Danfoss TP9000 Installation guide

MAKING MODERN LIVING POSSIBLE

TP9000

Electronic Programmable Room Thermostat

plus Domestic Hot Water Timer

Danfoss Heating

Installation Guide

For a large print version of these instructions please call Marketing on 0845 121 7400.

Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed material. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

2

TP9000

TP9000

Electronic Programmable Room Thermostat plus Domestic Hot Water Timer

Installation Instructions

1.0 Basics

 

1.0 Product specification...................................................................

4

1.1 Installation.......................................................................................

5

1.2 Wiring ................................................................................................

7

2.0Installer advanced programming options

2.1 Installer advanced programming options ...........................

9

2.2 Service Interval Timer ..................................................................

9

2.3 Entering Installer Advanced Programming Mode ............

9

Danfoss Heating

 

3

1.0 Basics

GB

Please note: This product should only be installed by a qualified electrician or competent Heating installer, and should be in accordance with the current edition of the IEEE wiring regulations.

PL

GR

ES

1.0 Product specification

Specification

230V model

 

24V model

 

 

 

 

Power supply

230 Vac, ±15%,

 

24 Vac, ±15%,

 

50/60 Hz

 

50/60 Hz

 

 

 

Switching action

2 x SPDT internally linked, Type 1BS

 

 

 

Unit switch rating

230 Vac, 3(1)A

 

24Vac, 3(1)A

 

 

 

Memory Backup

Retained for life of product

 

 

Heat Temperature Range

5°C - 30°C

Setting

 

 

 

 

 

Factory Set Calendar

Automatic Summer/Winter time

Clock

change

 

 

Remote Sensor Inputs

Can be set by installer for remote sen-

(‘A’ models only)

sor, limited sensor, window contact,

 

tele-switch or outdoor sensor

 

 

Programme resolution

± 1 minute

 

 

Timing Accuracy

± 1 minute

 

 

Dimensions, mm (W, H, D)

135 x 88 x 32mm

 

 

Design standard

EN 60730-2-7 +EN60730-2-9

 

 

Control Pollution Situ-

Degree 2

ation

 

 

 

 

 

 

Rated Impulse Voltage

2.5 kV

 

 

 

 

Ball Pressure Test

75°C

 

 

 

 

 

4

TP9000

1.1 Installation

Remove wallplate from unit by unscrewing the two screws on the bottom edge of the unit.

From the top left hand corner of the wallplate, there must be

clearances of at least 140 mm to the right, 15mm to the left, 30mm above and 100mm below in order to mount the plug-on module.

The wallplate must be securely mounted either directly to the

wall using suitable wood screws or to a flush mounted 1-gang electrical accessory box using M3.5 screws.

Cable access can either be from behind for concealed cabling, or

from below for surface cabling. If surface cable is used, cut out cable access slot on plug-on module prior to mounting.

For wiring connections refer to diagram on page 7.

The TP9000 is double insulated and does not require an earth connection, however a parking terminal is provided on the wallplate. This is clearly marked with an Earth symbol.

Prior to mounting the plug-on module, DIL switches on the rear of the plug-on module must be set. See diagram below for available options.

Mount plug-on module to wallplate by locating tabs on top of wallplate in apertures on rear of module, hinge down and press firmly to wallplate before tightening securing screws on bottom of wallplate.

Prior to mounting the unit the 2 DIL switches on the rear of the unit have to be moved to the required position. The factory presets are shown below.

Sw. No.

OFF

 

 

 

ON

1

Keyboard disabled

 

 

 

Keyboard enabled

 

 

 

2

Reset disabled

 

 

 

Reset enabled

 

 

 

 

 

 

 

 

 

 

 

 

GB

PL

GR

ES

Danfoss Heating

5

! IMPORTANT: The supply to this unit should by wired via a double pole isolation switch in accordance with BS EN60730-1, i.e. one which provides air gaps of at least 3mm in both poles of the mains, and incorporates a 3 amp fuse. It is strongly recommended that solid conductors be used.

GB

PL

GR

ES

 

 

 

Outline of unit

 

30mm minimum

Terminal block

 

 

 

C/L

 

 

 

 

 

 

 

 

Wall or Plaster box fitting

N & looping terminals

Clearance for

Surface fixed cable

Rear entry

screwdriver

bottom entry knockouts

cable access

access

 

 

 

 

 

 

 

 

Thermostat and Remote Room Sensor:

Fix at a height of approximately 1.5m from the floor, away from draughts or heat sources such as radiators, open fires or direct sunlight.

