Danfoss ASV-PV, ASV-BD, ASV-M Data sheet

Data sheet
Automatic balancing valves
ASV DN 15-50 (4th gen.)
ASV-PV ASV-BD ASV-M DN 15-50 DN 15-50 DN 15-50
Description
ASV whiteboa rd animation
ASV valves are automatic balancing valves. Together with Danfoss presetting radiator thermostatic valves they are part of the Danfoss two-pipe solution and are perfect for creating optimal hydronic balance in residential two-pipe heating systems.
One of the major challenges in heating systems is a lack of good hydronic balancing, caused by differential pressure, which is changing constantly and unpredictably in the heating system. This results in complaints from residents about poor indoor comfort, noise and high energy bills.
Trying to solve these complaints, larger pumps are often installed to improve - especially under heated - circulation of the water. Unfortunately, this affects pressure differentials and energy consumption within the system even more. Besides, the higher pressure differential, the greater the noise from the system, particularly from radiator valves.
ASV automatic balancing valves ensure an optimal pressure differential for control valves as well as the correct flow within the individual risers at all times. This is the reason why DIN 18380 requires control of differential pressure at partial loads. The ASV automatically creates an optimal hydronic balance within the installation, whether under full or partial load. This balance is never disrupted.
The ASV valves can also be used in cooling applications (fan coil, chilled beam, etc) with variable flow, to secure an automatic hydronic balance (see general ASV datasheet for details).
Benefits
Installing an ASV combination ensures:
• Fewer complaints: ASV makes the system more reliable, with less disturbances such as noisy radiators, under heating of rooms far away from the heat source, or over-heating of rooms close to the heat source. Fewer complaints means less call-backs to installer to solve the complaints.
• Improved indoor comfort:
ASV provides stable pressure conditions to radiator or floor heating control valves resulting in more accurate room temperature control.
• Lower energy bills: Higher energy efficiency is contributed by solving overheating problem and ensuring more accurate temperature control. Proper balance prevents overflows thus resulting in low return water temperature, which improves energy efficiency of condensing boilers and district heating systems.
• Simplicity:
ASV divides the piping system in pressure independent zones, typically individual risers or apartments so complex and time consuming calculation and commissioning methods are not needed anymore. It also allows a gradual connection of zones to the main constructions without additional balancing.
• Ease of use: The new generation of ASV automatic balancing valves is even simpler to use than
before. The improved setting scale can now be set without using an allen key, saves time for the installer during commissioning and maintenance of the system while new flushing function saves time during flushing of pipe network.
© Danfoss | 2016.11
VD.A9.J2.02 | 1
Data sheet Automatic balancing valves ASV
Applications ASV balancing valves are designed to guarantee
high quality of automatic balancing by:
a pressure released cone,
an adapted membrane for valve dimension
which provides constant quality performance for all sizes,
linear and accurate setting scale that makes setting required ∆p easy.
• low required 10 kPa pressure drop on ASV-PV valve contributes to smaller pump head.
The Danfoss ASV solution comprises an automatic balancing valve ASV-PV and an associated partner valve (Fig. 1 and 2). The ASV­PV is a differential pressure controller, fitted into the return pipe. The partner valve is fitted into the supply pipe. Both valves are connected to each other using a mpulse tube.
There are two basic configurations when using ASV partner valves:
Partner valve outside the control loop (Fi g .1). Recommended valve ASV-BD (default configuration: blue test plug needs to be open, red is in closed position) or ASV-M: It results in best performance since whole controlled pressure range is available to the riser. Flow limitation is done on each terminal unit in the riser (for example, RA-N with presetting on radiator, etc).
The pressure controller has a factory setting of 10 kPa or 30 kPa, perfect for typical radiator based heating systems. Of course it can easily be adjusted to another setting using the setting scale. If the pressure differential tends to become greater than this setting, then the ASV automatic balancing valve immediately reacts and keeps the pressure differential constant. By this the pressure in the controlled riser or loop does not increase due to any system load changes.
ASV balancing valves have integrated service functions such as: *Flushing *shutt-off *draining Shut-off function is separated from the setting mechanism.
Partner valve inside the control loop (Fig.2). Recommended valve ASV-BD (red test plug needs to be open, blue is in closed position): Offers flow limitation on the riser however part of the controlled pressure range is used by pressure drop on partner valve (∆pp). It is recommended when flow limitation on each terminal is not possible.
p
r
p
r
v
p
p
1)
Please note tha t blue test plug on ASV-BD ne eds to be open
(default co nfiguration)
Fig. 1 Setting of ASV-PV = p outside the control loop)
1)
p
a
(partner valve
riser
p
p
p
1)
Please note tha t the red test plug on ASV-BD ne eds to be
open and blu e test plug closed
Fig. 2 Setting of ASV-PV = p
p
p
1)
o
v
p
a
+ p
riser
p
ASV-BD can be used outside or inside the control loop by choice of which measuring nipple is open. Change of configuration can be done under pressure - simply by closing/opening test plugs. Configuration inside the control loop (default position) allows flow verification, while configuration outside the control loop allows flow limitation.
