Danfoss TPC, TPC-M Data sheet

Data sheet

Self-acting controllers integrated to heat exchanger (PN 10)

TPC TPC-M

Temperature controller (NC) with differential pressure controller built-in

Temperature controller (NC) with on/off valve for heating and differential pressure controller built-in

Description

TPC

TPC-M

These self-acting controllers are designed to be integrated directly to heat exchanger. They are developed to control direct heating and instantaneous heating of domestic hot water by means of heat exchanger.

The family of products offers full flexibility of different requirements regarding control performance.

Innovative design enables simple, fast and reliable connection to heat exchanger and most importantly production of compact and user friendly stations for heating and preparation of domestic hot water.

The capacity of controllers fully covers the needs of domestic hot water preparation and heating for flats, one family houses or dwellings. Controllers can be mounted to district heating network, different heating systems or centrally located boiler system in a dwelling house (see “Main data” for specifications for the network).

To avoid risk of leaking from one media to the other the controller is equipped with double sealing. Between both sealings (O-rings) there are several bores to the outside of the valve. In case of leakage from one sealing the media can escape through bores.

Controllers have DVGW and WRAS approval pending.

Main data:

DN 15

PN 10

∆p controller setting: 25 kPa (fixed)

kVS (DHW): 3,2 m3/h

kVS (heating): 4,0 m3/h

kVS (∆p controller): 4,2 m3/h

Setting range: 40 … 60 °C

Temperature: 2 … 95 °C

Connections: pin-lock connection with O-ring

DH-SMT/SI

VD.LR.Z2.02 © Danfoss 05/2014

1

 

 

 

 

Data sheet

TPC family (PN 10)

 

 

 

 

 

 

Ordering

Example 1:

Pilot activated temperature controller (NC) with ∆p controller built-in, DN 15, PN 10, setting range 40 ... 60 °C, pin-lock connection

- 1× TPC DN 15 controller Code No: 003L3953

Example 2:

Pilot activated temperature controller (NC) with ∆p controller built-in and on/off valve for heating, DN 15, PN 10, setting range 40 ... 60 °C, pin-lock connection

- 1× TPC-M DN 15 controller Code No: 003L3952

Option:

- 1× Thermal wax actuator

TPC Controllers 1)

Picture

Type 3)

DN

Setting range

Connection 2)

Code No.

(°C)

 

 

 

 

 

 

TPC

15

40 … 60

Pin-lock with O-ring

003L3953

 

TPC-M

15

40 … 60

Pin-lock with O-ring

003L3952

1)for application details see “Selection guideline” section

2)to heat exchanger and connecting pipes

3)controller is delivered with thermostatic actuator with M14 sensor stuffing box

Service kits / Accessories

Picture

Type designation

Code No.

 

Thermostatic actuator

003L3962

 

24 V AC

082F1262

 

Thermal wax actuator TWA-Z (NC)

082F1266

 

230 V AC

 

24 V AC

082F1260

 

Thermal wax actuator TWA-Z (NO)

082F1264

 

230 V AC

 

Flow activator

003L3964

Technical data

Nominal diameter (DN)

mm

15

kVS value of thermostatic control valve (TC)

 

3,2

kVS value of on/off valve for heating (ZV)

m3/h

4,0

kVS value of built in ∆p controller (DP)

 

4,2

Max. diff. pressure over primary side of substation

bar

0,25 1)

Min. flow rate on primary side (Q1,min)

 

40

Max. flow rate on primary side (Q )

 

850/950 2)

1,max

l/h

 

Min. flow rate on secondary side (Q2,min)

120

 

Max. flow rate on sec. side (Q2,max)

 

1200

Nominal pressure (PN)

bar

10 3)

Max. diff. pressure on primary side

bar

4

 

 

Min. required available diff. pressure on primary side

0,5

 

 

 

 

Medium

 

Circulation water / glycolic water up to 30 % 4)

 

Domestic hot water (chlorine (cl) content max. 200 ppm) 5)

 

 

Medium pH

 

Min. 7, max. 10 4)

Medium temperature

 

2 ... 95

Setting range

ºC

40 … 60

Max. permited temperature at sensor

 

70

 

 

 

Thermostat capillary tube length

m

0,6

Materials

 

 

 

 

 

Housing, connected to primary side

 

CuZn36Pb2As (CW 602N)

Housing, connected to secondary side

 

CuZn21Si3P (CW 724R)

Cone and diaphragm support

 

CuZn38Pb1.5, Grivory HT1V-4 FWA Black 9225, Ultramid A3WG7

 

 

 

Main spindles

 

CuZn36Pb2As, Stainless steel, mat. No. 1.4404

 

 

 

Diaphragm, O-rings

 

EPDM

 

 

 

Temperature sensor

 

Copper, mat. No. 2.0090

 

 

 

1)valid at 1 bar differential pressure over the station

2)850 26 PL HEX, 950 40 PL HEX and 60 PL HEX

3)on primary and secondary side

4)valid for primary side

5)valid for secondary side

2

VD.LR.Z2.02 © Danfoss 05/2014

DH-SMT/SI

Danfoss TPC, TPC-M Data sheet

Data sheet

TPC family (PN 10)

 

 

Technical data (continued)

Classification according to VDI 6003

 

Graph below shows flow on secondary side in

 

 

Type

Wash basin 1)

Showers 2)

relation to pressure drop over flow activator.

 

 

TPC, TPC-M

III

III

Secondary side

 

1)

Tapping rate changing in steps of 6-12-6 l/min.

 

 

 

2)

Tapping rate changing in steps of 9-12-9 l/min.

 

Setting range

Temperature setting depends on application parameters and

number of plates in heat exchanger. Values given are approximate.

Set point indication:

6 T22~ 60°C

3 T22~ 50°C

0 T22~ 40°C

T11 … primary flow temperature

T22 … domestic hot water temperature

XB 06H-1 26

XB 06H-1 40

XB 06H-1 60

DH-SMT/SI

VD.LR.Z2.02 © Danfoss 05/2014

3

Data sheet

Selection guideline

Installation positions

Application principle

4

TPC family (PN 10)

Type

Application

Description

 

 

Functions

 

 

Secondary flow activated temperature controller

 

 

(NC) with ∆p controller built in (NO).

 

 

Typical system conditions

TPC

 

Systems with varying supply temperature and

 

 

differential pressure. No demand for on/off

 

 

controll of heating system.

Type

Application

Description

 

 

Functions

 

 

Secondary flow activated temperature controller

 

 

(NC) with ∆p controller built in (NO) and on/off valve

 

 

for heating.

TPC-M

 

Typical system conditions

 

 

Systems with varying supply temperature and

 

 

differential pressure. Need for on/off controll of

 

 

heating system.

Temperature controller

Controller must be mounted on cold side of heat exchanger (district heating outlet and domestic hot water inlet side).

TPC and TPC-M controllers are delivered with standard sensor.

Remark:

The sensor must always be placed warmer than the thermostat/setting device. Sensor itself can be mounted in any direction. For best

preformance of TPC it is recommended to install sensor facing up (see picture on the right).

 

 

 

st

 

e

B

 

 

 

 

 

 

 

per

fo

r

m

a

n

ce