6

TP9000

1.2 Wiring

NOTE:

The 230V TP9000 does not have voltage free contacts, therefore it is NOT suitable for connection to extra low voltage equipment.

Remote Sensor to be wired with 1mm 2 core double insulated cable only. Cable length should not exceed 50 metres. Sensor cable should NOT be run parallel to mains cable.

GB

PL

N

L

B

C

N-L = 230V

B-C = 24V (B=0v / C=24v)

GR

ES

Remote sensor inputs

The TP9000 incorporates an input which can be used to connect one of the following:

1)remote room temperature sensor

2)limit sensor, for example, floor temperature sensor (sold as accessory).

3)window contacts, card reader contacts, outdoor sensor (sold as accessory) or teleswitch contacts.

See Installer Advanced Programming Options for set-up instructions.

Danfoss Heating

7

GB

PL

Remote sensor inputs

Terminals 5 and 6 are the designated remote sensor inputs. These can be found on the top right hand side of the wallplate.

5

6

5

6

5

6

GR

ES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Window

 

 

 

 

 

 

 

 

 

 

 

 

 

 

contact (NC)

 

 

 

 

 

 

 

 

Window or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

teleswitch

 

 

Teleswitch

 

 

 

 

 

 

 

 

contact

 

 

contact (NC)

 

 

 

 

 

 

 

 

(NO or NC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configured for

Configured for

Configured for

remote room,

window contact or

window contact

limit or outdoor

other contact such

and other contact

 

sensor

as teleswitch

such as teleswitch

8

TP9000

2.0 Installer advanced

programming options

TP9000 incorporates a number of advanced features which can be set by the user. These are accessed via a User Advanced Programming Mode, please refer to User Advanced Programming in the user instructions for details (see page 23)

2.1 Installer advanced programming options

TP9000 incorporates an additional number of advanced features which can be set by the installer to improve the operating e ciency of the system and where required, to change the user functionality of the product. These are accessed via an Installer Advanced Programming Mode. These settings are optional and need only be made if there is a demand for the enhanced functions.

2.2 Service Interval Timer

Instructions on how to access this feature are available from our customer support desk. Please note these are only issued to boni-fide Heating installers.

2.3 Entering Installer Advanced Programming

Mode

To access the Installer Advanced Programming Mode follow the steps below:

a)Press and hold V and PROG for 3 seconds to enter User Advanced Programming, the display will change to figure opposite.

b)Press and hold V, Λ and PROG for 5 seconds to enter Installer Advanced Programming, the display will change to figure opposite.

GB

PL

GR

ES

Danfoss Heating

9

GB

PL

GR

ES

c)Use + and - keys to scroll backwards and forwards between options then V and Λ keys to change the option settings. The flashing digit on the right hand of the display indicates the number of the selected option. The large characters display the option value selected.

d)To return to RUN, press and hold PROG until the display returns

to RUN mde.

Option 30 - Set upper limit of temperature range

This allows the upper limit of the thermostat setting range to be electronically limited. Press + until Option 30 is displayed, use V and Λ to select required setting.

Setting

40 - 5°C (factory setting is 30°C)

Option 31 - Set lower limit of temperature range

This allows the lower limit of the thermostat setting range to be electronically limited. Press + until Option 31 is displayed, use V and Λ to select required setting.

Setting 5 - 40°C (factory setting is 5°C)

Option 32 - Enable O at lower limit

This enables an OFF function to be selected if a set point below the lower limit is selected. Press + until Option 32 is displayed, use V and Λ to select required setting.

Setting 0 Disabled

Setting 1 Enabled (factory setting)

Option 33 - Enable On at upper limit

This enables an ON function to be selected if a set point above the upper limit is selected. Press + until Option 33 is displayed, use V and Λ to select required setting.

Setting 0 Disabled (factory setting)

Setting 1 Enabled

10

TP9000

Option 34 - Select On/O or Chrono-proportional

This allows the thermostat to be set to run in On/O mode or for a chrono-proportional cycle rate to be selected. Press + until Option 34 is displayed, use V and Λ to select required setting.

