Full-Duplex
RS485
Half-Duplex
20 mA C.L.
(with INT-30 only)
11, 15 TX232 TX485+ RTX485+ 12, 16 RTS232 TX485- RTX485-
17 RX232 * RX485+
18 CTS232 * RX485-
10, 14, 19
9, 13
SGND Main Isolated SGND Main Isolated SGND Main Isolated
RS485 Cable Shield RS485 Cable Shield
see INT-30 instructions
* Do not leave floating, see par. "RS485 Full-Duplex Interface" for connection details.
14
INSTALLATION
2

2.3.1 Main/Aux. Serial Interface and I/O Connector

The DS6400 master/slave model is equipped with a 25-pin male D-sub connector for connection to the host computer, power supply and input/output signals.
The DS6400 fieldbus models (Ethernet, DeviceNet, Profibus) adopt a 26-pin male connector instead of the 25-pin one.
The details of the connector pins are indicated in the following table:
1
1
10
Figure 16 - 26-pin Connector Figure 17 - 25-pin Connector
19
26
18
9
14
DS6400 25-pin/26-pin D-sub connector pinout
25
13
Pin Name Function
1 CHASSIS
Chassis - internally connected to GND
Cable shield connected to chassis 20 RXAUX Receive data of auxiliary RS232 (referred to GND) 21 TXAUX Transmit data of auxiliary RS232 (referred to GND)
8 OUT 1+ Configurable digital output 1 - positive pin 22 OUT 1- Configurable digital output 1 - negative pin 11 OUT 2+ Configurable digital output 2 - positive pin 12 OUT 2- Configurable digital output 2 - negative pin 16 OUT 3A Configurable digital output 3 - polarity insensitive 17 OUT 3B Configurable digital output 3 - polarity insensitive 18 EXT_TRIG/PS A External trigger (polarity insensitive) for PS 19 EXT_TRIG/PS B External trigger (polarity insensitive) for PS
6 IN 2/ENC A Input signal 2 (polarity insensitive) for Encoder 10 IN 2/ENC B Input signal 2 (polarity insensitive) for Encoder 14 IN 3A Input signal 3 (polarity insensitive) 15 IN 4A Input signal 4 (polarity insensitive) 24 IN_REF Common reference of IN3 and IN4 (polarity insensitive)
9,13 VS Supply voltage - positive pin
23,25,26 GND Supply voltage - negative pin
Main Interface Connector Pinout
Pin
RS232
RS485
Full Duplex
RS485
Half Duplex
20 mA C.L.
(INT-30 with C-BOX 100 only)
2 TX TX485 + RTX485 + see INT-30 instructions
3 RX * RX485 +
4 RTS TX485 - RTX485 -
5 CTS * RX485 -
7 GND_ISO GND_ISO GND_ISO
Pin 26 is only available for fieldbus models (Ethernet, DeviceNet, Profibus). * Do not leave floating, see par. "RS485 Full-Duplex Interface" for connection details.
15
2
DS6400
Main Interface
The main serial interface is compatible with the following electrical standards:
RS232 RS485 full-duplex RS485 half-duplex (20 mA current loop)
The 20 mA Current Loop interface is available by using the C-BOX 100 with the optional INT-30 accessory installed in it. The scanner communicates to the C-BOX 100 through the RS232 interface and the INT-30 converts the signals.
The main serial interface type and its relative parameters (baud rate, data bits, etc.) are selected via software using the Genius™ utility program. For more details refer to the section "Main Serial Port" in the Genius™ Help On Line.
Details regarding the connections and use of the main interface selection are given in the next paragraphs.
RS232 Interface
The main serial interface is used for communication with the Host computer and allows both transmission of code data and configuring the reader. The overall maximum cable length should not exceed 15 m (50 ft).
The following pins of the 25-pin and 26-pin connector are used for RS232 interface connection depending on the reader model:
Pin Name Function
2 TX Transmit
3 RX Receive 4 RTS Request to send 5 CTS Clear to send 7 GND_ISO Main signal ground
The RTS and CTS signals control data transmission and synchronize the connected devices.
If the RTS/CTS hardware protocol is enabled, the DS6400 activates the RTS output to indicate a message can be transmitted. The receiving unit must activate the CTS input to enable the transmission.
DS6400
TX
2
3
RX
RTS
4
CTS
5
7
GND_ISO
CHASSIS
1
Figure 18 - RS232 Connections
USER INTERFACE
RXD
TXD
SGND Main Isolated
Earth
Ground
16
INSTALLATION
2
RS485 Full-Duplex Interface
The RS485 full-duplex interface is used for non-polled communication protocols in point-to-point connections over longer distances than those acceptable for RS232 communications or in electrically noisy environments. The overall maximum cable length should not exceed 1200 m (3937 ft).
The following pins of the 25-pin and 26-pin connector are used for RS485 full-duplex interface connection:
Pin Name Function
2 TX485 + RS485 output (+)
3 RX485 + RS485 input (+) 4 TX485 - RS485 output (-) 5 RX485 - RS485 input (-) 7 GND_ISO Main signal ground
Figure 19 - RS485 Full-Duplex Interface Connections
DS6400
USER INTERFACE
2
TX485+
3
RX485+
4
TX485-
RX485-
5
7
GND_ISO
1
CHASSIS
RX485+
TX485+
RX485-
TX485-
SGND Main Isolated
Earth
Ground
For applications that do not use RX485 signals, do not leave these lines
NOTE
floating but connect them to GND_ISO as shown below.
DS6400
2
4
3
5
7
1
TX485+
TX485-
RX485+
RX485-
GND_ISO
CHASSIS
USER INTERFACE
RX485+
RX485-
SGND Main Isolated
Earth
Ground
Figure 20 - RS485 Full-Duplex Interface Connections Using Only TX Signals
17
2
DS6400
RS485 Half-Duplex Interface
The RS485 half-duplex interface can be used for multidrop connections with a Datalogic multiplexer or it can also be used for a master/slave layout. The overall maximum cable length should not exceed 1200 m (3937 ft).
The following pins of the 25-pin and 26-pin connector are used for RS485 half-duplex interface connection:
Pin Name Function
2 RTX485 + RS485 input/output (+)
4 RTX485 - RS485 input/output (-) 7 GND_ISO Main signal ground
Figure 21 – RS485 Half-Duplex Interface Connections
DS6400
MULTIPLEXER
2
RTX485+
4
RTX485-
7
GND_ISO
1
CHASSIS
RTX485+
RTX485-
RS485REF
Earth
Ground
18
INSTALLATION
2
Auxiliary Interface
The auxiliary serial interface is equipped with RS232 full-duplex interface connections. The interface type is exclusive and is selectable through the Genius™ configuration program. The overall maximum cable length should not exceed 15 m (50 ft).
The following pins of the 25-pin and 26-pin connector are used for RS232 full-duplex interface connection:
Pin Name Function
20 RXAUX Receive data
21 TXAUX Transmit data 23 SGND AUX Auxiliary signal ground
DS6400
USER INTERFACE
20
RXAUX
21
TXAUX
23
GNDAUX
1
CHASSIS
TXD
RXD
GND
Earth
Ground
Figure 22 - RS232 Auxiliary Interface Connections
19
2
DS6400
Inputs
The inputs of the reader are on the 25-pin and 26-pin connector (Figure D, 1 and Figure E, 1) of the DS6400.
These inputs are called EXT_TRIG/PS, IN2/ENC, IN3 and IN4.
Pin Name Function
18 EXT_TRIG/PS A External trigger (polarity insensitive) for PS 19 EXT_TRIG/PS B External trigger (polarity insensitive) for PS
6 IN2/ENC A Input signal 2 (polarity insensitive) for Encoder 10 IN2/ENC B Input signal 2 (polarity insensitive) for Encoder 14 IN3A Input signal 3 (polarity insensitive) 15 IN4A Input signal 4 (polarity insensitive) 24 IN_REF Common reference of IN3 and IN4 (polarity insensitive)
IN2/ENC is normally used for the Encoder input. In PackTrack™ mode, it detects the conveyor speed. The maximum Encoder frequency is 2 KHz.
EXT_TRIG/PS is the main presence sensor. When active, this input tells the scanner to scan for a code and that decoding can take place. The yellow LED (Figure C,3) indicates the EXT_TRIG/PS is active.
IN3 and IN4 can be used as the stop signal for the reading phase.
All inputs are optocoupled, polarity insensitive, and driven by a constant current generator; the command signal is filtered through an anti-disturbance circuit which generates a delay which can be set to 5 ms or 500 µs. In particular, EXT_TRIG/PS, IN3 and IN4 share the same value which usually corresponds to 5 ms when using a photoelectric sensor, while IN2/ENC has a different value which is set to 500 µs when this input is used for the Encoder.
+ 5V
DS6400
+
A/B
~
-
~
B/A
Vext
EXTERNAL TRIGGER/ENCODER
V
Ground
20
Figure 23 – PNP Command Input Connection using External Power
DS6400
VS
A/B
+ 5V
~
-
+
~
B/A
GND
EXTERNAL TRIGGER/ENCODER
V
Ground
Figure 24 - PNP Command Input Connection using Scanner Power
INSTALLATION
2
DS6400
+ 5V
EXTERNAL TRIGGER/ENCODER
Vext
A/B
~
-
+
~
B/A
V
Ground
Figure 25 - NPN Command Input Connection using External Power
+ 5V
DS6400
+
VS
A/B
~
-
~
B/A
GND
EXTERNAL TRIGGER/ENCODER
V
Ground
Figure 26 - NPN Command Input Connection using Scanner Power
DS6400
Vext
EXTERNAL DEVICE
V
+ 5V
+ 5V
~
+
~
~
+
~
IN3A
-
Ground
Vext
V
IN4A
-
INREF
Ground
Figure 27 - IN3/IN4 PNP Input Command using External Power
21
2
DS6400
+ 5V
+ 5V
DS6400
~
-
+
~
~
-
+
~
VS
INREF
IN3A
IN4A
GND
EXTERNAL DEVICE
V
Ground
EXTERNAL DEVICE
V
Ground
Figure 28 - IN3/IN4 NPN Input Command using Scanner Power
Input devices can be supplied by either scanner power (VS and GND) or external power supplies (Vext).
Electrical isolation between the input command logic and the scanner is maintained when powering the input devices from an external supply voltage (Vext).
The driving logic of the input signals may be powered, for convenience, with the voltage supply between pins 9 (VS) and 23 (GND) of the 26-pin I/O connector. In this case, however, the device is no longer electrically isolated.
The voltage available on the 26-pin I/O connector, is physically the same as used to power the scanner.
The electrical features of these inputs are:
Maximum voltage 30 V Maximum current 10 mA
Outputs
Three general purpose outputs are available.
Pin Name Function
8 OUT 1+ Configurable digital output 1 – positive pin 22 OUT 1- Configurable digital output 1 – negative pin 11 OUT 2+ Configurable digital output 2 – positive pin 12 OUT 2- Configurable digital output 2 – negative pin 16 OUT 3A Configurable digital output 3 – polarity insensitive 17 OUT 3B Configurable digital output 3 – polarity insensitive
The function of the three outputs OUT1, OUT2 and OUT3 can be defined by the user. Refer to Genius™ Help On-Line for further details.
22
INSTALLATION
2
By default, OUT1 is associated with COMPLETE READ event, which activates when the code has been read correctly. In case the reader has been programmed to read several codes within the same reading phase, the event activates when all codes have been read.
OUT2 is associated with NO READ event, which activates when no code has been read.
OUT3 is associated with NONE, which means that the output is always in Line State.
The OUT1 and OUT2 electrical features are given below:
Collector-emitter voltage 30 V Max. Collector current (pulse) 130 mA Max. Collector current (continuous) 40 mA Max. Saturation voltage (VCE) 1 V at 10 mA Max. Maximum power dissipation 90 mW at 50°C (Ambient temperature).
