Danfoss TLX, TLX Pro Installation Manual

TLX
Installation Manual
Three-phase – 6k, 8k, 10k, 12.5k and 15k
MAKING MODERN LIVING POSSIBLE
SOLAR INVERTERS
www.neoenerji.com
Safety and Conformity
Safety
All persons installing and servicing inverters must be:
Trained and experienced in general safety rules for work on electrical equipment
Familiar with local requirements, rules and regulations for the installation
Safety Message Types
WARNING
Safety information important for human safety. Warnings are used for indicating potentially hazardous situations that can cause serious injury or death.
CAUTION
Cautions with symbol are used for indicating potentially hazardous situations that can cause minor or moderate injuries.
CAUTION
Cautions without symbol are used for indicating situations that may result in equipment or property damage.
NOTE
Note is used for indicating highlighted information that should be regarded with attention.
General Safety
NOTE
Before installation Check for damage to inverter and packaging. If in doubt, contact the supplier before installing the inverter.
CAUTION
Installation For optimum safety, follow the steps described in this manual. Keep in mind that the inverter has two voltage carrying sides; the PV input and the AC grid.
WARNING
Disconnecting the inverter Before starting work on the inverter, switch off AC grid at the mains switch and PV using the PV load switch. Ensure that the device cannot be unintentionally reconnected. Use a voltage tester to ensure that the unit is disconnected and voltage free. The inverter can still be charged with very high voltage at hazardous levels even when it is disconnected from grid/mains and solar modules. Wait at least 30 min. following disconnection from grid and PV panels before proceeding.
CAUTION
Maintenance and modification Only authorised personnel are allowed to repair or modify the inverter. To ensure personal safety, only original spare parts available from the supplier should be used. If non­original spare parts are used, the compliance with CE guidelines in respect of electrical safety, EMC and machine safety is not guaranteed. The temperature of the cooling racks and components inside the inverter may exceed 70ºC. Observe the danger of burn injury.
CAUTION
Functional safety parameters Never change the parameters of the inverter without authorisation from the local energy supply company and instructions from Danfoss. Unauthorised changes of functional safety parameters may cause injury or accidents to people or inverter. Additionally, it will lead to the cancellation of all inverter operating approval certificates and Danfoss warranties. Danfoss cannot be held responsible for such injuries or accidents.
Safety and Conformity
L00410309-09_02
www.neoenerji.com
Hazards of PV Systems
DC voltages up to 1000 V are present in a PV system even when the AC grid is disconnected. Faults or inappropriate use may lead to electric arcing.
WARNING
Do not work on the inverter while disconnecting DC and AC.
The short-circuit current of the photovoltaic panels is only slightly higher than the maximum operating current and depends on the level of solar irradiation.
PV Load Switch
The PV load switch (1) enables safe disconnection of DC current.
Conformity
Go to the download area at www.danfoss.com/solar, Approvals and Certifications, for information.
CE marking - This certifies the conformity of the equipment with the regulations which apply in accordance with the directives 2004/108/EC and 2006/95/EC.
Table 1.1
Safety and Conformity
L00410309-09_02
www.neoenerji.com
Contents
1 Introduction
2
1.1.1 Installation Sequence 3
1.1.2 Overview of Inverter 4
2 Installation
5
2.1 Installation Dimensions and Patterns
5
2.2 Mounting the Inverter
8
2.3 Removing the Inverter
9
2.4 Opening and Closing the Inverter
9
2.5 AC Grid Connection
11
2.6 Parallel PV String Configuration
12
2.7 PV Connection
14
2.8 Auxiliary Input/Output
14
2.9 Autotest Procedure
14
3 Start-up and Check of Settings
15
3.1.1 Initial Setup 15
3.2 Troubleshooting
17
3.3 Master Mode
17
4 Technical Data
18
4.1 General Data
18
4.2 Norms and Standards
20
4.3 France UTE Requirements
21
4.4 Installation
21
4.5 Cable Requirements
22
4.6 Torque Specifications for Installation
25
4.7 Mains Circuit Specifications
26
4.8 Auxiliary Interface Specifications
27
4.9 RS-485 and Ethernet Connections
29
Contents
L00410309-09_02 1
www.neoenerji.com
1 Introduction
Illustration 1.1 Solar Inverter
This manual explains the installation and setup of the TLX Series solar inverter, for the installation technician.
The TLX Series inverter range comprises the variants: TLX TLX+ TLX Pro TLX Pro+
TLX TLX+ TLX Pro TLX Pro+ Common features Power 6 kVA - 15 kVA Enclosure IP54 PV connectors MC4 connectors User interface Display
Service web interface Web interface
Languages DK, GB, DE, FR, ES, ITA, CZ, NL, GR
Table 1.1 Common Features
Introduction
2 L00410309-09_02
11
www.neoenerji.com
Product Label
Illustration 1.2 Product Label
The product label on the side of the inverter shows:
Inverter type
Important specifications
Serial number, see (1), for identification by Danfoss
1.1.1
Installation Sequence
1.
