Danfoss PAH 2, PAH 4, PAH 6.3, PAH 10, PAH 12.5 Operating guide

Operating guide
PAH pumps PAH 2-12.5 Installation, Operation and Maintenance Manual
hpp.danfoss.com.
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
Table of Contents Contents
Table of Contents ..................................................................................2
1. Introduction ............................................................................5
1.1 General .................................................................................5
1.2 Symbols ................................................................................5
1.3 Manufacturer and customer service address:.............................................6
1.4 Country specic information ............................................................6
1.4.1 United Kingdom ........................................................................6
2. Safety ..................................................................................6
2.1 General information.....................................................................6
2.2 Preferred system design.................................................................6
2.3 Commissioning and servicing the unit ...................................................7
2.4 Adhere to the following important points ...............................................7
2.5 In case of doubt .........................................................................7
3. Technical data ..........................................................................7
3.1 Approved applications and operational limits for the pumps .............................7
3.2 Application range.......................................................................7
3.3 Electric motor data......................................................................7
3.4 Noise and vibration .....................................................................7
3.5 Dimension drawings ....................................................................7
3.6 Space requirement......................................................................7
3.7 Filtration................................................................................8
3.8 Properties of water ......................................................................8
3.9 Air bubbles .............................................................................8
3.10 Chemicals...............................................................................8
4. Arrival inspection, transportation, handling, lifting and storage ..........................8
4.1 Arrival inspection .......................................................................8
4.2 Warning ................................................................................8
4.3 General safety information ..............................................................8
4.4 Transport and handling .................................................................8
4.5 Return to supplier .......................................................................9
4.6 Storage .................................................................................9
5. Installation and commissioning ........................................................10
5.1 Important dimensions .................................................................10
5.2 Cleanliness.............................................................................10
5.3 Fluid temperature......................................................................10
5.4 Electrical data..........................................................................10
5.5 Local regulations.......................................................................10
5.6 Pre mounting checklist, based on Danfoss preferred system design .....................11
5.7 Lifting and positioning .................................................................11
5.8 Mount the dierent equipment ........................................................11
5.9 Electrics ...............................................................................11
5.10 Instrumentation .......................................................................11
5.11 Connections ...........................................................................11
5.12 Ensure free ow .......................................................................12
5.13 Verify setting of safety/relief valves .....................................................12
5.14 Bleed and remove air from the pump ...................................................12
5.15 Verify direction of rotation .............................................................12
5.16 Commissioning ........................................................................12
5.16.1 Op en system ...........................................................................12
5.16.2 Closed system .................................................................... 12
5.17 Check the lter condition...............................................................12
5.18 Instruct operator and maintenance personnel ..........................................12
6. Operation of motor pump unit ........................................................13
6.1 General safety information.............................................................13
6.2 What to listen and look for .............................................................13
2
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
7. Maintenance and service of the pump unit .............................................13
7.1 General safety information .............................................................13
7.2 Service and inspection interval for the pump ...........................................13
7.3 Shut down of the system ...............................................................13
7.4 Disassembling and assembling the pump unit ..........................................14
7.5 Assembling the pump unit .............................................................14
7.6 Procedure for mounting the pump back onto electric motor ............................14
7.7 Getting the pump unit back into operation .............................................14
7.8 Storage of the pump ...................................................................14
8. Troubleshooting and scrapping criteria .................................................15
8.1 General safety information .............................................................15
8.2 Operational conditions which can cause pump failures..................................15
8.3 Mechanical failure......................................................................15
8.4 Electrical failure ........................................................................15
8.5 Responsibility..........................................................................15
8.6 Scrapping criteria ......................................................................15
Appendices .......................................................................................17
1. Data sheet PAH 2- 12.5 (521B0835) ......................................................19
2. Pump instruction PAH/PAHT/PAHT G 2-12.5 (180R9277 ..................................33
3. Electric motor manual (180R9230) ......................................................43
4. Parts list PAH 2-12.5 (521B1408) .........................................................49
5. Trouble shooting guide for PAH, PAHT, PAHT G, PAHT 674 and PAH F pumps .............59
6. Right and wrong - Trouble shooting guide for water hydraulic systems (180R9042).......73
3
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
Validity
This manual is valid for PAH pumps both non ATEX and ATEX certied versions. An ATEX certied pump is indicated by Ex in the designation - example PAH 2 Ex.
No n ATEX ATE X
PAH 2
PAH 4
PAH 6 .3
PAH 10
PAH 12.5
Code no. 180B0024
Serial no. XXXXXX04-XXX XXXXXX04-XXX
Code no. 180B0022
Serial no. XXXXXX04-XXX XXXXXX04-XXX
Code no. 180B0023
Serial no. XXXXXX04-XXX XXXXXX04-XXX
Code no. 180B0008
Serial no. XXXXXX04-XXX XXXXXX04-XXX
Code no. 180B0007
Serial no. XXXXXX04-XXX XXXXXX04-XXX
PUMP
Type PAH 12.5 Code no. 180B0007
Serial no. XXXXXX04-XXX
MADE IN DENMARK
Danfoss A/S, 6430 Nordborg, Denmark
In case the pump delivered is ATEX certied, the additional ATEX instruction maus also be read.
