Danfoss EIM 316, EIM 336, EIM 365 Installation guide

ENGINEERING
R
80G8127
Battery
Pressure
80 mm / 3.15 in
TOMORROW
Installation guide
Electronic superheat controller
Type EIM 316 / 336 / 365
Introduction
Superheat controller EIM series is for use where superheat must be accurately controlled, typically in commercial air conditioning, heat pumps, commercial
080 R9347
refrigeration and food retailing applications.
Reference: For details please see EIM data sheet.
Technical specifications
Supply voltage 24 V AC / DC (+ 15%), 50 / 60 Hz, 15 VA / 8 W, Class II isolation
Idle
Power consumption
Input signals For the EMC compliance, sensor cable length must be < 3 m / 118 in. For longer sensor cable, a ferrite bead should be used.
Valve support
operating
Po 0.5 - 4.5 Vdc ratiometric pressure sensor i.e AKS 32R
S2 PT1000 (measuring range -60 – 120 °C /
S4 PT1000 or digital input from external contact
EIM 365: ETS 6 / ETS / ETS Colibri, KVS / KVS Colibri, CCM, CCMT EIM 316/336: ETS 6
Data communication RS 485 – MODBUS RTU (Not terminated internally)
Storage : -34 – 71 °C / -30 – 160 °F
Environment
Operating : -25 – 60 °C / -13 – 140 °F
Humidity : < 95% RH, non condensing
Battery backup (Only for EIM 365) 18 - 28 V DC, > 49 VmAh
Operation Standalone or via MODBUS data communication
Applications
1. Superheat controller: standalone 2. Valve driver
Max. 10 mA @ 24 V DC (EIM 316 & 336)/ 25mA @ 24V DC (EIM 365) Max. 150 mA @ 24 V DC (EIM 316 & 336)/ 625mA @ 24V DC (EIM 365)
-76 – 248 °F)
English
080 R9347
More info
EIM 316 / 335 / 336
© Danfoss | DCS (sb) | 2020.02
ETS Colibri®
ø 3 mm /
0.118 in
GND
5 mm / 0.2 in
S2 Pe
Power
1
2 4
3
5 mm / 0.2 in
BAckup
MODbus
11131 3
sensor
4
2
4
Danfoss
Danfoss
64-8040
R64-8040
ETS Colibri®
S2
S4
122
2
2
Danfoss
Reference signal via MODBUS
Danfoss R64-8041
Note:
S2 - Temperature sensor or DI S4 - Temperature sensor Weight : 40 gm
50 mm / 1.97 in
AN327425434124en -000201 | 1
Danfoss
80G165.10
PWR
COM
PWR
COM
Installation warnings
Colibri®
- Recommended mounting position: vertical
- Installation must comply with local standards and legislation
- Before working on the electrical connections, disconnect the device from the main power supply
- Before carrying out any maintenance operations on the device, disconnect all electrical connections
- For safety reasons the appliance must be fitted inside an electrical panel with no live parts accessible
- Do not expose the device to continuous water sprays or to a relative humidity greater than 90%
- Avoid exposure to corrosive or pollutant gases, natural elements, environments where explosives or mixes of flammable gases are present, dust, strong vibrations or shock, large and rapid fluctuations in ambient temperature that might cause condensation in combination with high humidity, strong magnetic and/or radio interference (e.g. transmitting antennae).
- When connecting loads be aware of the maximum current for each relay and connector
- Use cable ends suitable for the corresponding connectors. After tightening connector screws, tug the cables gently to check their tightness.
- Use appropriate data communication cables. Refer to the EIM data sheet for the kind of cable to be used and setup recommendations.
- Minimize the length of probe and digital input cables as much as possible, and avoid spiral routes around power devices. Separate from inductive loads and power cables to avoid possible electromagnetic noises.
- Avoid touching or nearly touching the electronic components fitted on the board to avoid electrostatic discharges.