Pay special attention to 1 Safety and Conformity.
2.
Install the inverter according to 2.1 Installation
Dimensions and Patterns and 2.2 Mounting the Inverter.
3.
Open the inverter according to 2.4 Opening and Closing the Inverter.
4.
Install AC according to 2.5 AC Grid Connection.
5. Install PV.
6.
Install Auxiliary input according to 2.8 Auxiliary Input/Output .
7.
Close the inverter according to 2.4 Opening and Closing the Inverter.
8. Turn on AC at the mains switch.
9. Set language, time, date, installed PV power, country and grid:
- For setup via the web interface, see the
TLX Series User Manual, Web Server Quick Guide section.
-
For setup via the display, see 3 Start-up and Check of Settings.
10. Turn on PV by turning the PV load switch on.
11. Verify the installation by comparing with the auto-detection result in the display, as described in 2.7 PV Connection.
12. The inverter is now ready for operation.
Introduction
L00410309-09_02 3
1 1
www.neoenerji.com
1.1.2 Overview of Inverter
Illustration 1.3 Overview of Danfoss TLX inverter
Live Parts
1. AC Connection Area
2. DC Connection Area
3. Terminal block for parallel connection
4. Auxiliary output: Potential free relay
PELV (Safe to touch)
5. Auxiliary interface: RS-485
6. Auxiliary interface: Temperature, Irradiation, Energy meter (SO)
7. Auxiliary interface: Ethernet
Other
8. PV load switch
The TLX Pro and TLX Pro+ variants can also be configured via the web interface. For further information refer to the Web Server User Manual.
Introduction
4 L00410309-09_02
11
www.neoenerji.com
2 Installation
2.1 Installation Dimensions and Patterns
CAUTION
Follow these instructions carefully to ensure correct instal­lation of the inverter.
NOTE
When choosing the installation place, ensure that all labels are visible at all times. For details refer to 4 Technical Data.
Illustration 2.1 Avoid constant stream of water
Illustration 2.2 Avoid direct sunlight
Illustration 2.3 Ensure adequate air flow
Illustration 2.4 Ensure adequate air flow
Illustration 2.5 Mount on non-flammable surface
Illustration 2.6 Mount upright on vertical surface
Illustration 2.7 Prevent dust and ammonia gases
Installation
L00410309-09_02 5
2
2
www.neoenerji.com
Illustration 2.8 Safe Distances
Observe these distances when installing one or more inverters. One-row mounting is recommended. Contact the supplier for information on mounting in more rows.
Installation
6 L00410309-09_02
2
www.neoenerji.com
Illustration 2.9 Wall Plate
NOTE
Use of the wall plate delivered with the inverter is mandatory.
Use screws that can safely carry the weight of the inverter. The inverter must be aligned and it is important that the inverter is accessible at the front to allow room for servicing.
Installation
L00410309-09_02 7
2
2
www.neoenerji.com
2.2 Mounting the Inverter
CAUTION
For safe handling of the inverter, two people must carry the unit, or a suitable transport trolley must be used. Safety boots must be worn.
Illustration 2.10 Position the Inverter
Tilt the inverter as shown in the illustration and place the top of the inverter against the mounting bracket. Use the two guides (1) at the top plate to control the inverter horizontally.
Illustration 2.11 Secure the inverter
Lift the inverter upwards (2) over the top of the mounting plate until the inverter tilts towards the wall (3).
Illustration 2.12 Place Inverter in Mounting Bracket
Place the lower part of the inverter against the mounting bracket.
Illustration 2.13 Fasten screws
Lower (4) the inverter and make sure that the hook of the inverter base plate is placed in the lower part of the
Installation
8 L00410309-09_02
2
www.neoenerji.com
mounting bracket (5). Check that it is not possible to lift the bottom of the inverter away from the mounting bracket. (6) Fasten the screws on either side of the wall plate to secure the inverter.
2.3 Removing the Inverter
Loosen the locking screws on either side of the inverter.
Removal is performed in the reverse order of mounting. With a firm grip at the lower end of the inverter, lift the inverter approximately 20 mm vertically. Pull the inverter slightly away from the wall. Push upwards at an angle until the wall plate releases the inverter. Lift the inverter away from the wall plate.
2.4 Opening and Closing the Inverter
WARNING
Remember to observe all ESD safety regulations. Any electrostatic charge must be discharged by touching the earthed housing before handling any electronic component.
Illustration 2.14 Loosen Front Screws
Use a TX 30 screwdriver to loosen the two front screws. Turn the screwdriver until the screws pop up. Screws are secured with a spring and cannot fall out.
Illustration 2.15 Open the Inverter
Push the front cover upwards. When a slight resistance is felt, give the front cover a tap on the bottom to snap it into holding position. It is recommended to use the holding position instead of dismounting the front cover completely.
Installation
L00410309-09_02 9
2
2
www.neoenerji.com
Illustration 2.16 Close the Inverter
To close the inverter, hold on to the lower end of the front cover with one hand and give it a tap on the top until it falls into place. Guide the front cover into place and fasten the two front screws.
