Danfoss KVS 15, KVS 42 Data sheet

Data sheet
Electric Regulating Valve Type KVS
KVS is a series of electronic suction modulating valves for AC transport and refrigeration applications.
Accurate temperature or pressure control is obtained by modulating the refrigerant flow in the evaporator with a current or voltage driver.
With an EKC 368 controller (current driver) and an AKS sensor placed in the media to be con­trolled, an accuracy better than ± 0.5K can be obtained.
The balanced design provides bi-flow operation as well as solenoid shut-off function in both flow directions at MOPD 33 bar (478 psig).
Features • Biflow.
• High resolution for precise control.
• Wide range for all common refrigerants R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R438A, R448A, R449A, R450A, R452A, R507, R513A, R410A, R1234ze and other refrigerants
• Balanced port design (KVS 42).
• Solenoid tight shut-off.
• Low power consumption.
• Corrosion resistant design external as well as internal.
• Cable and connector assemblies as accessories.
• For manual operation and service of KVS valves an AST-g service driver is available. For further information please contact Danfoss (Commercial Refrigeration & Air Conditioning Controls).
© Danfoss | DCS (sw) | 2017.10
DKRCC.PD.VC1.C7.02 | 1
.
Data sheet | Electric regulating valve type KVS 15 – KVS 42
Technical data
Electrical data
Parameter KVS 15 KVS 42
R22, R134a, R404A, R407A, R407C,
Compatible refrigerants
Refrigerant oil All mineral and ester oils All mineral and ester oils CE marking No Yes MOPD 33 bar / 478.6 psig 33 bar / 478 psig Max. working pressure 45.5 bar / 660 psig 34 bar / 493 psig Inlet fluid temperature -40 to +65 °C / -40 to +149 °F -40 to +65 °C / -40 to +149 °F Ambient temperature -40 to +60 °C / -40 to +140 °F -40 to +60 °C / -40 to +140 °F Total stroke 13 mm / 0.5 inch 17.2 mm / 0.68 inch Motor enclosure IP 67 IP 67
Material of Construction
Parameter KVS 15 and KVS 42 Stepper motor type Bi-polar - permanent magnet Step mode 2 phase full step Phase resistance 52 Ω ±10% Phase inductance 85 mH
Holding current
Step angle
Nominal voltage Constant voltage drive: 12 V DC -4% – 15%, 150 steps/sec. Phase current (Using chopper drive) 100 mA RMS -4% +15%, Max. total power Voltage / current drive: 5.5 / 1.3 W (UL: NEC class 2)
Step rate
Total steps
Full travel time
Lifting height
Reference position Overdriving against the full close position Electrical connection M12 connector
R407F, R422B, R422D, R438A, R448A, R449A, R450A, R452A, R507, R513A, R410A, R1234ze and other refrigerants
Body and AST Encloser: Brass Connector: Copper
Constant voltage drive: Depends on application. Chopper drive: full current allowed (100% duty cycle)
7.5° (motor),
0.9° (lead screw), Gearing ration 8.5:1. (38/13)2:1
Constant voltage drive: 150 steps/sec. Chopper current drive: 0 – 300 steps/sec. 300 recommended
KVS 15: 2625 [+160 / -0] steps KVS 42: 3810 [+160 / -0] steps
KVS 15: 17 / 8.5 sec. (voltage / current) KVS 42: 25.4 / 12.7 sec. (voltage / current)
KVS 15: 13 mm / 0.5 inch KVS 42: 17.2 mm / 0.68 in
R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R438A, R448A, R449A, R450A, R452A, R507, R513A, R410A, R1234ze and other refrigerants
Body and AST Encloser: Brass Connector: Copper
Flow curves
Compatible controller / driver EKC 368 / EKD 316 or EKD 316C
KVS 15 Capacity Curve
.
.
KVS 42 Capacity Curve
© Danfoss | DCS (sw) | 1017.10
DKRCC.PD.VC1.C7.02 | 2
Data sheet | Electric regulating valve type KVS 15 – KVS 42
Ordering
Accessories: M12 Female Connector Cable
Spare parts
KVS valves in single pack
Rated capacity
Type
R22 R134a R404A/R507 ODF Code no.
kW TR kW TR kW TR mm in.
