3. Electric motor manual (180R9230) ......................................................43
4. Parts list PAHT (AX322445815902en-000201) ............................................49
5. Trouble shooting guide for PAH, PAHT, PAHT G, PAHT 674 and PAH F pumps .............59
6. Right and wrong - Trouble shooting guide for water hydraulic systems (180R9042).......71
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
3
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
This manual is valid for PAHT pumps with the following code numbers/serial numbers:Validity
PAHT 2.0Code no. 180B 0031
Serial no.XXXXXX08-XXX
PAHT 3.2Code no. 180 B0077
Serial no.XXXXXX03-XXX
PAHT 4.0Code no. 180B0030
Serial no.XXXXXX08-XXX
PAHT 6.3Code no. 180B 0029
Serial no.XXXXXX08-XXX
PAHT 10Code no. 180 B0032
Serial no.XXXXXX07-XXX
PAH T 12. 5Code no. 180 B0033
Serial no.XXXXXX07-XXX
The serial number is referring to the Serial no. on
Serial
T
the product label. The digits shown (07) indicate
the version number of the pump.
This documentation is compatible with previous
pump versions.
4
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
1. Introduction
1.1 General
The PAHT pumps and pump units are manufactured by Danfoss A/S, and are sold and marketed
by a net of authorized distributors world wide.
This manual contains the necessary instructions
for the installation, operation and service of the
pumps used for technical water.
In case the pump delivered is ATEX certified, the
additional ATEX instruction must also be read.
The PAHT pumps must not be used for other
purposes than those recommended and
specified without first consulting your local
pump distributor.
Use of the pump in other applications not
suitable for the pump unit can cause damages to
the pump unit, with risk of personal injury.
All personnel being responsible for operation
and maintenance of the pump unit must read
and fully understand these instructions,
especially the section “Safety”, before:
• Transportation of the pump unit
• Lifting the unit
• Installing the pump unit
• Connecting the pump unit to the water
system
• Connecting the electric motor and instrumentation
• Commissioning the unit
• Servicing the motor pump unit, mechanical
and electrical parts
• Decommissioning the motor pump unit
The pump must always be installed and used in
accordance with existing national/local
sanitary, safety regulations and laws.
It is important that these instructions are
always available to the personnel concerned.
1.2 Symbols
Indicates something to be noted by the
reader
Indicates a situation which will or could
result in damage to the pump and its
function
Indicates a situation which will or could
result in personal injury and/or damage
to the pump
Electrical hazard - Indicates a high-
voltage warning
Safety glasses required
Hearing protection required
Safety shoes required
Safety helmet required
!
Protective
garments
must be wor n
Protective garments
must be worn
It is the responsibility of the safety officer or
Danger HOT.
the chief operator to assure compliance with all
local regulations that are not taken into
account in this manual.
Electrical
hazard
Electrical hazard
Changing the pumps’ or pump units’ operational limits and hardware:
• Changes to the delivered pump or motor
pump system may only be done with a
written approval from Danfoss High Pressure
Pumps.
• Operation outside the Danfoss specifications
requires a written approval from Danfoss
High Pressure Pumps.
• If any changes are made without written
approval the warranty will automatically
become void.
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Do not touch
5
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
Dangers that can arise from not following the
instructions:
When the pump or pump system is managed by
untrained personnel, there is a danger of:
• Death or fatal injuries
• Costly damages and claims
Electrical
hazard
All electrical installation work must only be
carried out by authorized personnel in
accordance with EN60204-1 and/or local
regulations.
Your local Danfoss pump distributor can be
found on our homepage.
1.4 Country specific information
1.4.1 United Kingdom
UK importer:
Danfoss Ltd.
22 Wycombe End
HP9 1NB Beaconsfield
United Kingdom
Under certain operational conditions the surface
of the pump can be above 60°C / 140°F.
Under these conditions the pump must be
labelled with a “Danger Hot” sign.
When using an electric motor, the motor must
always be supplied with adequate cooling
ventilation.
When using an electric motor together with a
VFD (Variable Frequency Drive), the motor must
be designed for operation with VFD. VFD
operation may increase the temperature inside
the electric motor if the motor is not designed
for VFD operation. This can damage the motor
and cause unintended breakdown.
It is recommended to install a lockable circuit
breaker to avoid inadvertent starting and/or
electrical hazard. The lockable circuit breaker
must be used during installation, operation and
maintenance.
It is recommended to place a local safety switch
nearby the pump, enabling service personnel to
cut power for the electric motor.
Protect the motor and other electrical equipment from overloads with suitable equipment.
In case the pump delivered is ATEX certified, the
additional ATEX instruction must also be read.
Protective
garments
!
must be wor n
Always wear suitable safety clothing when
handling the pump.
When working near the pump system, safety
shoes, safety glasses, hearing protection and
safety helmet must always be worn.
Before start-up, the settings for all protective
devices, such as sensors/switches and safety
valves must be verified and free flow from safety
valves must be ensured.
All pipe and hose connections must be stressfree mounted, securely fastened to the pump
and well supported. Improper installation will or
could result in personal injury and/or damage to
the pump.
Use of this manual does not relieve operation
and maintenance personnel of the responsibility of applying good judgment when operating
and maintaining the pump and its components.
2.2 Preferred system design
Danfoss recommends to build systems with a
high degree of safety. Danfoss preferred system
design and P&ID are found in appendix 1, Data
sheet, and appendix 2, Instruction.
6
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
• Do not try to lift the pump unit manually;
It is always the system builders´ responsibility
that the system design does not cause any kind
of hazard and is adapted to local regulations and
standards.
Proper installation, proper start up and shutdown devices as well as high-pressure protection
equipment is essential.
2.3 Commissioning and servicing the unit
It is recommended that commissioning and
servicing are carried out by a minimum of two
people, where one is acting as a supervisor.
most of the pumps weigh more than
20 kilos, see specific weight for the pump
in the appendix 1, Data sheet.
• Always bleed the pump prior to initial
start-up.
• Do not mount the pump without the bell
housing and a flexible coupling.
• Do not try to start the unit before the
system components are mounted, bleeded
and adjusted.
• Flush the system throughly before
connecting the pump or pump unit.
• Check rotation direction of the motor
before mounting the pump.
3. Technical data
2.4 Adhere to the following important
points
• Before using the pump/pump unit it is very
important to read and understand this user
manual.
3.1 Approved applications and operational
limits for the pumps
The pump and the pump units are designed for
the use in systems with technical water.
2.5 In case of doubt
Please contact Danfoss A/S in case of doubt.
Contact information are listed in section 1.3,
Manufacturer and customer service address.
3.2 Application range
See appendix 1, Data sheet.
3.3 Electric motor data
See recommended motor in appendix 1, Data
sheet or appendix 3, IOM for motors. The motors
mentioned are the most common used motors
by Danfoss High Pressure Pumps.
3.4 Noise and vibration
Noise level for a pump unit with a ”standard”
motor measured according to EN ISO 3744:2010,
see appendix 1, Data sheet. Possibilities to
reduce noise and vibration are described in the
same Data sheet.
3.5 Dimension drawings
Dimensions of the different pumps can be found
in appendix 1, Data sheet.
The PAHT G pumps must not be used for other
purposes than those recommended and
specified without first consulting your local
pump distributor.
Use of the pump in other applications not
suitable for the pump unit can cause damages
to the pump unit, with risk of personal injury.
For system integration of the pumps, please
see appendix 1, Data sheet and appendix 2,
Instruction.
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
3.6 Space requirement
When doing service or replacing the complete
pump unit, it is recommended to have sufficient
space available around the pump in order to
ensure easy access. Sufficient space means at
least 1 meter/40 inches around the pump. When
working with high pressures, it is important to
have the right space available around the pump
as stated in the safety requirements.
7
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
4. Arrival inspection,
transportation,
handling, lifting and
storage
3.7 Filtration
(10µm absolute [β
Requirements are specified in appendix 1, Data
≥ 5000])
10
sheet and appendix 2, Instruction.
Danfoss recommends not to build a filter bypass
function or use filters with an integrated bypass.
If the above recommendation is not followed the
warranty for the pump will automatically
become void.
It should be possible to monitor the condition of
the filter via the differential/delta pressure across
the filter.
Using insufficient filtration or a filter bypass
can cause a failure or decreased service life of
the pump.
3.8 Properties of water
It is recommended NOT to use the pump for
other media than specified in the Data sheet.
4.1 Arrival inspection
The pump is packed in a cardboard or wood box
with plugs in the port connections to protect the
pump from damage during transportation.
When the shipment has arrived it is important to
check the pump for any damages. The name
plate/type designation must be in accordance
with the delivery note and your order.
3.9 Air bubbles
Large bubbles in a pressurised system can result
in damage to piping, equipment and the pump.
All air must be bleeded from both the lowpressure and high-pressure side before the
system is pressurised. Special consideration
should be given in order to minimize air bubbles
in the feed flow. Air bubbles can cause cavitation.
3.10 Chemicals
The pumps should not be exposed to any
chemicals that can result in damage to piping,
equipment and internal parts of the pump.
e.g. an overhead crane or industrial truck to be
used as minimum.
4.4 Transport and handling
Small pumps which have a weight below 20 kilos
(weight can be found in appendix 1, Data sheet)
can be handled by hand if they are not mounted
together with an electric motor. The weight of a
small pump with a motor will be above 20 kilos.
In case of damage and/or missing parts, a report
should be documented and presented to the
carrier at once.
4.2 Warning
Before any lifting operation is performed,
environmental conditions must be taken into
consideration (Ex-rated areas, wind speed, wet/
dry conditions, lifting height, etc.).