The limit requested by the maximum power dissipation is more important than that of the maximum collector current: if one of these outputs is continuously driven, the maximum current must not be more than 40 mA although 130 mA may be reached in pulse conditions.
DS6400
USER INTERFACE
30 Vdc max
Vext
+
-
Figure 29 – Output 1 and Output 2 Interface
When the load is powered by an external power supply, the voltage must be less than 30 V.
OUT3 has different electrical features, since it is a bi-directional solid state relay with built-in current limit protection. If this output is continuously driven, the maximum current must be not more than 200 mA although more than 300 mA may be reached in pulse conditions for an ambient temperature of 25°C. At the maximum ambient temperature of 50°C the maximum respective current is 150 mA continuous and 240 mA pulse.
The OUT3 electrical features are given below:
Maximum voltage ± 100 V Collector current (pulse) 240 mA Max. Collector current (continuous) 150 mA Max. R on 6 – 15 R off > 500 Off-state leakage current < 1 µA
Maximum power dissipation 550 mW at 50°C (Ambient temperature).
23
2
DS6400
DS6400
A
B
USER INTERFACE
100 Vdc max
Vext
Figure 30 – Output 3 Interface
The command signal is filtered and generates a delay of about 50 µs for OUT1 and OUT2 and 1 ms for OUT3.
2.3.2 Lonworks Connectors
Do not connect an RS23 damage your Laptop PC.
CAUTION
The local network used by DS6400 exploits a Lonworks standard communication system requiring only two wires (polarity insensitive) to enable a connection. The connector also
rovides a positive and a negative supplying wire. In this way, all the slave readers can be
p powered by the master through the Datalogic standard cables.
When working in applications requiring enhanced synchronization capabilities, the DS6400 master reader (output) transmits two system signals named Sys_I/O and Sys_Enc_I/O to slave readers (input). For example, when working with applications requiring an encoder the signal is received by the master and directly transmitted to the slaves throug
he internal circuits generating the system signals are externally supplied by means of the
T VS_I/O and REF_I/O pins and are isolated from the reader supply voltage.
The use of these system circuits is not required in all the operating modes (see pa
etails). Anyway, for a correct system functioning it is suggested to use Datalogic cables and
d
ccessories and follow the description of the typical layout (see par. 2.7 for details).
a
5
1
2 port to the 9-pin Lonworks Connector. This may
the
h the cable.
r. 2.7 for
1
5
24
9
Female (all mode
6
ls)
Figure 31 – 9-pin Local Lonworks Connectors
Male (Master/Slave model)
6
9
INSTALLATION
2
DS6400 9-pin Lonworks connector pinout
Pin Name Function
1 CHASSIS cable shield internally connected by capacitor to chassis 9 VS Supply voltage - positive pin 2 GND Supply voltage - negative pin 6 VS_I/O Supply voltage of I/O circuit 3 Ref_I/O Reference voltage of I/O circuit 4 SYS_ENC_I/O System signal 5 SYS_I/O System signal 7 LON A Lonworks line (polarity insensitive) 8 LON B Lonworks line (polarity insensitive)
Network Termination
When building a Lonworks system the network must be properly terminated by positioning BTK-6000 terminator in the DS6400 master reader and in the last DS6400 slave reader.
Each side of the terminator provides a different connector; thus, it can be inserted either into the Lonworks 9-pin male connector of the master reader or in the Lonworks 9-pin female connector of the last slave reader:
Slave
Master
NOTE
Female
Male
Male
Female
Figure 32 - BTK-6000 Network Terminator
For Fieldbus models no terminator must be inserted in the reader, since it is internally integrated.
25
2
r
r
DS6400
Lonworks Interface
The Lonworks network is used for both input and output connection to build a multi-sided or omni-station system connecting several readers.
The DS6400 master usually employs the 9-pin female connector for output connection to the first slave, while the 9-pin male one is terminated by inserting the BTK6000 terminator (see par. 2.7.2 for details). If creating a T network configuration, it is necessary to use both connectors to create the double branch line of slave readers.
Both connectors are always employed when connecting together the slave readers. In particular, the 9-pin female connector is used for output connection and the male one for input connection. The female connector is always terminated in the last slave reader to close the system network.
The following diagram represents the connection between a DS6400-XXX-010 working as master and a DS6400-XXX-010 working as a slave reader.
The cable shield for LON A/B is connected to pin 1 - CHASSIS.
Master
VS_I/O
Slave
REF_I/O
LON A
LON B
CHASSIS
VS
GND
4
5
3
7
8
1
AWG 16
9
AWG 16
2
= male connecto = female connecto
4
5
3
7
8
CHASSIS
1
9
2
Figure 33 – DS6400-XXX-010 Master/Slave Lonworks Connection
The maximum current to be propagated to the slave readers through the master is 2 A. For this reason, it is suggested the use of a 24 V power supply allowing to
CAUTION
supply up to three readers (master + 2 slaves).
The following diagrams represent different network terminations using the BTK-6000 terminator. In each diagram the terminator is indicated by the
element, while the figure
elow shows its electrical circuit in details: b
Figure 34 – BTK-6000 Electrical Circuit
26
INSTALLATION
r
r
r
r
r
r
2
The diagram below represents the termination of a DS6400-XXX-010 working as master by means of the BTK-6000 terminator.
Master
VS
VS_I/O
LON A
LON B
GND
REF_I/O
9
6
7
8
2
3
= male connecto = female connecto
Figure 35 – DS6400-XXX-010 Master Termination
BTK-6000 Female Side
9
6
7
8
2
3
T
The diagram below represents the termination of a DS6400-XXX-010 working as slave by means of the BTK-6000 terminator.
Slave BTK-6000 Male Side
LON A
LON B
7
8
7
8
T
= male connecto = female connecto
Figure 36 – DS6400-XXX-010 Slave Termination
The diagram below represents the connection between a DS6400 Fieldbus model, which always works as master, and a DS6400-XXX-010 working as a slave reader.
Fieldbus Master
REF_I/O
VS_I/O
LON A
T
LON B
CHASSIS
VS
GND
4
5
3
7
8
1
AWG 16
9
AWG 16
2
= male connecto = female connecto
Figure 37 – DS6400-XXX-010 Master/Slave Lonworks Connection
Slave
4
5
3
7
8
CHASSIS
1
9
2
27
2
DS6400
2.3.3 Ethernet Connector
This connector is only available for DS6400 Ethernet models and allows the Ethernet connection between the host and the reader.
8
1
Figure 38 – Cable RJ45 Male Modular Connector
1
Figure 39 – DS6400 RJ45 Female Modular Connector
8
This interface and the connector pinout (see the following table) are IEEE 802.3 10 BaseT and IEEE 802.3u 100 Base Tx c
ompliant.
Modu
RJ45 lar Jack Pinout
P in Name Function
1 TX + Transmitted data (+) 2 TX - Transmitted data (-) 3 RX + Received data (+) 6 RX - Received data (-)
4, 5, 7, 8 N.C. Not connected
In order to meet EMC requirements:
use Eth shielded cable connect the Ethernet interface cable
shield to the plant earth ground
The cable shield must be connected to the chassis of both connectors. A ferrite (type Stewart 28A2029-0A0) may also be applied on the scanner
NOTE
side of the Ethernet cable to reduce electrical noise.
28
INSTALLATION
2
Ethernet Interface
The Ethernet interface (NIC) can be used for TCP/IP communication with remote or local host computer by connecting the scanner to a LAN as well as with a host PC directly connected to the scanner.
The following is an example of a connection to a LAN through a Hub using a straight through cable:
DS6400
HUB / SWITCH
TX+
1
TX-
2
RX+
3
n. c.
4
n. c.
5
RX-
6
n. c.
7
n. c.
8
n. c. = not connected
1
2
3
4
5
6
7
8
Figure 40 – Straight Through Cable
The following is an example of direct connection to a PC using an inverted cable:
DS6400
TX+
1
TX-
2
RX+
3
n. c.
4
n. c.
5
HOST PC
3
6
1
4
5
RX-
6
n. c.
7
n. c.
8
n. c. = not connected
2
7
8
Figure 41 – Inverted Cable
For further details refer to the “Ethernet Service Guide” document provided as reference documentation.
29
2
DS6400
2.3.4 DeviceNet Connector
When using DeviceNet, the Main serial interface is disabled and must not
NOTE
The 5-pin male connector is only available in the DS6400 DeviceNet model and allows connection between the host and the reader:
be physically connected.
NOTE
4
5
1
3
2
Figure 42 - DeviceNet 5-pin Male Connector
DS6400 evic
5-pin D eNet connector pinout
P n in Name Functio
2 V + Supply voltage – positive pin 5 CAN_L CAN bus data line – L 1 SHIELD Shield 4 CAN_H CAN bus data line – H 3 V - Supply voltage – negative pin
The power supplied on pin V+ and V- is used only to propagate power to the section of the DeviceNet board directly connected to the Bus. It is completely isolated from the DS6400 power which must be supplied on pin 9, 13 and pin 23, 25 of the 26-pin Main/Aux connector.
30
INSTALLATION
2
2.3.5 Profibus Connector
The 9-pin Profibus female connector (white) is only available in the DS6400 Profibus model and allows connection between the host and the reader:
5
9
Figure 43 - Profibus 9-pin Female Connector
DS6400 9-pin Profibus connector pinout
Pin Name Function
1 Shield* Shield, Protective Ground resp. 2 Free 3 B-LINE (RxD/TxD-P) Received/Transmitted Data-P 4 CNTR-P** Repeater Control Signal 5 DGND Data Ground (M5V) 6 +5 V Voltage Plus (P5V) 7 Free 8 A-LINE (RxD/TxD-N) Received/Transmitted Data 9 CNTR-N** Repeater Control Signal
1
6
* signal is optional ** signal is optional; RS485 level
Profibus Interface
The Profibus interface is used for communication with an Host and allows expanding the networking and remote diagnostic capabilities of the scanner.
For further details refer to the “Profibus_Fam6k.pdf” document provided as supplementary documentation.
31
2
DS6400
2.3.6 Power Supply
The supply voltage of a single scanner must be between 15 and 30 VDC.
Datalogic strongly recommends a minimum 24 VDC supply voltage when using a master/slave configuration.
The power consumption of the different DS6400 models is slightly different. In particular, when connecting several DS6400 readers in a master/slave connection, the typical power consumption for each scanner is 15 W. There is a power peak of about 20 W lasting 5..10 seconds caused by the motor starting.
A security system allows the laser to activate only once the motor has reached the correct rotational speed; consequently, the laser beam is generated after a slight delay from the power on of the scanner.
Note that GND is internally connected to chassis. The cable shield is also connected to pin 1 - CHASSIS.
DS6400