PAH 2 Ex
PAH 4 Ex
PAH 6.3 Ex
PAH 10 Ex
PAH 12.5 Ex
180B6124
180B6122
180B6123
180B6108
180 B6107
The serial number is referring to the Serial no. on the product label. The digits shown (04) indicate the version number of the pump. This documentation is compatible with previous pump versions.
4
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
1. Introduction
1.1 General
The PAH pumps and pump units are manufac­tured by Danfoss A/S, and are sold and marketed by a net of authorized distributors world wide.
This manual contains the necessary instructions for the installation, operation and service of the pumps used for tap water.
In case the pump delivered is ATEX certied, the additional ATEX instruction must also be read.
The PAH pumps must not be used for other purposes than those recommended and specied without rst consulting your local pump distributor.
Use of the pump in other applications not suitable for the pump unit can cause damages to the pump unit, with risk of personal injury.
All personnel being responsible for operation and maintenance of the pump unit must read and fully understand these instructions, especially the section “Safety”, before:
• Transportation of the pump unit
• Lifting the unit
• Installing the pump unit
• Connecting the pump unit to the water system
• Connecting the electric motor and instru­mentation
• Commissioning the unit
• Servicing the motor pump unit, mechanical and electrical parts
• Decommissioning the motor pump unit
The pump must always be installed and used in accordance with existing national/local sanitary, safety regulations and laws.
It is important that these instructions are always available to the personnel concerned.
1.2 Symbols
Indicates something to be noted by the
reader
Indicates a situation which will or could
result in damage to the pump and its function
Indicates a situation which will or could
result in personal injury and/or damage to the pump
Electrical hazard - Indicates a high-
voltage warning
Safety glasses required
Hearing protection required
Safety shoes required
Safety helmet required
!
Protective garments must be wor n
Protective garments
must be worn
It is the responsibility of the safety ocer or the chief operator to assure compliance with all local regulations that are not taken into account in this manual.
Changing the pumps’ or pump units’ opera­tional limits and hardware:
• Changes to the delivered pump or motor pump system may only be done with a written approval from Danfoss High Pressure Pumps.
• Operation outside the Danfoss specications requires a written approval from Danfoss High Pressure Pumps.
• If any changes are made without written approval the warranty will automatically become void.
Electrical
hazard
Danger HOT.
Do not touch
Electrical hazard
5
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
2. Safety
1.3 Manufacturer and customer service address:
Danfoss A/S High Pressure Pumps
Nordborgvej 81, DK-6430 Nordborg Denmark
Telephone: +45 7488 2222 Fax: +45 7445 3831 Email: highpressurepumps@danfoss.com Web: hpp.danfoss.com
2.1 General information
Dangers that can arise from not following the instructions:
When the pump or pump system is managed by untrained personnel, there is a danger of:
• Death or fatal injuries
• Costly damages and claims
Electrical
hazard
All electrical installation work must only be carried out by authorized personnel in accordance with EN60204-1 and/or local regulations.
Your local Danfoss pump distributor can be found on our homepage.
1.4 Country specic information
1.4.1 United Kingdom
UK importer:
Danfoss Ltd. Oxford road UB9 4LH Denham United Kingdom
Under certain operational conditions the surface of the pump can be above 60°C / 140°F. Under these conditions the pump must be labelled with a “Danger Hot” sign.
When using an electric motor, the motor must always be supplied with adequate cooling ventilation.
When using an electric motor together with a VFD (Variable Frequency Drive), the motor must be designed for operation with VFD. VFD operation may increase the temperature inside the electric motor if the motor is not designed for VFD operation. This can damage the motor and cause unintended breakdown.
It is recommended to install a lockable circuit breaker to avoid inadvertent starting and/or electrical hazard. The lockable circuit breaker must be used during installation, operation and maintenance.
It is recommended to place a local safety switch nearby the pump, enabling service personnel to cut power for the electric motor.
Protect the motor and other electrical equip­ment from overloads with suitable equipment.
In case the pump delivered is ATEX certied, the additional ATEX instruction must also be read.
Protective garments
!
must be wor n
Always wear suitable safety clothing when handling the pump.
When working near the pump system, safety shoes, safety glasses, hearing protection and safety helmet must always be worn.
Before start-up, the settings for all protective devices, such as sensors/switches and safety valves must be veried and free ow from safety valves must be ensured.
All pipe and hose connections must be stress­free mounted, securely fastened to the pump and well supported. Improper installation will or could result in personal injury and/or damage to the pump.
Use of this manual does not relieve operation and maintenance personnel of the responsibil­ity of applying good judgment when operating and maintaining the pump and its compo­nents.