0On/O

33 cycles per hour

6 6 cycles per hour (factory setting)

9 9 cycles per hour

12 12 cycles per hour

Option 35 - Set integration time (Option 34 set to 3, 6, 9 or 12) (seek advice prior to adjusting)

This adjusts the integration time of the PI algorithm to increase control accuracy. It is only active if option 34 has been set to Chrono 3, 6, 9 or 12. It should only be adjusted after seeking advice from the manufacturer. Press + until Option 35 is displayed, use V and Λ to select required setting.

2.5 Integration time set to 2.5% (factory setting)

5 Integration time set to 5%

10 Integration time set to 10%

Option 36 - Set temperature override rule

This establishes the degree of temperature override available to the user. Press + until Option 36 is displayed, use V and Λ to select required setting.

Setting 0 No limit (factory setting)

Setting 1 Limited to ±2°C

Setting 2 No override allowed

Danfoss Heating

 

11

Danfoss TP9000 Installation guide

Option 37 - Set time duration of override rule (Option 36 set to 1 or 2)

This establishes the duration of a temperature override available to the user. Press + until Option 37 is displayed, use V and Λ to select required setting.

Setting 0 Next event (factory setting)

Setting 1 1 hour

Setting 2 2 hours

Setting 3 3 hours

Setting 4 4 hours

Option 40 - Number of Events per Day (Heating)

This sets the thermostat to operate with either 2, 4 or 6 switching events per day or to run it in stat mode. Press + until option 40 is displayed, use Λ or V to select required setting.

1Stat mode

2 Two switching events per day

4Four switching events per day

6Six switching events per day (factory setting)

Option 41 - Operating Mode (Heating) (option 40 set to 2, 4, or 6)

This sets the thermostat to operate using either 5/2 day or 24 hour mode. Press + until option 41 is displayed, use Λ or V to select required setting.

77 Day programming (factory setting)

5-2 or A-B 5-2 Day programming or A-B programming

24 24 hour programming

Option 60 - Number of events per day (Hot Water)

This sets the number of Hot Water on/o switching times per day. Press + until option 60 is displayed, use Λ or V to select required setting.

Setting 1 1 on/o event per day

Setting 2 2 on/o events per day

Setting 3 3 on/o events per day (factory setting)

12

 

TP9000

Option 61 - Hot Water Event - Days per week

This sets the schedule of Hot Water on/o switching times per week. Press + until Option 61 is displayed, use V and Λ to select required setting.

24

24 Hour

 

 

 

5-2

Either 5+2 day or A+B days depending on user APM

 

 

setting

 

77 Day (factory setting)

Option 70 - Keyboard disable rules

This establishes the degree of functionality of the keyboard available to the user. It is only active if DIL switch 1 is set to “Disabled”. Press + until Option 70 is displayed, use V and Λ to select required setting.

Setting 0

Normal lock: Programming functions locked (factory

 

setting)

Setting 1

Full lock: All keys are disabled

Option 71 - Random start rules (24V/230 Volt models only)

This enables a random start on power-up following a power cut to reduce load on the electrical network. Random delay is in the range of 2 - 90 seconds. Press + until Option 71 is displayed, use V and Λ to select required setting.

Setting 0 Disabled (factory setting)

Setting 1 Enabled

Option 72 - Owner site reference number

This enables multi-site owners to store a site reference number in the thermostat. Press + until Option 72 is displayed, use V and Λ to select required setting.

Setting Any value between 00 and 99 can be set

Factory setting is 00

Danfoss Heating

 

13

Option 73 - Owner thermostat reference number

This enables site owners to store a thermostat reference number in the thermostat. Press + until Option 73 is displayed, use V and Λ to select required setting.

Setting Any value between 000 and 999 can be set

Factory setting is 000

Option 74 - Date format for calendar clock

This allows date format to be chosen. Press + until Option 74 is displayed, use V and Λ to select required setting.

Setting 0 European format (dd/mm/yy), (Factory setting)

Setting 1 North American format (mm/dd/yy)

Option 80 - Enable/Disable + Hrs Boost

Enables or disables the +Hrs button. use V and Λ to select required setting. Press + until Option 80 is displayed, use V and Λ to select required setting.

Setting 0 +Hrs Boost button disabled

Setting 1 +Hrs Boost button enabled (factory setting)

Option 81 - Thermostat calibration bias

This allows the thermostat calibration to be biased by up to ±1.5°C. Press + until Option 81 is displayed, use V and Λ to select required setting.