4.3 General safety information
Personnel involved in lifting and transporting the
equipment (see Safety, chapter 2) must be
trained in handling and safety procedures when
lifting heavy loads. Many of the pumps and
pump units weigh more than 20 kilos, which
requires lifting slings and suitable lifting devices;
8
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
Pumps which have a weight above 20 kilos (see
appendix 1, Data sheet) must be handled by
using lifting eyes and slings.
Wrong lifting:
When the pump is mounted together with an
electric motor, the pump unit always weigh more
than 20 kilos and must be handled by using
slings around the pump unit.
See below examples of where to/not to attach
the lifting slings on the pump unit:
Correct lifting with 2 separate slings:
When lifting the pump unit, one sling must be
attached to the electric motor and one sling
around the pump.
Only some motors and pumps have specific
lifting eyes.
Do not use connections/nozzles for lifting!
Do not use only one sling!
Make sure that the unit/load is balanced before
lifting. The centre of the mass varies from pump/
pump unit size to pump/pump unit.
How to mount the pump and the electric motor
correctly, see appendix 1, Data sheet or appendix
2, Instruction.
Incorrect lifting can result in personal injury
and/or damage to the pump unit, see appendix
2, Instruction.
4.5 Return to supplier
Please see maintenance chapter 7.
4.6 Storage
Each pump is tested before shipment, and will
therefore contain water. For storage temperature
and frost protection see appendix 2, Instruction.
The pumps are NOT delivered frost protected
from the factory.
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
9
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
PI
System
PI
M
5. Installation and
commissioning
5.1 Important dimensions
Physical dimensions and connections of the
pump unit are described in appendix 1, Data
sheet.
5.3 Fluid temperature
Before start-up, the fluid and pump housing
temperature must be within the specified
temperature range listed in appendix 1, Data
sheet.
5.2 Cleanliness
It is very important that the tubes and pipes are
completely clean: no dirt, chips or burrs are
allowed.
Flush all piping before connecting the highpressure pump to ensure the system is clean.
Internal surfaces of the piping must not be
corroded. If dirt or rust is not removed, the pump
and the valves can be damaged. In worst case
the pump can be damaged beyond repair!
Open system design
14556
PI
5.4 Electrical data
Check voltage, current frequency and rated
power on the electric motor and VFD settings on
the name plate placed on both the motor and
the VFD.
5.5 Local regulations
Commissioning must always be done in
accordance with valid regulations and local
standards.
M
2
PI
SYSTEM
8
73
Closed system design (not applicable for PAHT/PAHT G 256-308)
Reservoir
M
PI
2
10
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
PI
System
1
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
5.6 Pre mounting checklist, based on Danfoss preferred system designs
Table 1: Check points when assembling and commissioning system
Check pointsCommentOK ?
CP1Ensure that the environmental conditions are safe.See Arrival inspection,
CP2Minimum and maximum start-up temperature for fluid and
pump.
CP3Filtration condition (10µm absolute (β10 ≥ 5000)See Danfoss requirements in
CP4Power supply for electric motor and VFD.See Data sheet for the used
CP5Safety circuit / breaker must be sized for the motor and
environment (corrosion and humidity)
CP6Bolts and screws must conform to environmental conditions
as well as fluid and torque requirements.
CP7Instrumentation, pressure switch should be designed to
conform to the environment (corrosion and humidity).
CP8Check the factory settings of the safety/relief valves or
pressure relief valves (1).
CP9Check the settings of the pressure transmitter/switch (2) set
at min. inlet pressure.
CP10 Check that all pressure indicators (PI) are selected to be able
to measure the system pressure range.
CP 11 Check coupling distance ( air gab – movement of the spider )3 – 5 mm
CP12 Check correct connections on the pump ( in & outlet)
CP13 Check piping for possible air gaps.
transportation, handling,
lifting and storage, chapter 4.
See Data sheet or Instruction,
appendices 1 and 2.
Data sheet and Instruction,
appendices 1 and 2
motor and VFD.
See Data sheet for the used
safety circuit.
See Data sheet for the used
equipment.
See Data sheets for the used
valves.
See Data sheet or Instruction,
appendices 1 and 2.
Scaling should at least be 1 Bar
or more precise.
5.7 Lifting and positioning
Lift the pump unit onto base (Remember
vibration dampers, if needed). Fasten the motor
to the base.
See also chapter 4, Arrival inspection, transportation, handling, lifting and storage.
5.8 Mount the different equipment
(connections, pipes, tubes, check and safety/relief
valves, etc.)
• The hard piping and flexible hoses used must
be of proper design and must be installed in
accordance with the manufacturer’s recommendations.
• Misalignment of the hard pipes may give
unintended stress on the pump port
connection and may damage the pump.
• Prevent excessive external pipe load.
• Do not connect piping by applying external
force (use of wrenches, crane, etc.) Piping
must be aligned without residual stress.
• Do not mount expansion joints so that their
force applies internal pressure on the pump
connections.
5.9 Electrics
All electrical installation work must be carried
out by authorized personnel in accordance with
EN60204-1 and/or local regulations. (see also
Safety, chapter 2)
Turn off the safety circuit breaker and lock it.
Mount the power cable on the electric motor.
If a VFD is used, adjust the protective motor
switch/VFD to the current limits found on name
plate of the electric motor.
5.10 Instrumentation
The pressure switch/sensor should be mounted
as close to the pump as possible. It is recommended to test the pressure/sensor switch via an
instrumentation manifold.
Mount the pressure switch/sensors according to
the manufacturer’s instructions.
5.11 Connections
Mount and tighten connections and check
valve(s) as specified.
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
11
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
5.12 Ensure free flow
Ensure free flow from relief valve (table 1, item
5.6, CP 8). A blocked relief valve can cause
excessive build-up of pressure and thereby cause
dangerous situations and damage to the whole
system.
5.13 Verify setting of safety/relief valves
Make sure, the relief valve is placed correctly (see
open system design, item 1).
Check the pressure settings on the name plate
of the relief valve. If they are within specifications, you can continue.
5.14 Bleed and remove air from the pump
Open bleeding plugs. Keep the plugs open until
the high-pressure pump is bleeded.
If the pump is submerged, remove all bleeding
plugs before mounting in reservoir.
5.15 Verify direction of rotation
The direction of rotation must always follow the
arrow. The arrow is placed on the pump or pump
unit.
Check the direction of rotation before mounting
the pump.
Unlock the safety circuit breaker. Start the motor
for 1 second and observe the direction of
rotation either looking on the fan of the motor or
on the coupling through the hole in the bell
housing (not available on all bell housings). If the
motor is turning the wrong direction, switch two
phases in the connection box of the motor or
reprogram the direction in VFD.
• Check the temperature switch/controls. The
high-pressure pump must stop if temperature is above specified set point.
• Check the pressure switch/controls. The
high-pressure pump must stop if pressure is
below specified set point.
• If the system is running within the system
design limits, the system is released for
operation.
5.16.2 Closed system
• Check if the reservoir is clean.
• Check if filter element is present and
mounted correctly.
• Fill water at the reservoir using the filling
valve. Inspect immediately for leakage.
• Bleed high-pressure pump until only water
leaves the high-pressure pump. Remember
to close all bleeding and draining plugs.
• Adjust pressure relief valve to minimum
setting.
• Check rotation of the high-pressure pump
by description in 5.15.
• Start high-pressure pump for 2 minutes, to
make sure all air is out of the system.
• Check reservoir low level switch/controls.
The high-pressure pump must stop if low
level switch is activated.
• Adjust pressure relief valve to working
pressure.
• Check the temperature switch/controls.
The high-pressure pump must stop if
temperature is above specified set point.
• Check the filter pressure switch/controls. A
warning must be given if pressure is above
specified set point.
• If the system is running within the system
design limits, the system is released for
operation.
When the motor is turning in the right direction,
the pump can be mounted.
5.16 Commissioning
5.16.1 Open system
• Check if filter element is present and
mounted correctly.
• Switch on the circuit breaker for both
motor(s) and VFD(s).
• Check rotation of the feed pump.
• Start feed pump.
• Bleed high-pressure pump until only water
leaves the high-pressure pump. Remember
to close all bleeding and draining plugs.
• Adjust pressure relief valve to minimum
setting.
• Check rotation of the high-pressure pump
by description in 5.15.
• Start high-pressure pump for 2 minutes, to
make sure all air is out of the system.
• Adjust pressure relief valve to working
pressure.
• Check all fittings for leakage.
12
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
5.17 Check the filter condition
Evaluate contamination found in filter, replace
filter elements, if necessary.
5.18 Instruct operator and maintenance
personnel
Before using the pump/pump unit, the personnel
must be instructed in using the pump/pump
unit, its function, components, documentation
and safety.
Danfoss offers commissioning and service at
system manufacturer’s location. Rate quotes are
offered upon request.
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
6. Operation of motor
pump unit
6.1 General safety information
Before inspecting the pump unit, read the Safety
chapter 2 in this user manual.
6.2 What to listen and look for
If one or more of the following examples are
observed, please act as indicated:
A) Loose bolts – check all bolts and, if
necessary, contact the maintenance
department in order to have all bolts
tightened to the specified torque(s).
B) Leakage – if a small leakage from the bell
housing is observed. Contact the maintenance department.
C) Leakage – if there is a large leak, the unit
should be stopped immediately. Contact
the maintenance department.
D) High frequency tones – safety/relief valves
are either damaged or running very close
to their design pressure, stop the unit
immediately. Contact the maintenance
department.
E) Increased noise or vibration – requires the
unit to be stopped immediately. Contact
the maintenance department.
G) Drop in flow and/or pressure – may indicate
wear on one or more parts inside the
pump. The pump must be stopped
immediately and inspected before it is
restarted. Contact the maintenance
department.
H) Other observations or troubles, please see
appendix 7, Right and Wrong or appendix
6, Trouble shooting guide. Both appendices
give good advises on design, installation,
wiring and troubleshooting.