KVS 15 5.15 1.31 3.78 0.94 4.58 1.07
KVS 42 40.4 11 . 4 29.3 8.3 35.3 10.0
1
) Rated capacity is the valve capacity at evaporating temperature te = –10°C (14°F), condensing temperature tc = +25°C (77°F)
and pressure drop across valve p = 0.2 bar (2.9 psig).
1)
Connections
single
pack
16 ⁄ 034G4252 22 ⁄ 034G4253 22 ⁄ 034G2858 28 1⁄ 034G2850 35 1⁄ 034G2851
- 1⁄ 034G2852
Actuator with integrated M12 connection
Items Description Quantity
[pcs]
34G179.10 Danfoss
Actuator with integrated M12 with Ceramic bearing (incl. metal gasket) for KVS 15
Code no.
1 034G2088
34G179.10 Danfoss
Actuator with integrated M12 with ceramic bearing
1 034G2087
(incl. metal gasket) for KVS 42
Metal Gasket 1 034G2344
© Danfoss | DCS (sw) | 1017.10
DKRCC.PD.VC1.C7.02 | 3
34G211.10
Pr C
Data sheet | Electric regulating valve type KVS 15 – KVS 42
Accessories: M12 angle cable
M12 angle female connector is intended for use with a standard M12 male connector, available on stepper motor valves.
This cable is designed to offer high flexibility and small outer diameters with tensile strength. The angle way M12 cable consist of paired, twisted wires, which decreases mutual influence between signals transmitted along the cable and reduces influence of external sources of interference. The cables thus provides a higher degree of protection against lost steps compared to other cables.
Approvals
Specification
Ordering
Identification
RoHS
Jacket PVC - black
Cable outer sheath Oil - resistant
Water proof rating IP 67
Operating temperature range -40 – +80 °C
Wire type Twisted pair, cross section 20 AWG / 0.5 mm2
Cable outer diameter 7.0 mm
Minimum bending radius 10 x cable diameter
Cable combustibility / test Flame retardant / VW-1 / CSA FT - 1
M12 standard EN 61076-2-101
Reference standard UL style 2464 and DIN VDE 0812
LVD directive 73/23/EEC and 93/68/EEC
Cable Cable length (L) Insulation Packing format Code no.
PVC - black
2 m / 6.6 ft SR-PVC Single pack 034G7073
8 m / 26.2 ft SR-PVC Single pack 034G7074
oduct type
ode no
Connections
Dimensions
A2 black
A1 white
B1 red
B2 green
34G210.10
8 meters / 26.2 feet
Manufacturing date
Meters / Feets
Country
34G209.10
Ø 63 mm / 1/4 inch
35 mm / 1.4 inch2 meters / 6.6 feet 49 mm / 1.9 inch
© Danfoss | DCS (sw) | 1017.10
DKRCC.PD.VC1.C7.02 | 4
Danfoss
34G212.10
A
B
Data sheet | Electric regulating valve type KVS 15 – KVS 42
Design
Note:
Flow direction from A to B refers the normal flow.
KVS 42
1. M12 Connector
2. Glass seal
3. AST motor housing
4. Stepper motor
5. Bearing
6. Spindle
7. Top nut
8. Valve piston
9. Valve seat
10. Valve cone
Danfoss
34G45.12.10
A
B
KVS 15
1. M12 connection
2. Glass seal
3. AST motor housing
4. Stepper motor
5. Bearing
6. Spindle
7. Cone and lead nut
8. Valve seat
Electrical wiring
Note: Electrical check of stepper motor and wiring: coil I = 52 ohm coil II = 52 ohm
© Danfoss | DCS (sw) | 1017.10
DKRCC.PD.VC1.C7.02 | 5
Data sheet | Electric regulating valve type KVS 15 – KVS 42
Stepper motor switch sequence
Valve application
Coil I Coil II
Red Green White Black
CLOSING
STEP
1 + - + ­2 + - - + 3 - + - + 4 - + + ­1 + - + -
If the controller driving the KVS valve is from another manufacturer than Danfoss or a custom design, the following points must be considered in order to overcome potential step loss.
a. To ensure total closing of the valve, the con­troller should have a function to overdrive the valve in the closing direction. It is recommended to overdrive ten percent of the full step range at appropriate intervals.
