Danfoss TP9000 Data sheet

Datasheet
TP9000 Programmable Room Thermostat with DHW Time Control
Features
The TP9000 is a programmable room thermostat with remote temperature sensor. The TP9000 allows the user to select up to 6 dierent temperature levels per day and the times which the changes occur.
The TP9000 can be set at installation to operate both heating and hot water independently in either 7 day mode - individual times and temperatures for each day of the week, 5 day/2 day mode, which allows dierent programmes to be set for the weekend, or in 24 hour mode, in which case the programmed events are repeated every 24 hours.
Accessed via the APM (Advanced Programming Menu), settings made by the installer or the end user are stored for the life of the product in a non-volatile memory chip which does not require power.
Using the APM, the operating temperature range, which is factory preset to 5-30°C, can also be preset by the installer for any min/max temperature between 5-40°C. This makes the TP9000 a safe solution for use in sheltered accommodation where hypothermia may be of concern.
For installation convenience, the TP9000 is supplied with a remote room sensor which can be mounted up to 50 metres away from the programming unit.
In addition to the programmable room thermostat function, TP9000 also incorporates a Domestic Hot Water time control channel which allows up to 3 Domestic Hot Water on/o events to be programmed each day.
The TP9000 has the ability to be set in Holiday mode. Using the Holiday mode, the Hot Water is switched o and the Central Heating is placed in frost protection mode. Upon reaching the set holiday return date, normal operation is resumed.
The inclusion of an information button on the unit allows quick viewing of items like the next timed event, service due date (if activated), and outdoor temperature (if outdoor sensor is tted).
Designed to be fully compliant with Part L and Best Practice requirements, the TP9000 is the obvious choice for new and retrot applications.
The TP9000 incorporates convenient user overrides which allows the user to:
l Obtain an extra 1, 2, or 3 hour’s Hot Water or
Central Heating.
l Temporarily override room temperatures up or
down.
l Select Heating and Water O, with frost
protection for periods away from home.
l Up to 6 time/temperature changes per day for
heating.
l Can be set at installation for 24 hour, 5 day/2
day or 7 day operation.
l Remote sensor for installation convenience. l Integrated DHW time control. l Convenient user overrides. l Clear, easy to read LCD display and LED status
indicators.
l Wallplate construction for ease of installation.
© Danfoss HS | 09/2015 | 736v02 VDBYD202
1
Datasheet
Mains Water
TP9000 Programmable Room Thermostat
Application
Specications
Feed &
Expansion Tank
Wiring
Cylinder
Stat
AVDO
Box
Zone Valves
TP9000
Heatplan Control System
Remote
Sensor
Feed &
Expansion Tank
Mains Water
Wiring
Cylinder
Stat
AVDO
Box
Zone Valve
TP9000
Heatshare Control System
TP9000
Code Number 087N789200
Factory set clock
l
Room time and temperature changes up to 6 per day
Room temperature control range (°C) 5-30°C
Remote room temperature sensor
Selectable 7 day, 5/2 day or 24 hour operating mode
Fully independent Hot Water and Central Heating times
l
l
l
DHW time control events up to 3 on/o events per day
Frost protection override option
+1, +2, +3 hour DHW and/or CH override
Room temperature overrides
Holiday mode
l
l
l
l
Event 1 20°C 6:30am
Heating Programme Factory preset times and temperatures for every day in 24 hour mode or Mon-Fri 5/2 day or 7 day mode.
Event 2 15°C 8:30am
Event 3 20°C 11:30pm
Event 4 15°C 1:30pm
Event 5 21°C 4:30pm
Event 6 15°C 10:30pm
Event 1 20°C 7:30am
Heating Programme Factory preset times and temperatures Saturday and Sunday in 5/2 day or 7 day mode.
Event 2 20°C 9:30am
Event 3 20°C 11:30pm
Event 4 20°C 1:30pm
Event 5 21°C 4:30pm
Event 6 15°C 10:30pm
Event 1 On 6:30am
Hot Water Programme Factory preset times for every day in 24 hour mode or Mon-Fri in 5-2 day or 7 day mode
Event 2 O 8:30am
Event 3 On 11:30pm
Event 4 O 1:30pm
Event 5 On 4:30pm
Event 6 O 10:30pm
Event 1 On 7:30am
Hot Water Programme Factory preset times for Saturday and Sunday in 5-2 day or 7 day mode
Event 2 O 9:30am
Event 3 On 11:30pm
Event 4 O 1:30pm
Event 5 On 4:30pm
Event 6 O 10:30pm
Optional service interval operation
l
Voltage rating 230 Vac, 50Hz
Switch action 2 x SPDT (linked internally)
Switch current rating 3 (1) A
Maximum ambient temperature 45°C
Memory back-up Retained for life of product
Dimensions - Controller (mm) 135 wide x 88 high x 32 deep
Dimensions - TS2 Remote Sensor (mm) 61 wide x 45 high x 22 deep
Remote
Sensor
NB All may be changed as required.