If the pump is not stopped for inspection as
recommended, it can lead to damage of the
pump or break-down. See also service and
warranty section in appendix 1, Data sheet and
appendix 2, Instruction.
Danfoss offers service of the pump at the system
manufacturer’s location as well as we offer
training in how to service the pump. Quotes are
offered upon request.
Danfoss recommends simultaneously to check
the filter and membrane condition and to
evaluate contamination; filter and membrane
elements must be replaced if necessary.
7. Maintenance and
service of the pump
unit
F) Very high temperatures – may indicate that
one or more parts are damaged inside the
pump. The pump must be stopped
immediately and inspected before it is
restarted. Contact the maintenance
department.
7.1 General safety information
Before servicing the pump unit, it is necessary to
read and understand this user manual, especially
the Safety, chapter 2. Remember to wear suitable
safety equipment according to Safety, chapter 2.
7.2 Service and inspection interval for the
pump
Maintenance and service intervals are depending
on the cleanliness level of the water, hydraulic
load and temperature of the pump unit. The
most important parameter is the filtration of the
water.
See the section Service and warranty in the
appendix 1, Data sheet and appendix 2, Instruction.
Danfoss offers service of the pump at the system
manufacturer’s location and training in how to
service the pump. Quotes are offered upon
request.
7.3 Shut down of the system
A) Stop the high-pressure pump.
B) Release the pressure.
C) Stop the feed pump if used.
D) Switch off the safety circuit breaker for
both the high-pressure pump, feed pump
and VFD and lock them. Only personnel
servicing the pump unit should be able to
unlock/activate the switch again.
For spare parts and service tools, please see
appendix 4, Parts list.
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
E) Open bleeding and drain plugs. Wait until
the pump and system are emptied for
water.
13
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
F) Slowly unscrew and remove the bolts and
gaskets from the inlet/outlet hoses or
pipes, be careful about jets of water. Be
aware that the system can be pressurized.
G) Attach the lifting equipment to the pump
unit. For instructions on lifting the
complete pump unit, see chapter 4, Arrival
inspection, transportation, handling, lifting
and storage.
H) For the small pumps, unscrew the bolts
holding the pump to the bell housing and
for the bigger pumps, unscrew the bolts/
nuts from the pump and bell housing to
the motor and afterwards unscrew the
bolts/nuts holding the pump and bell
housing.
I) Carefully pull the pump out of the bell
housing by using lifting equipment, if
necessary.
J) Hold the pump in different positions above
a drip tray; this should allow most of the
water trapped in the pump to drain. Clean
and dry the pump surface and plug the
bleeding and draining plugs.
K) Move the pump to a clean and safe location
where the pump can be inspected/
serviced.
7.4 Disassembling and assembling the
pump unit
A) Remove all connections from the pump.
B) Disassemble the pump according to the
Disassembling and Assembling Instruction
(available at
www. danfoss.high-pressurepumps.com).
Clean all the parts and surfaces with a fluid
compatible with the materials found in the
pump. Wipe the parts clean and dry with a
lint-free clothing.
Returns without a return number will be
rejected !!!
7.5 Assembling the pump unit
Assemble the pump according to the Disassembling and Assembling Instruction (available at
hpp.danfoss.com).
7.6 Procedure for mounting the pump back
onto electric motor
Mount the flexible coupling and bell housing
according to appendix 2, Instruction.
7.7 Getting the pump unit back into
operation
Find instructions of how to put the pump unit
back into operation in chapter 4, Arrival inspection, transportation, handling, lifting and storage
and Installation and commissioning, chapter 5.
7.8 Storage of the pump
If the pump has to be shut down for a longer
period, instructions can be found in appendix 2,
Instruction.
C) Inspect all parts including shaft seal and if
necessary, replace them; see appendix 4,
Parts list.
D) If the pump is going to be returned to
Danfoss for repair or a warranty claim, it is
important to contact Danfoss in order to
receive a return number and a form to fill
out with product information. A copy of the
form together with contact information
and reason for returning should be sent to
the email address on the form. The same
documents should be attached to the
shipment.
14
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
8. Troubleshooting and
scrapping criteria
8.1 General safety information
Before inspecting the pump unit, it is necessary
to read and understand this user manual,
especially the Safety chapter 2.
Remember to wear suitable safety equipment
according to Safety chapter 2.
8.2 Operational conditions which can cause
pump failures
The following conditions can cause a pump
failure :
• The pump is running dry.
• The inlet pressure is too high.
• The inlet pressure is too low.
• The temperature of the fluid is too high.
• The ambient temperature is too high.
• The pump is running against a blocked
port/closed manual valve.
• The pump is operating at a pressure out of
specification.
• The pump is running with a non-specified/
approved fluid.
• The pump is running in the wrong
direction.
• The filtration is insufficient.
• There is excessive mechanical load on the
shaft coupling and piping.
Electrical
hazard
8.4 Electrical failure
If the wiring of the electric motor is incorrect or
the ground connection is missing, it can cause
electric shock, burn damages, fire or even death.
If a VFD is used and wrongly programmed, it can
damage the pump and lead to high temperatures or other dangers.
All electrical installation must be carried out by
authorized personnel in accordance with
EN60204-1 and/or local regulations.
8.5 Responsibility
Danfoss takes no responsibility for any abnormal
injuries, risks or damages that could arise caused
by abnormal conditions, vibrations, corrosion,
abrasives, foreign objects or excessive temperatures and shall not be liable for any consequential or incidental damages.
8.6 Scrapping criteria
Whether the pump can be repaired or need to be
scrapped, depends on in which conditions the
internal parts are, or how damaged the whole
unit is. Please use appendix 5, Trouble shooting
guide as guideline or send the pump to Danfoss
headquarter in Denmark for evaluation.
8.3 Mechanical failure
If the pump is running dry, the temperature will
quickly increase which can cause burns.
If there is any leakage at start-up or during
operation, a high pressure jet can cause eye or
skin damage.
Leakage can result in flooding, which can cause
slipping, tripping or falling.
If water is dripping into the electric motor; it can
cause electric shock, fire, short of circuit or even
death. When mounting the pump vertically,
always mount the motor above the pump to
avoid water leaking into the electric motor.
For other observations or troubles, please see
appendix 6, Right and Wrong which gives good
advises regarding design, installation, wiring and
troubleshooting.
In case the pump needs to be scrapped, please
follow your local environmental rules.
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
15
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
16
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Operation guide
Appendices
PAHT 2-12.5
Installation, Operation and
Maintenance Manual
hpp.danfoss.com
Operation guide | Installation, Operation and Maintenance Manual for PAHT 2-12.5 pumps
Table of Contents
1. Data sheet PAHT G 2-308 (AI106586503085en-000901) .................................19
2. Pump instruction PAHT 2-6.3 and PAHT 10-12.5 (180R9277) .............................33
3. Electric motor manual (180R9230) ......................................................43
4. Parts list PAHT (AX322445815902en-000201) ............................................49
5. Trouble shooting guide for PAH, PAHT, PAHT G, PAHT 674 and PAH F pumps .............59
6. Right and wrong - Trouble shooting guide for water hydraulic systems (180R9042).......71
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
The Danfoss range of PAHT high-pressure pumps
is specifically designed for use with technical
water such as:
• Ultra-pure water that has undergone
multiple reverse osmosis processes
• De-ionized water
• Demineralized water
Danfoss PAHT pumps are positive displacement
pumps, with axial pistons that move a fixed
amount of water in each cycle. Flow is proportional to the number of input shaft revolutions
(rpm). Unlike centrifugal pumps, they produce
the same flow at a given speed independently of
no matter what the discharge pressure.
20
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Data sheet PAHT 2-308 pumps
Below sectional drawing is an example of a PAHT pump.
1: Mounting flange
2: Shaft seal
3: Connecting flange
4: Port plate
5: Valve plate
6: Retainer plate
7: Swash plate
8: End cap
9: Spring
10: Pis ton
11: Cylinder barrel
12: Housing with bearing
2. Benefits• Zero risk of lubricant contamination:
- Oil lubricants are replaced with the
pumped medium, water, so there is no
contamination risk from the pump.
• Low maintenance costs:
- Efficient design and all-stainless steel
construction ensure exceptionally long
lifetime. When Danfoss specifications
are met, service intervals of up to 8,000
hours can be expected. Service is easy,
and can be carried out on site due to
the simple design and few parts.
• Low energy costs:
- The highly efficient axial piston design
provides the lowest energy consumption of any comparable pump on the
market.
• Easy installation:
- The lightest and most compact design
available.
3. Application examples• High-pressure cleaning with ultra-pure
water, as used in the manufacturing of
flat-panel displays and many other
electronic products.
• High-pressure cleaning with ultra-pure
water, as used in the manufacturing of
parts for the automobile industry.
• Adiabatic cooling systems to replace or
supplement standard A/C systems in server
rooms and factories.
- Pump can be installed horizontally or
vertically.
- No pulsation dampeners necessary due
to extremely low-pressure pulsation.
- Powered by electric motors or combustion engines.
- Suitable for both boosted inlet
pressure and water supply from a tank.
- No need for cooling circuits due to very
high mechanical efficiency.
• Certified quality:
- Fulfills the stringent hygiene requirements, VDI 6022, HACCP.
- Certificates:
ISO 9001, ISO 14001
API available on request
• Humidification in office buildings, elec-
tronic component manufacturing, dairies,
greenhouses, etc.
• Dust suppression and odor control
systems, for example in paper, textile and
wood production.
• Reduction of NOx emissions in diesel
engines and gas turbines.
• Gas turbine by inlet fogging and fuel wash
systems.
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
21
Data sheet PAHT 2-308 pumps
4. Technical data4.1 PAHT 2-12.5
Pump size23.246.31012 .5
Code number PAHT180B0031180B0077180B0030180 B0029180B0 032180B0033
1% per minute peak, 10% per minute during start up.