OPENING
b. The amount of lost steps may increase as a function of the amount of changes of the open­ing degree. Such designed controller should be able to compensate the lost steps after a defined number of changes in opening degree.
Warning: At power failure the KVS valve will remain in the opening position it has at the moment of power failure, unless a safety device in the form of a bat­tery backup is installed.
Evaporator
Valve operation The KVS valves operate modulating by electroni-
cally controlled activation of the AST stepper motor. The motor is a type 2-phase bipolar, which stays in position, unless power pulses from a driver initiate the two discrete sets of motor stator windings for rotation in either directions.
The direction of the rotation of the spindle depends on the phase relationship of the power pulses. This is decisive for the travel of the piston.
The motor is operating the spindle, whose rotat­ing movements are transformed into linear motion by the transmission in the cage assembly. The AST motor housing has an integrated M12 connector.
The KVS 42 valves have a pressure slide port respectively exponential cone, combining the best performance qualities at part load condi­tions as well as providing a zero-resistance at maximum capacity. The piston design is fully power balanced, giving identical bi-flow performance capabilities and nearby identical maximum capacities.
Closing the valve by overdriving, ensures that the reference number in steps is always correct.
Operating the KVS series requires a controller with either 12 V dc voltage drive (5.5 W) or using chopper drive (100 mA RMS).
Danfoss EKC 368 in an example of a qualified controller.
Note:
Cable length between driver and actuator exceeding 10 m (30 feet) can set off self-induc­tion with reduction in the transmitted power and irregularity in the sequences as consequence.
This may result in loss of steps now and again or more permanent inadequate power supply to the step motor.
The driver circuit as well as the cable specifica­tions are part of this interference.
Please contact Danfoss for further information and possible countermeasures.
© Danfoss | DCS (sw) | 1017.10
DKRCC.PD.VC1.C7.02 | 6
Data sheet | Electric regulating valve type KVS 15 – KVS 42
Coolselector2®
For easy and precise selection of valve, use Danfoss’ CoolSelector2® software. You can find the KVS valves on the group, “Control and regulating valves”. You can download it from http://coolselector.danfoss.com
Valve sizing For optimum performance, it is important to take
into consideration all system conditions and requirements. Selection is also dependent on an acceptable pressure drop across the valve. The following information will be needed when sizing a KVS valve:
Valve selection
Example
In valve selection it may be necessary to apply a correction factor to the actual evaporator capaity. This correction is required when system conditions are different than table conditions. Selection also depends on having an acceptable pressure drop across the valve. The following example illustrates correct sizing.
Step 1
Determine the correction factor for liquid tem­perature t
Correction factors for liquid temperature t
tl °C 10 15 20 25 30 35 40 45 50 R134 a 0.88 0.92 0.96 1.0 1.05 1.10 1.16 1.23 1.31 R22 0.90 0.93 0.96 1.0 1.05 1.10 1.13 1.18 1.24 R404A / R507 0.84 0.89 0.94 1.0 1.07 1.16 1.26 1.40 1.57 R407C 0.88 0.91 0.95 1.0 1.05 1.11 1.18 1.26 1.35
ahead of expansion valve.
l
l
• Refrigerant
• Evaporator capacity Qe in kW or TR
• Evaporating temperature te in °C or °F
• Liquid temperature ahead of expansion valve tl in °C or °F
• Max. acceptable pressure drop in the KVS valve in bar or psig
• Connection size
• Refrigerant: R 404A
• Evaporator capacity: Qe = 20 kW / 5.7 TR
• Evaporating temperature: te = –10°C ~ 3.4 bar / 14°F ~ 49.3 psig
• Liquid temperature ahead of expansion valve: t
= 25°C / 77°F
l
• Max. pressure drop in the valve: p = 0.2 bar / 2.9 psig
• Connection type: Solder
• Connection size: 11/8 in.
