Danfoss L66 User Manual

L66
L66
VI.JD.T2.02
2006.12
VI.JD.T2.02
2006.12
www.danfoss.com
User's Guide
Installer's Guide
www.danfoss.com
ECL Comfort
ECL Comfort
User's Guide
*087R8172*
*VIJDT202*
*087R8172* *VIJDT202*
(
)
Mixing and DHW controller
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
If the system you are about to install differs from the shown diagram of a standard heating system, feel free to sketch an outline for comparison. Adaptation of systems, see section 10.
Circuit
indicator
Circuit
selector
Shift
button
Adjust-
ment
Controller
mode
List of components:
ECL Comfort 301
S1 Outdoor temperature sensor
S3 Flow temperature sensor
S4 Return temperature sensor, circuit I
S5 DHW flow temperature sensor, circuit II
S6 DHW return temperature sensor, circuit II
P1-1 Circulation pump 1, heating, circuit I
P2-1 Circulation pump 2, heating, circuit I
P1-2 ECA 73 / 80 / 86, circulation pump 1, DHW, circuit II
P2-2 ECA 73 / 80 / 86, circulation pump 2, DHW, circuit II
M1 Motorized control valve, circuit I
M2 Motorized control valve, circuit II
This guide is associated with ECL Card 087B4875
Installer:
By:
Date:
Controller mode
Manual operation (used only at maintenance
and service)
Scheduled operation
Constant comfort temperature
Constant setback temperature
Standby mode
Arrow buttons. Switch between the lines of the ECL
Card.
Shift button. Switches between temperatures,
changeover points etc.
Adjust temperatures and values etc.
Circuit selector for switching between the circuits.
Safety Note
To avoid injury of persons and damages to the device, it is absolutely
necessary to read and observe these instructions carefully.
Necessary assembly, start-up, and maintenance work must be performed by
qualified and authorized personnel only.
Display indications, controlled units, L66
1
1
ON
2
ON
2
3
ON
A B C D E
A: P1-1 Blank = OFF ON = ON
B: M1 = Opens = Closes
C: P2-1 Blank = OFF ON = ON
D: M2 = Opens = Closes
E: R3 Blank = OFF ON = ON
Table of Contents
Sections in the Installer’s Guide
The documentation for the ECL Comfort controller is composed of numbered sections. Only sections relevant to your ECL Comfort controller are included here.
Before you start
Installation
10 Identifying the system type 11 Mounting the ECL Comfort controller 12 Electrical connections 230 V a.c. 14 Connecting and placing the temperature sensors 15 Inserting the ECL Card
Basic Set-up
16 Adjusting the ECL Card settings 17 Setting the time and date - line A 18 Monitoring temperatures and system units - line B 19 Manual control - line B 20 Setting the heat curve - line C 21 Heating cut-out - line 1 22 Flow temperature limits - line 2 23 Room temperature influence - line 3 26 Control parameters - lines 4-7
Control & Overviews
29 Check list 30 ECL Card settings 31 Service parameters
Extended Service
32 Adjusting the service parameters
Miscellaneous
34 Copying with the ECL Card
User's Guide (turn the guide over for sections 1-7)
1 Choose your favorite display 2 Select circuit mode 3 Set your room and DHW temperature 4 Set your personal schedule 5 Advantages of the ECL Card 6 Hot points 7 Definitions
VI.JD.T2.02
Card L66
2006.12
Sketch your application
The ECL Comfort controller series is designed for a wide range of heating, domestic hot-water (DHW) and cooling systems with different configurations and capacities. If your system differs from the diagrams shown in section 10, you may want to make a sketch of the system about to be installed. This makes it easier to use the Installer’s Guide, which will guide you step-by-step from installation to final adjustments before the end-user takes over.
The controller is pre-programmed with factory settings that are shown in the relevant sections of this guide.
However, you might come across some settings that are not listed in this instruc tion. These settings could be related either to recent updates or the use of optional modules (which are described in the instructions in question).
How to use this guide
This guide is divided into two parts:
• User’s Guide: Yellow sections 1-7
• Installer's Guide: Grey sections 10 and onwards
The application L66 is very flexible. These are the basic principles:
Both circuits can control two pumps.