2)
Measurements according to EN ISO 3744: 2010 / dB(A) [L
Measured at max pressure and rpm for a motor pump unit.
] values are calculated.
PA, 1m
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Data sheet PAHT 2-308 pumps
20
18
16
14
12
10
8
6
4
2
0rpm
PAHT 2.0
PAHT 3.2
PAHT 4.0
PAHT 6.3
l/min
1000
1250
1500
1750
2000
2500
2250
2750
3000
5. FlowThe flow (Q
calculated with the following equation:
Q
= Q
eff
) at various pressure (p
eff
– [(Q
(th)
– Q (p
(th)
)) x (p / p
max
max
max
The theoretical flow can be calculated with the
following equation:
V x n
Q
=
(th)
1000
5.1 PAHT 2-6.3 typical flow curves at max pressure
l/min
20
18
16
14
12
10
8
6
4
2
0rpm
1000
1250
1500
) can be
)]
1750
At zero pressure the true flow equals the
theoretical flow Q
: Theoretical flow (l/min / gpm)
Q
(th)
Q (p
): Flows at max. pressure (l/min and
max
p
p: Pressure (barg / psig)
gpm), see 4.1-4.4
: Max pressure (barg / psig)
max
V: Displacement (cm
.
(th)
3
/ rev.)
n: Motor speed (rpm)
2000
2250
2500
2750
PAHT 6.3
PAHT 4.0
PAHT 3.2
PAHT 2.0
3000
gpm
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0
1000
1250
1500
1750
2000
2250
2500
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
2750
PAHT 6.3
PAHT 4.0
PAHT 3.2
PAHT 2.0
rpm
3000
23
Data sheet PAHT 2-308 pumps
30
25
20
15
10
5rpm
PAHT 10.0
PAHT 12.5
l/min
1000
1200
1400
1650
1800
2200
2000
2400
5.2 PAHT 10-12.5 typical flow curves at max pressure
l/min
30
25
20
15
10
5rpm
PAHT 12.5
PAHT 10.0
1200
1200
1400
1400
gpm
8
7
6
5
4
3
2
1
0
1000
1000
1650
1650
1800
1800
2000
2000
2200
2200
2400
PAHT 12.5
PAHT 10.0
rpm
2400
24
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Data sheet PAHT 2-308 pumps
6. Motor requirements
The required motor power can be calculated by
using the following equation:
n x V x p
P =
600.000 x η
P: Power (kW)
M: Torque (Nm)
η: Mechanical efficiency
p: Pressure (barg)
n: Motor speed (rpm)
V: Displacement (cm
3
/rev.)
From the flow curves in item 5, you can determine the rpm of the pump at the desired flow.
The required torque is calculated as follows:
V x p
M =
62.8 x η
To determine the correct motor size, both the
power and torque requirement must be verified.
The mechanical efficiency of the pump, at max
pressure, is as follows:
PAHT 2, 3.2, 4, 6.30.8
PAHT 10, 12.50.9
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
25
Data sheet PAHT 2-308 pumps
7. InstallationSee the figure below for instructions on how to
mount the pump and connect it to an electric
motor or combustion engine.
ACB
A: Pump
B: Bell housing
C: Coupling
D: Motor
D
If alternative mounting is required, please
contact your Danfoss sales representative for
further information.
Note: Do not add any axial or radial loads to the
pump shaft.
7.1 Filtration
Proper filtration is crucial for the performance,
maintenance and warranty of your pump.
Protect your pump, and the application in which
it is installed, by always ensuring that filtration
specifications are met, and by always changing
filter cartridges according to schedule.
Since water has very low viscosity, Danfoss PAHT
pumps have been designed with very narrow
clearances in order to control internal leakage
rates and improve component performance. To
minimize wear on the pump, it is therefore
essential to filter inlet water properly.
The main filter must have a filtration efficiency
of 99.98% at 10 μm. We strongly recommend
that you always use precision depth filter
cartridges rated 10 μm abs. β
Please note that we do not recommend bag
filters or string-wound filter cartridges, which
typically have only 50% filtration efficiency. This
means that out of 100,000 particles that enter
such filters, 50,000 particles pass right through
them; compare this to precision depth filters that
are 99.98% efficient, and only allow 20 of the
same 100,000 particles to pass through.
≥ 5,000.
10
For more information on the importance of
proper filtration, including explanation of
filtration principles, definitions, and guidance on
how to select the right filter for your pump,
please consult our Filtration information and
specifications (Danfoss document number
521B1009).
7.2 Noise
Since the pump unit is mounted on a frame, the
overall noise level can only be determined for a
complete system. To minimize vibrations and
noise throughout the system, it is therefore very
important to mount the pump unit correctly on a
frame with dampers and to use flexible hoses
rather than metal pipes where possible.
The noise level is influenced by:
• Pump speed:
High rpm makes more fluid/structureborne pulsations/vibrations than low rpm.
• Discharge pressure:
High pressures make more noise than low
pressures.
• Pump mounting:
Rigid mounting makes more noise than
flexible mounting because of the structureborne vibrations. Be sure to use dampers
when mounting.
• Connections to pump:
Pipes connected directly to the pump make
more noise than flexible hoses because of
structure-borne vibrations.
• Variable frequency drives (VFDs):
Motors regulated by VFDs can produce
more noise if the VFD does not have the
right settings.
26
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Data sheet PAHT 2-308 pumps
7.3 Open-system design
A Inlet line:
Dimension the inlet line to obtain minimum pressure loss (large flow, minimum
pipe length, minimum number of bends/
connections, fittings with small pressure
losses and restrictions).
B Inlet filter:
Install the inlet filter (1) in front of the PAHT
pump (2). Please consult the Danfoss filter
data sheet for guidance on how to select
the right filter.
C Monitoring pressure switch:
Install the monitoring pressure switch (3)
between the filter and the pump inlet. Set
the minimum inlet pressure according to
specifications described in item 4, technical
data. The monitoring pressure switch stops
the pump if inlet pressure is lower than the
set minimum pressure.
D Monitoring temperature switch:
Install the monitoring temperature switch
(4) between the filter and the pump, on
either side of the monitoring pressure
switch. Set the temperature value according to technical data, item 4. The monitoring temperature switch stops the pump if
inlet temperature is higher than the set
value.
E Hoses:
Always use flexible hoses (5) to minimize
vibrations and noise.
F Inlet pressure:
In order to eliminate the risk of cavitation
and other pump damage, pump inlet
pressure must be maintained according to
specifications described in item 4, technical
data.
G Non-return valve (6):
Should be installed after the outlet to
prevent pump backspin, which may ruin
the pump.
H Pressure relief valve:
As the Danfoss PAHT pump begins to
create pressure and flow immediately after
start-up regardless of any counter pressure,
a pressure relief valve (7) should be
installed to prevent system damage.
Note: If a non-return valve is mounted in the
inlet line, a low-pressure relief valve is also
recommended between the non-return valve
(8) and the pump to protect against high-pressure peaks.
14556
PI
8
M
2
PI
SYSTEM
73
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
27
Data sheet PAHT 2-308 pumps
PI
System
PI
M
1
2
3
4
55
7
6
7.4 Closed-system design (not applicable
for PAHT 256-308)
A Inlet line:
Dimension the inlet line to obtain minimum pressure loss (large flow, minimum
pipe length, minimum number of bends/
connections, fittings with small pressure
losses and restrictions).
B Inlet filter:
Install the filter (1) in front of the tank (2).
Please consult the Danfoss filter data sheet
for guidance on how to select the right
filter.
C Monitoring pressure switch:
Install the monitoring pressure switch (3) in
front of the filter (1). Set the maximum inlet
pressure to 2 barg (29.0 psig). The monitoring pressure switch will stop the pump (5) if
inlet pressure is higher than 2 barg (29.0
psig), indicating that the filter element
must be changed.
D Monitoring temperature switch:
Install the monitoring temperature switch
(4) in the tank. Set the temperature value
according to technical data, item 4. The
monitoring temperature stops the pump if
inlet temperature is higher than the set
value.
E Hoses:
Always use flexible hoses (6) to minimize
vibrations and noise.
F Inlet pressure:
In order to eliminate the risk of cavitation
and other pump damage, pump inlet
pressure must be maintained according to
specifications described in item 4, technical
data.
G Non-return valve (7):
Should be installed after the outlet to
prevent pump backspin, which may ruin
the pump.
H Pressure relief valve:
As the Danfoss PAHT pump begins to
create pressure and flow immediately after
start-up regardless of any counter pressure,
a pressure relief valve (8) should be
installed to prevent system damage.
I System water filling:
To ensure proper filtration of new water
(10) supplied to the system, always use the
filling valve (9).
J Minimum level switch:
Install the minimum level switch (11) above
the outlet of the reservoir. The level switch
must stop the pump if the water in the
reservoir is below the switch, which
indicates that the reservoir is empty.
2
11
Reservoir
4
M
667
PI
5
PI
System
9
1
3
10
8
28
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Data sheet PAHT 2-308 pumps
8. Dimensions and
connections
8.1 PAHT 2-6.3
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
29
Data sheet PAHT 2-308 pumps
8.2 PAHT 10-12.5
30
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Data sheet PAHT 2-308 pumps
9. ServiceDanfoss PAHT pumps are designed for long
periods of service-free operation to ensure low
maintenance and life cycle costs. Provided that
the pump is installed and operated according to
Danfoss specifications, Danfoss PAHT pumps
typically run 8,000 hours between service.
However, the service schedule for your Danfoss
PAHT pump may vary according to the application and other factors.
The life of a pump may be greatly shortened if
Danfoss recommendations concerning system
design and operation are not followed.
In our experience, poor filtration is the number
one cause of pump damage.