Illustration 2.17 Fasten Front Screws
CAUTION
The two front screws are the PE connection to the front cover. Make sure that both screws are mounted and fastened with the specified torque.
Installation
10 L00410309-09_02
2
www.neoenerji.com
2.5 AC Grid Connection
NOTE
When choosing the installation place, ensure that all labels are visible at all times. For details refer to 4 Technical Data.
150AA059.10
10mm
140mm
16mm
L1 L2 L3 N
PE
Illustration 2.18 AC Cable Wire Strip
The illustration shows the stripping of insulation of all 5 wires of the AC cable. The length of the PE wire must be longer than the mains and neutral wires.
1
N
L3
L2
L1
PE
PE
150AA002.11
Illustration 2.19 AC Connection Area
1 Short-circuit bridge L1, L2, L3, N
3 mains (L1, L2, L3) and neutral (N) terminals
PE Protective earth wire
Table 2.1 Legend to Illustration 2.19
1. Verify the inverter matches the grid-voltage.
2. Release main circuit breaker and make precautions to prevent reconnection.
3. Open the front cover.
4. Insert the cable through the AC gland to the terminal blocks.
5. The three mains wires (L1, L2, L3) and the Neutral wire (N) are mandatory and must be connected to the 4-pole terminal block with the respective markings.
6. The Protective Earth wire (PE) is mandatory and must be connected directly to the chassis PE terminal. Insert the wire and fasten the screw to secure the wire.
7. All wires must be properly fastened with the correct torque. See 4.6 Torque Specifications for Installation.
8. Close the front cover, and remember to verify that both front screws are applied with the correct torque (6-8 Nm) to obtain PE connection.
9. Close main circuit breaker.
CAUTION
For safety, check all wiring. Connecting a phase wire to the neutral terminal may permanently damage the inverter. Do not remove the short-circuit bridge at (1).
Installation
L00410309-09_02 11
2
2
www.neoenerji.com
2.6 Parallel PV String Configuration
For parallel PV string configuration, always use the internal parallel jumper, together with an external parallel coupling.
150AA026.12
12A
12A
12A
12A
12A
12A
20A
20A
20A
Inverter PV module
12A
12A
12A
20A
20A
20A
30A
12A
12A
12A
20A
20A
20A
7A
7A
Cabling
12A
12A
12A
12A
12A
12A
12A
12A
12A
7A
7A
2
1
1
1
3
Illustration 2.20 Correct Parallel Connection
1
Parallel jumper 2 Parallel connection, 3 inputs 3 Parallel connection, 2 inputs
Table 2.2 Legend to Illustration 2.20
Installation
12 L00410309-09_02
2
www.neoenerji.com
150AA027.12
30A
12A
12A
12A
12A
12A
12A
20A
20A
20A
12A
12A
12A
20A
20A
20A
30A
12A
12A
12A
12A
12A
12A
20A
20A
20A
7A
7A
12A
12A
12A
7A
7A
Inverter
PV moduleCabling
1
2
3
4
1
Illustration 2.21 Incorrect Parallel Connection
1
Parallel jumper 2 Parallel connection, 1 input. Current in first input is
exceeded, thus overloading cable and PV load switch. 3 Parallel connection missing. All PV power feeds into one
input, thus risking overload of PV connector, cable and PV
load switch. 4 Parallel jumper missing, thus risking overload of PV
connector, cable and PV load switch in the event of inverter
failure.
Table 2.3 Legend to Illustration 2.21
Installation
L00410309-09_02 13
2
2
www.neoenerji.com
2.7 PV Connection
WARNING
Do NOT connect PV to earth!
NOTE
Use a suitable voltmeter that can measure up to 1000 V DC.
PV Connection Procedure:
1. First verify the polarity and maximum voltage of the PV arrays by measuring the PV open-circuit voltage. The PV open-circuit voltage must not exceed 1000 V DC.
2. Measure the DC voltage between the plus­terminal of the PV array and Earth (or the green/ yellow PE cable). The voltage measured should approximate zero. If the voltage is constant and not zero there is an insulation failure somewhere in the PV array. Locate and fix the failure before continuing.
3. Repeat this procedure for all arrays. It is allowed to distribute the input power on the inputs unevenly, presuming that:
The nom. PV power of the inverter is not exceeded (6.2 / 8.2 / 10.3 / 12.9 /
15.5 kW).
The maximum short-circuit current of the PV modules must not exceed 12 A per input.
4. On the inverter turn the PV load switch into off position. Connect the PV cables by means of MC4 connectors. Ensure correct polarity! The PV load switch can now be switched on when required.
Illustration 2.22 DC Connection Area
CAUTION
When unmated, the MC4 connectors are not IP54. Intrusion of moisture may occur. In situations where the PV connectors are not fitted, a seal cap must be mounted (included in the scope of the delivery). All inverters with MC4 connections are delivered with seal caps on inputs 2 and 3. During installation, the seal caps of those inputs that are to be used are discarded.