2.2 Preferred system design
Danfoss recommends to build systems with a high degree of safety. Danfoss preferred system design and P&ID are found in appendix 1, Data sheet, and appendix 2, Instruction.
6
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
3. Technical data
It is always the system builders´ responsibility that the system design does not cause any kind of hazard and is adapted to local regulations and standards.
Proper installation, proper start up and shut­down devices as well as high-pressure protection equipment is essential.
2.3 Commissioning and servicing the unit
It is recommended that commissioning and servicing are carried out by a minimum of two people, where one is acting as a supervisor.
2.4 Adhere to the following important points
Before using the pump/pump unit it is very important to read and understand this user manual.
Do not try to lift the pump unit manually; most of the pumps weigh more than 20 kilos, see specic weight for the pump in the appendix 1, Data sheet.
Always bleed the pump prior to initial start-up.
Do not mount the pump without the bell housing and a exible coupling.
Do not try to start the unit before the system components are mounted, bleeded and adjusted.
Flush the system throughly before connecting the pump or pump unit.
Check rotation direction of the motor before mounting the pump.
2.5 In case of doubt
Please contact Danfoss A/S in case of doubt. Contact information are listed in section 1.3, Manufacturer and customer service address.
3.2 Application range
See appendix 1, Data sheet.
3.1 Approved applications and operational limits for the pumps
The pump and the pump units are designed for the use in systems with tap water.
The PAH pumps must not be used for other purposes than those recommended and specied without rst consulting your local pump distributor.
Use of the pump in other applications not suitable for the pump unit can cause damages to the pump unit, with risk of personal injury.
3.3 Electric motor data
See recommended motor in appendix 1, Data sheet or appendix 3, IOM for motors. The motors mentioned are the most common used motors by Danfoss High Pressure Pumps.
3.4 Noise and vibration
Noise level for a pump unit with a ”standard” motor measured according to EN ISO 3744:2010, see appendix 1, Data sheet. Possibilities to reduce noise and vibration are described in the same Data sheet.
3.5 Dimension drawings
Dimensions of the dierent pumps can be found in appendix 1, Data sheet.
3.6 Space requirement
When doing service or replacing the complete pump unit, it is recommended to have sucient space available around the pump in order to ensure easy access. Sucient space means at least 1 meter/40 inches around the pump. When working with high pressures, it is important to have the right space available around the pump as stated in the safety requirements.
For system integration of the pumps, please see appendix 1, Data sheet and appendix 2, Instruction.
7
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
4. Arrival inspection, transportation, handling, lifting and storage
3.7 Filtration
(10µm absolute [β10 ≥ 5000])
Requirements are specied in appendix 1, Data sheet and appendix 2, Instruction.
Danfoss recommends not to build a lter bypass function or use lters with an integrated bypass. If the above recommendation is not followed the warranty for the pump will automatically become void.
It should be possible to monitor the condition of the lter via the dierential/delta pressure across the lter.
Using insucient ltration or a lter bypass can cause a failure or decreased service life of the pump.
3.8 Properties of water
It is recommended NOT to use the pump for other media than specied in the Data sheet.
4.1 Arrival inspection
The pump is packed in a cardboard or wood box with plugs in the port connections to protect the pump from damage during transportation.
When the shipment has arrived it is important to check the pump for any damages. The name plate/type designation must be in accordance with the delivery note and your order.
3.9 Air bubbles
Large bubbles in a pressurised system can result in damage to piping, equipment and the pump.
All air must be bleeded from both the low­pressure and high-pressure side before the system is pressurised. Special consideration should be given in order to minimize air bubbles in the feed ow. Air bubbles can cause cavitation.
3.10 Chemicals
The pumps should not be exposed to any chemicals that can result in damage to piping, equipment and internal parts of the pump.
4.4 Transport and handling
Small pumps which have a weight below 20 kilos (weight can be found in appendix 1, Data sheet) can be handled by hand if they are not mounted together with an electric motor. The weight of a small pump with a motor will be above 20 kilos.
In case of damage and/or missing parts, a report should be documented and presented to the carrier at once.
4.2 Warning
Before any lifting operation is performed, environmental conditions must be taken into consideration (Ex-rated areas, wind speed, wet/ dry conditions, lifting height, etc.).
4.3 General safety information
Personnel involved in lifting and transporting the equipment (see Safety, chapter 2) must be trained in handling and safety procedures when lifting heavy loads. Many of the pumps and pump units weigh more than 20 kilos, which requires lifting slings and suitable lifting devices; e.g. an overhead crane or industrial truck to be used as minimum.
8
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
appendix 1, Data sheet) must be handled by using lifting eyes and slings.
Wrong lifting:Pumps which have a weight above 20 kilos (see
When the pump is mounted together with an electric motor, the pump unit always weigh more than 20 kilos and must be handled by using slings around the pump unit.
See below examples of where to/not to attach the lifting slings on the pump unit:
Correct lifting with 2 separate slings:
When lifting the pump unit, one sling must be attached to the electric motor and one sling around the pump.