Heating : Typically, the flow temperature is adjusted according to your requirements. The flow temperature sensor (S3) is the most important sensor. The desired flow temperature at S3 is calculated in the ECL controller, based on the outdoor temperature (S1). The lower the outdoor temperature, the higher the desired flow temperature. The motorized control valve (M1) is opened gradually when the flow temperature is lower than the desired flow temperature and vice versa. The return temperature (S4) to the district heating supply should not be too high. If so, the desired flow temperature can be adjusted (typically to a lower value), thus resulting in a gradual closing of the motorized control valve. In boiler-based heating supply the return temperature should not be too low (same adjustment procedure as above). If the measured room temperature does not equal the desired room temperature, the desired flow temperature can be adjusted. Circulation pumps are ON when the desired flow temperature is higher than 20 °C or the outdoor temperature is lower than 2 °C.
DHW: If the measured DHW temperature (S5) is lower than the desired DHW temperature, the motorized control valve (M2) is opened gradually and vice versa. If the desired DHW temperature cannot be reached, the heating circuit can be closed gradually.
Before you start
Installation
Installation
The ECL Comfort controller is a universal controller that can be used for various systems. Based on the shown standard systems, it is possible to configure additional systems.
In this section you find the most frequently used systems. If your system is not quite as shown below, find the diagram which has the best resemblance with your system and make your own combinations.
The functions can only be realized with ECL Comfort 301 and as of controller version 2.00.
10.1 Indirectly connected heating system and DHW circuit
System diagrams in this instruction are principal drawings and do not contain all components which are necessary in your systems.
Identifying the system type
10a
10.2 Directly connected heating system and indirectly connected DHW circuit
10b
Installation
Installation
For easy access, you should mount the ECL Comfort controller near the system. Select one of the three following methods:
• Mounting on a wall
• Mounting on a DIN rail
• Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting on a wall
Socket for mounting on wall: Order code No. 087B1149. Mount the terminal box on a wall with a smooth surface. Establish the electrical connections and position the controller in the box. Secure the controller with the fixing screw.
Mounting on a DIN rail
Mounting kit: Order code No. 087B1145. A mounting kit is necessary to mount the box with the controller on a DIN rail.
Mounting in a panel
Connector set: Order code No. 087B1148. The panel plate thickness must not exceed 3 mm. Prepare a cut-out with the dimensions 93 x 139 mm. Pull off the right side of the lid by means of a screwdriver. Insert the controller into the panel cut-out and fix it with the two locks which are placed diagonally in two corners of the controller.
Mounting the ECL Comfort controller
11a
11b
Installation
Installation
12a
230 V a.c. connections - without safety thermostat
230 V a.c. connections - with safety thermostat
This circuit diagram is only valid if Danfoss actuators are used
The relays are to be connected as in the drawing without safety thermostat.
Electrical connections ­230 V a.c. - in general
Terminal Description Max. load
1 L Supply voltage 230 V a.c. 2 N Supply voltage 230 V a.c. 3 M1 Actuator - open, circuit I 0.2 A / 230 V a.c.
4 M1
Actuator - close, circuit I alt. thermo actuator
0.2 A / 230 V a.c.
5
230 V a.c. supply voltage for M1,
circuit I 6 M2 Actuator - open, circuit II 0.2 A / 230 V a.c. 7 M2 Actuator - close, circuit II 0.2 A / 230 V a.c.
8
230 V a.c. supply voltage for M2,
circuit II
9 P1-1
Circulation pump I for heating,
circuit I
4 (2) A / 230 V a.c.
10
230 V a.c. supply for pump relay
R1
11 P2-1
Circulation pump II for heating,
circuit I
4 (2) A / 230 V a.c.
12
230 V a.c. supply for pump relay
R2
13 R3 Alarm relay 4 (2) A / 230 V a.c.
14
230 V a.c. supply for alarm relay
R3
25 P1-2
Circulation pump I for DHW,
circuit II
4 (2) A / 230 V a.c.
26
230 V a.c. supply for pump relay
R4
28 P2-2
Circulation pump II for DHW,
circuit II
4 (2) A / 230 V a.c.
29
230 V a.c. supply for pump relay
R5
Wire cross section: 0.75 - 1.5 mm
2
Electrical connections
Max. 2 x 1.5 mm2 wires can be inserted into each screw terminal.
Incorrect connection can damage the TRIAC outputs. Max. load (terminals 3, 4, (6 and 7)) 0.2 A / 230 V a.c.!
12b
Installation
Installation
Connecting the temperature sensors and the bus
Terminal Description Type (recomm.)
