Features ..............................................................................................................................................................................................3
Introduction Saginomiya type RGE condenser fan speed
controllers are compact, robust phase controllers
designed for application on condensing units
and packaged air-conditioning systems. They
are particularly suitable in units that operate the
year around, and provide stable operation with
constant condensing pressure during winter or
moderate seasons. RGE controllers make possible
cost-ecient variable control of fan speed.
Features
Pressure sensing element integrated.
Sensor-bellows structure provides high
reliability
Single phase and 3 phase versions available.
All common refrigerants R22, R407C, R404A,
R134a, R410A
Designed for reduced-noise operation
Selectable slowdown mode or cut-o mode
¼” female connection with schraeder
depressor pin
Terminal for an external forced operation
switch is provided.
IP54 enclosure
CSA-us approved
CE and EMC
At approx. 45%
(50Hz) at approx
35% (60Hz). Cut O
or Minimum Speed
function is selectable
with changeover
switch.
Default setting: Cut
O
Ambient
Temp. (
-4 to 131
Refrigerants
o
F)
R22, R404A,
R407C (R134a)
R410A464
Factory
Set (psi)
3
276
Wt.
(kg)
0.36
0.50
0.54
0.58
0.36
0.50
0.54
061H3023RGE-Z1Q6-7DS
0.2 to 8A
061H3003RGE-Z3R4-7DS
116 to 406
061H3050RGE-Z3T4-7DS87
061H3027RGE-Z3R6-7DS
232 to 566
061H3051RGE-Z3T6-7DS
061H3006RGE-X3R4-7DS116 to 40658
061H3028RGE-X3R6-7DS232 to 566116R410A464
1
The pressure at which the control delivers 95% output effective voltage (VRMS).
2
Pressure width where effective voltage corresponds to the minimum speed or causes cut off operation.
3
When the refrigerant is R134a, please change the pressure setting.
58
116
681
Three phase
200 to 240V
AC 50/60Hz
Three phase
380 to 415V
AC 50/60Hz
0.2 to 5A
0.2 to 7A
0.2 to 5A
At approx. 35%, Cut
O or Minimum
Speed function
is selectable with
-4 to 122
changeover switch.
0.2 to 7A
Default setting: Min.
speed
0.2 to 5A5 to 122
R22, R404A,
R407C (R134a)
R410A464
R22, R404A,
R407C (R134a)
Minimum speed: Fan motor will be kept running at minimum speed when pressure decrease to the set value, (the specific value (V%)).
Cut off: Fan motor will be stopped when pressure decreases to the specific value (V%) for R.M.S.
The operating characteristic may vary according to the voltage, frequency, and fan motor characteristics.
Three –phase type
(RGE-Z3,X3)
Single –phase type
(RGE-Z1)
50Hz
F.V.S. (Adjustable)
Max. Speed
Pressure
100
95
45
35
60Hz
Min. Speed
E.P.B. (Fixed)
F.V.S. (Adjustable)
Max. Speed
Pressure
100
95
35
Min. Speed
E.P.B. (Fixed)
Adjusting Method
1) Range adjustment
Setting point is increased by turning the range
adjusting screw clockwise. It is decreased by
turning the screw counter-clockwise.
Adjustment should be within the range indicated
for the setting pointer.
2) Lower pressure operation selection
Following operation are selectable with the
change-over switch.
Minimum speed running : Fan motor operates at
the Minimum speed when the pressure decreases
below the value “Pmin”.
Cut-off : Fan motor stops when the pressure
decreases below the value “Pmin”.
Pmin = F.V.S – E.B.P.
F.V.S = Pressure setting for max. speed (Adjustable)