Only some motors and pumps have specic lifting eyes.
Do not use connections/nozzles for lifting! Do not use only one sling!
Make sure that the unit/load is balanced before lifting. The centre of the mass varies from pump/ pump unit size to pump/pump unit.
How to mount the pump and the electric motor correctly, see appendix 1, Data sheet or appendix 2, Instruction.
Incorrect lifting can result in personal injury and/or damage to the pump unit, see appendix 2, Instruction.
4.5 Return to supplier
Please see maintenance chapter 7.
4.6 Storage
Each pump is tested before shipment, and will therefore contain water. For storage temperature and frost protection see appendix 2, Instruction.
The pumps are NOT delivered frost protected from the factory.
9
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
5. Installation and commissioning
5.1 Important dimensions
Physical dimensions and connections of the pump unit are described in appendix 1, Data sheet.
5.3 Fluid temperature
Before start-up, the uid and pump housing temperature must be within the specied temperature range listed in appendix 1, Data sheet.
5.2 Cleanliness
It is very important that the tubes and pipes are completely clean: no dirt, chips or burrs are allowed.
Flush all piping before connecting the high­pressure pump to ensure the system is clean. Internal surfaces of the piping must not be corroded. If dirt or rust is not removed, the pump and the valves can be damaged. In worst case the pump can be damaged beyond repair!
Open system design
1 4 5 5 6
PI
5.4 Electrical data
Check voltage, current frequency and rated power on the electric motor and VFD settings on the name plate placed on both the motor and the VFD.
5.5 Local regulations
Commissioning must always be done in accordance with valid regulations and local standards.
M
2
PI
SYSTEM
8
73
Closed system design
10
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
5.6 Pre mounting checklist, based on Danfoss preferred system design
Check points Comment OK ?
CP1 Ensure that the environmental conditions are safe. See Arrival inspection,
CP2 Minimum and maximum start-up temperature for uid and
pump.
CP3 Filtration condition (10µm absolute (β10 ≥ 5000) See Danfoss requirements in
CP4 Power supply for electric motor and VFD. See Data sheet for the used
CP5 Safety circuit / breaker must be sized for the motor and
environment (corrosion and humidity)
CP6 Bolts and screws must conform to environmental conditions
as well as uid and torque requirements.
CP7 Instrumentation, pressure switch should be designed to
conform to the environment (corrosion and humidity).
CP8 Check the factory settings of the safety/relief valves or
pressure relief valves (1).
CP9 Check the settings of the pressure transmitter/switch (2) set
at min. inlet pressure.
CP10 Check that all pressure indicators (PI) are selected to be able
to measure the system pressure range.
CP 11 Check coupling distance ( air gab – movement of the spider ) 3 – 5 mm
CP12 Check correct connections on the pump ( in & outlet)
CP13 Check piping for possible air gaps.
transportation, handling, lifting and storage, chapter 4.
See Data sheet or Instruction, appendices 1 and 2.
Data sheet and Instruction, appendices 1 and 2
motor and VFD.
See Data sheet for the used safety circuit.
See Data sheet for the used equipment.
See Data sheets for the used valves.
See Data sheet or Instruction, appendices 1 and 2.
Scaling should at least be 1 barg or more precise.
5.7 Lifting and positioning
Lift the pump unit onto base (Remember vibration dampers, if needed). Fasten the motor to the base.
See also chapter 4, Arrival inspection, transporta­tion, handling, lifting and storage.
5.8 Mount the dierent equipment
(connections, pipes, tubes, check and safety/relief valves, etc.)
• The hard piping and exible hoses used must be of proper design and must be installed in accordance with the manufacturer’s recom­mendations.
• Misalignment of the hard pipes may give unintended stress on the pump port connection and may damage the pump.
• Prevent excessive external pipe load.
• Do not connect piping by applying external force (use of wrenches, crane, etc.) Piping must be aligned without residual stress.
• Do not mount expansion joints so that their force applies internal pressure on the pump connections.
5.9 Electrics
All electrical installation work must be carried out by authorized personnel in accordance with EN60204-1 and/or local regulations. (see also Safety, chapter 2)
Turn o the safety circuit breaker and lock it.
Mount the power cable on the electric motor.
If a VFD is used, adjust the protective motor switch/VFD to the current limits found on name plate of the electric motor.
5.10 Instrumentation
The pressure switch/sensor should be mounted as close to the pump as possible. It is recom­mended to test the pressure/sensor switch via an instrumentation manifold.
Mount the pressure switch/sensors according to the manufacturer’s instructions.
5.11 Connections
Mount and tighten connections and check valve(s) as specied.
11
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
5.12 Ensure free ow
Ensure free ow from relief valve (table 1, item
5.6, CP 8). A blocked relief valve can cause excessive build-up of pressure and thereby cause dangerous situations and damage to the whole system.
5.13 Verify setting of safety/relief valves
Make sure, the relief valve is placed correctly (see open system design, item 1).