From the correction factors table (see below) a liquid temperature of 25°C / 100°F, R404A corresponds to a factor of 1.0.
Step 2 Corrected evaporator capacity is
Qe = 20 × 1.0 = 20 kW / 5.7 × 1.0 = 5.7 TR
Step 3 Now select the appropriate capacity table,
R404A, and choose the column for an evaporating temperature of te = –10°C / 14°F.
Using the corrected evaporator capacity, select a valve that provides an equivalent or greater capacity at an acceptable pressure drop across the valve of 0.2 bar / 2.9 psig.
Rated Capacity (kW) SI units
t
e
Pressure drop ∆p [bar] Pressure drop ∆p [bar]
[°C] 0.05 0.1 0.2 0.3 0.5 0.7 0.05 0.1 0.2 0.3 0.5 0.7
10 3.30 4.65 6.52 7.93 10.1 11 .7 25.5 36.0 50.5 61.4 78.1 91.0
0 2.71 3.81 5.34 6.47 8 .18 9.46 21.0 29.6 41.4 50 .1 63.7 73.3
-10 2.20 3.09 4.30 5.19 6.49 7.4 3 17.0 23.9 33.3 40.2 50.3 57. 5
-20 1.75 2.45 3.39 4.06 5.00 5. 61 13. 6 19.0 26.3 31. 5 38.7 43.5
-30 1.37 1.91 2.60 3.08 3.67 3.97 10.6 14.8 20.2 23.9 28.5 30.8
-40 1.04 1.44 1.92 2.22 2.49 2.50 8.08 11.1 14.9 17. 2 19.3 19. 4
Step 4
R404A
KVS 42, 11/8 in.:
Single pack code no. 034G2850
KVS 42 delivers 33.32 kW / 9.5 TR at a 0.2 bar /
2.9 psig) pressure drop across the valve.
Based on the required connection size of 11/8 in, the KVS 42 is the proper selection for this example.
Rated capacity [kW]
KVS 15 KVS 42
© Danfoss | DCS (sw) | 1017.10
DKRCC.PD.VC1.C7.02 | 7
Data sheet | Electric regulating valve type KVS 15 – KVS 42
Correction factor table
tl °C 10 15 20 25 30 35 40 45 50 R134 a 0.88 0.92 0.96 1. 0 1.05 1.10 1.16 1. 23 1. 31 R22 0.90 0.93 0.96 1.0 1.05 1.10 1.13 1.18 1. 24 R404A / R507 0.84 0.89 0.94 1.0 1.07 1.16 1.26 1.40 1.57 R407C 0.88 0.91 0.95 1.0 1.0 5 1.11 1.18 1.26 1.35
SI units
Capacities
Rated Capacity (kW)
t
e
[°C]
0.05 0.1 0.2 0.3 0.5 0.7 0.05 0.1 0.2 0.3 0.5 0.7
10 2.94 4.12 5.73 6.91 8.62 9.84 22.75 31.92 44.43 53.54 66.82 76.28
R134a
R404A
R407C
R22
* The valves in the capacity table refer to the evaporator capacity and based on liquid temperature
* The conditions printed are the most common for the different refrigerants.
* The pressure drop across the valve is assumed to be the difference between evaporation pressure and suction pressure.
1
) The capacity of vapour flow will not increase for pressure drops above the critical pressure drop.