Other factors that affect pump performance and
lifetime include:
• running the pump at speeds outside
specifications
• supplying the pump with water at temperatures higher than recommended
• running the pump at inlet pressures
outside specifications
• running the pump at outlet pressures
outside the specifications.
We recommend that you inspect your pump
after 8,000 hours of operation even if it is
running without any noticeable problems.
Replace any worn parts if necessary, including
pistons and shaft seals, to keep your pump
running efficiently and to prevent breakdown. If
worn parts are not replaced, then our guidelines
recommend more frequent inspection.
31
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Dimension the inlet line to obtain minimum pressure loss (large flow, minimum
pipe length, minimum number of bends/
connections, and fittings with small
pressure losses).
B Inlet filter:
Install the inlet filter (1) in front of the tank
(2). Please consult the Danfoss filter data
sheet for guidance on how to select the
right filter.
C Monitoring pressure switch:
Install the monitoring pressure switch (3) in
front of the filter (1). Set the maximum inlet
pressure to 2 barg (29.0 psig). The monitoring pressure switch will stop the pump (5) if
inlet pressure is higher than 2 barg
(29.0 psig), indicating that the filter element
must be changed.
D Monitoring temperature switch:
Install the monitoring temperature switch
(4) in the tank. Set the temperature value
according to technical data, item 4. The
monitoring temperature stops the pump if
inlet temperature is higher than the set
value.
E Hoses:
Always use flexible hoses (6) to minimize
vibrations and noise.
11
F Inlet pressure:
In order to eliminate the risk of cavitation
and other pump damage, pump inlet
pressure must be maintained according to
specifications described in item 4, technical
data.
G Non-return valve (7):
Should be installed after the outlet to
prevent pump backspin, which may ruin
the pump.
H Pressure relief valve:
As the Danfoss PAHT pump begins to
create pressure and flow immediately after
start-up regardless of any counter pressure,
a pressure relief valve (8) should be
installed to prevent system damage.
I System water filling:
To ensure proper filtration of new water
(10) supplied to the system, always use the
filling valve (9).
J Minimum level switch:
Install the minimum level switch (11) above
the outlet of the reservoir. The level switch
must stop the pump if the water in the
reservoir is below the switch, which
indicates that the reservoir is empty.
180R9287 | AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps
|
35
Instruction | Pump instruction PAH / PAHT 2-12.5
2.2 Open-system design
A Inlet line:
Dimension the inlet line to obtain minimum pressure loss (large flow, minimum
pipe length, minimum number of bends/
connections, and fittings with small
pressure losses).
B Inlet filter:
Install the inlet filter (1) in front of the PAHT
pump (2). Please consult the Danfoss filter
data sheet for guidance on how to select
the right filter.
C Monitoring pressure switch:
Install the monitoring pressure switch (3)
between the filter and the pump inlet. Set
the minimum inlet pressure according to
specifications described in item 4, technical
data. The monitoring pressure switch stops
the pump if inlet pressure is lower than the
set minimum pressure.
D Monitoring temperature switch:
Install the monitoring temperature switch
(4) between the filter and the pump, on
either side of the monitoring pressure
switch. Set the temperature value according to technical data, item 4. The monitoring temperature switch stops the pump if
inlet temperature is higher than the set
value.
E Hoses:
Always use flexible hoses (5) to minimize
vibrations and noise.
F Inlet pressure:
In order to eliminate the risk of cavitation
and other pump damage, pump inlet
pressure must be maintained according to
specifications described in item 4, technical
data.
G Non-return valve (6):
Should be installed after the outlet to
prevent pump backspin, which may ruin
the pump.
H Pressure relief valve:
As the Danfoss PAHT pump begins to
create pressure and flow immediately after
start-up regardless of any counter pressure,
a pressure relief valve (7) should be
installed to prevent system damage.
Note: If a non-return valve is mounted in the
inlet line, a low-pressure relief valve is also
required between the non-return valve (8) and
the pump to protect against high-pressure
peaks.
14556
PI
8
M
2
PI
SYSTEM
73
36 |
180R9287 | AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps
A good filtration is vital to ensure a long and
trouble free life of the pump.
When selecting a filter or strainer, please note
that filter materials should be compatible with
water, i.e. should neither corrode or dissolve. Also
be aware of the electrochemical series of the
applied materials.
• Main filter must have a fineness of 10 µm
abs. β
≥ 5,000.
• The pressure loss across the filter should be
10
monitored.
• Please contact the Danfoss Sales Organization for further filter details.
Water tank
Must be made of corrosion-proof material such
as stainless steel or plastic and must be sealed to
prevent entrance of impurities from the environment.
180R9287 | AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps
Automatic pressure equalization between tank
and surroundings must be ensured.
Inlet from the water supply (the return line) and
inlet to the pump should be placed in opposite
ends of the tank to calm and deaerate the water,
and to ensure optimum opportunity for particles
to settle.
Pump suction line should be placed above the
tank bottom in order to prevent settled particles
from being led into the pump.
|
37
Instruction | Pump instruction PAH / PAHT 2-12.5
unit
We recommend a separation (“wall”) to separate
the inlet from the outlet end of the tank.
3.1 Mounting3. Building up the pump
Monitoring
It is recommended to continuously monitor the
following conditions:
• Water level in the tank
• Filter contamination
• Pressure (inlet- and outlet side of the
pump)
A: Elastic coupling
B: Bell housing
C: Motor shaft
If alternative mounting is desired, please contact
the Danfoss Sales Organization.
Choose proper tolerances to ensure an easy
mounting of the elastic coupling without use of
tools.
Please take care to observe the recommended
length tolerances of the chosen coupling, as an
axial force on the pump shaft must be avoided.
3.3 Orientation
The pump can be mounted/orientated in any
direction.
3.2 Direction of rotation
Is indicated by means of an arrow at the label of
the pump.
38 |
180R9287 | AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps
Recommended torque values refer to steel washers containing a rubber sealing element.
180R9287 | AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps
|
39
Instruction | Pump instruction PAH / PAHT 2-12.5
4. Initial start-upBefore start-up, loosen the top bleeding plug “C”.
5. Operation
When water appears from the bleeding plug,
retighten the plug. With its inlet line connected
to the water supply or the tank, the pump is now
started with open outlet port.
At the initial start of the system, the pump
should be run without pressure for about 5
minutes, thus removing possible impurities from
pipes, hoses, etc. However, the system should be
flushed before start-up.
Warning:
Make sure that the direction of rotation of the
electric motor corresponds to the direction of
rotation of the pump. Otherwise the pump will
be damaged if a check valve is placed between
pump and tank.
5.1 Water quality
Water of drinking water quality, confirming to
the EEC directive 98/83/EC and without abrasive
sediments. Please contact Danfoss sales
organization in case of doubt.
5.2 Temperature
5.5 Disconnection
If the inlet line is disconnected from the water
supply, the pump will be emptied of water
through the disconnected inlet line.
When starting up again, follow the bleeding
procedure described under section 4: Initial start
up.
Fluid
temperature
Ambient
temperature
Storage
temperature
In case of lower operating tempera tures, please
contact the Danfoss Sales Organization.
5.3 Pressure
The inlet pressure must be between min. 0 barg/
0 psig and max. 4 barg/60 psig. The use of pump
outside this range damage the pump.
Max. pressure on the pump’s outlet line should
be limited at 140 barg (2030 psig) continuously.
NB: The pump unit should include a pressure
gauge on the high pressure side.
5.4 Dry running
When running, the pump must always be
connected to the water supply in order to avoid
damage if it should run dry.
In systems with water tank it is recommended to
build in a level gauge in the tank to avoid the risk
of running dry.
Min. +2° C to
max. +50° C
Min. 0° C to
max. 50° C
Min. -40° C to
max. +70 ° C
5.6 Storage
When preparing the pump for long-term storage
or for temperatures below the freezing point,
flush the pump with an anti-freeze medium type
monopropylene glycol to prevent internal
corrosion or frost in the pump. For further
information on anti-freeze media, please contact
the Danfoss Sales Organization.
Recommended procedure
5.6.1 Water hydraulic systems, water recirculated
1. Disconnect the power pack from the
system.
2. Empty the tank of water. Fill up the tank
with anti-freeze medium to a level well
above the suction line.
3. Start up the power pack and, for a couple
of minutes, in a closed loop system let the
anti-freeze medium run back to tank
through the pressure relief valve or the
bypass valve.
4. Empty the tank of the anti-freeze medium.
Empty the pump through the lower
bleeding plug.
The pump is now protected against internal
corrosion and frost.
40 |
180R9287 | AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps
5.6.2 Open-ended systems with water supply
from tank.
1. Empty the tank of water and empty the
pump housing through the lower bleeding
plug. When the pump is empty, retighten
the plug.
2. Through the upper bleeding plug, fill the
pump housing with anti-freeze medium.
Pour anti-freeze medium into the tank.
Connect a hose to the outlet of the pump
and lead the other end of the hose back to
tank.
3. Quickly start and stop the pump. Make sure
that the pump does not run dry.
The pump is now protected against internal
corrosion and frost.
6. ServiceThe Danfoss PAHT pumps are designed for long
periods of service-free operation to provide
customers with low maintenance and life cycle
costs. Provided that the pumps are installed and
operated according to Danfoss specifications, the
Danfoss PAHT pumps typically run 8,000 hours
between service routines. However, the service
schedule for your PAHT pump may vary according to the application and other factors.
The life of a pump may be greatly shortened if
Danfoss recommendations concerning system
design and operation are not followed.
5.6.3 Open-ended systems with direct water
supply.
1. Disconnect the water supply to the pump.
2. Through the lower bleeding plug, empty
the pump housing of water and close it
again.
3. Connect the pump to a tank of e.g. 25 litre/
6 gal. of anti-freeze additive. Connect a
hose to the inlet port of the pump and via
another hose return the flow from the
outlet port port to the tank with anti-freeze
additives.