Check the pressure settings on the name plate of the relief valve. If they are within specica­tions, you can continue.
5.14 Bleed and remove air from the pump
Open bleeding plugs. Keep the plugs open until the high-pressure pump is bleeded.
If the pump is submerged, remove all bleeding plugs before mounting in reservoir.
5.15 Verify direction of rotation
The direction of rotation must always follow the arrow. The arrow is placed on the pump or pump unit.
Check the direction of rotation before mounting the pump.
Unlock the safety circuit breaker. Start the motor for 1 second and observe the direction of rotation either looking on the fan of the motor or on the coupling through the hole in the bell housing (not available on all bell housings). If the motor is turning the wrong direction, switch two phases in the connection box of the motor or reprogram the direction in VFD.
Check the temperature switch/controls. The high-pressure pump must stop if tempera­ture is above specied set point.
Check the pressure switch/controls. The high-pressure pump must stop if pressure is below specied set point.
If the system is running within the system design limits, the system is released for operation.
5.16.2 Closed system
Check if the reservoir is clean.
Check if lter element is present and
mounted correctly.
Fill water at the reservoir using the lling
valve. Inspect immediately for leakage.
Bleed high-pressure pump until only water
leaves the high-pressure pump. Remember to close all bleeding and draining plugs.
Adjust pressure relief valve to minimum
setting.
Check rotation of the high-pressure pump
by description in 5.15.
Start high-pressure pump for 2 minutes, to
make sure all air is out of the system.
Check reservoir low level switch/controls.
The high-pressure pump must stop if low level switch is activated.
Adjust pressure relief valve to working
pressure.
Check the temperature switch/controls.
The high-pressure pump must stop if temperature is above specied set point.
Check the lter pressure switch/controls. A
warning must be given if pressure is above specied set point.
If the system is running within the system
design limits, the system is released for operation.
When the motor is turning in the right direction, the pump can be mounted.
5.17 Check the lter condition
Evaluate contamination found in lter, replace
5.16 Commissioning
lter elements, if necessary.
5.16.1 Open system
Check if lter element is present and mounted correctly.
Switch on the circuit breaker for both motor(s) and VFD(s).
Check rotation of the feed pump.
Start feed pump.
Bleed high-pressure pump until only water leaves the high-pressure pump. Remember to close all bleeding and draining plugs.
5.18 Instruct operator and maintenance personnel
Before using the pump/pump unit, the personnel must be instructed in using the pump/pump unit, its function, components, documentation and safety.
Adjust pressure relief valve to minimum setting.
Check rotation of the high-pressure pump by description in 5.15.
Danfoss oers commissioning and service at system manufacturer’s location. Rate quotes are oered upon request.
Start high-pressure pump for 2 minutes, to make sure all air is out of the system.
Adjust pressure relief valve to working pressure.
Check all ttings for leakage.
12
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
6. Operation of motor pump unit
6.1 General safety information
Before inspecting the pump unit, read the Safety chapter 2 in this user manual.
6.2 What to listen and look for
If one or more of the following examples are observed, please act as indicated:
A) Loose bolts – check all bolts and, if
necessary, contact the maintenance department in order to have all bolts tightened to the specied torque(s).
B) Leakage – if a small leakage from the bell
housing is observed. Contact the mainte­nance department.
C) Leakage – if there is a large leak, the unit
should be stopped immediately. Contact the maintenance department.
D) High frequency tones – safety/relief valves
are either damaged or running very close to their design pressure, stop the unit immediately. Contact the maintenance department.
E) Increased noise or vibration – requires the
unit to be stopped immediately. Contact the maintenance department.
G) Drop in ow and/or pressure – may indicate
wear on one or more parts inside the pump. The pump must be stopped immediately and inspected before it is restarted. Contact the maintenance department.
H) Other observations or troubles, please see
appendix 7, Right and Wrong or appendix 6, Trouble shooting guide. Both appendices give good advises on design, installation, wiring and troubleshooting.
If the pump is not stopped for inspection as recommended, it can lead to damage of the pump or break-down. See also service and warranty section in appendix 1, Data sheet and appendix 2, Instruction.
Danfoss oers service of the pump at the system manufacturer’s location as well as we oer training in how to service the pump. Quotes are oered upon request.
Danfoss recommends simultaneously to check the lter condition and to evaluate contamina­tion; lter elements must be replaced if neces­sary.
F) Very high temperatures – may indicate that
one or more parts are damaged inside the pump. The pump must be stopped immediately and inspected before it is restarted. Contact the maintenance department.
7. Maintenance and service of the pump unit 7.1 General safety information
Before servicing the pump unit, it is necessary to read and understand this user manual, especially the Safety, chapter 2. Remember to wear suitable safety equipment according to Safety, chapter 2.
7.2 Service and inspection interval for the pump
Maintenance and service intervals are depending on the cleanliness level of the water, hydraulic load and temperature of the pump unit. The most important parameter is the ltration of the water.