Setting Any value between ±1.5 in 0.5°C steps (Factory setting is 0°C)

14

 

TP9000

Option 90 - Define remote sensor type

This allows type of remote sensor input type to be defined. Press + until Option 90 is displayed, use V and Λ to select required setting.

Setting 0 No remote sensor fitted

Setting 1 Remote room or duct sensor fitted, internal sensor disabled (factory setting)

Setting 2 Remote limit sensor fitted, refer to option 93 to define set-point

Setting 3 Configured as digital input for window, card reader or teleswitch, refer to option 94 to define o/c or s/c.

Setting 4 Outdoor sensor fitted internal sensor active, outdoor sensor used for display purposes only

Option 93 - Set limit sensor set-point (option 90 set to 2)

This allows the thermostat limit sensor to be set, typical application is floor Heating. Press + until Option 93 is displayed, use V and Λ to select required setting. If the temperature sensed by the limit sensor exceeds the limit setting the output will be turned o until the temperature has dropped by 2°C.“F10”will flash in the display while the output is disabled.

Setting Any value between 20 - 50°C (Factory setting is 27°C)

Option 94 - Configure digital input switch type,“A” models only, (option 90 set to 3)

This allows switch type of digital input to be configured. Press + until Option 94 is displayed, use V and Λ to select required setting.

Setting 0 Contacts NC, open circuit contact to force unit into thermostat mode, short circuit contacts to return to normal operation

Setting 1 Contacts NO, short circuit contacts to force unit into thermostat mode, open circuit contacts to return to normal operation (Factory setting)

GB

PL

GR

ES

Danfoss Heating

15

TP9000

Programowalny termostat pokojowy do układów C.O. i C.W.U.

Instrukcja montażu

 

1.0 podstawowy

 

1.0 Instrukcja montażowa..............................................................

17

1.1 Montaż ...........................................................................................

18

1.2 Przewody.......................................................................................

20

2.0Zaawansowane funkcje programowane przez instalatora

2.1 Zaawansowane funkcje programowane

 

przez instalatora ........................................................................

22

2.2 Wskaźnik czasu następnego przeglądu

 

serwisowego................................................................................

22

2.3 Wejście w tryb zaawansowanych funkcji

 

programowanych przez instalatora.....................................

23

16

 

TP9000

1.0 Podstawowy

Uwaga: Urządzenie to powinno być instalowane jedynie przez wykwalifikowanego elektryka lub uprawnionego instalatora urządzeń grzewczych. Montaż powinien spełniać wymagania stawiane przez aktualne przepisy Instytutu Inżynierów Elektryków i Elektroników (IEEE wiring regulations).

Dane techniczne

Model 230V

 

Model 24V

 

 

 

 

Zasilanie

230 V~, ±15%,

 

24 V~, ±15%,

 

50/60 Hz

 

50/60 Hz

 

 

 

Przełączanie

Dwa pojedyncze przełączniki dwupozy-

 

cyjne, wewnętrznie połączone, typ 1BS

 

 

 

 

Dane przełącznika

230 V~, 3(1)A

 

24V~, 3(1)A

urządzenia

 

 

 

 

 

 

Podtrzymanie pamięci

Na cały okres użytkowania urządzenia

 

 

Zakres ustawień tempera-

5°C - 30°C

tury

 

 

 

 

 

Zegar kalendarzowy

Automatyczna zmiana czasu z letniego

ustawiony fabrycznie

na zimowy i na odwrót

 

 

Sygnały wejściowe ze

Mogą być ustawiane przez instalatora dla

zdalnego czujnika (tylko

zdalnego czujnika, czujnika z ogranicze-

modele A)

niem, styku okiennego, teleprzełącznika

 

lub czujnika zewnętrznego

 

 

Skok czasowy programow-

± 1 minuta

ania

 

 

 

 

 

Dokładność regulatora

± 1 minuta

czasowego

 

 

 

 

 

Wymiary, mm (szerokość,

135 x 88 x 32mm

wysokość, grubość)

 

 

 

 

 

Zgodność z normą

EN 60730-2-7 +EN60730-2-9

 

 

Poziom zakłóceń

Stopień 2

 

 

 

Znamionowe napięcie

 

2.5 kV

impulsowe

 

 

 

 

 

 

Temperatura próby

 

75°C

twardości metodą Brinella

 

 

 

 

 

 

 

 

 

 

 

Danfoss Heating

 

 

 

GB

PL

GR

ES

17

GB

PL

GR

ES

1.1 Montaż

Zdjąć płytkę ścienną z urządzenia po uprzednim odkręceniu dwóch śrub na dolnej krawędzi.