0 2.38 3.33 4.60 5.50 6.75 7.56 18.46 25.81 35.67 42.65 52.32 58.56
-10 1.90 2.64 3.61 4.26 5.07 5.46 14.72 20.47 27.96 33.00 39.27 42.29
-20 1.48 2.05 2.74 3.15 3.52 3.551) 11.50 15.85 21.20 24.42 27.30 27.47 10 3.30 4.65 6.52 7.93 10.08 11.74 25.54 35.99 50.53 61.43 78.11 91.00
0 2.71 3.81 5.34 6.47 8.18 9.46 21.01 29.56 41.37 50.14 63.35 73.30
-10 2.20 3.09 4.30 5.19 6.49 7.43 17.03 23.91 33.32 40.20 50.28 57.54
-20 1.75 2.45 3.39 4.06 5.00 5.61 13.58 19.00 26.29 31.47 38.72 43.47
-30 1.37 1.91 2.60 3.08 3.67 3.97 10.61 14.76 20.18 23.85 28.47 30.78
-40 1.04 1.44 1.92 2.22 2.49 2.501) 10 3.58 5.04 7.06 8.56 10.84 12.57 27.73 39.04 54.69 66.34 83.98 97.37
0 2.94 4.14 5.77 6.97 8.74 10.03 22.81 32.05 44.71 54.01 67.74 77.75
-10 2.39 3.34 4.63 5.55 6.86 7.74 18.48 25.88 35.87 43.03 53.14 59.94
-20 1.90 2.64 3.62 4.29 5.16 5.62 14.70 20.48 28.07 33.26 39.96 43.56 10 3.74 5.26 7.38 8.96 11.36 13.19 28.95 40.76 57.16 69.40 88.01 102.22
0 3.14 4.41 6.16 7.45 9.38 10.80 24.30 34.16 47.73 57.74 72.66 83.70
-10 2.60 3.64 5.06 6.09 7.57 8.60 20.12 28.21 39.21 47.17 58.63 66.60
-20 2.12 2.96 4.07 4.85 5.90 6.54 16.40 22.90 31.55 37.59 45.75 50.67
-30 1.69 2.35 3.18 3.73 4.36 4.57 13.10 18.18 24.68 28.92 33.79 35.44
-40 1.32 1.81 2.39 2.71 2.891) x1) 10.23 14.02 18.52 20.99 22.371) x1)
tl=30°C, superheat= sub cooling = 0 K.
Other conditions can be calculated with Danfoss calculation software CoolSelector®
KVS15 KVS 42
Pressure drop ∆p [bar] Pressure drop ∆p [bar]
8.08 11.14 14.91 17.20 19.26 19.391)
1)
© Danfoss | DCS (sw) | 1017.10
DKRCC.PD.VC1.C7.02 | 8
Data sheet | Electric regulating valve type KVS 15 – KVS 42
Correction factor table
tl °F 50 60 70 80 90 100 110 120 R134 a 0.79 0.82 0.86 0.90 0.95 1. 0 1.06 1.13 R22 0.82 0.85 0.88 0.92 0.96 1.0 1.05 1.10 R404A / R507 0.71 0.75 0.80 0.85 0.92 1. 0 1.10 1.24 R407C 0.78 0.81 0.85 0.89 0.94 1.0 1. 07 1.15
US units
Capacities
Rated Capacity (TR)
(TR) = ton of refrigerants
t
e
[°F]
0.7 1.5 3 5 7 10 0.7 1.5 3 5 7 10
50 0.86 1.25 1.73 2.19 2.53 2.91 6.65 9.66 13.44 16.96 19.60 22.58
R134a
R404A
R407C
* The valves in the capacity table refer to the evaporator capacity and based on liquid temperature
* The conditions printed are the most common for the different refrigerants.
* The pressure drop across the valve is assumed to be the difference between evaporation pressure and suction pressure.
1
) The capacity of vapour flow will not increase for pressure drops above the critical pressure drop.