NB All may be changed as required.
NB All may be changed as required.
NB All may be changed as required.
2
© Danfoss HS | 09/2015 | 736v02 VDBYD202
Datasheet
TP9000 Programmable Room Thermostat
Installer Advanced Programme Options
Option Description Factory Setting Other Setting Installer Advanced Programming Options Use + or - key to scroll between options, use Λ or V keys to select option setting
30 Set range upper limit 30°C 40°C - 5°C 31 Set range lower limit 5°C 5°C - 40°C 32 Enable/disable O function at lower limit 1 Enabled 0 Disabled 33 Enable/disable On function at upper limit 0 Disabled 1 Enabled
34 Set chrono-proportional cycle rate 6 6 cycles per hour
35 Set integration time 2.5 2.5%
36 Set temperature override limit 0 No limit
37 Set time duration of override 0 Next event
40 Number of events per day (heating) 6 Six switching events
41 Heating events - days per week 7 7 day programming
60 Number of events per day (hot water) 3 3 on/o events per day
61 Hot water events - days per week 7 7 day programming
70 Keyboard lock type 0 Normal lock 1 Full lock 71 Random start rules 0 Disabled 1 Enabled 72 Site ID number (user dened) 00 01 to 99 73 Thermostat ID number (user dened) 000 001 to 999 74 Date format for calendar clock 0 European (dd/mm/yy) 1 North American (mm/dd/yy) 80 Enable/Disable +Hrs/Boost 1 Enabled 0 Disabled 81 Thermostat calibration bias 0 ±1.5K
90 Remote sensor conguration 0 Disabled
Limit sensor set point adjustment
93
(Only accessible if Option 90 is set to 2) Start-up (digital input) NO or NC
94
(Only accessible if Option 90 is set to 3)
27°C 20-50°C
NC, open circuit to change
0
to thermostat mode
3 3 cycles per hour 9 9 cycles per hour
12 12 cycles per hour
5 5%
10 10%
1 Limited to ±2°C 2 Disabled, no override 1 1 hour 2 2 hours 3 3 hours 4 4 hours 1 Stat mode 2 Two switching events 4 Four switching events
5-2 or
5-2 day or A-B programming
A-B
24 24 hour programming
1 1 on/o event per day 2 2 on/o events per day
24 24 hour programming
5-2 5-2 day programming
1 Room/duct 2 Limit, (oor) 3 Start-up (digital input) 4 Outdoor
NO, close circuit to change to
1
thermostat mode
Advanced User Settings
Option Description Factory Setting Other Setting User Advanced Programming Options Use + or - key to scroll between options, use Λ or V keys to select option setting
1 Enable/disable A/B block programming 0 Disabled 1 Enabled 2 Enable/Disable Advanced Copy 0 Disabled 1 Enabled
3 Automatic summer/winter time change 2 European rules
Time zone oset - UST models 00:00 Use UST clock setting
4
Time zone oset - CET models 01:00 Use CET clock setting
10 Set frost protection default temperature 5°C 5-40°C
11 Start-up type 0 Fixed time start-up
Optimum start control setting, maximum pre-heat period based upon 4°C deviation
12
from next event temperature (Only accessible if option 11 is set to 1)
OSC or delay start function active
13
(Only accessible if option 11 is set to 1 or 2)
© Danfoss HS | 09/2015 | 736v02 VDBYD202
0 Disabled 1 Manual time change 3 USA rules, post 2007 4 USA rules, pre-2006
-12 to Hours oset
+14
1 Optimum start control
2 Delayed start-up 0:15 15 minutes 0:30 30 minutes
1:00 60 minutes
0 First event of day only 1 All events
0:45 45 minutes 1:15 75 minutes 1:30 90 minutes 1:45 105 minutes 2:00 120 minutes
3
Datasheet
ErP
4
TP9000 Programmable Room Thermostat
ErP Class
Wiring Details
Product
Class
ERP Class
The products represented within this document are classied according to, and allow completion of, the Energy Related Product (ErP) Directive System Package che and the ErP system data label. ErP Labelling obligation is applicable from 26th September 2015.
ErP Class Product Function and ErP Description
TPI Room Thermostat, for use with on/off output heaters
An electronic room thermostat that controls both thermostat cycle rate and in-cycle on/o ratio
IV
of the heater proportional to room temperature. TPI control strategy reduces mean water tem­perature, improves room temperature control accuracy and enhances system eciency.
ELECTRONICS
N
N/O
N/C
N/O
N/C
L 1 2 3 4 5 6
OFF
OFF
DHW
HTGONDHW
ON
HTG
REMOTE SENSOR
Additional
eciency gain
2%
DIL Switch Settings
Sw. N o.
1
2
OFF
Keyboard disabled
Reset disabled Reset enabled
ON
Keyboard enabled
Danfoss Ltd.
Ampthill Road Bedford MK42 9ER Tel: 01234 364621 Fax: 01234 219705 Email: ukheating@danfoss.com Website: www.heating.danfoss.co.uk
Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
4