15 and 16 System device bus*,
connections for room panel** / remote control** / (relay module)
ECA 60 / 62 ECA 61 / 63
17 and 16 S1 Outdoor temperature
sensor
ESMT
18 and 16 S2
R
alarm
19 and 16 S3 Flow temperature sensor,
circuit I
ESM-11 / ESMC / ESMU
20 and 16 S4 Return temperature sensor,
circuit I
ESM-11 / ESMC / ESMU
21 and 16 S5 DHW flow temperature
sensor, circuit II
ESM-11 / ESMC / ESMU
22 and 16 S6 DHW return temperature
sensor, circuit II
ESM-11 / ESMC / ESMU
* The system device bus / room panel / rem ote control is only ac tive when the outdoor temperature sensor is conne cted. ** Either room panel or remote control
Establish the jumper from 16 to common terminal.
Wire cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 125 m (all sensors incl. system device
bus)
Cable lengths of more than 125 m may cause noise sensibility (EMC).
Terminals 16 and 18
External circuit for alarm contact: Rx and Ry are external alarm relay contacts, i.e. pressure controlled switches.. The contacts should be gold-plated. The resistance in the contacts must be lower than 10 ohm (operating conditions 5 V and 1.7 mA).
Connecting and placing the temperature sensors
14a
Terminal 16 Terminal 18
-> Alarm input circuit I
-> Alarm input circuit II
It is important that the sensors are mounted in the correct position in your system.
The temperature sensor mentioned below are sensors used for the ECL Comfort 200 and 300 series which not all will be needed for your application!
Outdoor temperature sensor (ESMT)
The outdoor sensor should be mounted on that side of the building where it is less likely to be exposed to direct sunshine. It should not be placed close to doors, windows or air outlets.
Flow temperature sensor (ESMU, ESM-11 or ESMC)
Place the sensor max. 15 cm from the mixing point. In systems with heat exchanger, Danfoss recommends that the ESMU-type to be inserted into the exchanger flow outlet.
Make sure that the surface of the pipe is clean and even where the sensor is mounted.
Return temperature sensor (ESMU, ESM-11 or ESMC)
The return sensor should always be placed in / on a pipe with return water flow.
Room temperature sensor (ESM-10, ECA 60 / 62 room panel or ECA 61 / 63 remote control)
Place the room sensor in the room where the temperature is to be controlled. Do not place it on outside walls or close to radiators, windows or doors.
DHW temperature sensor (ESMU or ESMB-12)
Place the DHW temperature sensor according to the manufacturer’s specification.
Boiler temperature sensor (ESMU, ESM-11 or ESMC)
Place the sensor according to the boiler manufacturer’s specification.
Flow / air duct temperature sensor (ESM-11, ESMB-12, ESMC or ESMU types)
Place the sensor so that it measures a representative temperature.
Slab temperature sensor (ESMB-12)
Place the sensor in the slab.
Valid for ESM-11: Do not move the sensor after it has been fastened in order to avoid damage to the sensor element.
14b
Installation
Installation
Comfor t Setbac k
Red
Brown
Green S1 .. . S6 (C14 = S5 only)
14c
Connecting the room panel / remote control
The ECA 60 / 61 / 62 / 63 is activated by the setting in line 10 (section 32).
The ECA 60 / 61 / 62 / 63 is powered by the system device bus which means that the bus must be active. The bus is activated by setting the controller address to 15 (section 32, line 199).
Override
For an active override, you have to choose the mode “scheduled operation”! Input S1 ... S6 (ECL Card C14 only uses S5) can be used for override purposes (section 32, line 141).
Connection example without ECA 9010
If the override switch has goldplated contacts, you can choose one of the following solutions or a combination of both:
(C14 = 21 only) (C14 = 21 only)
Closed switch: Closed switch: Comfort temperature Setback temperature
Open switch: Open switch: Scheduled operation Scheduled op eration
Connection example with ECA 9010
The ECA 9010 module is powered by the system device bus, which means that the bus must be active. The bus is activated by setting the controller address to 15 (line 199). To avoid influence from contact resistance, the use of ECA 9010 is recommended.
Comfor t Setbac k
Red
Brown
Green S1 .. . S6 (C14 = S5 only)
Installation
Installation
Understanding the ECL Card
The ECL Card contains factory settings for a standard system. If the actual system differs from the standard system, the controller must be adjusted accordingly. After the adjustment, the new settings should be stored on the ECL Card.
For ECL Card copying and daily use including adjustment of temperatures and schedules, insert the ECL Card with the yellow side facing you.
For system set-up adjustments, the grey side of the ECL Card - the installer’s side - must be facing you.