30 0.68 0.98 1.36 1.69 1.93 2.17 5.28 7.63 10.53 13.12 14.96 16.83 10 0.53 0.76 1.03 1.26 1.40 1.49 4.10 5.88 7.99 9.74 10.82 11.58
-5 0.43 0.61 0.82 0.96 1.03 1.031) 3.34 4.74 6.32 7.46 7.95 8.011)
50 0.98 1.43 2.00 2.56 3.00 3.53 7.59 11.06 15.53 19.84 23.23 27.33 30 0.79 1.15 1.61 2.04 2.38 2.78 6.12 8.90 12.45 15.83 18.45 21.52 10 0.63 0.91 1.26 1.59 1.84 2.12 4.85 7.03 9.78 12.34 14.26 16.41
-5 0.52 0.75 1.04 1.29 1.48 1.67 4.01 5.81 8.02 10.03 11.47 12.97
-20 0.42 0.61 0.83 1.03 1.15 1.26 3.28 4.72 6.46 7.95 8.94 9.80
-40 0.32 0.45 0.60 0.71 0.76 0.771) 2.44 3.47 4.64 5.50 5.89 5.951)
50 1.05 1.53 2.14 2.72 3.18 3.72 8.12 11.82 16.55 21.09 24.62 28.81 30 0.84 1.23 1.71 2.16 2.50 2.90 6.54 9.50 13.24 16.75 19.40 22.44 10 0.67 0.96 1.33 1.67 1.91 2.16 5.17 7.47 10.33 12.91 14.77 16.71
-5 0.55 0.79 1.08 1.33 1.50 1.64 4.26 6.14 8.40 10.34 11.62 12.73
50 1.08 1.58 2.21 2.82 3.30 3.87 8.40 12.24 17.16 21.88 25.58 29.99 30 0.89 1.30 1.81 2.30 2.67 3.10 6.92 10.06 14.04 17.80 20.68 24.01 10 0.72 1.05 1.45 1.82 2.10 2.39 5.60 8.11 11.25 14.13 16.24 18.54
R22
-5 0.61 0.88 1.21 1.50 1.70 1.90 4.72 6.81 9.36 11.62 13.18 14.69
-20 0.51 0.73 0.99 1.20 1.33 1.42 3.92 5.62 7.64 9.30 10.31 10.99
-40 0.39 0.54 0.72 0.83 0.861) x1) 2.98 4.22 5.56 6.43 6.641) x1)
tl=86°F, superheat= sub cooling = 0 K.
Other conditions can be calculated with Danfoss calculation software CoolSelector®
KVS15 KVS 42
Pressure drop ∆p [psi] Pressure drop ∆p [psi]
© Danfoss | DCS (sw) | 1017.10
DKRCC.PD.VC1.C7.02 | 9
Dimensions and weights
KVS 15
Type
KVS 15
KVS 42
Type
KVS 42
Connections H
ODF x ODF (A x B)
[in] [mm]
5
/8 × 5/816 × 16
7
/8 × 7/822 × 22
Connections H
ODF x ODF (A x B)
[in] [mm]
7
/8 × 7/822 × 22 4.8 12 0 7. 4 188 .5 5.6 143 3.7 93 3.8 95.5 2.4 60 0.95 24 1.9 4.2
1
[in] [mm] [in] [mm] [in] [mm] [in] [mm] [in] [mm] [in] [mm] [in] [mm] [kg] [lb.]
1.2 30 0.5 13 2.5 64 5.9 159 2.4 60 2.4 60 2.4 60 0.7 1.5
1
[in] [mm] [in] [mm] [in] [mm] [in] [mm] [in] [mm] [in] [mm] [in] [mm] [kg] [lb.]
H
2
L
1
H
3
L
2
Danfoss 34G102.13
H
4
L
3
L
1
B
L
4
øD
L
2
øD
1
Weight
A
1
B
1
Weight
11/8 × 11/828 × 28 4.8 12 0 6.7 168.5 5.6 143.0 3.3 83.0 3.4 85.5 2.4 60 0.95 24 1.9 4.2
13/8 × 13/835 × 35 4.8 120 7. 0 178 .5 5.6 143.0 3.5 88.0 3.6 90.5 2.4 60 0.95 24 1.9 4.2
15/8 × 15/
- 4.8 120 7.4 188 .5 5.6 143.0 3.7 93.0 3.8 95.5 2.4 60 0.95 24 1.9 4.2
8
Related products
EKD 316 driver EKC 368 controller AKS 11 / AKS 12 temperature sensor
AKS pressure transmitter
© Danfoss | DCS (sw) | 2017.10
Code no. 034G0013
AST-G service driver
DKRCC.PD.VC1.C7.02 | 10
Loading...