See the section Service and warranty in the appendix 1, Data sheet and appendix 2, Instruc­tion.
Danfoss oers service of the pump at the system manufacturer’s location and training in how to service the pump. Quotes are oered upon request.
7.3 Shut down of the system
A) Stop the high-pressure pump.
B) Release the pressure.
C) Stop the feed pump if used.
D) Switch o the safety circuit breaker for
both the high-pressure pump, feed pump and VFD and lock them. Only personnel servicing the pump unit should be able to unlock/activate the switch again.
For spare parts and service tools, please see appendix 4, Parts list.
E) Open bleeding and drain plugs. Wait until
the pump and system are emptied for water.
13
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
F) Slowly unscrew and remove the bolts and
gaskets from the inlet/outlet hoses or pipes, be careful about jets of water. Be aware that the system can be pressurized.
G) Attach the lifting equipment to the pump
unit. For instructions on lifting the complete pump unit, see chapter 4, Arrival inspection, transportation, handling, lifting and storage.
H) For the small pumps, unscrew the bolts
holding the pump to the bell housing and for the bigger pumps, unscrew the bolts/ nuts from the pump and bell housing to the motor and afterwards unscrew the bolts/nuts holding the pump and bell housing.
I) Carefully pull the pump out of the bell
housing by using lifting equipment, if necessar y.
J) Hold the pump in dierent positions above
a drip tray; this should allow most of the water trapped in the pump to drain. Clean and dry the pump surface and plug the bleeding and draining plugs.
K) Move the pump to a clean and safe location
where the pump can be inspected/ serviced.
7.4 Disassembling and assembling the pump unit
A) Remove all connections from the pump.
B) Disassemble the pump according to the
Disassembling and Assembling Instruction (available at www. danfoss.high-pressurepumps.com). Clean all the parts and surfaces with a uid compatible with the materials found in the pump. Wipe the parts clean and dry with a lint-free clothing.
Returns without a return number will be
rejected !!!
7.5 Assembling the pump unit
Assemble the pump according to the Disassem­bling and Assembling Instruction (available at www. danfoss.high-pressurepumps.com).
7.6 Procedure for mounting the pump back onto electric motor
Mount the exible coupling and bell housing according to appendix 2, Instruction.
7.7 Getting the pump unit back into operation
Find instructions of how to put the pump unit back into operation in chapter 4, Arrival inspec­tion, transportation, handling, lifting and storage and Installation and commissioning, chapter 5.
7.8 Storage of the pump
If the pump has to be shut down for a longer period, instructions can be found in appendix 2, Instruction.
C) Inspect all parts including shaft seal and if
necessary, replace them; see appendix 4, Parts list.
D) If the pump is going to be returned to
Danfoss for repair or a warranty claim, it is important to contact Danfoss in order to receive a return number and a form to ll out with product information. A copy of the form together with contact information and reason for returning should be sent to the email address on the form. The same documents should be attached to the shipment.
14
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
8. Troubleshooting and scrapping criteria
8.1 General safety information
Before inspecting the pump unit, it is necessary to read and understand this user manual, especially the Safety chapter 2.
Remember to wear suitable safety equipment according to Safety chapter 2.
8.2 Operational conditions which can cause pump failures
The following conditions can cause a pump failure :
The pump is running dry.
The inlet pressure is too high.
The inlet pressure is too low.
The temperature of the uid is too high.
The ambient temperature is too high.
The pump is running against a blocked port/closed manual valve.
The pump is operating at a pressure out of specication.
The pump is running with a non-specied/ approved uid.
The pump is running in the wrong direction.
The ltration is insucient.
There is excessive mechanical load on the shaft coupling and piping.
Electrical
hazard
8.4 Electrical failure
If the wiring of the electric motor is incorrect or the ground connection is missing, it can cause electric shock, burn damages, re or even death.
If a VFD is used and wrongly programmed, it can damage the pump and lead to high tempera­tures or other dangers.
All electrical installation must be carried out by authorized personnel in accordance with EN60204-1 and/or local regulations.
8.5 Responsibility
Danfoss takes no responsibility for any abnormal injuries, risks or damages that could arise caused by abnormal conditions, vibrations, corrosion, abrasives, foreign objects or excessive tempera­tures and shall not be liable for any consequen­tial or incidental damages.
8.6 Scrapping criteria
Whether the pump can be repaired or need to be scrapped, depends on in which conditions the internal parts are, or how damaged the whole unit is. Please use appendix 5, Trouble shooting guide as guideline or send the pump to Danfoss headquarter in Denmark for evaluation.
8.3 Mechanical failure
If the pump is running dry, the temperature will quickly increase which can cause burns.
If there is any leakage at start-up or during operation, a high pressure jet can cause eye or skin damage.
Leakage can result in ooding, which can cause slipping, tripping or falling.
If water is dripping into the electric motor; it can cause electric shock, re, short of circuit or even death. When mounting the pump vertically, always mount the motor above the pump to avoid water leaking into the electric motor.
