Data Sheet
VHS Valve with Integrated Pre-Setting
and Shut-o/Drain
Application
VHS straight VHS angle
The VHS is the ideal control valve for modern
base-connection radiators, as well as for universal
or bathroom radiators with connection distances
of 50mm between ow and return. Quick and
easy to install, it will accept standard Danfoss
snap-lock sensor elements.
System layout
The VHS incorporates an integral presetting
mechanism, for quick and accurate system
balancing, and a combined shut-o/drain device.
Connection to copper, soft steel, alupex and PEX
plastic pipes can be carried out with Danfoss
clamping joints. An optional ll-and-drain tting
is available.
To avoid the occurrence of scale and corrosion in
the system, the composition of the heating water
should comply with VDI guidelines 2035.
1. Co ver 2. Enclosure for
towel driers
To ensure an appealing nish dierent types of
valve covers are available:
1. In white ABS material (RAL 9010) which is suitable for wet lacquering or in black PPO suitable
for electrostatic powder lacquering.
2. Enclosure designed for towel dryers with
angled valves.
VD53D502 © Danfoss 10/2014
1

Data Sheet VHS Valve with Integrated Pre-Setting and Shut-o/Drain
Ordering and data
Connection Settings
VHS- UN 15
Angle
Straight 013G 4742
Angle
Straight 013G4744
1) The kV-values represent the ow volume (Q) in
m³/h at a pressure drop (Δp) through the valve
of 1 bar;
At setting N, the kV-values are given for Xp = 2 K.
At lower presettings, Xp is reduced for the
kV-values stated to 0.5 K at preset value 1.
The kV-values state Q at full ow, i.e. for a fully
opened valve.
2) If sensors RAW/RAS/RAE/Remote Setting Unit is
used, the P-band increases by a factor of 1.6.
Manufacturer’s value is at “N” setting.
VH S-UN 15 0.39 0.57
(ISO 228 -1)
Radiator System 1 2 3 4 5 6 7 N N
R½
G¾A 0.02 0.04 0.07 0.12 0.19 0.27 0.33 0.48 0.57
G¾
kV-values
Temperature and pressure*
Max. water temperature 120 °C
kV=
Q
√Δp
Recommended
dierential pressure
Max. technical
dierential pressure
Testing pressure 16 bar
Max. operating pressure 10 bar
*The stated max. technical dierential pressure indicates
the limit for maintaining optimum control. For low-noise
operation, system dierential pressures should be held
within the recommended range. Pumps should never be
kV at Xp = 2 k
VS
oversized; select those that generate just sucient pressure
to circulate the required volume of water. From experience,
a dierential pressureof 0.05-0.2 bar across the valve is
adequate in most systems.In systems where it is too high,
a Danfoss dierential pressure regulator can be used to
reduce it.
1) 2)
k
VS
0.05-0.2 bar
Code no.
013G 4741
013G 4743
0.6 bar
Presetting
Danfoss pre-settable valve bodies incorporate
easy setting adjustment collars with clearly
engraved setting markers from 1 - 7 and N.
Setting can be made quickly and precisely,
without the need for tools, as follows:
• Remove protective cap or sensor element.
• Lift setting collar.
• Turn anti-clockwise to the desired engraved
setting value. The setting mark always points
directly to the radiator connection point.
• Allow setting collar to fall back to its original
position.
Preset levels can be selected in 0.5 increments
between 1 and 7 (see chart for ow rates).
At setting N the valve is fully open ushing
option).
Settings in the hatched areas should be avoided.
2
VD53D502 © Danfoss 10/2014

Data Sheet VHS Valve with Integrated Pre-Setting and Shut-o/Drain
Accessories
Product Code no.
Cover* for VHS valve for panel radiators, straight pattern, white RAL 9016,
suitable for wet lacquering (see product carton)
Cover* for VHS valve for panel radiators, angle pattern, white RAL 9016,
suitable for wet lacquering (see product carton)
Cover* for VHS valve for towel rail radiators, straight pattern, white RAL 9010,
suitable for wet lacquering (see product carton)
Cover* for VHS valve for towel rail radiators, straight pattern, white RAL 9016,
suitable for wet lacquering (see product carton)
Cover* for VHS valve for towel rail radiators, angle pattern, white RAL 9010,
suitable for wet lacquering (see product carton)
Cover* for VHS valve for towel rail radiators, angle pattern, white RAL 9016,
suitable for wet lacquering (see product carton)
Cover for VHS valve, straight pattern, chrome
Cover for VHS valve, angle pattern, chrome
Enclosure* for VHS valve for towel rail radiators, angle pattern, white RAL
9010, suitable for wet lacquering (see product carton)
Enclosure* for VHS valve for towel rail radiators, angle pattern, white RAL
9016, suitable for wet lacquering (see product carton)
013G 4774
013G4775
013G 4672
013G 4674
013G 4671
013G4673
013G 4780
013G 4779
013G4751
013G4755
Sealing cone incl. seal for valve radiator with 3/4” ext. thread (20 pcs.) 003L0294
Self-sealing connection nipple for valve radiator with G½ int. thread (20 pcs.) 003L0295
Double rosette (PVC) for pipe diameter Ø 12-24 mm (min. distance 50 mm) 192H0161
Manual handwheel for all RA type valves (valve di. pressure max. 0.6 bar)
Fill-and-drain tting, not nickel-plated, with 3/4” ext. thread and hose nozzle 003L0152
Connection bracket for sensors without snap-lock connection (10 pcs.)
Cover for VHS, nickel-plated 003L0153
*Requires a sensor with snap-lock.
013G5002
013G 4925
VD53D502 © Danfoss 10/2014
3