Danfoss APP 53, APP 65, APP 78, APP 86, APP 92 Operating guide

Operation guide
APP pumps APP 53 / APP 65 / APP 78 / APP 86 / APP 92
Installation, Operation and Maintenance Manual
hpp.danfoss.com
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
Table of Contents ..................................................................................2
Validity .........................................................................................4
1. Introduction ............................................................................5
1.1 General.................................................................................5
1.2 Symbols ................................................................................5
1.3 Manufacturer and customer service address .............................................6
1.4 Country specific information ............................................................6
1.4.1 United Kingdom ........................................................................6
2. Safety ..................................................................................6
2.1 General information.....................................................................6
2.2 Preferred system design.................................................................6
2.3 Commissioning and servicing the unit ...................................................7
2.4 Adhere to the following important points ...............................................7
2.5 In case of doubt .........................................................................7
3. Technical data ..........................................................................7
3.1 Approved applications and operational limits for the pumps .............................7
3.2 Application range .......................................................................7
3.3 Electric motor data......................................................................7
3.4 VFD and Direct on line ..................................................................7
3.5 Noise and vibration .....................................................................7
3.6 Dimension drawings ....................................................................7
3.7 Space requirement......................................................................8
3.8 Filtration................................................................................8
3.9 Properties of water ......................................................................8
3.10 Air bubbles .............................................................................8
3.11 Chemicals...............................................................................8
4. Arrival inspection, transportation, handling, lifting and storage ..........................8
4.1 Arrival inspection .......................................................................8
4.2 Warning ................................................................................8
4.3 General safety information ..............................................................8
4.4 Transport and handling .................................................................8
4.5 Return to supplier .......................................................................9
4.6 Storage .................................................................................9
5. Installation and commissioning.........................................................10
5.1 Important dimensions .................................................................10
5.2 Cleanliness.............................................................................10
5.3 Fluid temperature......................................................................10
5.4 Electrical data..........................................................................10
5.5 Local regulations.......................................................................10
5.6 Pre mounting checklist, based on Danfoss preferred system design .....................11
5.7 Lifting and positioning.................................................................11
5.8 Mount the different equipment ........................................................11
5.9 Electrics ...............................................................................11
5.10 Instrumentation .......................................................................11
5.11 Connections ...........................................................................12
5.12 Ensure free flow .......................................................................12
5.13 Verify setting of safety/relief valves .....................................................12
5.14 Flush the pump ........................................................................12
5.15 Bleed and remove air from the pump...................................................12
5.16 Verify direction of rotation .............................................................12
5.17 Commissioning ........................................................................12
5.18 Check the filter condition...............................................................12
5.19 Instruct operator and maintenance personnel ..........................................12
2 | © Danfoss | DCS (im) | 2021.12 180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
6. Operation of pump unit ...............................................................13
6.1 General safety information.............................................................13
6.2 What to listen and look for .............................................................13
7. Maintenance and service of the pump unit .............................................13
7.1 General safety information .............................................................13
7.2 Service and inspection interval for the pump ...........................................13
7.3 Shut down of the system ...............................................................13
7.4 Disassembling and assembling the pump unit ..........................................14
7.5 Assembling the pump unit .............................................................14
7.6 Procedure for mounting the pump onto the electric motor..............................14
7.7 Getting the pump unit back into operation .............................................14
7.8 Storage of the pump ...................................................................14
8. Troubleshooting and scrapping criteria .................................................15
8.1 General safety information .............................................................15
8.2 Operational conditions which can cause pump failures..................................15
8.3 Mechanical failure......................................................................15
8.4 Electrical failure........................................................................15
8.5 Responsibility..........................................................................15
8.6 Scrapping criteria ......................................................................15
Appendices .......................................................................................17
1. Data sheet for APP pumps 53-92 AI167386503010en-001301) ...................
2. Instruction for APP pumps 53-92 (180R9368) ............................................43
3. Electric motors (180R9230) ..............................................................55
4. Bowex coupling manual .................................................................61
5. Recommended service intervals (AX281930801330en-000401) ..........................85
6. Parts list (AX191786502906en-001101) ...................................................89
7. Trouble shooting (521B1447) ...........................................................101
8. Right and wrong (180R9042) ..........................................................113
........19
© Danfoss | DCS (im) | 2021.12
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701 | 3
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
Validity
This manual is valid for APP pumps with the following type an serial number or higher:
Typ e Serial no.
APP 53 XXXXXX08-XXX
APP 65 XXXXXX08-XXX
APP 78 XXXXXX08-XXX
APP 86 XXXXXX08-XXX
APP 92 XXXXXX08-XXX
PUMP
Type APP 78 Code no. 180BXXXX
Serial no. XXXXXX08-XXX
MADE IN DENMARK
Danfoss A/S, 6430 Nordborg, Denmark
The serial number is referring to the Serial no. on the product label. The digits shown (08) indicate the version number of the pump.
4 | © Danfoss | DCS (im) | 2021.12 180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
© Danfoss | DCS (im) | 2021.12
1. Introduction
1.1 General
The APP pumps and pump units are manufac­tured by Danfoss A/S, and are sold and marketed by a net of authorized distributors world wide.
If any changes are made without written approval the warranty will automatically become void.
This manual contains the necessary instructions for the installation, operation and service of the pumps used in a Sea Water Reverse Osmosis (SWRO) system or Brackish Water Reverse Osmosis (BWRO) system.
In case the pump delivered is ATEX certified, the additional ATEX instruction must also be read.
The APP pumps must not be used for other purposes than those recommended and specified without first consulting your local pump distributor.
Use of the pump in other applications that are not suitable for the pump unit can cause damages to the pump unit, with risk of personal injury.
All personnel being responsible for operation and maintenance of the pump unit must read and fully understand these instructions, especially the section “Safety”, before:
It is important that these instructions are always available to the personnel concerned.