USER INTERFACE

Chassis
Figure 44 – Power Supply Using the 25/26-pin Connector
2.4 USER INTERFACE
1
9-pin male connector
Pin Name Pin Name
2 RX 3 RX 3 TX 2 TX 5 GND 7 GND 7 RTS 4 RTS 8 CTS 5 CTS
9/13
23/25
1
VS
GND
CHASSIS
V+ (15 – 30 Vdc)
V- (Ground)
RS232 PC-side connections
1
5
9 6
25-pin male connector
Earth Ground
13
25 14
32
INSTALLATION
2
How To Build A Simple Interface Test Cable:
The following wiring diagram shows a simple test cable including power, external (push-button) trigger and PC RS232 COM port connections.
DS6400
25-pin D-sub female
21
20
23
13
25
9
18
19
Trigger
TXAUX
RXAUX
GND
VS
GND
VS
EXT TRIG A
EXT TRIG B
9-pin D-sub female
Power Supply
VS (15 – 30 VDC) Power GND
2
RX
PC
3
TX
5
GND
Test Cable for DS6400
2.5 POSITIONING THE SCANNER
The DS6400 reader is able to decode moving barcode labels at a variety of angles, however significant angular distortion may degrade reading performance.
When mounting DS6400 take into consideration these three ideal label position angles: Pitch 0°, Skew 10° to 30° and Tilt 0°.
Follow the suggestions for the best orientation:
The Pitch angle is represented by the value P in Figure 45. Position the reader in order to minimize the Pitch angle.
P
Figure 45 - "Pitch" Angle
33
2
DS6400
The Skew angle is represented by the value S in Figure 46. Position the reader to assure at least 10° for the Skew angle. This avoids the direct reflection of the laser light emitted by the scanner. For oscillating mirror models, this angle refers to the most inclined or external laser line, so that all other laser lines assure more than 10° Skew.
S
Figure 46 - "Skew" Angle
The Tilt angle is represented by the value T in Figure 47.
Figure 47 - "Tilt" Angle
T
34
INSTALLATION
2
2.6 TYPICAL INSTALLATIONS
2.6.1 Standard Installation
The DS6400 scanner is mounted on the ST-237 106° mounting bracket (see Figure 9) which guarantees a built-in Skew angle (S in the figure below) of 16° with respect to the frame plane (typically the Skew angle should be between 10° - 20°). This avoids the direct reflection of the laser light emitted by the scanner. Furthermore, the bracket guides allow adjusting the Tilt angle (T in the figure below, which is typically 0°) for the best scanner orientation:
T
S
Conveyor Direction
Figure 48 – Standard Installation