2 | © Danfoss | 2016.11
VD.A9.J2.02
Data sheet Automatic balancing valves ASV
Applications (continuous)
ASV valves are to be used in radiator heating systems to control the differential pressure in risers (Fig. 3) or horizontal loops - mostly used in new installation (Fig. 4). To limit the flow for every radiator, the thermostatic radiator valve with pre­setting function is used together with a constant pressure provided by the ASV, thus providing balanced heat distribution.
Fig. 3 ASV in vertical riser / t ypical radiator heating
application (general example)
Fig. 4 ASV in horizontal loop / t ypical radiator heating application (general example)
ASV valves are also a perfect solution in floor heating systems (Fig. 5). To limit the flow, every manifold with integrated presetting should be used together with a constant pressure provided by an ASV-PV valve.
ASV-BD
ASV-PV
Fig. 5 ASV in manifold for floor heating system
Alternatively the flow for the whole manifold can be limited by using the setting function of the ASV-BD. Due to its small dimensions the ASV automatic balancing valves are easy to install in a wall mounted box for floor heating manifolds.
VD.A9.J2.02
© Danfoss | 2016.11 | 3
Data sheet Automatic balancing valves ASV
Ordering
ASV-PV balancing valve, included in the box:
1,5 m impulse tube (G ⁄ A)
k
Typ e DN
VS
(m3/h) (kPa)
15 1, 6
20 2,5 Rp ¾ 003Z5502 003Z5602
25 4,0 Rp 1 003Z5503 003Z5603
32 6,3 Rp 1¼ 003Z5504 003Z5604
40 10,0 Rp 1½ 003Z5505 003Z5605
50 16, 0 Rp 2 003Z5506 003Z56 06
15 1, 6
20 2,5 G 1 A 003Z5512 00 3Z5612
25 4,0 G 1¼ A 00 3Z5513 0 03Z5 613
32 6,3 G 1½ A 00 3Z5514 -
40 10,0 G 1¾ A 0 03Z5515 -
50 16, 0 G 2¼ A 003Z5516 -
15 1, 6
20 2,5 Rp ¾ 003Z5542
25 4,0 Rp 1 003Z5543
32 6,3 Rp 1¼ 003Z5544
40 10,0 Rp 1½ 003Z5545
50 16, 0 Rp 2 003Z5546
15 1, 6
20 2,5 G 1 A 003Z5552
25 4,0 G 1¼ A 003Z5553
32 6,3 G 1½ A 003Z5554
40 10,0 G 1¾ A 003Z5555
50 16, 0 G 2¼ A 003Z5556
Connection
Rp ½
Internal thread
IS O 7/1
G ¾ A
External thread
ISO 228/1
Rp ½
Internal thread
IS O 7/1
G ¾ A
External thread
ISO 228/1
∆p setting range Code No.
without insulation with EPP insulation
003Z 5501 003Z 5601
5-25
003 Z55 11 0 03 Z56 11
5-25
003Z5 541
20-60
003Z5551
20-60
-
-
ASV-BD shut-off valve, multifunctional partner
valve (shut-off, rotating measuring station) and EPP insulation
k
Typ e DN
VS
(m3/h)
15 3,0
20 6,0 Rp ¾ 003Z4042
25 9,5 Rp 1 003Z4043
32 18 Rp 1¼ 003Z404 4
40 26 Rp 1½ 003Z4045
50 40 Rp 2 003Z4046
Connection Code No.
Rp ½ 003Z4 041
Internal
thread IS O 7/1
ASV-M shut-off valve, without test plugs and with EPS insulation
k
Typ e DN
VS
(m3/h) 15 1, 6
20 2,5 Rp ¾ 0 03L7692
25 4,0 Rp 1 0 03L7693
32 6,3 Rp 1¼ 0 03L7694
40 10 Rp 1½ 0 03L7695
15 1, 6
20 2,5 G 1 A 003L7697
25 4,0 G 1¼ A 0 03L7698
32 6,3 G 1½ A 003L7699
40 10 G 1¾ A 003L7700
50 16 G 2¼ A 003L7702
Connection Code No.