1.2 Symbols
Indicates something to be noted by the reader
Indicates a situation which will or could result in damage to the pump and its function
Indicates a situation which will or could result in personal injury and/or damage to the pump
Electrical hazard - Indicates a high­voltage warning
Safety glasses required
Transportation of the pump unit
Lifting the unit
Installing the pump unit
Connecting the pump unit to the water system
Connecting the electric motor and instru­mentation
Commissioning the unit
Servicing the pump unit, mechanical and electrical parts
Decommissioning the pump unit
The pump must always be installed and used in accordance with existing national/local sanitary, safety regulations and laws.
It is the responsibility of the safety officer or the chief operator to assure compliance with all local regulations that are not taken into account in this manual.
Changing the pumps’ or pump units’ opera­tional limits and hardware:
Changes to the delivered pump or motor pump unit may only be done with a written approval from Danfoss High Pressure Pumps.
Operation outside the Danfoss specifications requires a written approval from Danfoss High Pressure Pumps.
!
Hearing protection required
Safety shoes required
Safety helmet required
Protective garments must be wor n
Protective garments must be worn
Danger HOT. Do not touch
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701 | 5
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
2. Safety
1.3 Manufacturer and customer service address
Danfoss A/S
Danfoss High Pressure Pumps
RO Solutions
Nordborgvej 81, DK-6430 Nordborg Denmark
Telephone: +45 7488 4024 Fax: +45 7445 3831 Email: highpressurepumpss@danfoss.com Homepage: hpp.danfoss.com
2.1 General information
Dangers that can arise from not following the instructions:
When the pump or pump unit is managed by untrained personnel, there is a danger of:
• Death or fatal injuries
• Costly damages and claims
Your local Danfoss pump distributor can be found on our homepage.
Data sheets and instructions on all accessories are available on hpp.danfoss.com
1.4 Country specific information
1.4.1 United Kingdom
UK importer:
Danfoss Ltd. 22 Wycombe End HP9 1NB Beaconsfield United Kingdom
When using an electric motor, the motor must always be supplied with adequate cooling ventilation.
When using an electric motor together with a VFD, the motor must be designed for operation with a VFD.
VFD operation may increase the temperature inside the electric motor if the motor is not designed for VFD operation. This can damage the motor and cause unintended breakdown.
All electrical installation work must only be carried out by authorized personnel in accordance with EN60204-1 and/or local regulations.
It is recommended to install a lockable circuit breaker to avoid inadvertent starting and/or electrical hazard. The lockable circuit breaker must be used during installation, operation and maintenance.
It is recommended to place a local safety switch nearby the pump, enabling service personnel to cut power for the electric motor.
Protect the motor and other electrical equip­ment from overloads with suitable equipment.
In case the pump delivered is ATEX certified, the additional ATEX instruction must also be read.
Protective garments
!
must be wor n
Always wear suitable safety clothing when handling the pump.
When working near the pump system, safety shoes, safety glasses, hearing protection and safety helmet must always be worn.
Danger
Installation and maintenance must always take place during complete shutdown in an unpressurised condition. The drive unit must be secured against switching-on (with signs, switching off electricity power supply) in order to avoid serious injuries due to rotating parts. Do not reach inside the working area during the operation of the coupling. For protection against accidental contact appropriate security must be installed.
Before start-up, the settings for all protective devices, such as sensors/switches and safety valves must be verified and free flow from safety valves must be ensured.
All pipe and hose connections must be stress­free mounted, securely fastened to the pump and well supported. Improper installation will or can result in personal injury and/or damage to the pump.
Use of this manual does not relieve operation and maintenance personnel of the responsibil­ity of applying good judgment when operating and maintaining the pump and its compo­nents.
inadvertent
Under certain operational conditions the surface of the pump can be above 60°C / 140°F. Under these conditions the pump must be labelled with a “Danger Hot” sign.
6 | © Danfoss | DCS (im) | 2021.12 180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
2.2 Preferred system design
Danfoss recommends to build systems with a high degree of safety. Danfoss preferred system design and P&ID are found in appendix 1, Data sheet, and appendix 2, Instruction.
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
© Danfoss | DCS (im) | 2021.12
It is always the system builder´s responsibility that the system design does not cause any kind of hazard and is adapted to local regulations and standards.
Proper installation, proper start up and shut­down devices as well as high-pressure protection equipment is essential.
2.3 Commissioning and servicing the unit
It is recommended that commissioning and servicing are carried out by a minimum of two people, where one is acting as a supervisor.
Do not try to lift the pump unit manually; most of the pumps weigh more than 20 kilos, see specific weight for the pump in the appendix 1, Data sheet.
Always bleed the pump prior to initial start-up.
Do not mount the pump without the bell housing and a flexible coupling.
Do not try to start the unit before the system components are mounted, bleeded and adjusted.
Flush the system throughly before connecting the pump or pump unit.
Check rotation direction of the motor before mounting the pump.
3. Technical data
2.4 Adhere to the following important points
Before using the pump/pump unit it is very important to read and understand this user manual.
3.1 Approved applications and operational limits for the pumps
The pump and the pump units are designed for the use in a Sea Water Reverse Osmosis (SWRO) or Brackish Water Reverse Osmosis (BWRO) systems.
The APP pumps must not be used for other purposes than those recommended and specified without first consulting your local pump distributor.
Use of the pump in other applications not suitable for the pump unit can cause damages to the pump unit, with risk of personal injury.
2.5 In case of doubt
Please contact Danfoss A/S in case of doubt. Contact information is listed in section 1.3, Manufacturer and customer service address.
3.2 Application range
The Danfoss range of APP high-pressure pumps is designed according to EN 809 for use in RO applications with low viscosity and corrosive uids such as sea water.
