DART Controls 65 series, 65E10 Instruction Manual

CONTROLS
Instruction Manual
For DC Input Variable Speed Controls
P.0. Box 10 5000 W. 106th Street
65E10 CONTROL SERIES
LT56 (IM-65E10-0303)
Zionsville, Indiana 46077
Phone (317) 873-5211
www.dartcontrols.com
A-5-3180A
TABLE OF CONTENTS
WARRANTY .................................................................................................................................................................................1
STANDARD FEATURES..............................................................................................................................................................1
CONTROL DIMENSIONS.............................................................................................................................................................1
MOUNTING DIMENSIONS ...........................................................................................................................................................2
65E10 MOUNTING .......................................................................................................................................................................2
INSTALLATION.............................................................................................................................................................................2
HOOK-UP DIAGRAMS ................................................................................................................................................................. 2
65E10 HOOK-UP DIAGRAM ....................................................................................................................................................... 3
65E10 REVERSING HOOK-UP DIAGRAM .................................................................................................................................3
INHIBITING THE CONTROL ........................................................................................................................................................3
TRIMPOT ADJUSTMENTS ..........................................................................................................................................................4
IN CASE OF DIFFICUL TY ............................................................................................................................................................4
MODEL SELECTION ....................................................................................................................................................................4
SPECIFICA TIONS ........................................................................................................................................................................5
WARRANTY
Dart Controls, Inc. (DCI) warrants its products to be free from defects in material and workmanship. The exclusive remedy
for this warranty is DCI factory replacement of any part or parts of such product which shall within 12 months after delivery to the purchaser be returned to DCI factory with all transportation charges prepaid and which DCI determines to its satisfaction to be defective. This warranty shall not extend to defects in assembly by other than DCI or to any article which has been repaired or altered by other than DCI or to any article which DCI determines has been subjected to improper use. DCI assumes no responsibility for the design characteristics of any unit or its operation in any circuit or assembly. This warranty is in lieu of all other warranties, express or implied; all other liabilities or obligations on the part of DCI, including consequen­tial damages, are hereby expressly excluded.
NOTE: Carefully check the control for shipping damage. Report any damage to the carrier immediately. Do not attempt to operate the drive if visible damage is evident to either the circuit or to the electronic components.
All information contained in this manual is intended to be correct, however information and data in this manual are subject to change without notice. DCI makes no warranty of any kind with regard to this information or data. Further, DCI is not respon­sible for any omissions or errors or consequential damage caused by the user of the product. DCI reserves the right to make manufacturing changes which may not be included in this manual.
WARNING
Improper installation or operation of this control may cause injury to personnel or control failure. The control must be installed in accordance with local, state, and national safety codes. Make certain that the power supply is disconnected before attempting to service or remove any components!!! If the power disconnect point is out of sight, lock it in disconnected position and tag to prevent unexpected application of power. Only a qualified electrician or service personnel should perform any electrical troubleshooting or maintenance. At no time should circuit continuity be checked by shorting terminals with a screwdriver or other metal device.
STAND ARD FEATURES
●●
Provides smooth variable speed capability for mobile equipment
●●
●●
Maintains variable speed control as batteries discharge
●●
●●
Adjustable maximum speed, minimum speed, current limit, I.R. compensation, and accel
●●
●●
Inhibit terminal permits optional start-stop without breaking battery lines
●●
●●
Speed potentiometer, knob, and dialplate included
●●
●●
Increases range or running time of battery operated equipment through high efficiency
●●
MODEL WIDTH LENGTH DEPTH WEIGHT
65E10 3.625 (9.21) 4.25 (10.76) 1.30 (3.30) 6.0 (170)
CONTROL DIMENSIONS
inches (centimeters) oz. (gms.)
1
MOUNTING DIMENSIONS
65E10 MOUNTING
4.250"
.188" DIA.
(6 SLOTS)
11/32"
SLOT DEPT
MIN
MAX
ACCEL
IR COMP
CUR LIM
TOP VIEW
P1
-9
-8
-7
-6
-5
-4
-3
-2
-1
.694"
1.750"
.380"
3.625"
1.300"
.315"
3.750"
SIDE VIEW
Caution: Do not mount controller where ambient temperature is outside the range of -10° C (15° F) to 45° (115° F).
INSTALLATION
Before attempting to wire the control, make sure all power is disconnected. Recheck code designation to assure proper voltage is present for the control. Caution should be used in selecting proper size of hook-up wire for current and voltage drop.