2.6.2 “45° Skew” Installation

The DS6400 scanner is mounted on the ST-210 90° mounting bracket (see Figure 11). By adjusting the mounting bracket guides, reach 45° for the Skew angle (S in the figure below) to avoid the direct reflection of the laser light emitted by the scanner:
45°
Figure 49 – 45° Skew Installation
S
35
2
ATTENTION
If using the “45° Skew” installation, the scanner reading performance is not guaranteed to match that measured for the standard installation with Skew angle between 10° - 20° (see reading diagrams in par. 4.4.1).
DS6400
NOTE
The ST-210 mounting bracket is an accessor model available in the US-60 kit (890001020).
y of the DS6400 standard
2.7 TYPICAL LAYOUTS
The DS6400 scanners can be connected in a variety of layouts depending on the number of scanners used and the required complexity of the reading station. These layouts range from Single Stand Alone to Complex Lonworks Networks.
everal power supplies are available to power the reading stations. Photoelectric sensors
S used as code presence sensors and optical encoders to signal conveyor speed are also available accessories.
The following typical layouts refer to the system hardware configurations, but they also require the correct setup of the software configuration paramete
rs (see par. 3.2 for details).
he accessories and cables indicated in the following figures are Datalogic products. We
T suggest their use to guarantee
the correct system functioning.
2.7.1 Point-to-Point
Using a Point-to-Point layout, the data is transmitted on the Main interface as well as on the Auxiliary inte communications. Two different layouts are available according to the DS6400 reader model used for the connection.
rface. The Main interface can be selected for RS232 or RS485 full-duplex
36
INSTALLATION
2
Master/Slave Models
When On-Line operating mode is used, the reader is activated by an External Trigger (photoelectric sensor) when the object enters its reading zone. In the following case, the signal is passed to the DS6400 by the C-BOX 100, which also supplies the system.
M/S
CAB-600X
C-BOX 100
Local Host
Presence
Sensor*
PG6000
* P.S. (Presence Sensor) connected to External Trigger/PS input.
Figure 50 – Point-to-Point for Master/Slave Models
Fieldbus Models
In this case no External Trigger is used and the C-BOX 100 only supplies the reader. The DS6400 (Ethernet, DeviceNet or Profibus model) is connected to a fieldbus remote Host. It can be activated by a signal generated by the remote Host or be always active if working in Automatic operating mode.
Fieldbus Network
Fieldbus
CAB-601X
C-BOX 100
PG6000
Remote Host
Figure 51 – Point-to-Point for Fieldbus Models
37
2
A
A
A
DS6400
2.7.2 Pass Through
When Pass Through is activated on the Auxiliary interface, the DS6400 reader (all models) can be integrated in a network consisting of different scanners not provided with a Lonworks interface.
This connection mode allows two or more devices to be connected to a single external serial interface. The DS6400 transmits the messages received by its auxiliary interface (RS232 only) onto its main interface.
In this configuration a series of scanners can be connected together using RS232 on the main interface and all messages will be passed through this chain to the host. The reading phase of each scanner is independent from the others. In Pass Through connections each scanner is provided with its relative External Trigger (multi P.S.).
Applications can be implemented to connect a device such as a hand-held reader to the Auxiliary port for manual code reading capability.
For the RS232 connections the maximum cable length is 15 m (50 ft).
The DS4600A scanners represented in the following figures are configured in Pass Through mode.
P.S.* P.S.*
DS4600
<
T
N
DS6400
CAB-600X
P.S.*
PWR-120
C-BOX 100
MAIN
AUX
1
.
2
Local Host
E
<
C-BOX 100 C-BOX 100
2
1
1
Main Serial Interface
uxiliary Serial Interface
2
* P.S. (Presence Sensor) connected to External Trigger/PS input.
Figure 52 – Pass Through Connection for DS6400 Master/Slave Models
Gryphon
DS4600
<
T
N
E
<
1
38
INSTALLATION
A
A
A
Remote Host
2
P.S.*
<
T N
E
<
C-BOX 100
DS4600
Gryphon
DS6400
PWR-120
bus
Field
Network
CAB-601
P.S.*
P.S.*
<
DS4600
T
N E
<
X
AUX
C-BOX 100
2 1 2 1
C-BOX 100
uxiliary Serial Interface
1
Main Serial Interface
2
* P.S. (Presence Sensor) connected to External Trigger/PS input.
Figure 53 – Pass Through Connection for Fieldbus Models
2.7.3 RS232
Master/Slave
The RS232 mas network consisti
ter/slave connection is used to integrate a DS6400 reader (all models) in a
ng of different scanners not provided with a Lonworks interface.
The Sla e scan
v scanner transmi . All messages wi
ners use RS232 only on the main and auxiliary interfaces. Each slave ts the messages received by the auxiliary interface onto the main interface ll be transferred towards the master.
he master scanner is connected to the Host PC on the main RS232 serial interface through
T the C-BOX 100 (20 mA C.L. can be used if the INT-30 accessory is installed).
In RS232 Master/Slave connections the External Trigger signal is unique to the system (single P.S.).
The DS6400 master/slave scanner model (DS6400-10X-010 only),
working as Master in an
connected to a
Lonworks network consisting of DS6400 slave scanners.
RS232 network, may be simultaneously
Be careful when assigning the slave address, since the number of the first
Lonworks slave must be a progressive number with respect to the
NOTE
address number defined for the last slave scanner of the RS232 network.
For example, if the RS232 network consists of Slave 1 and Slave 2, the
address to be assigned to the first Lonworks slave scanner will be Slave 3
(not Slave 1).
39
2
A
A
DS6400
DS6400- Master
C-BOX 100
1
DS4600A
Slave 1
<
T
<
N E
CAB-600X
P.S.*
AUX
MAIN
2
Local Host
C-BOX 100
2
<
T
N
E
<
DS4600A
Slave 2
PWR-120
C-BOX 100
1
Main Serial Interface
uxiliary Serial Interface
2
1
* P.S. (Presence Sensor) connected to External Trigger/PS input.
Figure 54 – RS232 Master/Slave for DS6400 Master/Slave Models
DS6400
Master
Fieldbus
Net
CAB-601X
work
1
Remote Host
DS4600A
Slave 2
T
<
N
E
1
C-BOX 100
* P.S. (Presence Sensor) connected to
External Trigger/PS input.
1
Main Serial Interface
uxiliary Serial Interface
2
Figure 55 – RS232 Master/Slave for DS6400 Fieldbus Models
40
<
DS4600A
Slave 1
<
T N
E
<
C-BOX 100
2
P.S.*
1
PWR-120
AUX
C-BOX 100
2
INSTALLATION
A
A
2
2.7.4 Multiplexer
The Multiplexer connection is used to integrate a DS6400 network consisting of different scanners not provided with a Lonworks interface.
Each scanner is connected to a Multiplexer (MX4000) with the RS485 half-duplex main interface.
P.S.*
P.S.*
P.S.*
slave reader in a Multidrop
<
T
N
E
<
OX 10
C-B 0
#0
DS4600
Local Host
PWR-120
MX4000
1
CAB-600X
C-B 0
OX 10
DS6400
<
DS4600
T
N
E
<
OX 10
C-B 0
#1 #31
1
RS485 HD Main Interface
* P.S. (Presence Sensor) connected to External Trigger/PS input.
Figure 56 – Multiplexer for DS6400 Master/Slave Models
The auxiliary serial interface of the slave scanners can be used to visualize collected data or to configure it using the Genius™ utility.
When On-Line operating mode is used, the scanner is activated by an External Trigger when the object enters its reading zone.
41
2
DS6400
2.7.5 Local Lonworks Network
A local Lonworks network allows logically connecting a DS6400 master reader with up to 31 DS6400 slaves. Actually, the maximum number of readers to be employed in the network depends on the system operating conditions; that is adopted operating mode and amount of data stream.
When creating your network, always keep in mind the following guidelines:
the Lonworks network logically supports a maximum number of 32 devices (master + slaves);
it is recommended to adhere to the 8-in-16 rule (not more than 8 devices in any 16 meter bus segment;
for DS6400 scanners the total bus length may extend up to 130 m (426 ft);
the maximum number of DS6400 readers supported also depends on the type of power
propagation adopted by the system (see the specific power supply installation manual for details).
Typically the layouts can be divided into Synchronized (single P.S.) or Multidata (multi P.S.) networks. They can be small (up to 10 scanners) or large (more than 10 scanners).
Contact Datalogic Automation S.r.l. if your network requires a higher number of readers or in case the application throughput is very high.
For further information on Lonworks network cabling and connections see the “LonWorks® TPT Twisted Pair Transceiver Module User’s Guide”, available from the website: www.echelon.com.
NOTE
For some DS6400 Lonworks Network layouts power is propagated through the scanners. For these layouts a special setting is required C-BOX 100 to pass scanner power to the presence sensor, encoder, etc.
in
42
INSTALLATION
2
Small Synchronized Network
When building a small local Lonworks network (less than 10 scanners), the DS6400 master reader must be connected to a local host computer or a C-BOX 100 by means of a CAB-60XX cable connected to the 25-pin or 26-pin D-sub male connector.
The master reader connects to the first slave reader of the system through the local Lonworks 9-pin female connector. For Master/Slave models, the local Lonworks 9-pin male connector must be properly terminated by inserting the BTK-6000 Lonworks terminator. Fieldbus models are provided with an internal Lonworks terminator.
The slave readers are connected together through the local Lonworks connectors. Only the 9-pin female connector of the last slave reader must be terminated by the BTK-6000 terminator.
The presence sensor is connected and powered through the C-BOX 100 by the scanner and is unique to the system. There is only a single reading phase and a single message from the master reader to the Local Host. The On-Line operating mode is used for this layout.
CAB-610X
BTK-6000
CAB-60XX
C-BOX 100**
Master
BTK-6000
P.S.*
Slave 1
CAB-63XX
PWR-120
* P.S. (Presence Sensor) connected to External Trigger/PS input.
** C-BOX 100 modified to accept scanner power.
*** Encoder connected to IN2/ENC input.
Figure 57 – Small Synchronized Network with 2 Readers
Encoder***
Local Host
43
2
DS6400
The following image shows a system consisting of six readers where:
the system is powered by the PWR-240
the master and all slaves are connected together through the CAB-610X cables
the external signals (trigger, encoder, serial to host, etc.) are connected to the master
through the C-BOX 100
one or more slaves are connected through CAB-63XX. The last slave must be terminated with the BTK-6000
Slave 2 Slave1
Master
CAB-610 CAB-610
X X
X CAB-610
CAB-610X
BTK-6000
Slave 5 Slave 4 Slave 3
CAB-610X
CAB-63XX
BTK-6000
CAB-60XX
* P.S. (Presence Sensor) connected to External Trigger/PS input.
** C-BOX 100 modified to accept scanner power
*** Encoder connected to IN2/ENC input.
Figure 58 – Small Synchronized Network with more than 2 Readers and Single Power Unit
C-BOX 100**
CAB-63XX
PWR-240
Host
PS*
Encoder
***
44
NOTE
If a single power source is used, it is not necessary to separate groups of scanners with "no power" cables (CAB-611X).
INSTALLATION
2
Large Synchronized Network
When building a large local Lonworks network (more than 10 scanners), an SC6000 Controller must be used together with a PWO power supply/junction box unit. In this case the SC6000 unit acts as the system master and is connected to the host through one of its interfaces.
All scanners act as slaves and are connected to the SC6000 through the PWO power supply/junction box. For DS6400 scanners, a single branch connector provides Lonworks communications between the scanners and the SC6000 unit. Power is distributed evenly by connecting groups of up to 4 Slave scanners through CAB-63XX cables. The last scanner on the line requires a Termination connector.
The allowed maximum bus length is 130 m.
External devices such as a presence sensor and an encoder are all connected to the PWO.
* P.S. (Presence Sensor) connected to External Trigger/PS input.
** Encoder connected to ENC input.
Figure 59 – Large Synchronized Network with DX6X00 and DS6XXX Scanners
**
*
45
2
r
r
r
r
DS6400
Multidata Network
In this layout, one master and up to 7 DS6400 slave readers have their own P.S. and therefore multiple reading phases. Each P.S. is connected through a C-BOX 100, which in turn is connected to its relative scanner through a CAB-60XX cable.
The master sends all the individual messages collected from the Lonworks interface as well as its own to the Local Host through its C-BOX 100.
The following image shows a system consisting of five readers, which are all connected together using CAB-611X cables and each scanner is individually powered by PG6000 through C-BOX 100.
C-BOX 100
Host
P.S.*
C-BOX 100
P.S.*
C-BOX 100
C-BOX 100
P.S.* P.S.*
C-BOX 100
P.S.*
PG6000
CAB-611X
BTK-6000
* P.S. (Presence Sensor) connected to External Trigger/PS input.
No powe
Slave 1 Master Slave 2 Slave 3 Slave 4
PG6000
CAB-611X CAB-611X
No powe
PG6000
No powe
Figure 60 – Multidata Network
PG6000
CAB-611X
No powe
PG6000
BTK-6000
46
INSTALLATION
2
2.7.6 Fieldbus Network
The Fieldbus Ethernet model offers connectivity without any converter or adapter needed.
The DS6400 master Fieldbus communicates with a remote host (for ex. remote PC connected via Internet) by means of a cable connected to the Fieldbus connector provided. It can be activated by a signal generated by the remote Host or by a physical presence sensor.
The external signals (trigger, encoder) are connected to the master through the C-BOX 100.
The master reader connects to the first slave reader of the system through the local Lonworks 9-pin female connector. Fieldbus models are provided with an internal Lonworks terminator.
The slave readers are connected together through the local Lonworks connectors. Only the 9-pin female connector of the last slave reader must be terminated by the BTK-6000 terminator.
The example below shows a system powered by the PWR-240 where multiple slaves are connected through CAB-63XX power cable. The master and all slaves are connected together through the CAB-610X cables.
The same network layouts are available as for the DS6400 standard model.
Remote Host