NOTE
The inverter is protected against reversed polarity but it will not generate power until the polarity is corrected. To achieve optimum production, the open-circuit voltage (STC) of the PV modules must be lower than the max. input voltage of the inverter (see 4.1 General Data), multiplied with a factor of 1.13. UOC, STC x 1.13 ≤ U
MAX
, inv.
2.8 Auxiliary Input/Output
The inverter has the following auxiliary input/output:
2 x RJ-45 for RS-485
2 x RJ-45 for Ethernet
1 x 8 pole terminal block for RS-485
1 x 10 pole terminal block for
- PT1000 temperature sensor input x 3
- Irradiation sensor input
- Energy meter (S0) input
1 x 2 pole terminal block for relay outputs
Refer to the specifications for an overview of the communication board and to the inverter user manual for details regarding auxiliary input configuration via the display.
2.9
Autotest Procedure
An automatic test of the inverter can be initialised by activating the inverter autotest procedure:
Via the display, go to [Setup Autotest] and press OK.
Via the web interface, go to [Inverter level: Setup Setup details Autotest] and click on [Start Test].
The inverter autotest manual can be downloaded from www.danfoss.com/solar.
Installation
14 L00410309-09_02
2
www.neoenerji.com
3 Start-up and Check of Settings
3.1.1 Initial Setup
The inverter is shipped with a predefined set of settings for different grids. All grid specific limits are stored in the inverter and must be selected at installation. It is always possible to see the applied grid limits in the display. The inverter accounts for daylight saving automatically. After installation, check all cables and then close the inverter. Turn on AC at the mains switch.
Follow the setup wizard in the display, or, alternatively, set up the inverter via the web interface.
When prompted by the display select language. This selection has no influence on the operating parameters of the inverter and is not a grid code selection.
Illustration 3.1 Select Language
The language is set to English at initial start-up. To change this setting press the OK button. Press ‘▼’ to scroll down through the languages. Select language by pressing ‘OK’.
NOTE
To use the default language (English) simply press the 'OK' button twice to select and accept.
Illustration 3.2 Set Time
Set time as prompted by the display. Press 'OK' to select number. Press ‘▲’ to scroll up through the numbers. Select by pressing 'OK'. The clock is 24-hour format.
NOTE
It is very important to set the time and date accurately as the inverter uses this for logging. If an incorrect time/date is accidentally set, correct it immediately in the set date and time menu [Setup Inverter details Set date and time].
Illustration 3.3 Set Date
Set date as prompted by the display. Press 'OK' to select. Press ‘▲’ to scroll up through the numbers. Select by pressing 'OK'.
Start-up and Check of Setti...
L00410309-09_02 15
3 3
www.neoenerji.com
Illustration 3.4 Installed PV Power
Enter the amount of installed PV power for each of the PV inputs. When two or more PV inputs are connected in parallel, each PV input in the parallel group must be set to the total amount of PV power installed to that group divided by the number of parallel inputs. See Table 3.1.
Illustration 3.5 Select Country
Select the country in which the inverter is installed. Press '▼' to scroll down the list of countries. To select a country, press 'OK'.
Illustration 3.6 Select Grid Code
The display will now show “Select grid”. The grid code is set to “undefined” at initial start-up. To select grid code, press 'OK'. Press ‘▼’ to scroll down through the list of countries. Select the grid code for the installation by pressing ‘OK’. It is very important that the correct grid code is chosen.
Illustration 3.7 Confirm Grid Code Selection
Confirm the choice by selecting the grid code again and press 'OK’. The settings for the chosen grid code have now been activated.
Start-up and Check of Setti...
16 L00410309-09_02
33
www.neoenerji.com
CAUTION
Correct selection of grid code is essential to comply with local and national standards.
NOTE
If the two grid code selections do not match they will be cancelled and it will be necessary to redo the selections. If an incorrect grid code is accidentally accepted at the first selection, simply accept the “Grid: Undefined” in the confirm grid code screen. This will cancel the country selection and a new selection is possible.
NOTE
If an incorrect grid code is selected twice, call service.
The inverter will start automatically if sufficient solar radiation is available. The start-up will take a few minutes. During this period, the inverter will carry out a self-test.
Actual Configuration
“Installed PV power” to be
programmed PV1, PV2 and PV3 are all set into individual mode. The nominal PV power installed are: PV 1: 6000 W PV 1: 6000 W PV 2: 6000 W PV 2: 6000 W PV 3: 3000 W PV 3: 3000 W PV1 and PV2 are set into parallel mode and have a total of 10 kW PV power installed. PV3 is set into individual mode and has nominal 4 kW PV power.
PV 1: 5000 W
PV 2: 5000 W
PV 3: 4000 W
PV1 and PV2 are set into parallel mode and have a total of 11 kW PV power installed. PV3 is set to ‘Off’ and has no PV installed.
PV 1: 5500 W
PV 2: 5500 W
PV 3: 0 W
Table 3.1 Examples of Installed PV Power
3.2
Troubleshooting
For information on Troubleshooting, see the TLX Reference Manual.