HOOK-UP DIAGRAMS
WARNING: DO NOT REVERSE POSITIVE AND NEGATIVE BATTERY LEADS. THIS WILL DAMAGE THE CONTROL. TO CHANGE MOTOR DIRECTION, INTERCHANGE THE POSITIVE AND NEGATIVE ARMATURE LEADS.
Refer to the wiring diagrams below for proper connection of DC Voltage, Armature, and Speedpot wiring to the control. CAUTION !! TURN POWER
OFF WHILE MAKING CONNECTIONS.
To properly adjust the CURRENT LIMIT setting, a DC ammeter should be placed in series with the armature line. This meter can be removed after the control is adjusted.
2
Min Speed
Max Speed
Accel
Min Speed
Current Limit
I.R. Comp.
Inhibit (P1-9)
Common (P1-8)
Pot Low (P1-7)
Pot Wiper (P1-6)
Pot High (P1-5)
-Arm (P1-4)
+Arm (P1-3)
+Battery (P1-2)
-Battery (P1-1)
P1
5K
Speedpot
Red
Orange
Optional
Inhibit
(see hook-up
below)
Battery
Customer supplied
SPST switch or relay
White
Motor
Customer supplied
3PDT Center-off
Center-blocked switch
Max Speed
Accel
I.R. Comp.
Current Limit
65E10 HOOK-UP DIAGRAM
Optional
Inhibit
(see hook-up
below)
P1
Inhibit (P1-9)
Common (P1-8)
Pot Low (P1-7)
Pot Wiper (P1-6)
Pot High (P1-5)
-Arm (P1-4)
+Arm (P1-3)
+Battery (P1-2)
-Battery (P1-1)
Orange
Red
White
Speedpot
Battery
Customer supplied
SPST switch or relay
65E10 REVERSING HOOK-UP DIAGRAM
5K
Motor
Using inhibit input - provides fast start-
stop by bypassing accel/decel circuit
Inhibit (P1-9)
Common (P1-8)
Pot Low (P1-7)
Pot Wiper (P1-6)
Pot High (P1-5)
P1
Note: Always use a shielded cable when connecting to the inhibit terminal. The shield of the cable should connect to the Common terminal of the control.
INHIBITING THE CONTROL
Inhibit via speedpot - provides starting and
stopping through accel/decel parameters
Inhibit (P1-9)
SPST Switch
open = run
close = stop
Common (P1-8)
Pot Low (P1-7)
Pot Wiper (P1-6)
Pot High (P1-5)
P1
3
SPST Switch
open = stop
close = run
Orange
Red
White
5K
Speedpot
TRIMPOT ADJUSTMENTS
Before the power is applied, the speed potentiometer and trimpots should be preset as follows: TRIMPOT PRESET
1. Preset speedpot fully CCW, preset Max trimpot CW 1/2 way, preset Current Limit trimpot fully CW, preset Min trimpot fully CCW, preset Accel trimpot CW 1/2 way, preset I.R. trimpot fully CCW.
DC power can now be applied to the system and the control adjusted as directed below: TRIMPOT ADJUSTMENT
2. Increase the MIN trimpot in a clockwise direction until just before reaching an output voltage (deadband) or until the desired minimum speed is reached.
3. Turn the Speedpot fully clockwise and adjust the MAX trimpot until the desired maximum speed is reached.
4. Adjust the ACCEL trimpot to achieve the desired soft start time. CW rotation will increase accel time.
5. Rotate the CURRENT LIMIT trimpot fully CCW. Apply a full load to the motor. While motor is stalled adjust the CURRENT LIMIT trimpot CW until a desired current setting is obtained. Approximately 125% of rated motor current is recommended.
6. Set speedpot to approximately 50% and note the motor RPM. Load the motor to normal load condition and adjust I.R. trimpot CW until motor RPM is equal to unloaded speed.