3.3 Electric motor data
See recommended motor in appendix 1, Data sheet or appendix 3, IOM for motors. The motors mentioned are the most common used motors by Danfoss High Pressure Pumps.
3.4 VFD and Direct on line
Danfoss APP pumps can be used with VFD and direct on line. Torque limits can be found in the table below:
Nm APP 53APP 65APP 78APP 86APP
92
MAWT 878 1,118 1,257 1,112 1,112
MAST 1,700 1,70 0 1,70 0 1,70 0 1,70 0
MAWT: Maximum allowable working torque MAST: Maximum allowable starting torque
3.5 Noise and vibration
Noise level for a pump unit with a ”standard” motor measured according to EN ISO 3744: 2010, see appendix 1, Data sheet. Possibilities to reduce noise and vibration are described in the same Data sheet.
For system integration of the pump, please see appendix 1, Data sheet and appendix 2, Instruction.
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701 | 7
3.6 Dimension drawings
Dimensions of the different pumps can be found in appendix 1, Data sheet.
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
3.7 Space requirement
When doing service or replacing the complete pump unit, it is recommended to have sufficient space available around the pump in order to ensure easy access. Sufficient space means at least 1 meter/40 inches around the pump. When working with high pressures, it is important to have the right space available around the pump as stated in the safety requirements.
3.8 Filtration
(10µm absolute [ß Requirements are specified in appendix 1, Data
≥ 5000])
10
sheet and in appendix 2, Instruction.
Danfoss recommends not to build a filter bypass function or to use filters with an integrated bypass. If the above recommendation is not followed the warranty for the pump will automatically become void.
It should be possible to monitor the condition of the filter via the differential/delta pressure across the filter.
Using insufficient filtration or a filter bypass can cause a failure or decreased service life of the pump.
3.9 Properties of water
It is recommended NOT to use the pumps in feed water concentrations higher than 50,000 ppm TDS without consulting your local Danfoss pump distributor.
3.10 Air bubbles
Large bubbles in a pressurised RO system can result in damage to piping, equipment and the pump.
All air must be bleeded from both the low­pressure and high-pressure side before the RO system is pressurised. Special consideration should be given in order to minimize air bubbles in the feed flow. Air bubbles can cause cavitation.
3.11 Chemicals
The pump should not be exposed to any chemicals as it can result in damage to piping, equipment and internal parts in the pump.
4. Arrival inspection, transportation, handling, lifting and storage
4.1 Arrival inspection
The pump is packed in a cardboard or wood box with plugs in the port connections to protect the pumps from damage during transportation.
When the shipment has arrived it is important to check the pump for any damages. The name plate/type designation must be in accordance with the delivery note and your order.
In case of damage and/or missing parts, a report should be documented and presented to the carrier at once.
4.2 Warning
Before any lifting operation is performed, environmental conditions must be taken into consideration (Ex-rated areas, wind speed, wet/ dry conditions, lifting height, etc.).
4.3 General safety information
Personnel involved in lifting and transporting the equipment (see Safety, chapter 2) must be trained in handling and in safety procedures for lifting heavy loads. Many of the pumps and pump units weigh more than 20 kilos, which requires lifting slings and suitable lifting devices; e.g. an overhead crane or industrial truck to be used as minimum.
4.4 Transport and handling
Small pumps which have a weight below 20 kilos can be handled by hand if they are not mounted together with an electric motor. The weight of a small pump with a motor will be above 20 kilos.
Do not use connections/nozzles for lifting! Do not use only one sling!
8 | © Danfoss | DCS (im) | 2021.12 180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
© Danfoss | DCS (im) | 2021.12
Pumps which have a weight above 20 kilos must be handled by using lifting eyes and slings.
Wrong lifting:
When the pump is mounted together with a bell housing, the pump can be rotated and in that case the lifting eye cannot be used in all positions. When lifting a pump with bell housing, a sling can be used to lift the pump by position­ing it on the drive end of the pump outlet.
When the pump is mounted together with an electric motor, it must not be lifted in the lifting eye. A pump unit with motor must be handled by using two slings around the pump unit. One sling must be attached to the electric motor and one sling around the pump. Make sure that the unit/load is balanced before lifting. The centre of the mass varies from pump/ pump unit size to pump(pump unit).
See below examples of where to/not to attach the lifting slings on the pump unit with motor:
Correct lifting with 2 separate slings:
Some motors and pumps have specific lifting eyes.
Do not use connections/nozzles for lifting! Do not use only one sling!
Make sure that the unit/load is balanced before lifting. The centre of the mass varies from pump/ pump unit size to pump/pump unit.
How to mount the pump and the electric motor correctly, see appendix 1, Data sheet or appendix 2, Instruction.
Incorrect lifting can result in personal injury and/or damage to the pump unit, see appendix 2, Instruction.
Once the lifting is done the lifting eye must be removed from the pump.
4.5 Return to supplier
Please see maintenance chapter 7.
4.6 Storage
Each pump is tested before shipment, and will therefore contain water. For storage temperature and frost protection see appendix 2, Instruction.
The pumps are NOT delivered frost protected from the factory.
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701 | 9
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
5. Installation and commissioning
5.1 Important dimensions
Physical dimensions and connections of the pump unit are described in appendix 1, Data sheet.
5.4 Electrical data
Check voltage, current frequency and rated power on the electric motor and VFD settings on the name plate placed on both the motor and the VFD.
5.2 Cleanliness
It is very important that the tubes and pipes are completely clean: no dirt, chips or burrs are allowed. Flush all piping before connecting the high-pressure pump to ensure the system is clean. Internal surfaces of the piping must not be corroded. If dirt or rust is not removed, the pump and the valves can be damaged. In worst case the pump can be damaged beyond repair!
