Condensing pressure regulator, type KVR
Differential pressure valve, type NRD
The condensing pressure regulator, type KVR can
be mounted in either the gas or liquid side of the
condenser in refrigeration and air conditioning
systems.
They are used to maintain a constant and
sufficiently high condensing pressure with systems
using air-cooled condensers.
They can also be used with valve types NRD
or KVD to assure that adequate pressure is
maintained on the receiver.
R1233zd (E) **, R123 4ze (E)*, R 1234 y f*, R 1270*
KVR 12 – KVR 22 only; see more details in the note below the table
**NRD only
HCFC and non-flammable HFC: KVR 28 – KVR 35
Regulation range
Maximum working pressure
Maximum test pressure
Pe = 73.00 – 254.00 psig
Factory setting = 145 psig
KVR: PS/MWP = 406 psig
NRD: PS/MWP = 667 psig
KVR: Pe = 450 psig
NRD: Pe = 870 psig
Medium temperature rangeKVR: - 49 – 266 °F
P band (full valve stroke)
Opening differential pressure for NRD
This product (KVR 12 - KVR 22) is evaluated for R290, R454A,
R454C, R455A, R600, R600a, R1234ze(E), R1234yf, R1270 by ignition
source assessment in accordance with standard EN ISO80079-36.
KVR 12 – KVR 22: 90 psi
KVR 28 – KVR 35: 72.5 psi
Start opening: Δp= 20 psi
Fully open: Δp = 43 psi
For complete list of approved refrigerants,
visit http://store.danfoss.com/ and search for individual code
numbers, where refrigerants are listed as part of technical data.
Flare connections are only approved for A1 and A2L refrigerants.
NRD is evaluated for R32, R290, R452B, R454A, R454B, R454C
R455A, R600, R600a, R1233zd(E), R1234ze(E), R1234yf, R1270
by ignition source assessment in accordance with standard EN
ISO80079-36.
Condensing pressure regulator, type KVR and differential pressure valve, type NRD
Sizing
Valve selection
For optimum performance, it is important to select
a KVR valve according to system conditions and
application.
Example
When selecting the appropriate valve it may be
necessary to convert the actual evaporator capacity
using a correction factors. This is required when
your system conditions are different than the table
conditions.
The selection is also dependant on the acceptable
pressure drop across the valve.
The following example illustrates how this is done.
Application example
Liquid capacity application
• The following data must be used when sizing
• a KVR valve:
• Refrigerant: HCFC, HFC and HC: KVR 12 – KVR 22,
HCFC and non-flammable HFC: KVR 28 – KVR 35
Condensing pressure regulator, type KVR and differential pressure valve, type NRD
Valve selection
(continued)
Step 1
Determine the correction factor for evaporating
temperature te.
From the correction factors table an evaporating
temperature of -40 °F, R22 corresponds to
a factor of 1.12.
Correction factors
t
e
[°F]
R221.121.091.051.031.00.98
R134a1.221.161.101.041.00.96
R404A, R5071.321.221.141.061.00.95
R407C1.201.151.091.041.00.96
Plant capacity x correction factor = table capacity
-40-30-20-10010
Step 2
Corrected evaporator capacity is
Qe = 28.7 x 1.12 = 32.14 TR
Step 3
Now select the appropriate capacity table and
choose the line for a condensing temperature
tc= 90 °F.
Using the corrected evaporator capacity, select a
valve that provides an equivalent or greater
KVR 12, KVR 15, KVR 22 delivers 38.2 TR
at a 25 psi pressure drop across the valve.
Based on the required connection size of
5
⁄8 in. ODF, the KVR 15 is the proper selection
for this example.
capacity at an acceptable pressure drop.
Step 4
KVR 15, 5⁄8 in. solder connection:
code no. 034L0097
Condensing pressure regulator, type KVR and differential pressure valve, type NRD
Design / FunctionKVRNRD
1. Seal cap
2. Gasket
3. Setting screw
4. Main spring
5. Valve body
6. Equalizing bellows
7. Valve plate
8. Valve seat
9. Damping device
10. Pressure gauge connection
11. Cap
12. Gasket
13. Insert
14. Piston
15. Valve plate
16. Piston guide
17. Valve body
18. Spring
1
= 5⁄16 in.
2
3
4
5
6
7
8
9
10
11
12
13
The condensing pressure regulator, type KVR
opens upon a rise in pressure on the inlet side, i.e.
when the pressure in the condenser reaches the set
value. KVR regulates on the inlet pressure only.
Pressure variations on the outlet side of the
regulator do not affect the degree of opening, as
the valve is equipped with equalization bellows (6).
The bellows has an effective area corresponding to
that of the valve seat neutralizing any changes to
the setting.
14
15
16
17
18
19
20
The valve is also equipped with a damping device
(9) providing protection against pulsations which
can normally arise in a refrigeration system.
The damping device helps to ensure long life
for the regulator without impairing regulation
accuracy.
Differential valve type NRD begins to open when
the pressure drop in the valve is 20 psig.
Condensing pressure regulator, type KVR and differential pressure valve, type NRD
P-band and OffsetPrinciple diagram
Capacity
100%
75%
50%
25%
Setting
Metric conversions
1 psi = 0.07 bar
5
⁄9 (t1°F -32) = t2 °C
Proportional band
The proportional band or P-band is defined as
the amount of pressure required to move the
valve plate from closed (set point) to fully open
position.
Example
If the valve is set to open at 120 psig and the
valve P-band is 90 psi, the valve will give maximum
capacity when the inlet pressure reaches 210 psig.
[psi]
Offset
P-band
Offset
The offset is defined as the permissible pressure
variation in condenser pressure (temperature). It is
calculated as the difference between the required
working pressure and the minimum allowable
pressure. The offset is always a part of the P-band.
Example with R22
A working temperature of 110 °F ~ 230 psig is
required, and the temperature must not drop
below 100 °C ~ 200 psig (set point).
The offset will then be 30 psi.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order pro
All trademarks in this material are property of the respec
Dimensions and weightsKVRNRD
L
D
Metric conversions
1 in. = 25.4 mm
1 lb = 0.454 kg