IN CASE OF DIFFICULTY
PROBLEM POSSIBLE CAUSE(S) CORRECTIVE ACTION
Motor doesn’t run • Incorrect or no power
• Speedpot set at zero
• Worn motor brushes
• Current limit set too low
Motor “hunts” • Max trimpot set too high
• I.R. Comp. trimpot set too high Motor runs at “full speed” uncontrollable
Motor rotates in wrong direction • Motor armature hooked up backwards Reverse armature + and - leads Motor stalls under a light load • Current limit trimpot improperly adjusted See “Trimpot Adjustments” - page 3-4
• Loose speedpot connections
• Min. or Max. trimpots not properly adjusted
• Possible control failure
Install proper service Rotate speedpot fully CW Replace motor brushes Adjust current limit trimpot CW See “Trimpot Adjustments” - page 3-4 See “Trimpot Adjustments” - page 3-4 Secure all connections See “Trimpot Adjustments” - page 3-4 Send to Dart Controls, Inc.
If a newly installed control will not operate, it is likely that a terminal or connection is loose. Check to make sure connections are secure and correct. If the control is still inoperative, refer to the following chart for reference:
MODEL SELECTION
INPUT VOLTAGE OUTPUT VOLTAGE CONTINUOUS CURRENT MODEL NUMBER
12 VDC ± 15% 0 - 12 VDC 10 amps D.C. 65E10-12 24 VDC ± 15% 0 - 24 VDC 10 amps D.C. 65E10* 36 VDC ± 15% 0 - 36 VDC 10 amps D.C. 65E10*
* 24 volt and 36 volt units with the same current ratings are interchangeable (ie. 24 volt unit will operate with 36 volt input
and a 36 volt unit will operate with 24 volt input, same current rating).
4
SPECIFICATIONS
65E10
Load current (continuous) 10 amps Speed adjustment
Speed range 30 : 1 Overload capacity 200% for 10 seconds; 150% for one minute Current limit adjustable 100% to 200% of full motor load, up to 200% of control current rating Acceleration adjustable - 0 to 10 seconds Deceleration non-adjustable - 0.5 seconds Maximum speed adjustable - 50 to 100% of base speed Minimum speed adjustable - 0 to 30% of max speed Connections Euro-style terminal block (14Ga. to 28Ga..) Speed regulation
Operating temperature -10°C to +45°C (14°F to 113°F) Package configuration
Internal operating frequency approximately 18K Hertz
5K potentiometer or 0 to +10VDC input signal
1% of base speed via adjustable I.R. Compensation trimpot
black anodized aluminum extrusion
5
NOTES:
6
REPAIR PROCEDURE
In the event that a Product manufactured by Dart Controls Incorporated (DCI) is in need of repair service, it should be shipped, freight paid, to: Dart Controls, Inc., 5000 W. 106th Street, Zionsville, IN. 46077, ATTN: Repair Department.
Please include with each order a P.O. number to cover any repair charges (a P.O. is needed even on warranty returns to cover misuse or other failures that have voided warranty), and include a note with a brief description of the problem experienced. NO WORK WILL BE DONE ON ANY ORDER WITHOUT A P.O. NUMBER.
Completed repairs are returned with a Repair Report that states the problem with the control and the possible cause. Repair orders are returned via UPS Ground unless other arrangements are made. If you have further questions regarding repair procedures, contact your Dart Distributor or Representative.
YOUR MOTION SYSTEMS SOLUTION PROVIDER
125D SERIES
AC INPUT - VARIABLE DC OUTPUT
1/50 HP through 1.0 HP
700/COMMUTROL SERIES
DC BRUSHLESS
5 & 20 Amp for
12,24,& 36VDC Inputs
Dart Controls, Inc. is a de­signer, manufacturer, and marketer of analog and dig­ital electronic variable speed drives, controls, and acces­sories for AC, DC, and DC brushless motor applica-
tions.
Shown above is just a sam­pling of the expanded line of Dart controls that feature the latest in electronic technology and engineering. Products are manufactured in the U.S.A. at our Zionsville (Indianapolis,
250G SERIES
AC INPUT - VARIABLE DC OUTPUT
1/50 HP through 2.0 HP
MDP SERIES
PROGRAMMABLE
CLOSED LOOP DC
SPEED CONTROL
Indiana) production and head­quarters facility - with over 2,000,000 variable speed units in the field.
In addition to the standard off­the-shelf products, you can se­lect from a wide variety of op­tions to customize controls for your specific application. For further information and appli­cation assistance, contact your local Dart sales representa­tive, stocking distributor, or Dart Controls, Inc.
www.dartcontrols.com
ISO9001 REGISTERED
DC INPUT - VARIABLE DC OUTPUT
CURRENT RATINGS OF 20, 40, AND
60 AMPS
DM SERIES
65 SERIES
FIELD PROGRAMMABLE
DIGITAL TACHOMETER