3.3
Master Mode
The TLX Pro and TLX Pro+ inverters include a Master mode feature that allows one inverter to be appointed as master inverter. From the web interface of the master inverter, it is possible to access any inverter in the network from one single point using a standard web browser. The master inverter can act as a datalogger, collecting data from all inverters in the network. These data can be displayed graphically from the web interface of the master inverter, or the data can also be uploaded to external webportals or exported directly to a PC. The master inverter is also able to replicate settings and data to the other TLX Pro and TLX
Pro+ inverters in the network, enabling easy commis­sioning and data management of larger networks.
Illustration 3.8 Master Mode
To enable Master mode go to the Inverter details menu [SetupInverter detailsMaster mode] and set Master mode to Enabled. Ensure that no other master inverters are present in the network prior to carrying out this action. When Master mode is enabled, it is possible to initiate a network scan [SetupInverter detailsMaster modeNetwork]. This will show all inverters connected to the master inverter.
NOTE
Only 1 master per network is possible.
NOTE
The master inverter can operate in a network of up to 99 follower inverters.
CAUTION
All inverters connected to the internet through Ethernet must be behind a firewall.
CAUTION
At first login to the web ,server change the default password. Plant level: [Setup Web server Admin].
Start-up and Check of Setti...
L00410309-09_02 17
3 3
www.neoenerji.com
4 Technical Data
4.1 General Data
Nomenclat ure
1)
Parameter TLX Series
6k
TLX Series
8k
TLX Series
10k
TLX Series
12.5k
TLX Series
15k
AC |S| Rated apparent power 6000 VA 8000 VA 10000 VA 12500 VA 15000 VA P
ac,r
Rated active power
*)
6000 W 8000 W 10000 W 12500 W 15000 W
Active power at cos(phi) =
0.95
**)
5700 W 7600 W 9500 W 11875 W 14370 W
Active power at cos(phi) =
0.90
**)
5400 W 7200 W 9000 W 11250 W 13500 W
Reactive power range 0-3.6 kVAr 0-4.8 kVAr 0-6.0 kVAr 0-7.5 kVAr 0-9.0 kVAr V
ac,r
Rated grid voltage (range) 3P + N + PE - 230 V / 400 V (± 20%) Rated current AC 3 x 8.7 A 3 x 11.6 A 3 x 14.5 A 3 x 18.1 A 3 x 21.7 A I
acmax
Max. current AC
3 x 9.0 A 3 x 11.9 A 3 x 14.9 A 3 x 18.7 A 3 x 22.4 A
AC current distortion (THD
%)
< 4% < 5%
cosphi
ac,r
Power factor at 100% load
> 0.99
Controlled power
factor range
0.8 over-excited
0.8 under-excited
Power loss, Connecting
mode
10 W
Night-time power loss (off
grid)
< 5 W
f
r
Grid frequency (range)
50 Hz (± 5 Hz) DC P
mpptmax
Maximum PV input power per MPPT
8000 W
ΣP
mpptmax
Max./nom. converted PV input power, total
6200 W 8250 W 10300 W 12900 W 15500 W
V
dc,r
Nominal rated voltage DC
700 V
V
mppmin
-
V
mppmax
MPP voltage - nominal power
2)
260-800 V 345-800 V 430-800 V 358-800 V 430-800 V
MPP efficiency, static 99.9% MPP efficiency, dynamic 99.7% V
dcmax
Max. DC voltage
1000 V
V
dcstart
Turn on voltage DC
250 V
V
dcmin
Turn off voltage DC
250 V
I
dcmax
Max. current DC
2 x 12 A 3 x 12 A
Max. short circuit current
DC at STC
2 x 12 A 3 x 12 A
Min. on grid power 20 W Efficiency Max. efficiency 97.8% 97.9% 98.0%
Technical Data
18 L00410309-09_02
44
www.neoenerji.com
Nomenclat ure
1)
Parameter TLX Series
6k
TLX Series
8k
TLX Series
10k
TLX Series
12.5k
TLX Series
15k
Euro efficiency, V at
dc,r
96.5% 97.0% 97.0% 97.3% 97.4% Other Dimensions (H,W,D) 700 x 525 x 250 mm Mounting Wall bracket Weight 35 kg Acoustic noise level 56 dB(A) MPP trackers 2 3 Operation temperature
range
-25..60 °C
Nom. temperature range -25..45 °C Storage temperature -25..60 °C Overload operation Change of operating point
Active power control
3)
Included
Reactive power control TLX+ and TLX Pro+
Table 4.1 General Specifications
1) According to FprEN 50524 where relevant.
2) At identical input voltages. At unequal input voltages, V
mppmin
can
be as low as 250 V depending on total input power.
3) Remotely controlled via CLX monitoring and grid management product or third-party device.
*) At rated grid voltage (V
ac,r
), Cos(phi) = 1.
**) At rated grid voltage (V
ac,r
).