4. Quickly start and stop the pump. Make sure
that the pump does not run dry.
The pump is now protected against internal
corrosion and frost.
Other factors that affect pump performance and
lifetime include:
• running the pump at speeds outside
specifications
• supplying the pump with water at temperatures higher than recommended
• running the pump at inlet pressures
outside specifications
• running the pump at outlet pressures
outside the specifications.
7. Recommended service
intervals
In our experience, poor filtration is the number
one cause of pump damage.
7.1 General information
This guideline provides information on the
recommended service intervals for the PAHT
pumps. The recommendation is based upon
good engineering practice and on experience
gained from operation even under extreme
conditions.
The recommendation is for guidance only.
7.2 Inspection of pump parts
Danfoss recommends to inspect the pumps after
8,000 hours. Typical signs of wear are seen on the
contact/sliding surfaces in the pumps. If the
pumps must run for additional 8,000 hours, the
following parts will have to be inspected:
• Pistons
• Retainer plate, ball and bearing
• Valve plate
• Port plate
• Sealings
If service inspection due to the application is
complicated, the plant operator can decide to
extend the service interval by evaluating the
following deviations:
• Sound - does the pump have any unusual
sounds?
• Electric motor power consumption and
speed compared with measurement made
in the past.
• Pressure/flow according to measurements
made in the past?
We advise that the above mentioned parameter
during the extended service interval is inspected
for every 500-2,000 hours beyond the 8,000
hours. The pump must in any case be inspected
after maximum 16,000 hours or 2 years.
7.3 How to inspect the pump
Service manuals are available on the internet
www.danfoss.high-pressurepumps.com
This manual concerns the following types of standard
induction motors from Hoyer:
HMA3, HMC3, HMA2, HMC2, HMD, HMT, MS, Y2E1, Y2E2, YDT
These motors are manufactured in accordance with IEC/EN
60034-4 and IEC/EN 60072.
Motors are rated for the ambient temperature range -20°C to
+40°C and site altitudes ≤1000 m above sea level.
Low-voltage motors are components for installation in
machinery. They are CE marked according to the Low Voltage
Directive 2014/35/EU.
Motors not fulfilling the IE3 efficiency level must be equipped
with a variable speed drive when used in EU.
Transport and storage
Check the motor for external damage immediately upon
receipt and, if found, inform the forwarding agent right away.
Check all rating plate data, and compare it with the
requirement of the motor.
Turn the shaft by hand to check free rotation, remove
transport locking if used.
Transport locking must be used again for internal transport
also. It is also important that transport locking is used when
motors are transported mounted on equipment.
All motors should be stored indoors, in dry, vibration- and
dust-free conditions.
Lifting eyebolts must be tightened before use. Damaged
eyebolts must not be used, check before use. Lifting eyes at
motor must not be used to lift the motor when it is attached
to other equipment.
Before commissioning, measure the insulation impedance. If
values are ≤ 10MΩ at 25°C, the winding must be oven dried.
The insulation resistance reference is halved for each 20°C
rise in motor temperature.
It is recommended that shafts are rotated periodically by
hand to prevent grease migration.
etc.) using suitable tools, never hit the drive components
with a hammer as this will cause damage to the bearing.
The motor are balancing with half key, ensure that the drive
components are also the same.
Correct alignment is essential to avoid bearing, vibration and
shaft failure.
Use appropriate methods for alignment.
Re-check the alignment after the final tightening of the bolts
or studs.
Check that drain holes and plugs face downwards. We
recommend opening the drain hole for motors placed
outdoors and not running 24 hours / day, so that the motor
can breathe, thus ensuring a dry motor.
Electrical connection
Work is only permitted to be carried out by qualified
specialists and must to be carried out in accordance with
local regulations.
Before work commences, ensure that all power is switched
off and cannot be switched on again. This also applies to the
auxiliary power circuits, e.g. anti-condense heaters.
Check that supply voltage and frequency are the same as
rated data.
Motors can be used with a supply deviation of ± 5% voltage
and ± 2% frequency, according to IEC60034-1.
Connection diagrams for main supply and accessory as PTC
or heater are located inside the terminal box.
Connections must be made in such a way as to ensure that
a permanently safe electrical connection is maintained, both
for the main supply and the earth connection.
We recommend that crimped connections are made in
accordance with IEC 60352-2.
Tightening torques for terminal board screws:
ThreadM5M6M8M10M12M16M20M24
T.(Nm)2.53.571218355580
Installation
The motor must be fixed on a stable, clear and flat foundation.
It must be sufficiently rigid to withstand possible short
circuit forces.
It is important to ensure that the mounting conditions do
not cause resonance with the rotational frequency and the
doubled supply frequency.
Only mount or remove drive components (pulley, coupling,
44
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
Ensure that the terminal box is clean and dry.
Unused glands must be closed with blind caps.
Check the terminal box gasket before it is remounted.
Maintenance
Inspect the motor at regular intervals, keep it clean and
ensure free ventilation air flow, check the condition of shaft
seals and replace if necessary. Both electrical and mechanical
Motor
Manual
connections must be checked and tightened if necessary.
Bearing size and type are specified on the rating plate. Motor
types HMA3 and HMC3 is as standard with lifetime greased
bearings in motors size ≤180 for cast iron and size ≤132 for
aluminium. Motor types HMA2 and HMC2 is as standard
with lifetime greased bearing in motors size ≤225.
Motor types MS and Y2E is as standard with lifetime greased
bearing in motors size ≤160.
Typical duty hours for lifetime lubricated bearings.
Frame sizePolesTypical lifetime
56 - 1602 - 840,000h
180235,000h
200227,000h
225223,000h
180 - 2254 - 840,000h
Motors with a re-greasing system must be lubricated with
high quality lithium complex grease, NLGI grade 2 or 3, with
a temperature range of between -40°C to +150°C.
Motors are normal fitted with a data plate with greasing
information; if it is missing use the following re-greasing
intervals.
Frame
size
160204200700085008500
180204200700085008500
200253100650085008500
225253100650085008500
250352000600070007000
280352000600070007000
315501500550065006500
355601000400050006000
40080800300040006000
Grease
(g)
2 pole
(h)
4 pole
(h)
6 pole
(h)
8 pole
(h)
Grease the motor while running, open the grease outlet plug
and let the motor run 1-2 hours before the outlet grease plug
is closed again.
Grease the motor for the first time during commissioning.
The following applies in general for both lifetime lubricated
and re-lubricated bearings:
At 60Hz the time will be reduced by app. 20%.
Data for vertically mounted motors are half of the above
values.
The table values are based on an ambient temperature of
25°C. The values must be halved for every 15K increase in
bearing temperature.
Higher speed operations, e.g. frequency converter drive will
require shorter greasing intervals. Typically, doubling the
speed will reduce the values by 50%.
Special note for Atex Zone 22 and nA motors
Designation of motor according to IEC standard:
II 3D Ex tc IIIB T120°C
II 3G Ex nA IIC T3
The hazardous 3-phase asynchronous motors are in
accordance with International standard IEC 60079-31 and
IEC 60079-15.
Only one electrical installation may be installed in one
specified area (zone).
Only certificated cable glands may be used. Unused glands
must be closed.
Connections must be made in such a way as to ensure that
a permanently safe electrical connection is maintained, both
for the main supply and earth connection.
Installations must be in accordance with actual standards
for installation in hazardours area.
It is recommended that the IEC standard is followed according
to temperature and dust on the motor surface.
The use of motors with so much surface dust that the motor
temperature increases is not permitted.
Regularly cleaning is recommended.
The radial shaft sealing ring is part of the ATEX certification.
It is important that the ring is always intact.
The shaft sealing must be regularly checked, and if dry it
must be lubricated. It is recommended that the seal is relubricated regularly.
Always use the original seal ring when replaced.
Replacing bearings also means replacing the seals.
All machines must be inspected regularly for mechanical
damage.
The user is responsible for changing parts in accordance
with the lifetime of parts, in particular:
bearings, grease and lubrication of shaft sealing.
Maintenance, repairs and replacement on this type must
only be carried out by qualified specialists.
180R9287 |AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps | 01.2022
180R9287 |AQ073186503097en-000901 | IOM PAHT 2-12.5 pumps | 11.2020
Guideline | Trouble shooting guide for PAH, PAHT, PAHT C , PAHT G, PAHT 674 and PAH F pumps
Trouble shooting
fish bone chart
PUMP FAILED
2. Reduced ow/pressure
(hoses/pipes)
inlet/outlet line
2.3 RPM
2.2 Low inlet pressure
2.1.5 Pre-treatment
2.1.6 Main ltration
2.1.8 High uid temperature
2.1.7 Type of uid
(internal leakage)
2.1 Wear in pump
1. No ow/pressure
5.1 Inlet/outlet connections
5.2 Length/dimensions of
4.1 Air in uid
4.2 Bleeding conditions of pump
directly on frame
5.3 Hose stiness
inlet pressure
4.3 Min/max nominal
electric motor
5.4 Hoses/pipes mounted
5.5 Vibr ation damper under the
4.4 Pump reversin g
4.5 High rot ation speed (RPM)
4.6 Outlet pressure
5. Noise from installation
4. Noise from pump
4.7 Soft sta rt/stop
1.6 Pump damage
1.5 Axial force o n pump shaft
1.4 No rotation of pump
1.3 No rotation of e lectric motor
1.2 Pump reversing
1.1 Dry running
from pump
3.1 Too high outlet pressure
3.2 Pump starts against pressure
3.3 Constant torque
3.4 Water pump damage
180R9287 |AQ073186503097en-000901 | IOM PAHT 2-12.5 pumps | 11.2020
3. High torque on el. motor
61
Guideline | Trouble shooting guide for PAH, PAHT, PAHT C , PAHT G, PAHT 674 and PAH F pumps
1. No flow/no pressure
Cause RemedyComments
1.1 Dry running
(no water supply to the pump)
1.2 Pump reversing
(electric motor is running the wrong direction,
i.e. counter-clockwise)
If no water comes out of the pump:
1.1.1 Check that inlet valve is open.
1.1.2 Check that booster pump is running.
1.2.1 Change the phase on the electric motor to
make it run clockwise.