5.3 Fluid temperature
Before start-up, the fluid and pump housing temperature must be within the specified temperature range listed see appendix 1, Data sheet.
Schematic 1: Recommended system design
Media filter
Feed
PI
PI
PI PI
PT
5.5 Local regulations
Commissioning must always be done in accordance with valid regulations and local standards.
M
PI
Permeate
Fresh water
permeat flush
PI
Brine
10 | © Danfoss | DCS (im) | 2021.12 180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
© Danfoss | DCS (im) | 2021.12
5.6 Pre mounting checklist, based on Danfoss preferred system design
Table 1: Check points when assembling and commissioning system
Check points Comment OK ?
Ensure that the environmental conditions are safe. See Arrival inspection,
CP1
Minimum and maximum start-up temperature for fluid and
CP2
pump.
Filtration condition (10 µm absolute (ß
CP3
Power supply for electric motor and VFD. See Data sheet for the used
CP4
Safety circuit / breaker must be sized for the motor and
CP5
environment (corrosion and humidity)
Bolts and screws must conform to environmental conditions
CP6
as well as fluid and torque requirements.
Instrumentation, pressure switch should be designed to
CP7
conform to the environment (corrosion and humidity).
Check the factory settings of the safety/relief valves or
CP8
pressure relief valves (page 11).
Check the settings of the pressure transmitter/switch (3) set
CP9
at min. inlet pressure (page 11).
Check that all pressure indicators (PI) are selected to be able
CP10
to measure the system pressure range (page 11).
Check that the coupling is installed according to manufac-
CP 11
turers instruction
Ensure all pipings have been flushed and are correct installed
CP12
Check piping for possible air gaps.
CP13
transportation, handling, lifting and storage, chapter 4.
See Data sheet or Instruction, appendices 1 and 2.
≥ 5000) See Danfoss requirements in
10
Data sheet and Instruction, appendices 1 and 2
motor and VFD.
See Data sheet for the used safety circuit.
See Data sheet for the used equipment.
See Data sheets for the used valves.
See Data sheet or Instruction, appendices 1 and 2.
Scaling should at least be 1 bar or more precise.
5.7 Lifting and positioning
Lift the pump unit onto base (Remember vibration dampeners, if needed). Fasten the motor to the base.
See also chapter 4, Arrival inspection, transporta­tion, handling, lifting and storage.
5.8 Mount the different equipment
(connections, pipes, tubes, check and safety/relief valves, etc.)
The hard piping and flexible hoses used, must be of proper design and must be installed in accordance with the manufactur­er’s recommendations. (see also Design guides 180R9084 and 180R9367 - both available on hpp.danfoss.com).
Misalignment of the hard pipes may give unintended stress on the pump port connections and may damage the pump.
Prevent excessive external pipe load.
Do not connect piping by applying external force (use of wrenches, crane, etc.) Piping must be aligned without residual stress.
Do not mount expansion joints so that their force applies internal pressure on the pump connections.
5.9 Electrics
All electrical installation work must be carried out by authorized personnel in accordance with EN60204-1 and/or local regulations. (see also Safety, chapter 2)
Turn off the safety circuit breaker and lock it.
Mount the power cable on the electric motor.
If a VFD is used, adjust the protective motor switch/VFD to the current limits found on the name plate of the electric motor.
5.10 Instrumentation
The pressure switch/sensor should be mounted as close to the pump as possible. It is recom­mended to test the pressure/sensor switch via an instrumentation manifold.
Mount the pressure switch/sensors according to the manufacturer’s instructions.
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701 | 11
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
5.11 Connections
Mount and tighten connections and check valve(s) as specified. Danfoss check valve VCM 92 comes with a flange connection that is easily mounted directly on the outlet port (outlet connection is not required). Note: Bolts (ref. 11) must be tightened with torque 95Nm ± 9.5 Nm. Use only Style 77DX coupling or equivalent for the 3” victaulic OSG outlet on the VCM 92.
95 Nm ± 9.5 Nm
5.12 Ensure free flow
Ensure free flow from the safety/relief valves 8 and 9 (schematic1, page 10). A blocked safety/ relief valve can cause excessive build-up of pressure and thereby cause dangerous situations and damage to the whole system.
5.13 Verify setting of safety/relief valves
Make sure, the safety/relief valves 8 and 9 are placed correctly.
Check the pressure settings on the name plates of the safety/relief valves. If they are within specifications, you can continue.
Unlock the safety circuit breaker. Start the motor for 1 second and observe the direction of rotation either looking at the fan of the motor or the coupling through the inspection hole in the bell housings (not available on all bell housings). If the motor is turning the wrong direction, switch two phases in the connection box of the motor or reprogram the direction in VFD.
When the motor is turning in the right direction, the pump can be mounted.
5.17 Commissioning
Close all the bleeding and draining plugs.
Open the pressure valve at the brine site.
Switch the safety circuit breaker on for both motor(s) and VFD(s).
Start the feed pump.
Start the high-pressure pump.
If a VFD or a soft starter is used, a ramp up time of minimum 10 seconds is required to avoid damage of the pump.
Monitor the inlet and outlet pressure of the high-pressure pump and look for leakages.
Check the function of the pressure indicators by slowly closing the valves. The pump unit should stop when the minimum inlet pressure and maximum outlet pressure has been reached.
Adjust the pressures to the specified inlet and outlet pressure for the system and let the pump unit run until the electric motor and pump temperature is stable.
If the system is running within the system design limits, the system is released for operation.
5.14 Flush the pump
Fully open the pressure valve at the brine outlet.
Close all the bleeding and draining plugs on the high-pressure pump.
Start the feed pump and ensure free flow to the high-pressure pump.
5.15 Bleed and remove air from the pump
Open the bleeding plugs. Keep the plugs open until the high-pressure pump is bleeded.