Fieldbus Network

Slave 2*** Slave1***
CAB-610X
BTK-6000
Slave 5*** Slave 4*** Slave 3***
CAB-610X
CAB-610X
CAB-60XX
CAB-610X
CAB-63XX
Master
C-BOX 100**
CAB-610X
PS*
Encoder****
CAB-63XX
PWR-240
* P.S. (Presence Sensor) connected to External Trigger/PS input.
** C-BOX 100 modified to accept scanner power.
*** The Slave scanners are Master/Slave models, which allow Lonworks network propagation.
**** Encoder connected to IN2/ENC input.
Figure 61 – Fieldbus Small Synchronized Network
47
2
DS6400
2.8 FLASH™ DYNAMIC FOCUS
The DS6400 has an innovative linear motor designed to control the focus position of the scanner via software. This dynamic system, called FLASH
TM,
is able to move the focus
position rail to rail, from the minimum position to the maximum position.
The FLASHTM functionalities are programmed via the GENIUS™ tool (refer to the GENIUS™ Help On-Line for details) and can operate in the following modes:

Fixed Mode

Continuous Mode

Triggered Mode
D-Flash™ Mode
2.8.1 Fixed Mode
In Fixed mode, the focus is set in the wished position via software (expressed in cm). This mode represents the basic Flash™ function, in which the focus position is adjusted in software and is stored in the scanner decoder. This function is similar to the focus adjustment available for the DS6300 scanner with the great difference that the adjustment is performed via software through the GENIUS™ tool and not through a manual adjustment of an external screw.
Figure 62 – Flash™ Fixed Mode
2.8.2 Continuous Mode
In Continuous mode, the focus position is continuously moving from a minimum position to a maximum position with a defined frequency (f1 in the figure below). This Flash™ function allows exploiting the whole reading range of the current DS6400 when the object to be detected is large and slow moving. Typical examples of applications for the Continuous mode are front side reading of big pallets, or reading on a fork lift truck.
Figure 63 – Flash™ Continuous Mode
48
INSTALLATION
2
2.8.3 Triggered Mode
In Triggered mode, the focus position can be set depending on the received external input (photocell, barrier, serial message…). This mode represents the most traditional Flash™ function, since it requires photocells, barriers or a dedicated interface to the Host (PC or PLC). The excellent performance of the DS6400 optic platform allows covering an area of 80 x 80 cm containing a 38 mm/15 mils resolution code by using one photocell only.
Figure 64 – Flash™ Triggered Mode
2.8.4 D-FLASH™ Mode
In D-Flash™ mode, the focus position can be set depending on the measured distance (Dn in the figure below) between the scanner and the scanned object. This is the most innovative and flexible function, that makes different software implementations possible. The D-FLASH™ solve the according to the specific application needs.
development has been based on the minimum distance detected. Thus, it can
main part of the applications. Further developments of D-FLASH™
will be provided
Figure 65 – Flash™ D-Flash™ Mode
49
2
DS6400
2.9 KEYPAD AND DISPLAY
The DS6400 keypad allows entering a menu for selection of one of the following functions:
Welcome: shows the current software release and operating mode;
Autolearn: starts the procedure making it possible to obtain an automatic, accurate and
fast configuration of DS6400 without the necessity of directly checking/modifying the relevant parameters;
Internal Net: defines scanner function within the network (see below);
Ethernet Mode: allows setting the scanner IP address to be used within the network;
LCD Contrast: sets the LCD contrast;
Bus: allows setting the scanner address (value range 0-125) to be used in a Profibus
network;
Test Mode: allows verifying the scanner reading position and features (see below).
The same settings may be performed by using the Genius™ program (see chapter 3 for details).
2.9.1 Internal Net
This submenu can be used as an alternative to configuration through Genius™, to assign the DS6400 scanner within a master/slave network. It allows defining the scanner function (slave/master) within the network and, if configured as Slave, its address. To enter the Internal Net submenu and configure the scanner follow the given procedure:
1) Press and hold both the (up arrow) and (down arrow) keys for about 2 seconds to enter the Main menu;
2) Use the ▲ (up arrow) or ▼ (down arrow) key to select the “Internal Net” item, then press the ENT (enter) key to confirm;
3) Use the ▲ (up arrow) or ▼ (down arrow) key to select the “LonWAddrSel”” item, then press the ENT (enter) key to confirm;
4) Use the ▲ (up arrow) or ▼ (down arrow) key to select your scanner function among “Master”, “Slave n”, “Slave jolly”, “Disabled”; then, press the ENT (enter) key to confirm;
5) Use the ▲ (up arrow) or ▼ (down arrow) key to select the “Exit” item, then press the ENT (enter) key to confirm. Repeat this step again to exit the Main Menu and return to the scanner current operating mode.
50
INSTALLATION
2
2.9.2 Test Mode
Test Mode is particularly advised during the installation phase, since it causes the reader to be continuously activated allowing to verify its reading features and its reading position with respect to the barcode. To enter the Test Mode submenu and configure the scanner follow the given procedure:
1) Press and hold both the (up arrow) and (down arrow) keys for about 2 seconds to enter the Main menu.
2) Use the ▲ (up arrow) or ▼ (down arrow) key to select the “Test Mode” item, then press the ENT (enter) key to confirm. The reader enters Test Mode.
3) Press the ▲ (up arrow) key to exit the Test Mode.
4) Use the ▲ (up arrow) and ▼ (down arrow) key to select the “Exit” item, then press the ENT (enter) key to confirm. The scanner exits the Main Menu and returns to its current operating mode.
51
3
DS6400
3 SOFTWARE CONFIGURATION
3.1 GENIUS™ INSTALLATION
Genius advantages:
Wizard approach for low skilled users;
Multi-language version;
Defined configuration directly stored in the reader;
Communication protocol independent from the physical interface allowing to consider the
To install Genius™, proceed as follows:
1) Turn on the PC that will be used for configuration, running either Windows 98, 2000/NT or
is a new Datalogic scanner configuration tool providing several important
reader as a remote object to be configured and monitored.
XP;
2) Insert the Genius™ CD-ROM;
3) Wait for the CD autorunning and follow the installation procedure.
3.2 GUIDE TO RAPID CONFIGURATION

3.2.1 Wizard for Quick Reader Setup

After installing the Genius™ software program (see par. 3.1) the following window appears asking the user to choose the desired configuration level:
Figure 66 - Genius™ Wizard Opening Window
The Wizard option is advised to low skilled users, since it shows a step by step scanner configuration. The parameters to be defined are the following:
- Barcode selection and definition;
- Operating mode selection and definition (see sub-paragraphs for further details);
- Digital Inputs/Outputs configuration;
- Hardware interface selection;
- Output data format configuration.
52
SOFTWARE CONFIGURATION
3
After defining the parameter values the following window appears allowing to complete the reader configuration as follows:
- Saving the configuration to disk;
- Switching to Advanced mode;
- Sending the configuration to the scanner.
Figure 67 - Genius™ Wizard Closing Window
est Operating Mode
T
This operating mode is not available when DS6400 works as slave.
NOTE
Figure 68 - Test Mode Selection
This operating mode causes the reader to be continuously activated allowing to verify its reading features and its reading position with respect to the barcode. For this reason, it is particularly advised during the installation phase of the reader.
After 100 scan, the values relative to an internal counter and the decoded code are displayed and transmitted on the serial interface. The counter reports the percentage of good reads of the label.
53
3
DS6400
On Line Operating Mode
Figure 69 - On Line Mode Selection
This operating mode requires the reader to be connected to an external Presence Sensor using EXT TRIG/PS A and EXT TRIG/PS B inputs.
During the active phase of the presence sensor, the DS6400 reader tries to acquire and correctly decode the code. In case the decoding phase is successful, the barcode characters are transmitted on the serial interface. Otherwise, a no read message is sent.
Automatic Operating Mode
Figure 70 - Automatic Mode Selection
This operating mode does not require the connection to an external Presence Sensor.
When working in this mode the reader is continuously scanning, while the reading phase is activated each time a barcode enters the reader reading zone. The reader stops reading after an N number of scans without a code. Barcode characters are transmitted on the serial interface. In case of a failed reading phase no message is sent to the host computer.
54
SOFTWARE CONFIGURATION
3