Parameter TLX Series Functional Safety Passive Active AC discon-
nection Safety (protective class) Class I PELV on the communi­cation and control card
Class II
Islanding detection - loss of mains
Three-phase
monitoring ROCOF Voltage magnitude Included Frequency Included Insulation resistance Included RCMU - Type B Included Indirect contact protection
Yes (class I,
grounded)
Table 4.2 Functional Safety Specifications
Technical Data
L00410309-09_02 19
4 4
www.neoenerji.com
4.2 Norms and Standards
Normative References
TLX Series
6k 8k 10k 12.5k 15k Directive LVD 2006/95/EC Directive EMC 2004/108/EC Safety IEC 62109-1/IEC 62109-2 Integrated PV load switch
VDE 0100-712
EMC immunity
EN 61000-6-1 EN 61000-6-2
EMC emission
EN 61000-6-3
EN 61000-6-4 Utility interference EN 61000-3-2/-3 EN 61000-3-11/-12 CE Yes
Utility characteristics
IEC 61727
EN 50160 S0 Energy Meter EN62053-31 Annex D Functional Safety For transformerless inverter Germany
VDE 0126-1-1/A1
1)
VDE AR-N 4105 (August 2011)
2)
Greece
Technical requirements for the connection of independent generation to the grid, Public Power Corporation
(PPC).
Italy
-
CEI 0-21:2012-06, Terna Guida Tecnica Allegato A.70
2)
Spain
RD1699 (2011)
RD661 (2007) Portugal VDE 0126-1-1, ISO/IEC Guide 67: 2004 - System No.5 UK - G59/2-1, G83/1-1 G59/2-1
Ancillary Services
TLX Series
TLX+ and TLX Pro+
6k 8k 10k 12.5k 15k Austria TOR – Hauptabschnitt D4, TOR – Hauptabschnitt D2 Belgium Synergrid C10/11 – Revisie 2012-06, Synergrid C10/17- revisie 8 mei 2009 Czech Republic Czech Energy Act (Act No. 458/2000), Article 24, Paragraph 10 part I,II,III rev09 2009
France
UTE NF C 15-712-1 (UNION TECHNIQUE DE L'ELECTRICITE, GUIDE PRATIQUE, Installations photovoltaïques
raccordées au réseau public de distribution).
NF C 15-100 (Installations électriques à basse tension).
Journal Officiel, Décret n°2008-386 du 23 avril 2008 relatif aux prescriptions techniques générales de conception
et de fonctionnement pour le raccordement d'installations de production aux réseaux publics d'électricité.
Germany -
BDEW- Technische Richtlinie Erzeugungsanlagen am Mittelspannungsnetz Ausgabe, Juni
2008 und Ergänzungen von 01/2009, 07/2010, 02/2011
2)
Spain REE BOE núm. 254
Table 4.3 Norms and Standards
1) Deviant from VDE 0126-1-1 section 4.7.1, the isolation resistance measurement limit is set to 200 kΩ, in accordance with authorities.
2) TLX+ and TLX Pro+ only.
Technical Data
20 L00410309-09_02
44
www.neoenerji.com
4.3 France UTE Requirements
NOTE
In France, observe the UTE C 15-712-1 and NF C 15-100 requirements.
For installation in France, apply warning label to front of inverter.
Illustration 4.1 Position of Warning Label
4.4 Installation
Parameter Specification Temperature
25 °C - +60 °C (>45 °C derating) Environmental class according to IEC
IEC60721-3-3 3K6/3B3/3S3/3M2
Air quality - general ISA S71.04-1985
Level G2 (at 75% RH) Air quality - coastal, heavy industrial and agricultural zones
Must be measured and classified acc. to
ISA S71.04-1985
Vibration 1G Ingress protection class
54
Max. operating altitude
3000 m above sea level.
PELV protection is effective up to 2000
m above sea level only. Installation Avoid constant stream of water.
Avoid direct sunlight.
Ensure adequate air flow.
Mount on non-flammable surface.
Mount upright on vertical surface.
Prevent dust and ammonia gases.
Table 4.4 Conditions for Installation
Parameter Condition Specification
Wall Plate Hole diameter 30 x 9 mm
Alignment Perpendicular ± 5° all
angles
Table 4.5 Wall Plate Specifications
Technical Data
L00410309-09_02 21
4 4
www.neoenerji.com
4.5 Cable Requirements
Cable Condition Specification
AC 5 wire cable Copper Outer diameter 18-25 mm Max. recommended cable length TLX Series 6k, 8k and 10k
2.5 mm
2
21 m
4 mm
2
34 m
6 mm
2
52 m
10 mm
2
87 m
Max. recommended cable length TLX Series
12.5k
4 mm
2
28 m
6 mm
2
41 m
10 mm
2
69 m
Max. recommended cable length TLX Series 15k
6 mm
2
34 m
10 mm
2
59 m
DC Max. 1000 V, 12 A Cable length
4 mm2 - 4.8 Ω /km
< 200 m*
Cable length
6 mm2 - 3.4 Ω /km
>200-300 m* Mating connector Multi-contact PV-ADSP4./PV-ADBP4. * The distance between inverter and PV array and back, plus the cumulative length of PV array cabling.