5.16 Verify direction of rotation
The direction of rotation must always follow the arrow. The arrow is placed on the pump or pump unit.
Check the direction of rotation before mounting the pump.
5.18 Check the filter condition
Evaluate contamination found in filter, replace filter elements, if necessary.
5.19 Instruct operator and maintenance personnel
Before using the pump/pump unit, the personnel must be instructed in using the pump/pump unit, its function, components, documentation and safety.
Danfoss offers commissioning and service at system manufacturer’s location. Rate quotes are offered upon request.
12 | © Danfoss | DCS (im) | 2021.12 180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
© Danfoss | DCS (im) | 2021.12
6. Operation of pump unit
6.1 General safety information
Before inspecting the pump unit, read the Safety chapter 2 in this user manual.
6.2 What to listen and look for
If one or more of the following examples are observed, please act as indicated:
A) Loose bolts – check all bolts and, if
necessary, contact the maintenance department in order to have all bolts tightened to the specified torque(s).
B) Leakage – if a small leakage from the bell
housing is observed. Contact the mainte­nance department.
C) Leakage – if there is a large leak, the unit
should be stopped immediately. Contact the maintenance department.
D) High frequency tones – safety/relief valves
are either damaged or running very close to their design pressure, stop the unit immediately. Contact the maintenance department.
E) Increased noise or vibration – requires the
unit to be stopped immediately. Contact the maintenance department.
F) Very high temperatures – may indicate that
one or more parts are damaged inside the pump. The pump must be stopped immediately and inspected before it is restarted. Contact the maintenance department.
G) Drop in flow and/or pressure – may indicate
wear on one or more parts inside the pump. The pump must be stopped immediately and inspected before it is restarted. Contact the maintenance department.
H) Other observations or troubles, please see
appendix 7, Right and Wrong or appendix 6, the Trouble shooting guide. Both appendices give good advises regarding design, installation, wiring and troubleshooting. See also service and warranty section in appendix 1, Data sheet and appendix 2, Instruction.
If the pump is not stopped for inspection as recommended, it can lead to damage of the pump or break-down. See also service and warranty section in the appendix 1, Data sheet, in appendix 2, Instruction or appendix 4, Instruction for recommended service intervals.
Danfoss offers service of the pump at the system manufacturer’s location as well as we offer training in how to service the pump. Quotes are offered upon request.
Danfoss recommends simultaneously to check the filter and membrane condition and to evaluate contamination; filter and membrane elements must be replaced if necessary.
7. Maintenance and service of the pump unit
7.1 General safety information
Before servicing the pump unit, it is necessary to read and understand this user manual, especially the Safety, chapter 2. Remember to wear suitable safety equipment according to Safety, chapter 2.
7.2 Service and inspection interval for the pump
Maintenance and service intervals are depending on the cleanliness level of the water, hydraulic load and temperature of the pump unit. The most important parameter is the filtration of the water.
See the section Service and warranty in the appendix 1, Data sheet, in appendix 2, Instruc­tion and appendix 4, Instruction for recom­mended service intervals.
For spare parts and service tools, please see appendix 5, Parts list.
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701 | 13
Danfoss offers service of the pump at the system manufacturer’s location and training in how to service the pump. Quotes are offered upon request.
7.3 Shut down of the system
A) Stop the high-pressure pump.
B) Open the pressure valves at the brine site
to release the pressure.
C) Stop the feed pump.
D) Switch off the safety circuit breaker for
both the high-pressure pump, feed pump and VFD and lock them. Only personnel servicing the pump unit should be able to unlock/activate the switch again.
E) Open bleeding and drain plugs. Wait until
the pump and system are emptied for water.
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
F) Make sure the system is not pressuized! Slowly unscrew and remove the bolts and
gaskets from the inlet/outlet hoses or pipes, be careful about jets of water. Beware that the system can be pressur­ized!
G) Attach the lifting equipment to the pump
unit. For instructions on lifting the complete pump unit, see chapter 4, Arrival inspection, transportation, handling, lifting and storage.
H) For the small pumps, unscrew the bolts
holding the pump to the bell housing. For the bigger pumps, unscrew the bolts/nuts from the pump and bell housing to the motor. Afterwards unscrew the bolts/nuts holding the pump and bell housing.
I) Carefully pull the pump out of the bell
housing by using lifting equipment, if necessar y.
J) Hold the pump in different positions above
a drip tray; this should allow most of the water trapped in the pump to drain. Clean and dry the pump surface and plug the bleeding and draining plugs.
K) Move the pump to a clean and safe location
where the pump can be inspected/ serviced.
7.4 Disassembling and assembling the pump unit
A) Remove all connections from the pump.
Returns without a return number will be
rejected !!!
7.5 Assembling the pump unit
Assemble the pump according to the Dis­assembling and Assembling Instruction (available at hpp.danfoss.com).
7.6 Procedure for mounting the pump onto the electric motor
Mount the flexible coupling and bell housing according to appendix 2, Instruction.
7.7 Getting the pump unit back into operation
Find instructions of how to put the pump unit back into operation in chapter 4, Arrival inspec­tion, transportation, handling, lifting and storage and Installation and commissioning, chapter 5.
B) Disassemble the pump according to the
Disassembling and Assembling Instruction (available at hpp.danfoss.com)
Clean all parts and surfaces with a fluid
compatible with the materials found in the pump. Wipe the parts clean and dry with a lint-free clothing.
C) Inspect all parts including shaft seal and if
necessary, replace them; see appendix 5, Parts list.
D) If the pump is going to be returned to
Danfoss for repair or a warranty claim, it is important to contact Danfoss in order to receive a return number and a form to fill out with product information. A copy of the form together with contact information and reason for returning should be sent to the email address on the form. The same documents should be attached to the shipment.