Connection overview
TxD -
3
2
Temperature sensors
3
PT 1000 i.e. AKS 11
1
TxD
+
D
11 1
1
12
2
3
2 2
44
2
ETS 6 with JST-XHP 5 connector
JST XHP-5 CONNECTOR
Pressure transmitter Ratiometric 0.5 – 4.5 V i.e. AKS 32R
Power Supply 24 V AC or DC
+
-
MODBUS to master controller
GND
1 3
2 4
Connector on ETS 6 coil
Connector on EIM 336 controller
MODBUS connection overview
MODBUS in Daisy Chain
Note:
• If two EIMs are connected remember to remove the addressing jumper on one of the EIMs
• MODBUS transmission lines usually require termination resistors, especially for longer cable lengths
© Danfoss | DCS (sb) | 2020.02
Black
B2 B1 A2 A1
EIM slave 1
RS485 (+)
Master controller
RS485 (-)
Red Yellow Orange
ETS 6 valve
Green Red Black White
ETS / KVS
RS485 (+)
RS485 (-)
EIM slave 2
R = 120 Ohm Min. 0.25 W
AN327425434124en -000201 | 2
80G159.10
11.6 mm
10.7 mm
8.5 mm
0.33 in
6.3 mm
0.25 in
80G161.10
10.6 mm
Mating connectors for EIM Controller
80G163.10
Type Molex Mini-Fit Jr.™
4 WAY MINI-FIT RECEPTACLE Molex 39-01-2040 or similar
0.46 in
0.42 in
80G160.10
Connector kit for 5x EIM controller 080G1601
Quick guide for parameter selection
A. Setting controller in Superheat control mode.
Make sure that r12 = 0 (OFF) and change the settings. The setting will depends on the system requirement.
Enabling Regulation control ON / Off switch (optional)
HwMainSwitch = 1 (default is 0, i.e S4 sensor). For standalone configuration it is recommended to enable Regulation control ON / Off switch in order to control start/stop regulation when needed, otherwise the controller will start regulating when controller is powered up.
Select Refrigerant
o30 = 1 – 49
Select valve setting
For EIM 365, first select Proper Danfoss valve t ype (PNU 3002). For EIM 316/336, the default valve type is ETS 6. n37 = 384 x 10 micro step (3840 micro steps = 480 half steps) n38 = Max. steps / sec
Define pressure sensor range in bar absolute (x10)
o20 = Min. Transducer pressure o21 = Max. Transducer pressure
Define min/max superheat
Define SH control type: SH Mode : 1 = MSS , 2= LoadAP (PNU 3026 ) n10 = min. superheat reference n09 = max. superheat reference For fixed superheat define n09 = n10
Define MOP (optional)
n11 = maximum operating pressure
2 WAY MINI-FIT RECEPTACLE Molex 39-01-2020 or similar
0.42 in
RECEPT CONTACT 24-18AWG Molex 39-00-0039 or similar
80G162.10
Set force opening of the valve (optional)
Start-up OD% (PNU 3015) Start-up time (PNU 3017)
For EIM 365, Startup mode P-control has been enabled as default. for detail check startup mode parameter (PNU 64322).
To start the superheat control
Set r12= ON
B. Setting controller in valve driver mo de using MODBUS signal
Make sure that r12 = 0 (OFF) and change the settings so they fit to their application:
Select Application mode
o18 (PNU 2075 )= 1 i.e Manual control
Select valve setting (optional)
For EIM 365, first select Proper Danfoss valve t ype (PNU 3002). For EIM 316/336, the default valve type is ETS 6. n37 = 384 x 10 micro step (3840 micro steps = 480 half steps). n38 = Max steps / sec
Select manual opening degree
o45 Manual OD % (PNU 2064) 0 = fully closed, 100 = fully open
By changing parameter o45 Manual OD, the valve will move accordingly regardless of r12 parameter value.
