Radiator Thermostat RAS-C2 Combi

BI-DIRECTIONAL VALVE WITH FLOW-SELECTABLE FEATURE

<![if ! IE]>

<![endif]>013R9355

Installation of valve

The valve is a bi-directional valve * and can be installed horizontally or vertically in either the flow or return pipe.

A built in flow direction selection feature can be used to eliminate the risk of water hammer.

Troubleshooting

In the unlikely event of water hammer being encountered turn the setting ring (see diagram 4) to the other setting. Alternatively if commissioning the whole system, establish the flow direction through each valve using the diagrams below.

If the flow direction needs to be changed there is no need to remove the valve, simply turn the setting ring.

1

2

3

Close all radiator valves by turning

Start boiler/heating.

Open one valve and determine

the valve cover cap clockwise.

 

flow direction. Which pipe heats

Leave system to cool.

 

first?

Keymark reference: This package contains sensor 013G6040, valve 013G6281 (15mm) or valve 013G6283 (8/10 mm)

Setting ring

4

Remove cap and turn setting ring according to the drawings - the setting ring is turned by hand only.

5

Repeat step 3 and 4 until all valves have been set correctly. Sensor may now be fitted or the valve cap temporarily refitted.

* Maximum pressure drop should not exceed 0.45 bar