As a main rule, the ECL Card should always remain in the controller during service, maintenance and setting.
If the card is removed or left in the controller with the grey side facing you, please note that:
• After approx. 25 min.:
- The controller cannot be operated.
- The controller reverts to display C (section 1).
• The ECL Card must not be exposed to direct heat or sunshine.
If several controllers are installed in the system you can write a title on the ECL Card with a permanent ink pen.
Do not remove the ECL Card while copying. The data on the ECL Card can be damaged!
When you store your personal settings on your ECL Card, the factory settings will be overridden.
15b
How to insert your ECL Card the first time
After the power has been switched on, open the lid on the front side of the controller.
Place the ECL Card with the yellow side facing you. This enables the controller to read the ECL Card data. The controller immediately starts to copy the application type and factory settings from the ECL Card. After copying, the display will show you the application type. After approx. 10 sec. the display will change to display line C.
Display example:
Software
version, ECL
Card
Line
Circuit
Time
Outdoor
temp.
C
C 99
Y
0
P
C 73
05 109
8
0 3 6 9 12 15 18 21 24
1
023
5
C
3
Application t ype
Software version, controller
Desired room temp.
The controller is now ready to be set to control your system.
If the display keeps showing CPY, see section 34b.
Inserting the ECL Card
15a
The grey side of the ECL Card
Basic set-up
The grey
side of the
ECL Card
Basic set-up
General principles
When the controller is connected and operating you can check and adjust all or some of the basic settings. Turn the ECL Card so that the grey side is facing you (see the example below).
Use the arrow buttons to move from line to line of the ECL Card, for example line 2:
Circuit
Line
Setting
to be
adjusted
1
1
ON
2
ON
09
2
04
2
3
ON
Value in range indicator
Use the plus / minus buttons to adjust the settings.
In some displays more than one setting or value can be adjusted. Use the shift button to switch between the options.
The circuit selector shifts between circuit I and II. You can adjust all settings and service parameters individually.
Update of the ECL Card after maintenance and service
All new settings can be stored on the ECL Card. For details about copying, see section 34.
Adjusting the ECL Card settings
16
Actual time
Year
07
01
2 220
5
A
3
1
Month, day
Use the shift button to switch between minutes, hours, years, months and days.
Set the correct time and date.
In case of a power break, which lasts longer than 12 hours, the time and the date have to be set again. All other settings are stored as programmed.
Use the yellow side of the card to change the schedules.
See User’s Guide, section 4.
Setting the time and date ­line A
17
The grey side of the ECL Card
Basic set-up
The grey
side of the
ECL Card
Basic set-up
Controlled units
Flow
temp.
(S3)
5 036
B
2
ON
1
1
ON
3
ON
2
Return temp. (S4)
Push and hold the shift button to see:
- the calculated flow temperature
- the desired return temperature limitation.
This display can also show the actual and desired flow and return temperatures for circuit II.
The activity of the motorized control valve is shown as arrows below the valve symbol. When the circulation pump is operating, it is indicated as ON below the pump symbol.
If a sensor is not mounted or is disconnected, the display will indicate it as “- -”.
If the sensor is short-circuited, the display will indicate it as “- - -“.
If you are in doubt, remove the controller and check the ohmic value between the relevant terminals.
Relationship between temperature and ohmic value
-50
800
900
1000
1100
1200
1300
1400
1500
1600
-25 0 25 50 7
5 100 125 150
°C
805 845
883
922
961 1000 1039 1078 1117 1155 1194 1232 1271 1309 1347 1385 1423 1462 1501 1539 1578
°C
-50
-40
-30
-20
-10 0
10 20 30 40 50 60 70 80
90 100 110 120 130 140 150
Monitoring temperatures and system units - line B
18
Shift to manual mode.
Controlled units
5 036
B
2
ON
1
1
ON
3
2
Controller mode
Choose the unit you want to control. The selected unit symbol will blink.
Controlled units are switched OFF or ON when the relevant button is pushed.
The motorized actuator (gear motor)
closes or opens the controlled unit as long as the relevant button is pushed. If pushed for more than 3 seconds, the actuator continues to close or open the valve.
The thermo actuator
activates the valve as long as the button is pushed. If pushed for more than 3 seconds, the actuator continues to open the valve.
Check the activation direction of the actuator either by looking at it or by feeling whether the temperature of the actual pipe changes as expected.
This operation applies to both circuits, if available.
During manual operation, all control functions are deactivated.
Manual control ­line B
19
Loading...
+ 26 hidden pages