Rp ½ 003L7691
Internal
thread IS O 7/1
G ¾ A 003L7696
External
thread
ISO 228/1
4 | © Danfoss | 2016.11
VD.A9.J2.02
Data sheet Automatic balancing valves ASV
Ordering (continuous)
Spare parts
Typ e Description Comments Connection/Dimension Code No.
ASV-PV handle
ASV-PV Service kit 20- 60 kPa
ASV-PV Service kit 5-25 kPa
ASV-PV Service kit 20-80 kPa
Differential pressure measuring connector For ASV-PV drain connection 003L8143
ASV-PV drain connection DN 15-50 00 3L8141
ASV-BD handle
Impulse tube, with O-rings
2)
DN 15-25 003Z7855
DN 32-50 003Z7857
DN15 -20 003 Z7831
DN 25 003Z7832 DN 32 003Z7833 DN 40 003Z7834 DN 50 003Z7835
DN15 -20 0 03Z7841
DN 25 003Z7842 DN 32 003Z7843 DN 40 003Z7844 DN 50 003Z7845 DN 32 003Z7836 DN 40 003Z7837 DN 50 003Z7838
1,5 m 003L 8152 2,5 m 003Z0690
5 m 0 03L8153
003Z4652
O-ring for impulse tube Set of 10 pieces 2,90 × 1,7 8 003L8175
Plug for impulse tube connection ASV-BD/M Set of 10 pieces G ⁄ A 0 03L 8174
1)
With handle
2)
For com plete range of ASV-BD accessori es please refer to LENO™ MSV-BD datashe et.
Accessories - Fittings
Typ e Comments to pipe to valve Code No.
R / DN 15 003Z0232
R / DN 20 0 03Z0233
Tailpiece threaded (1 pcs.)
Tailpiece welding (1 pcs.)
R 1 DN 25 003Z0234
R 1 / DN 32 003Z0235
R 1/ DN 4 0 003Z0273
R 2 DN 50 (2 /”)
DN 15
DN 20
DN 25
DN 32
DN 40
DN 50 DN 50 (2 /”)
DN 15 003Z0226
DN 20 003Z0227
DN 25 003Z0228
DN 32 003Z0229
DN 40 003Z0271
00 3Z0274
003Z0272
VD.A9.J2.02
© Danfoss | 2016.11 | 5
Data sheet Automatic balancing valves ASV
Accessories
Typ e Description Comments Connection/Dimension Code No.
ASV-PV flushing accessory 003Z7850
Two test plugs and one locking plate For ASV-M, rectus t ype 00 3L8145
3 mm test plugs, 2 pcs For ASV- BD
ASV-BD drain connection
Plastic impulse tube with connec tors and adapters
Commissioning label
2)
½” hose connection 003Z4096
¾” hose connection 003Z4097
For making set of 10 pieces
Set of 10 pieces DN15 -50 003Z7860
1)
3)
Plug for connecting impulse tube G ⁄-R ¼ connection 00 3L8151
EPP insulation cap for ASV-PV
EPP insulation cap for ASV-BD
max. 120 °C
EPP insulation cap for ASV-M
1)
For com plete range of ASV-BD accessori es please refer to LENO™ MSV-BD datashe et.
2)
To be fitte d on insulation
3)
10m of impulse tube
003Z4662
003Z0689
DN 15-20 003Z7800
DN 25 0 03Z7802
DN 32 003Z7803
DN 40-50 003Z7804
DN 15 003Z4781
DN 20 0 03Z4782
DN 25 0 03Z4783
DN 32 003Z4784
DN 40 003Z4785
DN 50 0 03Z4786
DN 15 00 3L8170
DN 20 0 03L 8171
DN 25 0 03L8172
DN 32 00 3L817 3
DN 40 0 03L8139
Technical data
6 | © Danfoss | 2016.11
Typ e ASV-P V ASV-M ASV-B D
Nominal diameter DN 15- 50 15- 50 15-50
Max. pressure (PN)
Test pressure 25 25 30
bar
Differential pressure over the valve kPa 10-250 10-150
Shut Off leakage No visible leakage
Working temperature
Storage and transport temperature –40 … 70
°C
16 16 20
1)
2)
2)
D
10-2 50
2)
A
0 … 120 –20 … 120 –20 … 120
Material of parts in contact with water
Valve body Brass Brass DZR brass
Cone DZR brass Brass
Membrane / O-rings EPDM EPDM EPDM
Spring Patent wire - -
Ball - - Brass / chromium plated
1)
Pl ease note that the maximum adm issible differential p ressure across the valve 150 kPa should also not be excee ded at partial load.
2)
ISO 5208
VD.A9.J2.02
Loading...
+ 14 hidden pages