Table 4.6 Cable Requirements
NOTE
Avoid power loss in cables greater than 1% of nominal inverter rating.
[%]
2.5 mm
2
4 mm
2
6 mm
2
10 mm
2
2
1.5
1
0.5
0
0 20 40 60 80
[m]
150AA044.11
Illustration 4.2 TLX Series 6k Cable Losses [%] versus Cable Length [m]
Technical Data
22 L00410309-09_02
44
www.neoenerji.com
[%]
2.5 mm
2
4 mm
2
6 mm
2
10 mm
2
2
1.5
1
0.5
0
0 20 40 60 80
[m]
150AA045.11
Illustration 4.3 TLX Series 8k Cable Losses [%] versus Cable Length [m]
[%]
2.5 mm
2
4 mm
2
6 mm
2
10 mm
2
2
1.5
1
0.5
0
0 20 40 60 80
[m]
150AA046.11
Illustration 4.4 TLX Series 10k Cable Losses [%] versus Cable Length [m]
Technical Data
L00410309-09_02 23
4 4
www.neoenerji.com
[%]
4 mm
2
6 mm
2
10 mm
2
2
1.5
1
0.5
0
0 20 40 60 80
[m]
150AA047.11
Illustration 4.5 TLX Series 12.5k Cable Losses [%] versus Cable Length [m]
[%]
4 mm
2
6 mm
2
10 mm
2
2
1.5
1
0.5
0
0 20 40 60 80
[m]
150AA048.11
Illustration 4.6 TLX Series 15k Cable Losses [%] versus Cable Length [m]
Consider also the following when choosing cable type and cross-sectional area:
- Ambient temperature
- Layout type (inside wall, under ground, free air etc.)
- UV resistance
Technical Data
24 L00410309-09_02
44
www.neoenerji.com
4.6 Torque Specifications for Installation
Illustration 4.7 Overview of Inverter with Torque Indications, 1-3
6
4
5
7
150AA007.11
Illustration 4.8 Overview of Inverter with Torque Indications, 4-7
Parameter Tool Tightening Torque
1 Terminal blocks (large) Straight slot 1.0 x 5.5 mm Min. 1.2 Nm 2 Terminal blocks (small) Straight slot 1.0 x 5.5 mm 0.5 Nm 3 PE Straight slot 1.0 x 5.5 mm 2.2 Nm 4 M16 SW 19 mm 2-3 Nm 5 M25 SW 30 mm 2-3 Nm 6 Front screw TX 30 6-8 Nm 7 Locking screw TX 30 5 Nm
Table 4.7 Legend to Illustration 4.7 and Illustration 4.8, Nm Specifications
Technical Data
L00410309-09_02 25
4 4
www.neoenerji.com
4.7 Mains Circuit Specifications
TLX Series
6k 8k 10k 12.5k 15k Maximum inverter current, I
acmax.
9.0 A 11.9 A 14.9 A 18.7 A 22.4 A
Recommended blow fuse type gL/gG13 A 16 A 20 A 20 A 25 A
Recommended automatic fuse typeB16 A 20 A 20 A 25 A 32 A
Table 4.8 Mains Circuit Specifications
Technical Data
26 L00410309-09_02
44
www.neoenerji.com
4.8 Auxiliary Interface Specifications
Parameter Parameter Details Specification
Serial Communication RS-485 Common cable specification
Cable jacket diameter ()
2 x 5-7 mm
Cable type
Shielded Twisted Pair (STP) (Cat 5e)
2)
Cable Characteristic Impedance 100 Ω – 120 Ω Max. cable length 1000 m
RJ-45 (2 pcs.) connectors Wire gauge 24-26 AWG (depending on mating metallic RJ-45
plug)
Cable shield termination Via metallic RJ-45 plug
Terminal block Maximum wire gauge
2.5 mm
2
Cable shield termination Via EMC cable clamp
Max. number of inverter nodes
63
4)
Galvanic interface insulation Yes, 500 Vrms Direct contact protection Double/Reinforced insulation Yes Short-circuit protection Yes Communication Star and daisy chain Ethernet Common cable Max. cable length between inverters 100 m (total network length: unlimited) Specification Max. number of inverters
100
1)
Cable type
Shielded Twisted Pair (STP) (Cat 5e)
2)
Temperature sensor input
3 x PT1000
3)
Cable specification
Cable jacket diameter ()
4-8 mm Cable type Shielded Single Pair - 2-wire Cable shield termination Via EMC cable clamp Maximum wire gauge
2.5 mm
2
Maximum resistance per wire
10 Maximum cable length 30 m
Sensor specification Nominal resistance/temperature coefficient
3.85 /oC
Measurement range
-20 oC - +100 oC
Measurement accuracy ±3%
Direct contact protection Double/Reinforced insulation Yes Short-circuit protection Yes Irradiation sensor input x 1 Cable specification
Cable jacket diameter ()
4-8 mm Cable type Shielded Single Pair - Number of wires depend on
the sensor type used Cable shield termination Via EMC cable clamp Maximum wire gauge
2.5 mm
2
Maximum resistance per wire
10 Maximum cable length 30 m
Sensor Specification Sensor type Passive
Measurement accuracy ±5% (150 mV sensor output voltage) Output voltage of sensor 0-150 mV Max. output impedance (sensor)
500 Input impedance (electronics)
22 k
Direct contact protection Double/Reinforced insulation Yes Short-circuit protection Yes Energy meter input S0 input x 1
Technical Data
L00410309-09_02 27
4 4
www.neoenerji.com
Parameter Parameter Details Specification
Cable specification
Cable jacket diameter ()
4-8 mm Cable type Shielded Single Pair - 2-wire Cable shield termination Via EMC cable clamp Maximum wire gauge
2.5 mm
2
Maximum cable length 30 m
Sensor Input Specification Sensor input class Class A
Nominal output current
12 mA for an 800 load Maximum short-circuit output current 24.5 mA Open-circuit output voltage +12 VDC Maximum pulse frequency 16.7 Hz
Direct contact protection Double/Reinforced insulation Yes Short-circuit protection Yes
Table 4.9 Auxiliary Interface Specifications
1)
A maximum of 100 inverters can be connected in 1 network. If GSM modem is used for portal upload, the number of inverters in a network is limited to 50.