WARNING:
- The pump must not run without water for
more than a few seconds.
- If the pump takes in water from the high-
pressure outlet line, it builds up pressure in
pump housing and will eventually break
down.
Mount a low pressure switch in front of the
pump and check its set point/ function. The low
pressure switch ensures that the pump does not
start until the inlet pressure has reachedminimum inlet pressure (see Data sheet).
Rotation direction for the pump is shown by an
arrow on the label on the pump.
1.3 No rotation of electric motor1.3.1 Check that main switch is switched on.
1.4 No rotation of pump1.4.1 Ensure that coupling between electric
1.5 Axial load on pump shaft
(may cause high internal leakage)
Only applying to
PAH 2-12. 5
PAHT 2-308
PAH F 20-40
PAHT C 2-308
PAHT G 2-308
1.3.2 Check the electricity at the facility.
1.3.3 Ensure that motor relay is switched on.
1.3.4 Ensure that fuse is not blown.
1.3.5 Ensure that booster pump is started.
1.3.6 Check that the monitor switches are
working correctly.
1.3.7 Disconnect pump from electric motor and
check that the motor is capable of running
with no load.
motor and pump is connected.
1.4.2 Check if coupling is damaged.
1.4.3 Check that electric motor is sized correctly.
1.4.4 Check that the electrical installation is
correctly sized.
1.4.5 Contact Danfoss Sales office for guidelines
in how to troubleshoot internal pump
parts.
1.5.1 Ensure that the air gap between the two
coupling parts is min 5 mm. It should
always be possible to move the plastic part
on the coupling at least 3 mm.
If motor-type relay or the electrical fuse is
blown, check that electric motor is sized
correctly.
To ensure easy mounting of the flexible coupling
without using tools, the tolerances must be
dimensioned accordingly.
WARNING:
Any axial and/or radial loads on the shaft must
be avoided. Any axial or radial load will cause
breakdown.
A - Bell housing
B - Flexible coupling
C - Motor shaft
1.6 Pump damage
(the internal parts may be damaged)
62
ABC
1.6.1 Contact Danfoss sales office for guidelines
in how to troubleshoot internal pump
parts.
180R9287 |AQ073186503097en-000901 | IOM PAHT 2-12.5 pumps | 11.2020
Instructions on internal elements are available
on www.danfoss.high-pressurepumps.com
Guideline | Trouble shooting guide for PAH, PAHT, PAHT C , PAHT G, PAHT 674 and PAH F pumps
2. Reduced flow/reduced pressure
Cause RemedyComments
2.1 Wear on pump
Large internal leakage due to:
2.1.1 Dismantle the pump.
2.1.2 Check valve plate.
Valve plate has marks/scratches on the
surface facing the port plate. Minor wear
on valve plate can cause large internal
leakage. See Index 6.1.
2.1.3 Check port plate.
Port plate has marks/scratches on the
surface facing the valve plate. Minor wear
on port plate can cause large internal
leakage. See Index 6.2.
2.1.4 Check cylinder barrel.
Liners in cylinder barrel may be scratched
or worn. Insert a piston in the liner and
check the fit. If there is any space (clearance) between liner and piston, liner or
piston is worn.
2.1.5 Pre-treatment:
Analyse fluid for content of particles.
- Check that filters are OK and working
correctly.
2.1.6 Main filtration:
Check that the correct filter type is used
(particles in fluid must not exceed 10 μm).
Danfoss High Pressure Pumps supplies
filters, please contact the sales office.
Typical signs of wear:
Polished surface all over the swash plate.
Normally, only half of the swash plate = the
pressure side is polished. See index 6.3.
If the ring is missing, the piston is very worn.
The filters can be bypassed, even if they are
correctly mounted. Some filters can create
channelling where particles can pass through
the filter in tunnels. String wounded filters are
typically channelling filters. A string wound filter
may have a filtration efficiency of only 50%,
which will cause internal wear and must always be followed by a main filter.
2.1.7 Fluid type:
The PAH/PAH F (tapwater) and PAHT/PAHT
G (ultra pure water) pumps are designed
for water operation; for any other fluid,
please contact Danfoss High Pressure
Pumps sales office for further help.
2.1.8 High fluid temperature:
If fluid temperature is above 50°C, stop the
pump immediately.
- Check internal parts (see above).
2.2 Low inlet pressure2.2.1 Check that booster pump supplies the
right pressure/flow.
2.2.2 Check if filters require replacement.
2.3 Rotation speed (rpm)2.3.1 If VFD-operated, check frequency.
2.3.2 Check that rotation speed of the electric
motor is as stated on name plate on
electric motor. Check that the motor rotor
winding is not damaged.
Insufficient filtration means that too many or too
large hard particles can pass the main filter
because it is damaged, bypassed or simply too
poor. Filtration efficiency must be 99.98%
(Beta = 5000) at 10 μm to prevent abnormal
wear of the pump.
Temperature > 50° C will cause wear on internal
pump parts. Mount a temperature switch and
check its set point / function. The temperature
switch will ensure that the pump stops at fluid
temperatures > 50° C.
If the pressure drop across the filters is too high,
the booster pump does not deliver sufficient
flow/pressure. No pressure or low pressure
results in cavitation and insufficient internal
lubrication causing wear on internal pump parts.
Mount a low-pressure switch in front of the
pump and check its set point/ function. The
low- pressure switch ensures that the pump does
not start until the inlet pressure has reached 1
bar.
Speeds below minimum limit (see Data sheet)
result in insufficient internal lubrication causing
wear on the internal pump parts.
180R9287 |AQ073186503097en-000901 | IOM PAHT 2-12.5 pumps | 11.2020
63
Guideline | Trouble shooting guide for PAH, PAHT, PAHT C , PAHT G, PAHT 674 and PAH F pumps
3. High torque on electric motor
Cause RemedyComments
3.1 Too high outlet pressure from pump3.1.1 Check for blocked nozzles or a faulty
adjusted relief valve.
Pressure changes due to flow restrictions. This
will also cause high motor torque.
3.2 Pump starts against pressure3.2.1 Check that electric motor is correctly sized.
3.2.2 Check internal parts (see item 2.1).
3.2.3 Systems with more than one electric motor
installed:
Start motors simultaneously.
3.4 Water pump damage3.4.1 Dismantle pump and check for wear.Too heavy damage in the pump will increase
Pumps run in parallel with cascade start, may
switch off the motor relay due to too high
torque caused by high outlet pressure.
If the electric motor is too small for the pump, it
cannot provide sufficient torque.
friction causing a high torque (see item 6,
Typical signs of wear).
64
180R9287 |AQ073186503097en-000901 | IOM PAHT 2-12.5 pumps | 11.2020
Guideline | Trouble shooting guide for PAH, PAHT, PAHT C , PAHT G, PAHT 674 and PAH F pumps
4. Noise from pump
Cause RemedyComments
4.1 Air in fluid4.1.1 Ensure that the entire inlet line is bled
before starting up the system.
4.1.2 Ensure that air cannot enter into the inlet
line.
4.2 Bleeding conditions of pump4.2.1 Follow the instructions “Initial start-up”
supplied with the new pump.
4.2.2 Ensure that the pump is completely bled
before start-up.
4.3 Min/max nominal inlet pressure4.3.1 Ensure that inlet pressure is within
the limits specified in the Data sheet.
4.3.2 Check the pump for internal damage.
4.4 Pump reversing4.4.1 Dismantle pump and check if anything is
broken or worn (See “1. No flow”, item 1.2
Pump reversing”).
WARNING:
The pump must not run without water for
more than a few seconds. If the pump
takes in water from the high-pressure
outlet line, it builds up pressure and will
eventually be damaged.
4.5 High rotation speed (rpm)4.5.1 If electric motor rpm is too high, dismantle
pump and check for damage.
4.5.2 If the rpm is within the specified range of
the pump data sheet and abnormal noise
remains, dismantle pump and check for
damage.
Small air bubbles will accumulate and create
large bubbles causing internal cavitation and
thus making the pump very noisy.
WARNING:
The pump can only run few minutes with air in
the fluid without being damaged.
The pump and the inlet line must be completely
bled before start-up, otherwise the pump will
cavitate and make high noise.
WARNING:
The pump can only run few minutes with air in
the fluid without being damaged.
Too high inlet pressure causes too high pressure
inside the pump damaging the pistons and
eventually the pump.
Inlet pressure below min. limit causes cavitation
and insufficient internal lubrication resulting in
wear on internal pump parts.
Mount a low-pressure switch in front of the
pump and check its set point/ function. The
low-pressure switch will ensure that the pump
does not start until the minimum inlet pressure
has been reached.
If pump rotates in wrong direction, it will take in
water from the high-pressure outlet line.
Pressure will be built up inside the pump and it
will eventually be damaged.
Higher rpm than specified in the pump data
sheet results in wear of the pistons, i.e. pistons
may be damaged.
High rpm will also increase pressure pulsations
from the pump, and the noise level will increase.
4.6 Outlet pressure4.6.1 If outlet pressure is too low, check set point
of outlet pressure valve.
4.6.2 If outlet pressure is lower than mentioned
in the pump data sheet, please contact
Danfoss High Pressure Pumps technical
support.
4.6.3 If outlet pressure has exceeded its
maximum, check set point of outlet
pressure valve.