For other observations or troubles, please see appendix 6, Right and Wrong which gives good advises regarding design, installation, wiring and troubleshooting.
In case the pump needs to be scrapped, please follow your local environmental rules.
15
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
16
Operation guide
PAH pumps
PAH 2-12.5 Appendices for Operation, Installation and Maintenance Manual
hpp.danfoss.com
Operation guide | Installation, Operation and Maintenance Manual for PAH 2-12.5 pumps
Table of Contents
1. Data sheet PAH 2- 100 (521B0835) ......................................................19
2. Pump instruction PAH/PAHT/PAHT G 2-12.5 (180R9277 ..................................33
3. Electric motor manual (180R9230) ......................................................43
4. Parts list PAH 2-12.5 (521B1408) .........................................................49
5. Trouble shooting guide for PAH, PAHT, PAHT G, PAHT 674 and PAH F pumps .............59
6. Right and wrong - Trouble shooting guide for water hydraulic systems (180R9042).......73
18
Data sheet
Data sheet
PAH pumps
PAH 2/4/6.3, PAH 10/12.5,
PAH 2/4/6.3, PAH 10/12.5, PAH 20/25/32 and
PAH 20/25/32 and
PAH 50/63/70/80/100
PAH 50/63/70/80/100 pumps
danfoss.high-pressurepumps.com
hpp.danfoss.com
Data sheet PAH 2/4/6.3, PAH 10/12.5, PAH 20/25/32 and PAH 50/63/70/80/100 pumps
Table of Contents
Contents
1. Introduction ...........................................................................20
2. Benets................................................................................21
3. Application examples ..................................................................21
4. Technical data .........................................................................22
4.1 PAH 2-12.5 .............................................................................22
5. Flow ...................................................................................23
5.1 PAH 2-6.3 typical ow curves at max pressure ..........................................23
5.2 PAH 10-12.5 typical ow curves at max pressure.........................................24
6. Motor requirements....................................................................25
7. Installation.............................................................................26
7.1 Filtration ..............................................................................26
7.2 Noise ..................................................................................26
7.3 Open-system design ...................................................................27
7.4 Closed-system design .................................................................28
8. Dimensions and connections...........................................................29
8.1 PAH 2-6.3 ..............................................................................29
8.2 PAH 10-12.5 ............................................................................30
9. Service.................................................................................31
1. Introduction
The data sheet is valid for PAH pumps both non ATEX and ATEX certied. The ATEX certied versions are indicated with Ex in the designation.
The Danfoss range of PAH high-pressure pumps is designed to supply water ow under high­pressure for a varity of tap water applications.
Danfoss PAH pumps are positive displacement pumps, with axial pistons that move a xed amount of water in each cycle. Flow is propor­tional to the number of input shaft revolutions (rpm). Unlike centrifugal pumps, they produce the same ow at a given speed no matter what the discharge pressure.
All components are designed to provide long service life with a constantly high eciency and minimum service required.
In the following all pumps are named PAH.
20 | 180R9379 | IOM PAH 2-12.5 pumps - v06
© Danfoss | DCS (im) | 2020.11
Data sheet PAH 2/4/6.3, PAH 10/12.5, PAH 20/25/32 and PAH 50/63/70/80/100 pumps
Below sectional drawing is an example of a PAH pump.
1: Shaft sealing 2: Mounting ange/ housing with bearing 3: Retaining ring 4: Piston/shoe 5: Valve trust plate 6: Swash plate 7: Cylinder barrel8: 8: Spring 9: Port plate 10: Connecting ange
2. Benets Zero risk of lubricant contamination:
- Oil lubricants are replaced with the
pumped medium, water, so there is no contamination risk from the pump.
Low maintenance costs:
- Ecient design and all-stainless steel
construction ensure exceptionally long lifetime. When Danfoss specications are met, service intervals of up to 8,000 hours can be expected. Service is easy, and can be carried out on site due to the simple design and few parts.
Low energy costs:
- The highly ecient axial piston design
provides the lowest energy consump­tion of any comparable pump on the market.
Easy installation:
- The lightest and most compact design
available.
3. Application examples Stationary and mobile hydraulic systems
High-pressure systems
Fire ghting
- Pump can be installed horizontally or vertically.
- No pulsation dampeners necessary due to extremely low-pressure pulsation.
- Powered by electric motors or combus­tion engines.
- Suitable for both boosted inlet pressure and water supply from a tank.
- No need for cooling circuits due to very high mechanical eciency.