Aby zamontować moduł nasadzany, od górnego lewego rogu

płytki ściennej musi być odstęp co najmniej 140 mm w prawo, 15 mm w lewo, 30 mm w górę i 100 mm w dół.

Płytka ścienna musi być odpowiednio przymocowana, albo bezpośrednio do ściany przy pomocy wkrętów do drewna lub do jednobiegunowej puszki instalacyjnej przy pomocy śrub M3,5.

Przewody można podłączyć albo od tyłu (gdy biegną w ścianie), albo od dołu (gdy nie są schowane). Przed podłączeniem przewodu znajdującego się na powierzchni ściany należy wyciąć w module nasadzanym odpowiedni otwór na jego przeprowadzenie.

Sposób podłączenia przewodów przedstawiono na diagramie na stronie 20.

Model TP9000 jest podwójnie izolowany i nie wymaga uziemienia. Istnieje jednak możliwość podłączenia przewodu uziemiającego do płytki ściennej – miejsce podłączenia jest wyraźnie oznaczone symbolem uziemienia.

Przed zainstalowaniem modułu nasadzanego należy ustawić przełączniki DIL (dwupozycyjne) z tyłu modułu. Możliwe warianty pokazano na diagramie poniżej.

Założyć moduł nasadzany na płytkę ścienną przez wsunięcie wypustek na górze płytki do otworów z tyłu modułu, obrócić go do pozycji pionowej i docisnąć mocno do płytki przed dokręceniem śrub zabezpieczających na dole płytki.

18

TP9000

oPrzed zamontowaniem urządzenia przełączniki DIL znajdujące się z tyłu muszą być ustawione w wymaganym położeniu. Poniżej pokazano ustawienia fabryczne.

Numer przełącznika Wyłączony

ączony

 

 

 

 

 

1 Klawiatura nieaktywna

 

 

 

 

klawiatura aktywna

 

 

 

 

 

 

 

 

 

 

 

 

GB

PL

2 Resetowanie nieaktywne

 

 

 

resetowanie aktywne

 

 

 

 

 

 

 

 

!WAŻNE: Zasilanie tego urządzenia powinno odbywać się poprzez dwuobwodowy przełącznik izolacyjny zgodny z normą BS EN60730-1, tzn.taki,którytworzyconajmniejtrzymilimetroweszczelinypowietrzne na obu obwodach (fazowym i zerowym) przewodu zasilającego i posiadabezpieczniktrzyamperowy.Zalecasięstosowanieprzewodów

jednożyłowych.

 

 

 

Obrys urządzenia

 

Minimum 30 mm

Zespół złączy

 

 

 

C/L

 

 

 

 

 

 

 

 

Otwory na wkręty mocujące do ściany lub płyty gipsowej

Złącza pętlowe N (zerowe) i uziemienia

Miejsce na

Miejsce na samodzielnie

Miejsce na podłączenie

włożenie

wykonywane dolne otwory dla

przewodów od tyłu

śrubokręta

przewodów zewnętrznych

 

 

 

 

 

 

 

GR

ES

Danfoss Heating

19

GB

PL

GR

ES

Termostat i zdalny czujnik pokojowy:

Zamocować na wysokości około 1,5 m od podłogi, z dala od ciągów powietrza i źródeł ciepła, takich jak grzejniki i kominki, oraz miejsc bezpośrednio nasłonecznionych.

1.2 Przewody

UWAGA:

Model 230V TP9000 nie posiada styków beznapięciowych, dlatego NIE można go podłączać do urządzeń o bardzo niskim napięciu.

Zdalny czujnik powinien być podłączany wyłącznie za pomocą jednomilimetrowego, dwużyłowego, podwójnie izolowanego przewodu. Długość przewodu nie powinna przekraczać 50 m. Przewód czujnika NIE powinien być prowadzony równolegle do przewodu zasilającego.

Układy elektroniczne

N-L = 230V

B-C = 24V (B=0v / C=24v)

N

L

B

C

Wyłączony Włączony ogrzewanie ogrzewanie

Wyłączony

Włączony

 

ciepła woda

ciepła woda

Zdalny czujnik

użytkowa

użytkowa

 

20

TP9000

Loading...
+ 44 hidden pages