3.2.2 Genius™ Network Setup Through Master

The Network Setup allows configuring your Local Lonworks Network through the Master using Genius™.
Three different procedures are available to define the number of network slave scanners, their label and address according to two main conditions:
Condition Available Procedure Feature
Unknown Slave Addresses Net-Autoset
Known Slave Addresses
Network Wizard
Express Network Setup
automatically assigns random addresses to slave or Stand Alone scanners.
customizes the network (slave label and address definition and of a specific slave within network), updates configuration to a file and makes it ready to be sent to the Master.
automatically performs all the operations of the Network Wizard apart from the identification
of a specific slave scanner.
physical identification
physical
The Network Setup procedure as described requires Genius™ software version 1.06 or later. In addition, the Net-Autoset procedure requires
NOTE
scanner software version 6.40 or later.
1.
The first operation to perform is the configuration of your scanner as "Master" from the Local Device Network Settings item in the Device Menu, see figure below:
Figure 71 – Local Device Network Settings
55
3
DS6400
The following dialog box appears asking whether to send the configuration to the Master or not:
2. Click the "Yes" button, then click on the
icon available on the Toolbar to make the
“Devices” area appear next to the Parameter Explorer window. By repeatedly clicking the icon this area will be displayed or hidden.
Figure 72 – Cluster Configuration
Each scanner of the cluster is indicated by the following graphical objects:
check box allowing to select/deselect a specific scanner to perform the desired
operations (i.e. program downloading);
icon representing the scanner status;
a label reporting information transmitted by the scanner when connected (the scanner
address, generated errors, scanner description).
56
SOFTWARE CONFIGURATION
3
Then, proceed with the network setup by using one of the icons availab
3.
Bar according to the procedure to follow:
=
= Network Wizard procedure
=
Net-Autoset procedure
Express Network Setup procedure
le on the Tool
Net-Autoset
This procedure is to be used when all scanner addresses and labels are unknown (typically when configuring the network for the first time or whenever a network r
q
re uired).
By clicking the
-Autoset procedure is started allowing automatic assignment of random addresses to all
t
Ne
e or Stand Alone scanners connected w
slav ithin the network.
nc t is possible to:
O e the procedure has been completed, i
icon or selecting the "Net_Autoset" option from the right-click menu, the
econfiguration is
define customized addresses and labels through the Network Wizard
display the scanner default labels through the Express Network Setup.
;
Express Network Setup
Before performing this procedure, a Lonworks address must be assigned to each slave scanner. The most practical method is through the alternative address assignment methods.
Once all addresses have been assigned, the Express Network Setup is to be used when all scanner addresses and labels
By clicking on the procedure is started which automatically performs the following operations:
- opening the wizard;
- polling the network to discover connected scanners;
- transferring all scanners found to the "Requested Devices" area of the wizard where
your network customization is defined;
- saving the new network configuration;
Once the procedure has been completed, a dialog box will appear asking whether to send the configuration to the Master. Choose the “Yes” option to start this procedure.
icon or by choosing the related option from the right-click menu, the
do not need to be modified.
Net-Autoset procedure. See par. 3.2.3 for
57
3
DS6400
Network Wizard
Before performing this procedure, a Lonworks address must be assigned to each slave scanner. The most practical method is through the alternative address assignment methods.
Once all addresses have been assigned, the Network Wizard is to be used when one or more scanner addresses and labels
need to be modified.
Net-Autoset procedure. See par. 3.2.3 for
1. Click on the
a. if the
the Autodetect button to start a polling procedure of the current network. All slave scanners found will be represented in the “Current Devices” area. Then, select the
button to open the Network Wizard dialog box:
slave scanners have already been configured and wired to the network, click on
58
desired slave scanner from the “Current Devices” area and click on the drag and drop) to transfer it to the “Requested Devices” area where your network customization is defined. The following dialog box will appear allowing (if necessary) to change the slave address ("Available Device" field) and label ("Description" field):
if the slave scanners have not been configured and wired to the network, click on the
b.
icon to add a new device defining its address and model. The added slave scanner will be then displayed in the “Requested Devices” area. This option in any case requires that all slave scanners have their address set before the network can function.
icon (or
SOFTWARE CONFIGURATION
2. If desired, select a slave scanner within the "Current Devices" area and click on the
icon (or select the "Show Device" option from the right-click menu) to make the
dialog box appear as follows:
3
The "Show Device" option is particularly useful after the Net-Autoset procedure or whenever it is necessary to know which address is assigned to a specific slave scanner. Indeed, it activates the following signals which physically indicate the scanner corresponding to the one selected, in particular:
in Network Wizard the icon corresponding to the selected slave scanner starts
blinking red;
in the Physical Network all slave scanner lasers turn off except the one of the
selected scanner which turns on.
3. If desired, select the transferred/added slave scanner within the “Requested Devices”
area and click on the
icon to customize the scanner label and address.
4. Once your network has been customized, close the network wizard. Before closure, the program will show a dialog box asking whether to send the new configuration to the Master. Choose the “Yes” option to start this procedure.
59
3
DS6400
3.2.3 Alternative Slave Address Assignment
As alternatives to Network Setup through the Master, each Slave scanner can be assigned an address through the following methods:
address setting through the Local Device Network Settings item in the Device Menu
with the slave scanner connected to Genius™
manual address setting through slave scanner keyboard (see par. 2.9.1 for details).
3.3 ADVANCED GENIUS™ CONFIGURATION
The ADVANCED selection available when starting the Genius™ program is addressed to expert users being able to complete a detailed scanner configuration. By choosing this option it is possible either to start a new scanner configuration or to open and modify an old one. The desired parameters can be defined in the following window, similar to the MS Explorer:
Figure 73 - Genius™ Parameter Explorer Window
The procedure for setting the scanner parameters is supported by a help on-line, which is displayed in an HTML browser. It can be selected from the Configuration Help option available in the Help menu. In addition, a context-sensitive help can be enabled by pressing the <F1> key after selecting the desired parameter.
60
SOFTWARE CONFIGURATION
3
3.4 PARAMETER DEFAULT VALUES
The following table contains the list of the factory default settings for the DS6400. Genius™ also allows checking the parameter default values by selecting the "Compare parameters" option available in the Tools menu and comparing the current scanner configuration to the default one.
Parameter Default Setting Code Definition
Code Combination Single Label No read Message No Read String <CAN> Multiple Read Filters Disabled (unchecked) Code Label Settings #1 Code Symbology Interleaved 2 of 5 Label Length 8 Min Code Position 0 Max Code Position 255 Check Digit Disabled (unchecked) Decoding Safety 1 Decoding Severity 3 Match String Rule Match Pattern Match String Empty Match Direction Rule Disable Code Label Settings #2 Code Symbology Code 39 Label Length Variable Minimum Label Length 1 Maximum Label Length 60 Min Code Position 0 Max Code Position 255 Check Digit Disabled (unchecked) Decoding Safety 1 Decoding Severity 3 Match String Rule Match Pattern Match String Empty Match Direction Rule Disable Operating Modes Operating Mode Selection On Line On Line Options On Line 1 Input Start Input Number 1 Start Input Active Level Active Closed Reading Phase Timeout Disabled (unchecked) Verifier Disabled (unchecked)
Reading System Layout
Device Assignment Alone Modify&Backup Lon Slave Configuration Disabled (unchecked) Enable A.S.R. Disabled (unchecked)
Global No Read Message
61
3
DS6400
Parameter Default Setting Reading Parameters
Beam Shutter Disabled Overflow Start Ratio 5 Overflow Stop Ratio 5 Reading Mode Reconstruction Reading Condition Standard Reconstruction Parameters Enabled Stacked Code Disabled (unchecked) Extended Min Match 0 Position Tolerance 50 Duration Tolerance 50 Min Start/Stop Number 2 Inter Char Gap 8 Addon Overflow Ratio 2 Scan Line Amplitude Amplitude Settings Enable Disabled (unchecked) Flash Flash Mode Fixed Fixed Distance 60 Data Communication Settings Host Application Protocol Type Standard Data Format Header TX Start With data Termination After No Read Message Enabled (checked) Message Tx Trigger Selection On Decoding Format Type Standard Tx Max Delay After Phase Off Disabled Code Identifier Disabled Parameters Header String <STX> Code Position Disabled (unchecked) Code Direction Identifier Enable Disabled (unchecked) Termination String <CR><LF> Data Packet Separators <CR><LF> Code Field Length Setting Variable Length Main Serial Port Data Tx Enabled (checked) Heartbeat Disable Parameters Main Port Communication Mode Standard Main Port Electrical Interface RS232 Handshake None Baud Rate 9600 Parity None
62
SOFTWARE CONFIGURATION
Parameter Default Setting
Parameters Data Bits 8 Stop Bits 1 Auxiliary Serial Port Data Tx Enabled (checked) Heartbeat Disable Pass Through Disabled (unchecked) Parameters Baud Rate 115200 Parity None Data Bits 8 Stop Bits 1 Digital I/O Setting Digital Input Lines Setting Debouncing For Input 1, 3 and 4 5 ms Debouncing For Input 2 500 µs Input 1 Active Level Overridden by Op. Mode Active Closed Input 2 Active Level Overridden by Op. Mode Active Closed Input 3 Active Level Overridden by Op. Mode Active Closed Input 4 Active Level Overridden by Op. Mode Active Closed Output 1 Line State Normally Open Activation Event Complete Read Alternative Activation Event Wrong Deactivation Event Timeout Alternative Deactivation Event None Deactivation Timeout (ms) 50 Output 2 Line State Normally Open Activation Event No Read Alternative Activation Event Partial Read Deactivation Event Timeout Alternative Deactivation Event None Deactivation Timeout (ms) 50 Output 3 Line State Normally Open Activation Event None Alternative Activation Event None Deactivation Event None Alternative Deactivation Event None
System Information Section
User Information Section End User Name Empty Device Name Empty Line Name Empty
3
63
3
DS6400
Parameter Default Setting Diagnostics
PackTrack Debug Message Tx Disabled (unchecked) Enable Unchecked
Statistics
Disabled (unchecked)
64

READING FEATURES

α
4
4 READING FEATURES
4.1 ADVANCED CODE RECONSTRUCTION (ACR™ 4)
The traditional way of barcode reading could be called “Linear Reading”. In this case, the laser beam crosses the barcode symbol from its beginning to its end as shown in the following figure:
Laser Beam
Figure 74 – Linear Reading
In Advanced Code Reconstruction mode it is no longer necessary for the laser beam to cross the label from the start to the end. With just a set of partial scans on the label (obtained using the motion of the label itself), the DS6400 is able to “reconstruct” the barcode. A typical set of partial scans is shown in the figure below:
Code Direction
Figure 75 – Partial Scans
None of the partial scans contains the whole label. The decoder aligns each partial scan correctly and combines them in order to obtain the entire code.
The alignment is performed by calculating the time difference from one partial scan to another using a reference code element.