Certied quality:
Certicates:
ISO 9001, ISO 14001, ITF 16949
ATEX available on request ABS and DNV GL certications on request
Flushing and cleaning processes
Humidication systems
© Danfoss | DCS (im) | 2020.11
180R9379 | IOM PAH 2-12.5 pumps - v06 |
21
Data sheet PAH 2/4/6.3, PAH 10/12.5, PAH 20/25/32 and PAH 50/63/70/80/100 pumps
4. Technical data
4.1 PAH 2-12.5
Pump size 2 4 6.3 10 12.5
Code number 180B0024 180B0022 180B0023 180B0008 180B0007
Code number ATEX
Housing material AISI 304 AISI 304 AISI 304 AISI 304 AISI 304
Geometric displacement
Pressure
Min. outlet pressure
Max. outlet pressure
Inlet pressure, continuous
Speed
Min. speed, continuous
Max. speed rpm 1800 1800 180 0 18 00 1800
Typical ow - Flow curves available in section 5
1000 rpm at max. pressure
1500 rpm at max. pressure
1200 rpm at max. pressure
1800 rpm at max. pressure
Typical motor size
1500 rpm at max. pressure
1800 rpm at max. pressure
Torque at max. spec.
Media temperature
Ambient temperature
Sound pressure level
Weight kg 4.4 4.4 4.4 7.7 7.7
For certied pumps specications on inlet and outlet pressure is stated on the 3.1 inspection certicate and may vary from generic specications stated above.
2)
180B6124 180B6122 180 B6123 180B6108 180B6107
cm³/rev 2 4 6.3 10 12 .5
in³/r ev 0.12 0.24 0.38 0.60 0.75
barg 30 30 30 30 30
psig 435 435 435 435 435
barg 140 140 140 160 160
psig 2030 2030 2030 2320 2320
barg 0-4 0-4 0-4 0-4 0-4
psig 0-58 0-58 0-58 0-58 0-58
rpm 700 700 700 700 700
l/min 1.0 3.2 5.6 8.4 11.0
l/min 2.0 5.2 8.7 13 .4 17.2
gpm 0.4 1.0 1.8 2.7 3.5
gpm 0.7 1.7 2.8 4.3 5.5
kW
hp
0.9 1.7 2.6 4.5 5.6
1.5 2.7 4.2 7. 3 9.0
Nm 5.9 10.9 16.7 29.0 35.8
lbf-ft 4.4 8.0 12 .3 21.4 26.4
°C 2-50 2-50 2-50 2-50 2-50
°F 36 -122 36 -122 36-122 3 6-122 36 -122
°C 0-50 0-50 0-50 0-50 0-50
°F 32-122 32-122 32-122 32-122 32-122
dB(A) 76 76 76 75 75
1)
lbs 9.7 9.7 9.7 17. 0 17.0
1)
Measurements according to EN ISO 3744: 2010 / dB(A) [L
Measured at max pressure and rpm for a motor pump unit.
2)
Category 2, Zone 1 or Category 3, Zone 2.
22 | 180R9379 | IOM PAH 2-12.5 pumps - v06
] values are calculated.
PA, 1m
© Danfoss | DCS (im) | 2020.11
Data sheet PAH 2/4/6.3, PAH 10/12.5, PAH 20/25/32 and PAH 50/63/70/80/100 pumps
l/min
1100
1300
1500
1700
1800
12
10
8
6
4
2
0 rpm
PAH 2.0
PAH 4.0
PAH 6.3
l/min
700
900
1100
1300
1500
1700
1800
gpm
5. Flow
The ow (Q e) at various pressure (p calculated with the following equation:
Q e = Q
(th)
– [(Q
– Q (p
(th)
)) x (p / p
max
) can be
max
)]
max
The theoretical ow can be calculated with the following equation:
V x n Q
=
(th)
1000
At zero pressure the true ow equals the theoretical ow Q
Q
: Theoretical ow (l/min / gpm)
(th)
Q (p
): Flows at max. pressure (l/min and
max
gpm), see 4.1-4.4
p
: Max pressure (barg / psig)
max
p: Pressure (barg / psig)
.
(th)
V: Displacement (cm3 / rev.) n: Motor speed (rpm)
5.1 PAH 2-6.3 typical ow curves at max pressure
12
PAH 6.3
10
8
6
4
2
PAH 4.0
PAH 2.0
0 rpm
700
3
2.5
2
1.5
1
0.5
0 rpm
700
900
PAH 6.3
PAH 4.0
PAH 2.0
900
© Danfoss | DCS (im) | 2020.11
180R9379 | IOM PAH 2-12.5 pumps - v06 |
23
Data sheet PAH 2/4/6.3, PAH 10/12.5, PAH 20/25/32 and PAH 50/63/70/80/100 pumps
l/min
1100
1300
1500
1700
1800
PAH 12.5
19
23
21
17
15
13
11
9
7
5
3
l/min
gpm
1100
900
1300
1500
1700
1800
700
rpm
PAH 12.5
PAH 10
PAH 12.5
5.2 PAH 10-12.5 typical ow curves at max pressure
23
21
19
17
15
13
11
9
7
5
3
700
6
5
4
3
2
900
PAH 10
rpm
PAH 10
24 | 180R9379 | IOM PAH 2-12.5 pumps - v06
1
0
700
900
rpm
© Danfoss | DCS (im) | 2020.11
Loading...
+ 56 hidden pages