The design of the system must ensure that
self-emptying of the pump during standstill is
avoided.
The inlet pressure of the pump must never
exceed the outlet pressure. This may typically
occur in boosted or open-ended systems with
direct water supply.
2.1 Open-ended systems with direct water
supply
Axial piston pumps require a certain inlet
pressure to perform as intended. Please nd min.
required feed pressure in the pump data sheet.
Please also note that feed pressure must not
exceed 5 barg (72.5 psig).
2.2
Preferred RO system design without ERD
1. Dimension the inlet line to obtain minimum pressure loss (large ow, minimum
pipe length, minimum number of bends/
connections, and ttings with small
pressure losses).
2. Place an inlet lter (1) in front of the APP
pump (2). Please consult Danfoss lter data
sheet for guidance on how to select the
right lter. Thoroughly clean pipes and
ush system prior to start-up.
3. Place a monitoring pressure switch (3) set
at min. inlet pressure between lter and
pump inlet. The monitoring switch must
stop the pump at pressures lower than
minimum pressure.
4. Use exible hoses (4) to minimize vibrations
and noise.
5. In order to eliminate the risk of damage
and cavitation, a positive pressure at the
inlet (5) is always to be maintained at min.
inlet pressure and max. inlet pressure.
To protect the pump from being damaged by
peaks of high-pressure in case the pump stops
momentarily, it is required to mount a lowpressure relief valve on the inlet line.
Note: The inlet connection must be properly
tightened, as possible entrance of air will cause
cavitation.
It is recommend to install safety valve or a
pressure relief valve (9) in order to avoid
high-pressure peaks in case the pump stops
momentarilly or is spinning backwards.
6. For easy system bleeding and ushing, a
bypass non-return valve (6) is integrated in
the APP pump.
7. A non-return valve (7) in outlet can be
installed in order to avoid backspin of the
pump. The volume of water in the membrane vessel works as an accumulator and
will send ow backwards in case of the
pump stops momentarily.
8. A safety valve or a pressure relief valve (8)
can be installed in order to avoid system
damage as the Danfoss APP pump creates
pressure and ow immediately after startup, regardless of any counter pressure.
Note: If a non-return valve is mounted in the
inlet line, a low-pressure relief valve is also
required between non-return valve and pump
as protection against high-pressure peaks.
For P&ID of a setup with an iSave, please see the
iSave® Data sheet 521B1378
2.4 Preferred RO system design with pumps
and ERDs in parallel
For systems with Danfoss pumps and ERDs in
parallel, please see our publication 180R9354,
Guideline for Parallel-coupled pumps and ERD.
2.5 Reversible pumps
If exposed to high-pressure in the outlet while
the electric motor is not energized, the pumps
may start spinning backwards. This will not harm
the pumps as long as the pressure in the inlet
does not exceed the max. pressure peak of
10 barg(145 psig).
If a non-return valve is mounted in the inlet line,
a low-pressure relief valve is required as protection against high-pressure pulses and high-pressure in general.
Alternatively a high-pressure check valve can be
mounted in the pump discharge line to prevent
the pump from reversing.
The setup of “open-end system” ensures that the
inlet pressure does not exceed 10 barg (145 psig),
when a nonreturn valve is mounted in the inlet.
2.6 General comments
A good ltration is vital to ensure a long and
trouble-free life of the pump.
As water has very low viscosity, the APP pumps
have been designed with very narrow clearance
in order to control internal leakage rates and
improve component performance. Therefore it is
important that the inlet water is ltered properly
to minimize the wear of the pump.
The main lter must have a ltration eciency of
99.98% at 10 μm. We recommend to use
precision depth lter cartridges rated 10 μm abs.
β10 ≥ 5000 (equivalent to a ltration eciency of
99.98%). Bag lters and string wounded lter
cartridges typically have only 50% ltration
eciency. This means that for each 100,000 particles reaching the lter, 50,000 particles pass
through it compared to only 20 particles in a
lter with an eciency of 99.98%.
For more information on the importance of
proper ltration, please see our data sheet
521B1009 on “Filtration”, which also will provide
you with an explanation of ltration denitions
and a guidance on how to select the right lter.
Monitoring
It is recommended to continuously monitor the
following conditions:
• Filter clogging
• Pressure (inlet- and outlet side of the
pump)
3. Building up the
pump unit with BoWex
coupling
3.1 Assembly of the coupling
We recommend to inspect bores, shaft,
keyway and feather key for dimensional
accuracy before assembly.
Heating the hubs lightly (approx. 80 °C)
allows for an easier mounting on the
shaft.
Please pay attention to the ignition risk
in potentially explosive atmospheres!
3.2 Alignment between the motor and pump shaft
Touching the heated hubs causes
burns.
Please wear safety gloves.
With the assembly please make sure
that the spline of the hub is fully covered by the internal spline of elastomer (please observe mounting dimensions L
may cause damage to the coupling.