4.1.1 Tilt Angle for Advanced Code Reconstruction

The most important parameter in Advanced Code Reconstruction is the value of the maximum tilt angle (α maximum) under which the code reconstruction process is still possible.
Laser Beam
0° toαmax
= tilt angle
α
Figure 76 – Tilt Angle
65
4
α
KOKOKOK
K
DS6400
The decoder will be able to read the label with a tilt angle between + α max and - α max as shown in the following figure:
0°
O
O
No Read
-α+
No Read
Laser Beam
Figure 77 – Reading Zones with α Max
No Read
Conveyor
4.2 PACKTRACK™
PackTrack™ is a patented operating mode for Datalogic Omni-Directional Reading Stations used to read and correctly assign codes read on different packs when placed in the scanner Reading Area at the same time.
In fact, in the following example, the codes of two or more consecutive packs are found at the same time in the scanner reading area. Therefore, the condition occurs where, in the sequence of the two packs, the code of the second pack is read first, just before the code of the previous pack. A system without PackTrack™ would assign the code of the second pack to first pack and vice versa, thus causing a gross error in sortation.
Figure 78 – PackTrack™ System Layout
Working in PackTrack™ mode requires the presence of an encoder and a presence sensor to track the moving packs.
All PackTrack™ functionalities are programmed via the Genius™ tool (refer to the Genius™ Help On-Line for details).
66
READING FEATURES
4
For correct functioning, the PackTrack™ operating mode requires a calibration just after the installation of the scanners. This operation is absolutely necessary to make the scanner recognize its position in space. Thus, a fixed reference system is required.
PackTrack™ uses a right-handed reference system (right hand with thumb = X axis; forefinger = Y axis; middle finger = Z axis) where the axis X coincides with the PS line, the Y axis coincides with the conveyor direction and the Z axis is oriented upwards from the conveyor (see figure below).
This coordinate system is absolute for the reading station, i.e. is valid for all the scanners independently from their position or orientation with respect to the conveyor.
Three barcodes are placed along the scanline. For each of them, three coordinates are shown.
DS Scanner PackTrack™ Reference System
Figure 79 – DS Scanner PackTrack™ Reference System
67
4
DS6400

4.2.1 PackTrack™ Calibration for DS6400

By means of the Genius™ software tool SPY, the user can perform PackTrack™ calibration. Select the “SPY” option from the Tools menu or click on the related icon on the Genius™ toolbar to open the following dialog box:
Note: When selecting a slave scanner through the Master, click on the slave to calibrate in the Devices window, then click the SPY icon.
SPY ICON
Figure 80 – Opening the Spy Window
Once the Spy window has been opened, select the “PackTrack Calibration” option from the Tools menu:
68
Figure 81 – Selecting PackTrack™ Calibration
READING FEATURES
4
By selecting the “PackTrack Calibration” option a further dialog box appears allowing to start calibration:
Position 1
Position 2
Position 3
Figure 82 – Performing the PackTrack™ Calibration
1. Place the code at the desired position on the scan line (i.e. Position 1)
2. Measure the X, Y and Z coordinates relative to the center of the code and enter them into the corresponding edit boxes.
3. Press the Calibrate button for Position 1 to start the calibration.
4. Repeat the same procedure for Position 2 and Position 3.
5. Press the “Validate Calibration” button to validate the calibration settings.
Before closing the dialog box, press the Run Test button to test the calibration results and efficiency.
cessary. For
NOTE
In the vast majority of systems the x and z data are not ne these cases set x = 0, z= 0 during the calibration procedure.
69
4
DS6400

4.2.2 PackTrack™ Calibration for DS6400 Oscillating Mirror Models

The DS6400 oscillating mirror models can be used in PackTrack™ operating mode only when the scanner is mounted so that the shown in the following figure:
Conveyor
Direction
Figure 83 – Oscillating Mirror Models in PackTrack™ Mode
PackTrack™ Calibration must be made while the conveyor plane and fixed (not oscillating).
scan line is parallel to the conveyor direction as
Scan
Line
scanning plane is perpendicular to the
4.3 PERFORMANCE
The scan rate is 800 scans/sec.
Refer to the diagrams in par. 4.4 for further details on the reading features. These diagrams are taken on various resolution sample codes at a 25 °C ambient temperature depending on the conditions listed under each diagram.
4.3.1 Reading Conditions
ANSI Grade B minimum
800 scans/sec
The following tables describe the requirements for standard applications.
Minimum Code Height for ACR Reading (mm) 45° 30°
Conveyor Speed (m/s) 0.5 1 1.5 2 2.5 3 0.5 1 1.5 2 2.5 3
10 12 14 16 18 20 7 9 10 12 13 15 12 14 15 17 19 21 8 9 11 12 14 15 13 14 16 18 20 22 8 10 11 13 14 16 14 16 18 19 21 23 9 11 12 14 15 17 18 19 21 23 25 26 11 12 14 15 17 18 24 25 27 28 30 32 15 16 17 19 20 22 33 34 35 36 38 40 20 21 22 23 25 26
2/5 Interleaved
Code Resolution
(mm)
0.25
0.30
0.33
0.38
0.50
0.72
1.00
Ratio 3:1
70
Table 1
READING FEATURES
4
Minimum Code Height for ACR Reading (mm) 45° 30°
Conveyor Speed (m/s) 0.5 1 1.5 2 2.5 3 0.5 1 1.5 2 2.5 3
9 10 12 14 16 17 6 7 9 10 12 13 10 11 13 15 17 18 7 8 9 11 12 14 11 12 13 15 17 19 7 8 10 11 13 14 12 13 14 16 18 20 8 9 10 12 13 15 15 16 17 18 20 22 10 10 11 13 14 16 20 21 22 23 24 26 13 13 14 15 17 18 27 28 29 30 31 32 17 17 18 19 20 21
Code 39
Code Resolution
(mm)
0.25
0.30
0.33
0.38
0.50
0.72
1.00
Ratio 3:1; Interdigit = Module Size
Table 2
Minimum Code Height for ACR Reading (mm) 45° 30°
Conveyor Speed (m/s) 0.5 1 1.5 2 2.5 3 0.5 1 1.5 2 2.5 3
8 9 11 13 15 17 5 7 8 10 11 13
8 10 12 14 16 18 6 7 9 10 12 13
9 11 13 14 16 18 6 8 9 11 12 14 10 11 13 15 17 19 7 8 10 11 13 14 12 13 15 17 19 21 8 9 11 12 14 15 16 17 19 21 22 24 10 11 13 14 16 17 22 23 24 25 27 29 13 14 15 17 18 20
Code 128 – Ean 128
Code Resolution
(mm)
0.25
0.30
0.33
0.38
0.50
0.72
1.00
Table 3
Minimum Code Height for ACR Reading (mm) 45° 30°
Conveyor Speed (m/s) 0.5 1 1.5 2 2.5 3 0.5 1 1.5 2 2.5 3
8 9 11 13 15 17 5 7 8 10 11 13
9 10 12 14 16 18 6 7 9 10 12 13
9 11 13 14 16 18 6 8 9 11 12 14 10 11 13 15 17 19 7 8 10 11 13 14 13 14 15 17 19 21 8 9 11 12 14 15 17 18 19 21 22 24 11 12 13 14 16 17 23 24 25 26 27 29 14 15 16 17 18 20
Codabar
Code Resolution
(mm)
0.25
0.30
0.33
0.38
0.50
0.72
1.00
Ratio 3:1; Interdigit = Module Size
Table 4
Minimum Code Height for ACR Reading (mm) 45° 30°
Conveyor Speed (m/s) 0.5 1 1.5 2 2.5 3 0.5 1 1.5 2 2.5 3
7 9 10 12 14 16 5 6 8 9 11 12
8 9 11 13 15 17 6 7 8 10 11 13
9 10 11 13 15 17 6 7 9 10 12 13 10 11 12 14 16 18 7 7 9 10 12 13 12 13 14 15 17 19 8 9 10 11 13 14 16 17 18 19 20 22 10 11 12 13 14 16 22 23 24 24 25 26 13 14 15 16 16 18
EAN 8-13, UPC-A
Code Resolution
(mm)
0.25
0.30
0.33
0.38
0.50
0.72
1.00
Table 5
71
4
DS6400
4.4 READING DIAGRAMS
The reading diagram given below illustrates the convention used to calculate the minimum and maximum reading distance for barcodes. This procedure allows calculating the reading distance of your scanner when working with a focus different from the one displayed in the reading diagrams given in par. 4.4.1 and par. 4.4.2.
Draw a straight vertical line at the minimum focus distance value; the points of intersection between this line and the global reading area give the minimum reading distance.
Draw a circumference from the origin (0,0) with a radial distance equal to the maximum scanner focus distance. The points of intersection between this circumference and the global reading area give the maximum reading distance.
Maximum Reading
Minimum Reading
Distance
Distance
Global
Reading Area
0
Minimum Reading
Distance
Maximum Reading
Maximum Reading
Distance
Distance
Figure 84 – Calculating a Scanner Reading Area
72
READING FEATURES
4