© Danfoss | DCS (sb) | 2020.02
AN327425434124en -000201 | 3
EIM – Commonly used parameter identification
Group PNU Param-
Regulation
117 r12 Main switch 0 1 0
Control
2075 o18 Manl control 0 1 0
2064 o45 Ma nual OD 0 100 0 %
3026 n21 SH Mode 1 2 2
Super Hea t
3015 n09 Max. superheat 20 200 90 K
Control
3021 n10 Min. superheat 10 200 40 K
3032 n37 Max steps 10 0
3033 n38 Max steps / sec 10 400 16
Valve
(Valve selec tion valid for EIM 365, FOR EIM 316
3002
and 336 default i s ETS 6 )
Refriger-
2551 o30 Refrigerant 1 49
ant
113 r09 Adjust S2 -100 100 0 K
2033 o21
Sensors
2034 o20
Note :
• “e2” is the value stored in EEPROM. “W” is writing to the register possible “*10” is scale of the parameter.
• For detail parameter list, refer to the EIM datasheet.
• Default Modbus setting 19200 8E1.
Symbol ic
eter
name
n03 Valv e Type
Max. transduc­er pressure
Min. transducer pressure
Min. Max. Default Units e2 W *10 Description
With this setting the regulation can be started and stopped. This can also be accomplished with
ü
the external hardware main switch. 0 = Superheat control, 1 = Manual control
ü
Manual opening degree for manual control. Used when the o18 Manual Control is set
ü
to 1 (fully closed = 0% , fully open = 100%). 1: MSS, 2: Load AP Maximum superheat reference setting Minimum superheat reference setting
Maximum number of steps (384 x 10 microsteps = 480 half steps) (Values in bracket is for EIM 316,336)
Steps per second
0 : ETS 12.5, ETS 25, KVS 15 1 : ETS 50, CCM 10, CCM 20, CCM30 2 : ETS 100, CCM 40 3 : ETS 250, KVS 42 4 : ETS 400 5 : User defined 6 : UKV, SKV, VKV, PKV 7 : ETS 6 8 : CCMT 2, CCMT 4, CCMT 8 9 : CTM16 10 : CCMT 24 11 : CCMT 30 12 : CMT 42 13 : CTR 14 : CCMT 0 15 : CCMT 1 16 : No valve sele cted 17 : ETS 12C, 24C, 25C, 50 C, 100C, KVS 2C, 3 C, 5C
0: None 1: R12 2: R22 3: R134a 4: R502 5: R717 6: R13 7: R13B1 8: R23 9: R500 10: R503 11: R114 12: R142b 13: User 14: R32 15:R227ea 16: R401A
S2 Offset adjustment Maximum transducer pressure
(in bar absolute * 10) Minimum transducer pressure
(in bar absolute * 10)
8000
(1000)
0 17 EIM 365: 16
10 600 16 0
-10 0 0
240
(384)
EIM 365: 0
EIM 316,
336: 23
bar
(abs.)
bar
(abs.)
ü ü ü ü ü ü ü ü
ü ü
ü ü
ü ü
ü ü
ü ü ü
ü ü ü
ü ü ü
17: R507A
18: R402A 19: R404A 20: R407C 21: R407A 22: R407B 23: R410A 24: R170 25: R290 26: R600 27: R600a 28: R744 29: R1270 30: R417A 31: R422A 32: R413A 33: R422D
Related products
Pressure transducer
AKS 32R, NSK BExx
Temperature sensor
AKS 21, AKS 11, ACCPBT
Programming key / display
MYK - EIM interfacer
Electric Expansion valve
ETS series
Backup power module
EKE 2U
34: R427A 35: R438A 36: R513A 37: R407F 38: R1234zeE 39: R1234yf 40: R448A 41: R449A 42: R452A 43: R450A 44: R452B 45: R454B 46: R1233zdE 47: R1234zeZ 48: R449B 49: R407H
© Danfoss | DCS (sb) | 2020.02
AN327425434124en -000201 | 4
Loading...