14 | © Danfoss | DCS (im) | 2021.12 180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
7.8 Storage of the pump
If the pump has to be shut down for a longer period, instructions can be found in appendix 2, Instruction.
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
© Danfoss | DCS (im) | 2021.12
8. Troubleshooting and scrapping criteria
8.1 General safety information
Before inspecting the pump unit, it is necessary to read and understand this user manual, especially the Safety chapter 2.
Remember to wear suitable safety equipment according to Safety chapter 2.
If water is leaking into the electric motor; it can cause electric shock, fire, short circuit or even death. When mounting the pump vertically always mount the motor above the pump to avoid water leaking into the electric motor.
8.2 Operational conditions which can cause pump failures
The following conditions can cause a pump failure :
The pump is running dry.
The inlet pressure is too high.
The inlet pressure is too low.
The temperature of the fluid is too high.
The ambient temperature is too high.
The pump is running against a blocked port/closed manual valve.
The pump is operating at a pressure out of specification.
The pump is running with a non-specified/ approved fluid.
The pump is running in the wrong direction.
The filtration is insufficient.
The pump is not being serviced according to Danfoss specifications (end of life).
There is excessive mechanical load on the shaft coupling and piping.
8.3 Mechanical failure
If the pump is running dry, the temperature will quickly increase which can cause burns.
If there is any leakage at start-up or during operation, a high-pressure jet can cause eye or skin damage.
Leakage can result in flooding, which can cause slipping, tripping or falling.
8.4 Electrical failure
If the wiring of the electric motor is incorrect or the ground connection is missing, it can cause electric shock, burn damages, fire or even death.
If a VFD is used and wrongly programmed, it can damage the pump and lead to high tempera­tures or other dangers.
All electrical installation must be carried out by authorized personnel in accordance with EN60204-1 and/or local regulations.
8.5 Responsibility
Danfoss takes no responsibility for any abnormal injuries, risks or damages that could arise caused by abnormal conditions, vibrations, corrosion, abrasives, foreign objects or excessive tempera­tures and shall not be liable for any consequen­tial or incidental damages.
8.6 Scrapping criteria
Whether the pump can be repaired or need to be scrapped, depends on in which conditions the internal parts are, or how damaged the whole unit is. Please use appendix 6, Trouble shooting guide as guideline or send the pump to Danfoss headquarter in Denmark for evaluation.
For other observations or troubles, please see appendix 7, Right and Wrong which gives good advises regarding design, installation, wiring and troubleshooting.
In case the pump needs to be scrapped, please follow your local environmental rules.
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701 | 15
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
16 | © Danfoss | DCS (im) | 2021.12 180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
Operation guide
APP pumps APP 53 / APP 65 / APP 78 / APP 86 / APP 92
Appendices for Installation, Operation and Maintenance Manual
hpp.danfoss.com
Operation guide | Installation, Operation and Maintenance APP 53-92 pumps
Table of Contents
Appendices .......................................................................................17
1. Data sheet for APP pumps 53-92 AI167386503010en-0013
2. Instruction for APP pumps 53-92 (180R9368) ............................................43
3. Electric motors (180R9230) ..............................................................55
4. Bowex coupling manual .................................................................61
5. Recommended service intervals (AX281930801330en-000401) ..........................85
6. Parts list (AX191786502906en-001101) ...................................................89
7. Trouble shooting (521B1447) ...........................................................101
8. Right and wrong (180R9042) ..........................................................113
01) ...........................19
18 | © Danfoss | DCS (im) | 2021.12 180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
Data sheet
Data sheet
APP Pumps
APP pumps
APP 53 / APP 65 / APP 78 / APP 86 / APP 92
APP 53-86
hpp.danfoss.com
ro-solutions.com
Data sheet | APP 53-92 Pumps
Table of Contents
1. Introduction ...........................................................................21
2. Benefits................................................................................21
3. Application examples ..................................................................21
4 Technical data .........................................................................22
4.1 APP 53-92..............................................................................22
5. Performance curves....................................................................24
5.1 APP 53 flow at different rpm............................................................24
5.2 APP 65 flow at different rpm............................................................25
5.3 APP 78 flow at different rpm............................................................26
5.3 APP 86 flow at different rpm............................................................27
5.4 APP 92 flow at different rpm............................................................28
6. Flushing valve curves ..................................................................29
6.1 APP 53-92 integrated flushing valve ....................................................29
7. Motor requirements....................................................................29
7.1 Calculation factor at 60 barg / 870 psig for APP 53-92 ...................................29
8. Temperature and corrosion.............................................................30
8.1 Operation..............................................................................30
9. Installation.............................................................................30
9.1 Filtration...............................................................................31
9.2 RO system with direct supply: ..........................................................31
10. Dimensions and connections...........................................................33
10.1 APP 53.................................................................................33
10.2 APP 65 - 92.............................................................................34
10.3 APP 53-92 with IE3 motor, IEC 315S - 4 ..................................................36
10.4 APP 53-92 with IE3 motor, IEC 315M - 4..................................................36
10.5 APP 53-92 with IE3 motor, IEC 315L 1-4 .................................................37
10.6 APP 53-92 with IE3 motor, IEC 315L 2 - 4 ................................................37
11. Pump connections .....................................................................38
11.1 APP 53 - 92.............................................................................38
12. VCM 3” Victaulic........................................................................39
12.1 Technical data .........................................................................39
12.2 Flow versus pressure ...................................................................40
13. Accessories ............................................................................41
14. Service and warranty...................................................................41
20 | © Danfoss | DCS (im) | 2021.12
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
Data sheet | APP 53-92 Pumps
1. Introduction
The Danfoss range of APP high-pressure pumps is designed according to EN 809 for use in RO applications with low viscosity and corrosive fluids such as sea water. Danfoss APP pumps are positive displacement pumps with axial pistons that move a fixed amount of water in each cycle. Flow is propor­tional to the number of input shaft revolutions (rpm).