4.4.1 DS6400 Standard Model

DS6400-100-0XX - Resolution: 0.20 mm/8 mils
The diagram shows a global reading area, which includes all possible focus positions, and the reading area obtained for the DS6400-100-0XX operating with focus position = 65 cm and barcode density of 0.20 mm (8 mils). It is possible to obtain the minimum and maximum distance values by referring to the radial distance curves displayed in Figure 86.
16
14
12
10
8
0 14 20
0 35 40 45 50 55 60 65 70
40
35
30
25
20
16 18 22 24
2826 30 32
75 80
36 34 38 40
85 90 95 100
Global Reading
Area
(in) (cm)
6
15
4
10
2
5
0
-2
-4
-6
-8
-10
-12
-14
-16
(in)
0
-5
-10
-15
-20
-25
-30
-35
-40
(cm)
Figure 85 – Standard Model 0.20 mm / 8 mils Reading Diagram
Note: (0,0) is the center of the laser beam output window.
CONDITIONS
Code = Interleaved 2/5 or Code 39 PCS = 0.90 Pitch angle = 0° Skew angle = 10° - 20° Tilt angle = 0°
Focus
Position = 65 cm
73
4
The curves show the minimum and maximum radial distance.
Reading distance
(in)
(cm)
40
100
38
95
36
90
34
85
Max. Reading
32
30
28
26
80
75
70
65
Distance
DS6400
Min. Reading
Distance
24
22
20
18
16
60
55
50
45
40
0
0
40 45 50 55 60 65 70 75
16 22
18 20 24 26 3028 32 34 38 36 40
Figure 86 – Standard Model 0.20 mm / 8 mils Radial Distance
80 85 90 95
100
(cm)
(in)
Focus Distance
74
READING FEATURES
DS6400-100-0XX - Resolution: 0.25 mm/10 mils
The diagram shows a global reading area, which includes all possible focus positions, and the reading area obtained for the DS6400-100-0XX operating with focus position = 90 cm and barcode density of 0.25 mm (10 mils). It is possible to obtain the minimum and maximum distance values by referring to the radial distance curves displayed in Figure 88.
0 12 24
16 20
28
32
40
36 44 48
56 52
4
(in)
24
20
16
12
8
4
0
-4
-8
-12
0 30 40 50 60 70 80 90 100
60
50
Global Reading
Area
40
30
20
10
0
-10
-20
-30
110 120
130 140
(cm)
-16
-24
(in)
Note: (0,0) is the center of the laser beam output window.
-40
-50
-20
-60
(cm)
Figure 87 – Standard Model 0.25 mm / 10 mils Reading Diagram
CONDITIONS
Code = Interleaved 2/5 or Code 39 PCS = 0.90 Pitch angle = 0° Skew angle = 10° - 20° Tilt angle = 0°
Focus
Position = 90 cm
75
4
The curves show the minimum and maximum radial distance.
Reading distance
(cm)
(in)
48
120
46
115
44
110
42
105
40
100
38
36
34
95
90
85
Max. Reading
Distance
DS6400
32
80
30
28
26
24
22
20
75
70
65
60
55
50
0
45 50 55 60 65 70 75 80
18 24
20 22 26 28 3230 34 36 4038 42
Figure 88 – Standard Model 0.25 mm / 10 mils Radial Distance
85 90 95 100 105
Min. Reading
Distance
110 115
44 46
Focus Distance
(cm)
(in)
76
READING FEATURES
DS6400-100-0XX - Resolution: 0.30 mm/12 mils
The diagram shows a global reading area, which includes all possible focus positions, and the reading area obtained for the DS6400-100-0XX operating with focus position = 110 cm and barcode density of 0.30 mm (12 mils). It is possible to obtain the minimum and maximum distance values by referring to the radial distance curves displayed in Figure 90.
0 16 28
20 24 32 36
4440 48 52
60 56
64
4
(in)
24
20
16
12
8
4
0
-4
-8
-12
0 40 50 60 70 80 90 100 110
60
50
Global Reading
Area
40
30
20
Focus
10
Position = 110 cm
0
-10
-20
-30
120 130
140 150
160
(cm)
-16
(in)
Note: (0,0) is the center of the laser beam output window.
-40
-50
-20
-60
-24
(cm)
Figure 89 – Standard Model 0.30 mm / 12 mils Reading Diagram
CONDITIONS
Code = Interleaved 2/5 or Code 39 PCS = 0.90 Pitch angle = 0° Skew angle = 10° - 20° Tilt angle = 0°
77
4
The curves show the minimum and maximum radial distance.
Reading distance
(cm)
(in)
72
180
68
170
64
160
60
150
56
140
52
130
48
44
120
110
Max. Reading
Distance
DS6400
40
100
36
90
32
28
24
20
16
80
70
60
50
40
0
55 60 65 70 75 80 85 90
22 28
24 26 30 32 3634 38 40 4442 46
Figure 90 – Standard Model 0.30 mm / 12 mils Radial Distance
95 100 105 110 115
Min. Reading
Distance
120
48 50
Focus Distance
125
130
52
(cm)
(in)
78
READING FEATURES
4
DS6400-100-0XX - Resolution: 0.38 mm/15 mils
The diagram shows a global reading area, which includes all possible focus positions, and the reading area obtained for the DS6400-100-0XX operating with focus position = 140 cm and barcode density of 0.38 mm (15 mils). It is possible to obtain the minimum and maximum distance values by referring to the radial distance curves displayed in Figure 92.
(in)
0 16 28
20 24 32 36
4440 48 52
60 56
64
68
72
28
24
20
16
12
8
4
-4
-8
-12
0
0 40 50 60 70 80 90 100 110
70
60
50
40
30
20
10
0
-10
-20
-30
Global Reading
Area
Focus
Position = 140 cm
120 130
140 150
160
170 180
(cm)
-40
-16
-50
-20
-60
-24
-28
-70
(in)
(cm)
Figure 91 – Standard Model 0.38 mm / 15 mils Reading Diagram
Note: (0,0) is the center of the laser beam output window.
CONDITIONS
Code = Interleaved 2/5 or Code 39 PCS = 0.90 Pitch angle = 0° Skew angle = 10° - 20° Tilt angle = 0°
79
4
The curves show the minimum and maximum radial distance.
Reading distance
(in)
(cm)
72
180
68
170
64
60
56
52
48
44
160
150
140
130
120
110
Max. Reading
Distance
DS6400
40
36
32
28
24
20
16
100
90
80
70
60
50
40
0
40
50 60 70 80 90 100 110 120
20 32
16
Figure 92 – Standard Model 0.38 mm / 15 mils Radial Distance
24 28 36 40 4844 52 56 64 60 68
130 140 150 160 170
Min. Reading
Distance
(cm)
180
(in)
72
Focus Distance
80
READING FEATURES
4
DS6400-100-0XX - Resolution: 0.50 mm/20 mils
The diagram shows a global reading area, which includes all possible focus positions, and the reading area obtained for the DS6400-100-0XX operating with focus position = 120 cm and barcode density of 0.50 mm (20 mils). It is possible to obtain the minimum and maximum distance values by referring to the radial distance curves displayed in Figure 94.
72
28
24
20
16
12
0 16 28
0 40 50 60 70 80 90 100 110
70
60
50
40
30
20 24 32 36
Global Reading
Area
4440 48 52
120 130
6056
140 150
68
16064170 180
76
190
80
200
(in)
(cm)
8
20
4
10
0
0
-10
-4
-20
-8
-30
-12
-40
-16
-50
-20
-60
-24
-28
-70
(cm)
(in)
Figure 93 – Standard Model 0.50 mm / 20 mils Reading Diagram
Note: (0,0) is the center of the laser beam output window.
CONDITIONS
Code = Interleaved 2/5 or Code 39 PCS = 0.90 Pitch angle = 0° Skew angle = 10° - 20° Tilt angle = 0°
Focus
Position = 120 cm
81
4
The curves show the minimum and maximum radial distance.
Reading distance
(in)
(cm)
80
200
76
190
72
180
68
170
64
160
DS6400
60
56
52
48
44
40
36
32
28
24
20
150
140
130
120
110
100
90
80
70
60
50
0
40
16
Figure 94 – Standard Model 0.50 mm / 20 mils Radial Distance
Max. Reading
Distance
Min. Reading
50 60 70 80 90 100 110 120
20 32
24 28 36 40 4844 52 56 64 60 68
130 140 150 160 170
Distance
(cm)
180
(in)
72
Focus Distance
82
READING FEATURES
4

4.4.2 DS6400 Oscillating Mirror Model

DS6400-105-0XX - Resolution: 0.20 mm/8 mils
The diagram shows a global reading area, which includes all possible focus positions, and the reading area obtained for the DS6400-105-0XX operating with focus position = 60 cm and barcode density of 0.20 mm (8 mils). It is possible to obtain the minimum and maximum distance values by referring to the radial distance curves displayed in Figure 96.
16
14
12
10
8
0 14 20
0 35 40 45 50 55 60 65 70
40
35
30
25
20
16 18 22 24
2826 30 32
75 80
Global Reading
3634 38 40
85 90 95 100
Area
(in)
(cm)
6
15
4
10
2
5
0
0
-5
-2
-10
-4
-15
-6
-20
-8
-25
-10
-30
-12
-35
-14
-16
-40
(cm)
(in)
Figure 95 – Oscillating Mirror Model 0.20 mm / 8 mils Reading Diagram
Note: (0,0) is the center of the laser beam output window.
CONDITIONS
Code = Interleaved 2/5 or Code 39 PCS = 0.90 Pitch angle = 0° Skew angle = 10° - 20° Tilt angle = 0°
Focus
Position = 60 cm
83
4
The curves show the minimum and maximum radial distance.
Reading distance
(in)
(cm)
DS6400
36
34
32
30
28
26
24
22
20
18
16
90
85
80
75
70
65
60
55
50
45
40
Max. Reading
Distance
Min. Reading
Distance
0 0
40 45 50 55 60 65 70 75
16 22
18 20 24 26 3028 32 34 36
80 85 90
Focus Distance
Figure 96 - Oscillating Mirror Model 0.20 mm / 8 mils Radial Distance
(cm)
(in)
84
Loading...