2)
For underground use, outdoor burial type cable is recommended for both Ethernet and RS-485.
3)
Third input is used for compensation of the irradiation sensor.
4)
The number of inverters to be connected in the RS-485 network depends on which peripheral device is connected.
CAUTION
To ensure fulfilment of IP enclosure rating, correctly mounted cable glands are essential for all peripheral cables.
CAUTION
To ensure EMC compliance, shielded cables must be applied for sensor inputs and RS-485 communication. Unshielded cables may be applied for alarm outputs. Other auxiliary cables must pass through the designated EMC cable clamps to establish mechanical fixing and in case of shielded cable termination to the shielding device.
Parameter Condition Specification
Potential free contact
Relay output x 1
Rating AC 250 V AC, 6.4 A, 1600 W Rating DC 24 V DC, 6.4 A, 153 W Maximum wire gauge
2.5 mm
2
Overvoltage category
Class III
Modem GSM
Table 4.10 Auxiliary Input Specifications
Technical Data
28 L00410309-09_02
44
www.neoenerji.com
150AA058.11
RS485
2 x RJ45
Ethernet 2 x RJ45
L N
+ /
+ / + /
+ /
+ /
1
2 3 4
5
6
7
Illustration 4.9 Communication Board
1
8-pole terminal blocks 2 PT1000/module temp. 3 PT1000/ambient temp. 4 PT1000/irradiation sensor temp. 5 Irradiation sensor 6 S0/Energy meter 7 Relay 1
Table 4.11 Legend to Illustration 4.9
4.9 RS-485 and Ethernet Connections
RS-485 Terminate the RS-485 communication bus at both ends. To terminate the RS-485 bus:
Connect Bias H to RX/TX B
Connect Bias L to RX/TX A
The RS-485 address of the inverter is unique, and defined at the factory.
Illustration 4.10 RS-485 Communication Detail - Cat 5 T-568A
Technical Data
L00410309-09_02 29
4 4
www.neoenerji.com
150AA019.10
1
2
3
4
5
6
7
8
Illustration 4.11 RJ-45 Pinout Detail for RS-485
1 GND 2 GND 3 RX/TX A (-) 4 BIAS L 5 BIAS H 6 RX/TX B (+) 7 Not connected 8 Not connected
Table 4.12 Legend to Illustration 4.11
Bold=Compulsory, Cat5 cable contains all 8 wires For Ethernet: 10Base-TX and 100Base-TX auto cross over
Ethernet Ethernet connection is available for TLX Pro and TLX Pro+ variants only.
150AA019.10
1
2
3
4
5
6
7
8
Illustration 4.12 RJ-45 Pinout Detail for Ethernet
Colour Standard
Pinout Ethernet Cat 5
T-568A
Cat 5
T-568B 1 RX+ Green/white Orange/white 2 RX Green Orange 3 TX+ Orange/white Green/white 4 Blue Blue 5 Blue/white Blue/white 6 TX- Orange Green 7 Brown/white Brown/white 8 Brown Brown
Table 4.13 Legend to Illustration 4.12
CAUTION
TLX Pro and TLX Pro+ inverters connected to the internet through Ethernet must be behind a firewall.
CAUTION
At first login to the web server, change the default password. Plant level: [Setup Web server Admin].
Technical Data
30 L00410309-09_02
44
www.neoenerji.com
Danfoss Solar Inverters A/S
Ulsnaes 1 DK-6300 Graasten Denmark Tel: +45 7488 1300 Fax: +45 7488 1301 E-mail: solar-inverters@danfoss.com www.danfoss.com/solar
Rev. date 2012-11-25 Lit. No. L00410309-09_02
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
www.neoenerji.com
Loading...