4.6.4 Check internal parts for wear/damage.
4.7 Soft start/stop4.7.1 Check if noise is normal when the pump is
running at operation speed.
4.7.2 If noise is abnormal at operation speed,
check internal parts (see above).
180R9287 |AQ073186503097en-000901 | IOM PAHT 2-12.5 pumps | 11.2020
If rpm is changed, noise frequency will also
change.
At too low outlet pressure, the pump will create
higher pressure pulsations and thus make noise.
Too low pressure also causes insufficient internal
lubrication and wear on internal parts. Pump
may eventually be damaged.
Too high outlet pressure may damage the pump.
Noise frequency changes during soft start-up/
stop.
65
Guideline | Trouble shooting guide for PAH, PAHT, PAHT C , PAHT G, PAHT 674 and PAH F pumps
5. Noise from installation
Cause RemedyComments
5.1 Inlet/outlet connections (hoses/pipes)5.1.1 Use flexible hoses at inlet/outlet connec-
5.2 Length/dimension of inlet/outlet line5.2.1 Increase pipe diameter and/or reduce the
5.3 Hose stiffness5.3.1 Use a more flexible hose. Too stiff hoses cannot dampen the small
5.4 Hoses/pipes mounted directly on frame5.4.1 Mount the connections to the frame by a
5.5 Vibration dampener under the electric
motor
tions.
5.1.2 Mount the connections to the frame by a
vibration dampener mounting plate.
number of bends.
vibration dampener mounting plate.
5.5.1 Mount a vibration dampener below the
motor/pump.
Non-flexible connections mounted directly on
the frame will cause even small pressure
pulsations from pump and create vibrations in
the system/plant.
Too small pipes or too many bends may create
too fast flow/turbulence through the pipes and
thus increase the noise level.
pressure pulsations from the pump, and
subsequently vibrations occur in the system/
plant.
If the hoses are mounted directly on the frame,
the small pressure pulsations from the pump
can be transferred to the frame and the rest of
the system/plant.
When no dampener is installed below the
electric motor, vibrations from the motor and
pump may be transferred to the frame and the
rest of the system/plant.
66
180R9287 |AQ073186503097en-000901 | IOM PAHT 2-12.5 pumps | 11.2020
Guideline | Trouble shooting guide for PAH, PAHT, PAHT C , PAHT G, PAHT 674 and PAH F pumps
6. Typical signs of wear6.1 Valve plate
Picture 1
Picture 2
Scratches
A normally worn valve plate has no marks/scratches but only a slightly
polished surface.
No scratches or marks should be felt. The surface must be flat and level.
A worn valve plate has scratches, and/or a polished surface. Even small
scratches will give a loss of flow.
Picture 3A good way to identify a worn valve plate is to hold a straight knife edge
over the valve plate. When holding it up to the light, it will be possible to
see any space between the knife edge and the valve plate. See picture 3.
If any light can be seen between the two arrows on the picture, the valve
plate is worn.
If any scratches or ma rks can be felt by runnin g a fingernail over the surface,
the valve plate is worn.
The valve plate on picture 3 is highly damaged.
180R9287 |AQ073186503097en-000901 | IOM PAHT 2-12.5 pumps | 11.2020
67
Guideline | Trouble shooting guide for PAH, PAHT, PAHT C , PAHT G, PAHT 674 and PAH F pumps
6.2 Port plate
Picture 1
Scratches
Level differences between
dull and shining PEEK
If the por t plate has scratches, level diffe rences or both betwe en the arrows,
the port plate must be replaced.
Even small scratches or wear will cause loss of flow.
To check: See item 6.1, picture 3
6.3 Swash plate
Picture 1If the swash plate is polished 360°, it is an indication of insufficient filtration.
The surf ace of the swash plate must be pla ne and even at same level all over.
To check this, please see item 6.1, picture 3.
If the surface has any marks/scratches, it is worn/damaged and a new one
is required.
Please contact Danfoss High Pressure Pumps sales office for further information.
68
180R9287 |AQ073186503097en-000901 | IOM PAHT 2-12.5 pumps | 11.2020
Guideline | Trouble shooting guide for PAH, PAHT, PAHT C , PAHT G, PAHT 674 and PAH F pumps
180R9287 |AQ073186503097en-000901 | IOM PAHT 2-12.5 pumps | 11.2020
Trouble shooting guide for water hydraulic systems
water hydraulic systems
hpp.danfoss.com
Design
4.
Pump location
1.
.
.
Choice of material
Rubber
Plastic
. Stainless steel
Always use system components made
of corrosion proof materials
2.
Non-corrosion proof materials
may cause damage
Choice of filter
.
Iron
.
Copper
. Brass
. Aluminium
Pump always to be placed below water
surface level
5.
System to be dimensioned to provide
a suction pressure of the pump inlet of
max. 0.1 bar vacuum
6.
Suction conditions
Pressure Relief valve
Pump location above water surface
level will cause damage
Poor suction conditions will cause
malfunction and damage the pump
mmabs.
< 10
Install a 10 micron absolute filter with
pressure switch
3.
Locate the return filter in the return line
immediately before the tank
Filter location
mm
> 10
Return filter with bypass valve and
poorer filterability than 10
damage the system
Placing the return filter upstream of the
final load may damage the pump
m will
Pressure relief valve to be mounted
vertically or with vertical outlet and
connected to return hose or tank
7.
System to be filled via filter
Coupling the pressure relief valve outlet
directly to the pump inlet may damage
the pump
Water supply
Filling system with unfiltered
water causes damage
180R9287 | AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps| 01.2022
Installation
8.
Prior to installation, burrs and chips and
other impurities must be removed from
pipes and hoses, eg with a felt plug
9.
Impurities
Chips or other impurities in the system
may cause damage
Sealing
11.
The coupling must be easy and simple
to assemble (see product instruction)
Assembly of coupling
12.
= min. 3 mm
Never use force when assembling the
coupling parts, as this will damage the
motor/pump
Coupling
0 mm
Fittings in screwed components to be
sealed with O-rings or bonded seals
10.
Correctly limited quantities of grease
prevent seizing
Using teflon tape or packing yarn in
joints may cause damage
Grease
Too much grease may develop
biofilm causing operational failures
Ensure always to have 3 mm distance
between coupling flanges
13.
Fill system with water before starting
to ensure lubrication and cooling
Water supply
Insufficient distance and/or misalignment between the coupling flanges
will damage the pump
Starting without water will cause
damage
180R9287 | AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps| 01.2022
Wiring
Starting procedure
Cleaning procedure
14.
Level and temperature indicators
must be fitted. Follow installation
instructions
15.
1
?
2
Level indicator
Missing or incorrectly connected level
and temperature indicators cause
damage
Rotation direction
1. Fill cold water into the system via the return filter and
bleed the pump (Power Packs PPH 4 - 6.3 - 10 and 12.5 are
self-bleeding)
2. Start and bleed the system -without pressure by opening
the bypass valve
3. Add the cleaning agent to give 3% agent/water solution
4. Run the system for 60 min. and activate all components as
often as possible to ensure effective flushing with the
cleaning agent
5. Empty the system of the cleaning agent solution
Flushing procedure
6. Fill cold water through the return filter and bleed the
pump (Power Packs PPH 4 - 6.3 - 10 and 12.5 are
self-bleeding)
7. Run the system for 30 min. and activate all components as
often as possible
8. Empty the system of the water
Check pump drive motor rotation
direction matches that of the pump
prior to installation
16.
Bleeding the pump will ensure correct
cooling and lubrication
Incorrect rotation direction will
damage the pump
Bleeding
Insufficient bleeding may cause damage (not applicable to Power Packs)
9. Alternatively the system may be flushed by running the
unit without the return hose while continuously filling up
water. The flushing should continue until there is no trace
of cleaning agent in the return water
10. Change the return filter element, fill cold water through
the return filter and bleed the pump during start up
11. The system is now ready for operation
Starting procedure
60 min.
Observing the starting procedure will
ensure problem-free operation
If the system is not cleaned before
starting, the filter will clog
180R9287 | AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps| 01.2022
days
2-3
Trouble shooting
Open ended water systems
.
No
.
No water supply
Is the water supply ok?
Is water supplied to the pump?
Yes
.
Is water coming
out of the tap?
No
.
Are all taps open?
.
Is the control light
for “low pump suction
Yes
pressure” on?
.
The filter is clogging
.
Is water coming
through the filter?
.
Replace filter element
Yes
No
No
Yes
.
Is the electric motor of
the pump unit rotating?
Yes
No
.
Is the water in the tank
very hot? Ie above 50
.
Is the power supply ok?
.
Are control lights on?
.
Is the filter clogged?
No
.
Is the filter control
light on?
.
Replace filter element
No
Yes
Yes
.
Yes
o
No
Lower inlet
temperature or
provide better cooling
.
A blown fuse / or short
circuit?
. Check power supply
and fuses and contact
electrician
.
Turn on the tap for
water supply
Contact serviceman
Stamp
180R9287 | AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps| 01.2022
Trouble shooting
Closed water systems
.
Is there sufficient water
No
in the tank?
Yes
The system
does not work
.
Fill water into the system
.
Is the electric motor of
the pump unit rotating?
Yes
No
.
A blown fuse/or short
circuit?
. Check power supply
and fuses and contact
electrician
.
Is the water in the tank
very hot? Ie above 50
.
Is the power supply ok?
No
.
Are control lights on?
.
Is the filter clogged?
.
Is the filter control
light on?
Contact serviceman
No
Yes
No
Yes
o
.
At temperatures
higher than 50o the
pump drive cuts out.
Consequently the
cooler must be
checked/cleaned
Yes
.
Replace filter element
.
Trace leakage, if any
Stamp
180R9287 | AQ073186503097en-001001 | IOM PAHT 2-12.5 pumps| 01.2022
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.