1 Housing 2 Shaft 3 Swash plate (non drive end) 4 Retainer plate 5 Piston 6 Cylinder barrel 7 Bleeding / drain plug 8 Valve plate 9 Port plate (non drive end)
Unlike centrifugal pumps, they produce the same flow at a given speed no matter what the discharge pressure. The sectional drawing below illustrates the main components of the APP 53-92 pump range.
10 Center flange 11 Spring cartridge 12 Eye bolt 13 Port plate (drive end) 14 Swash plate (drive end) 15 Shaft seal 16 Motor flange 17 Flushing valve 18 Tail stock screws
2. Benefits
3. Application examples Danfoss APP pumps are built into a broad range
Zero risk of lubricant contamination:
- Oil lubricants are replaced with the pumped medium, water, so there is no contamination risk from the pump.
Low maintenance costs:
- Efficient design and all-stainless steel
construction ensure exceptionally long life. When Danfoss specifications are met, service intervals of 8,000 hours can be expected. Service is easy, and can be carried out on-site due to the simple design and few parts.
Low energy costs:
- The highly efficient axial piston design provides the lowest energy consumption of any comparable pump on the market.
Easy installation:
- The most compact and lightest design
available.
- The pump can be installed horizon-
tally in different positions rotating it around the shaft (see section 10 for example).
of RO desalination plants around the world:
Containerized solutions for hotels, resorts and residences on islands and in coastal regions
No pulsation dampeners necessary due to extremely low pressure pulsation.
- Powered directly by electric motors or combustion engines (with special coupling).
- All pumps are supplied with an integrated flushing valve that allows the fluid to flow from inlet to the outlet, when the pump is not running.
High reliability:
- All parts are made of high corrosion resistant materials e.g. Duplex (EN1.4462/ UNS S31803) and Super Duplex (EN1.4410/UNS S32750) stainless steel and carbon reinforced PEEK.
Certified quality:
- Available with positive material idenfication (PMI) certification on request.
- ISO 9001, ISO 14001, IAFT 16949
- ATEX certification available for APP S (all Super Duplex) and APP S 674 (API). Please see relevant data sheets.
Mobile systems for humanitarian and military organizations
Onboard systems for ships and yachts
Offshore platforms for the oil and gas industry
Municipal and regional waterworks
© Danfoss | DCS (im) | 2021.12
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701 | 21
Data sheet | APP 53-92 Pumps
4.1 APP 53-924 Technical data
Pump size APP 53/1500 APP 65/1500 APP78 /1500 A PP 8 6/1700 APP 92 /178 0
Code number 180B7806 180B7807 180B7808 180B7809 180B7810
Geometric displacement
Pressure
Max. outlet pressure (MAWP)
Min. inlet operating pressure
Max. inlet operating pressure
Max. inlet pressure peak
Min. outlet pressure
Speed
Min. speed continuous
Max. speed continuous
Flow
Min. flow
700 rpm at max. pressure
1000 rpm at max. pressure
1200 rpm at max. pressure
1500 rpm at max. pressure
1700 rpm at max. pressure
1780 rpm at max. pressure
Efficiency
1000 rpm
1200 rpm
1500 rpm
170 0 rp m
178 0 rp m
cm³/rev. 617 778 888 888 888 in³/rev. 37. 7 47. 3 54.2 54.2 54.2
1)
barg 83 83 83 70 70
psig 1,200 1,200 1,200 1,015 1,015
barg 2 2 2 2.5 3.5
psig 29 29 29 36 50
barg 5 5 5 5 5
psig 73 73 73 73 73
barg 10 10 10 10 10
psig 145 145 145 145 145
barg 30 30 30 30 30
psig 435 435 435 435 435
rpm 700 700 700 700 700
rpm 1,500 1,500 1, 500 1,700 1,780
m³/h 24 32 36 36 36
gpm 106 141 158 158 15 8
m³/h 24 32 36 36 36
gpm 106 141 158 158 15 8
m³/h 35 45 52 52 52
gpm 15 4 198 228 228 228
m³/h 42 54 62 62 62
gpm 187 238 275 275 275
m³/h 53 68 78 78 78
gpm 235 299 345 345 345
m³/h 88 88
gpm 387 387
m³/h 92
gpm 405
3)
% 88 88 89 89 89
3)
% 89 89 90 89 89
3)
% 88 89 89 88 88
3)
% 88 88
3)
% 87
22 | © Danfoss | DCS (im) | 2021.12
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
Data sheet | APP 53-92 Pumps
Pump size APP 53/150 0 APP 65/15 00 APP 78/1500 APP 86/1700 APP 92 /1780
Code number 180B7806 180B7807 180B7808 180B7809 18 0B7810
Technical specifications
2)
Media temperature
Ambient temperature
Weight (dry)
Weight (operation)
°C 2–50 2-50 2–50 2-50 2-50
°F 36–122 36-122 3 6–122 36-122 36-12 2
°C 0–50 0-50 0–50 0-50 0-50
°F 32–122 32-12 2 32–122 32-12 2 32-122
kg 196 196 196 19 6 196
lb 432 432 432 432 432
kg 204 204 204 204 204
6)
lb 450 450 450 450 450
Sound pressure level
Footprint with IE3 motor
db(A) 84-95 84-95 84-93 84-96 84-96
1.49 1.49 1. 50 1.50 1.50
4)
Foot² 16.0 17. 0 16.1 16.1 16.1
Typical motor size
Max.speed at max. pres-
5)
sure
1)
Max. allowable working pressure at continuous operation. The pump is designed according to EN809, i.e. to
withstand hydrostatic test pressure (HTP) of 1.3 x MAWP. For lower and higher pressure, please contact Danfoss.
