ASV balancing valves are designed to guarantee
high quality of the automatic balancing by:
- a pressure released cone,
- an adapted membrane for every valve
dimension which provide constant quality
performance for all sizes.
A 90° angle between all service features (shut-off,
draining, measuring) allows an easy access under
any installing condition.
ASV valves (DN 15-40) are packaged in styropore
(EPS) which can be used for insulation at
ASV-P valves are automatic balancing valves
with fixed setting (10 kPa) for creating optimal
hydronic balance in residential heating systems.
The setting can be increased to 20 or 30 kPa
by spring replacement. Spring can be replaced
under pressure.
temperatures up to 80 °C. An insulation cap is
available as an accessory for insulation at higher
temperatures (up to 120 °C).
ASV-P valves are to be mounted in return pipe,
in combination with partner valves mounted
in f low pipe. As a partner valve ASV-M/I/BD are
recommended.
ASV-P balancing valve, inclusive in the box: 1.5 m impulse tube (G ⁄ A) and drain cock (G ⁄ A)
Constant differential pressure 10 kPa ; can be upgraded to 20 or 30 kPa setting respectively
Internal thread
k
Typ eDN
151.6 Rp ½003L7621G ¾ A003L7626
202.5 Rp ¾003L7622G 1 A0 03L7627
254.0 Rp 10 03L7623G 1¼ A003L7628
326.3 Rp 1¼003L7624G 1½ A003L762 9
4010Rp 1½003L7625G 1¾ A003L7630
Note: for whole rang e of ASV partner valves, spa re parts and accessories pl ease refer to ASV datasheet.
Please note tha t the maximum admissible dif ferential pressure across t he valve 150 kPa should also not be e xceeded at partial lo ad.
bar
16 (PN 16)
1)
There are two basic configurations when using
ASV partner valves (ASV-BD, ASV-I, ASV-M,
MSV-F2):
- partner valve outside the control loop (Fig. 1).
Recommended configuration: it results in best
performance since whole controlled pressure
range is available to the riser. Flow limitation
is done on each terminal unit in the riser (for
example, RA-N with presetting on radiator,
- partner valve inside control loop (Fig. 2).
Offers flow limitation on the riser however
part of the controlled pressure range is used
by pressure drop on partner valve (p
recommended when flow limitation on each
Fig. 1 Setting of ASV-P = ΔpriserFig. 2 Setting of ASV-P = ∆priser + ∆p
i
ASV-BD can be used outside or inside control loop by choice of which measuring nipple is open.
To be used outside control loop, blue measuring nipple needs to be open. In this position, flow
verification can be done (default position). To be used inside control loop, red measuring nipple
needs to be open. In this position, flow verification & flow verification can be done.
Fig. 3 ASV in riser / typical heating application (general example)
VD.A9.L1.02
Data sheet Automatic balancing valves ASV-P
Design
1. Shut-off knob
2. Shut-off spindle
3. O-ring
4. Reference spring
5. Impulse tube connection
6. Diaphragm element
7. Control diaphragm
8. Pressure-relieved valve cone
9. Valve body
10. Seat
Dimensions - insulation
Pressure testing
ASV-P must be installed in the return pipe with
flow in the direction of the arrow on the valve
body. Partner valves (ASV-M/I/BD, MSV-F2 must
be installed in the flow pipe, with flow in the
Max. test pressure is 25 bar. When pressure
testing the system you must secure that both
sides of the membrane have the same static
pressure to prevent damage of the pressure
controller. That means the impulse tube must
be connected and any needle valves must be
open. If ASV-P is installed in combination with
The ASV-P is designed to maintain constant
differential pressure across a riser. Via an internal
connection and together with the reference
spring, pressure in the return pipe acts on the
underside of the control diaphragm ⑦ while via
an impulse tube ⑤, pressure in the f low pipe
acts on the top of the diaphragm. In this way the
balancing valve maintains a fixed differential
pressure of 10 kPa.
The setting can be increased to 20 or 30 kPa
by spring replacement. Spring can be replaced
under pressure. The ability to increase the
setting is especially useful in case of trouble
shooting. It gives insurance that design flow can
be achieved even if calculation doesn’t match
actual installation.
direction of the arrow on the valve body. The
impulse tube must be installed between partner
valve and ASV-P. The impulse tube must be
flushed through before installation.
ASV-M both valves must be open or closed (both
valves must be in the same position!). If ASV-P
is installed in combination with ASV-I /ASV-BD
both valves must be open. During this operation
(closing or opening the valves) please make sure
that there is never lower pressure on upper side
of the membrane to prevent damaging it.
Starting
Appendix A-Sizing diagram
During system start – opening the shut-off on
ASV and partner valve-please secure that there
is the same static pressure on both sides or
higher pressure on upper side of the membrane.
If filling is done by opening ASV-P and partner
valve, please make sure there is a pressure on the
upper side of the membrane by opening partner
valve first before ASV-P is opened.
Danf
already on order pro
All trademarks in this material are property of the respec
Data sheet Automatic balancing valves ASV-P
Dimensions
L1L2L3H1H2D1D2Sabc
DN
651201398215286127Rp ½G ¾ A
15
7513 615910318357632Rp ¾G 1 A
20
8515516913223459841Rp 1G 1¼ A
25
9517 2179165295512250R p 1¼G 1½ A
32
100206184170315512 255R p 1½G 1¾ A
40
mmIS O 7/1ISO 228/1
G ¾ A
Insulation
ABCD
A
D
BC
DN
156111011137
207612013645
2510013515555
3211814816070
4011814 818070
mm
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
vided that such alterations can be made without subsequential changes being necessaryeady agreed.