2)
Dependent on the NaCI concentration.
3)
Typical efficiency at max. pressure after a system has been commissioned and run in.
4)
Maximum area covered with recommended IE3 motor configurations (excl. of space to service pump)
5)
IE3 and NEMA motors, 4-pole, current insulated ND non drive end bearing
6)
Operating with water
kW 132 16 0 160 200 200
HP 200 250 250 300 300
© Danfoss | DCS (im) | 2021.12
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701 | 23
Data sheet | APP 53-92 Pumps
100,00
120,00
140,00
160,00
180,00
200,00
220,00
240,00
260,00
280,00
300,00
320,00
340,00
360,00
380,00
400,00
Flow [gpm]
Speed [RPM]
5. Performance curves
If the flow required and the rotation speed (rpm) of the pump is known, it is easy to select the pump, fitting the application best, by using the diagram below.
5.1 APP 53 flow at different rpm
90,00
85,00
80,00
75,00
70,00
65,00
60,00
55,00
50,00
Flow [m3/h]
45,00
40,00
35,00
30,00
25,00
20,00
Furthermore, this diagram shows that the flow can be changed by changing the rotation speed of the pump. The flow/rpm ratio is constant, and the “required” flow can be obtained by changing the rotation speed to a corresponding value. Thus, the required rpm can be determined as:
Required flow x Rated rpm
Required rpm =
Rated flow
24 | © Danfoss | DCS (im) | 2021.12
Speed [RPM]
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
Data sheet | APP 53-92 Pumps
20,00
25,00
30,00
35,00
40,00
45,00
50,00
55,00
60,00
65,00
70,00
75,00
80,00
85,00
90,00
Flow [m3/h]
Speed [RPM]
100,00
120,00
140,00
160,00
180,00
200,00
220,00
240,00
260,00
280,00
300,00
320,00
340,00
360,00
380,00
400,00
Flow [gpm]
Speed [RPM]
5.2 APP 65 flow at different rpm
© Danfoss | DCS (im) | 2021.12
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701 | 25
Data sheet | APP 53-92 Pumps
20,00
25,00
30,00
35,00
40,00
45,00
50,00
55,00
60,00
65,00
70,00
75,00
80,00
85,00
90,00
Flow [m3/h]
Speed [RPM]
5.3 APP 78 flow at different rpm
26 | © Danfoss | DCS (im) | 2021.12
400,00
380,00
360,00
340,00
320,00
300,00
280,00
260,00
240,00
Flow [gpm]
220,00
200,00
180,00
160,00
140,00
120,00
100,00
Speed [RPM]
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
Data sheet | APP 53-92 Pumps
100,00
120,00
140,00
160,00
180,00
200,00
220,00
240,00
260,00
280,00
300,00
320,00
340,00
360,00
380,00
400,00
Flow [gpm]
Speed [RPM]
5.3 APP 86 flow at different rpm
90,00
85,00
80,00
75,00
70,00
65,00
60,00
55,00
50,00
Flow [m3/h]
45,00
40,00
35,00
30,00
25,00
20,00
Speed [RPM]
© Danfoss | DCS (im) | 2021.12
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701 | 27
Data sheet | APP 53-92 Pumps
20,00
25,00
30,00
35,00
40,00
45,00
50,00
55,00
60,00
65,00
70,00
75,00
80,00
85,00
90,00
95,00
100,00
Fl ow [m3/h]
Speed [RP M]
100,00
120,00
140,00
160,00
180,00
200,00
220,00
240,00
260,00
280,00
300,00
320,00
340,00
360,00
380,00
400,00
420,00
Fl ow [gpm]
Speed [RPM]
5.4 APP 92 flow at different rpm
28 | © Danfoss | DCS (im) | 2021.12
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
Data sheet | APP 53-92 Pumps
6. Flushing valve curves
6.1 APP 53-92 integrated flushing valve
Pressure [barg]
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0
0
100
200
300
400
500
Flow [l/min]
600
The power requirements can be determined using one of the following guiding equations:7. Motor requirements
3
l/min x barg 16.7 x m
/h x barg 0.35x gpm x psig Required power = [kW] or [kW] or Calc. factor Calc. factor Calc. factor
1 hp = 0.75 kW 1 gpm = 3.79 l/min
3
1 m
/h = 4.40 gpm 1 kW = 1.34 hp 1 l/min = 0.26 gpm 1 gpm = 0.23 m
3
/h
7.1 Calculation factor at 60 barg / 870 psig for APP 53-92
Name rpm
APP 53 1500 528
APP 65 150 0 534
APP 78 150 0 534
APP 86 170 0 528
APP 92 178 0 522
Calculation
factor
[Hp]
© Danfoss | DCS (im) | 2021.12
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701 | 29
Data sheet | APP 53-92 Pumps
8. Temperature and corrosion
8.1 Operation
The chart below illustrates the corrosive resistance of different types of stainless steel related to NaCl concentration and temperature.
All wetted parts of the APP pump are made of Duplex or Super Duplex.
º
80
C
Duplex
70
60
50
316L
40
30
20
100
160 1600
1000
10 000
16000
If the water pump is operated at high salinity always flush the water pump with fresh water at operation stop in order to minimize the risk of crevice corrosion.
NaCI vs. temperature
Super Duplex
-
100 000
160000
CI ppm
NaCI ppm
9. Installation See example below on how to mount the pump and connect it to an electric motor or combus­tion engine (special coupling). For further instruction on installation of coupling see APP Pump Instruction 180R9368.
If alternative mounting is required. please contact your Danfoss sales representative for further information.
Note: Do not add any axial or radial loads to the pump shaft.
30 | © Danfoss | DCS (im) | 2021.12
180R9346 | IOM APP 53-92 pumps | AQ240486503020en-001701
Loading...
+ 90 hidden pages