Danfoss APP 53, APP 65, APP 78, APP 86, APP 92 Installation guide

Instruction
APP Pump Instruction APP 53 / APP 65 / APP 78 / APP 86 / APP 92
hpp.danfoss.com
Instruction | APP Pump Instruction APP 53-92
Table of Contents
1. Identication ...........................................................................2
2. System design ..........................................................................3
2.1 Open-ended systems with direct water supply...........................................3
2.2
Preferred RO system design without ERD ..................................................3
2.3 Preferred RO system design with ERD....................................................4
2.4 Preferred RO system design with pumps and ERDs in parallel.............................4
2.5 Reversible pumps .......................................................................4
3. Building up the pump unit with BoWex coupling.........................................4
3.1 Assembly of the coupling ...............................................................4
3.2 Alignment between the motor and pump shaft..........................................4
3.3 Overall assembly with coupling BoWex-ELASTIC®, type HEW compact ....................5
3.3.1 Mounting ...............................................................................6
3.4 Direction of rotation ....................................................................7
3.5 Orientation .............................................................................7
3.6 Protection from too high pressures ......................................................7
4. Building up the pump unit with jaw coupling ............................................7
4.1 Mounting...............................................................................7
4.2 Connections ............................................................................8
5. Initial start-up ...........................................................................9
6. Operation..............................................................................10
6.1 Temperature...........................................................................10
6.2 Pressure ...............................................................................10
6.3 Dry running............................................................................10
6.4 Disconnection .........................................................................10
6.5 Storage ................................................................................11
1. Identication
7. Service and warranty...................................................................11
PUMP
Type APP 78 Code no. 180BXXXX
Serial no. XXXXXX08-XXX
MADE IN DENMARK
Danfoss A/S, 6430 Nordborg, Denmark
2 | © Danfoss | DCS (im) | 2021.05 AN220686503013en-000901 | 180R9368 | 521B1392
Instruction | APP Pump Instruction APP 53-92
2. System design
The design of the system must ensure that self-emptying of the pump during standstill is avoided.
The inlet pressure of the pump must never exceed the outlet pressure. This may typically occur in boosted or open-ended systems with direct water supply.
2.1 Open-ended systems with direct water supply
Axial piston pumps require a certain inlet pressure to perform as intended. Please nd min. required feed pressure in the pump data sheet. Please also note that feed pressure must not exceed 5 barg (72.5 psig).
2.2
Preferred RO system design without ERD
1. Dimension the inlet line to obtain mini­mum pressure loss (large ow, minimum pipe length, minimum number of bends/ connections, and ttings with small pressure losses).
2. Place an inlet lter (1) in front of the APP pump (2). Please consult Danfoss lter data sheet for guidance on how to select the right lter. Thoroughly clean pipes and ush system prior to start-up.
3. Place a monitoring pressure switch (3) set at min. inlet pressure between lter and pump inlet. The monitoring switch must stop the pump at pressures lower than minimum pressure.
4. Use exible hoses (4) to minimize vibrations and noise.
5. In order to eliminate the risk of damage and cavitation, a positive pressure at the inlet (5) is always to be maintained at min. inlet pressure and max. inlet pressure.
To protect the pump from being damaged by peaks of high-pressure in case the pump stops momentarily, it is required to mount a low­pressure relief valve on the inlet line.
Note: The inlet connection must be properly tightened, as possible entrance of air will cause cavitation.
It is recommend to install safety valve or a pressure relief valve (9) in order to avoid high-pressure peaks in case the pump stops momentarilly or is spinning backwards.
6. For easy system bleeding and ushing, a bypass non-return valve (6) is integrated in the APP pump.
7. A non-return valve (7) in outlet can be installed in order to avoid backspin of the pump. The volume of water in the mem­brane vessel works as an accumulator and will send ow backwards in case of the pump stops momentarily.
8. A safety valve or a pressure relief valve (8) can be installed in order to avoid system damage as the Danfoss APP pump creates pressure and ow immediately after start­up, regardless of any counter pressure.
Note: If a non-return valve is mounted in the inlet line, a low-pressure relief valve is also required between non-return valve and pump as protection against high-pressure peaks.
Feed
Media filter
PI
PI
PI PI
Fresh water
permeat flush
PT
M
PI
PI
Brine
Permeate
© Danfoss | DCS (im) | 2021.05 AN220686503013en-000901 | 180R9368 | 521B1392 | 3
Instruction | APP Pump Instruction APP 53-92
2.3 Preferred RO system design with ERD
For P&ID of a setup with an iSave, please see the iSave® Data sheet 521B1378
2.4 Preferred RO system design with pumps and ERDs in parallel
For systems with Danfoss pumps and ERDs in parallel, please see our publication 180R9354, Guideline for Parallel-coupled pumps and ERD.
2.5 Reversible pumps
If exposed to high-pressure in the outlet while the electric motor is not energized, the pumps may start spinning backwards. This will not harm the pumps as long as the pressure in the inlet does not exceed the max. pressure peak of 10 barg(145 psig).
If a non-return valve is mounted in the inlet line, a low-pressure relief valve is required as protec­tion against high-pressure pulses and high-pres­sure in general.
Alternatively a high-pressure check valve can be mounted in the pump discharge line to prevent the pump from reversing.
The setup of “open-end system” ensures that the inlet pressure does not exceed 10 barg (145 psig), when a non­return valve is mounted in the inlet.
2.6 General comments
A good ltration is vital to ensure a long and trouble-free life of the pump.
As water has very low viscosity, the APP pumps have been designed with very narrow clearance in order to control internal leakage rates and improve component performance. Therefore it is important that the inlet water is ltered properly to minimize the wear of the pump.
The main lter must have a ltration eciency of
99.98% at 10 μm. We recommend to use precision depth lter cartridges rated 10 μm abs. β10 ≥ 5000 (equivalent to a ltration eciency of
99.98%). Bag lters and string wounded lter cartridges typically have only 50% ltration eciency. This means that for each 100,000 parti­cles reaching the lter, 50,000 particles pass through it compared to only 20 particles in a lter with an eciency of 99.98%.
For more information on the importance of proper ltration, please see our data sheet 521B1009 on “Filtration”, which also will provide you with an explanation of ltration denitions and a guidance on how to select the right lter.
Monitoring
It is recommended to continuously monitor the following conditions:
Filter clogging
Pressure (inlet- and outlet side of the pump)
3. Building up the pump unit with BoWex coupling
3.1 Assembly of the coupling
We recommend to inspect bores, shaft, keyway and feather key for dimensional accuracy before assembly.
Heating the hubs lightly (approx. 80 °C) allows for an easier mounting on the shaft.
Please pay attention to the ignition risk in potentially explosive atmospheres!
3.2 Alignment between the motor and pump shaft
Touching the heated hubs causes burns. Please wear safety gloves.
With the assembly please make sure that the spline of the hub is fully co­vered by the internal spline of elasto­mer (please observe mounting dimen­sions L may cause damage to the coupling.
). Disregarding this advice
coupling
max. 0. 5 mm
max. 0.02 in ch
4 | © Danfoss | DCS (im) | 2021.05 AN220686503013en-000901 | 180R9368 | 521B1392
Instruction | APP Pump Instruction APP 53-92
3.3 Overall assembly with coupling BoWex-ELASTIC®, type HEW compact
Danfoss recommends to use a Bowex Elastic HEW Compact Coupling. See the Coupling Manual from BoWex.
1: Bolts 190 Nm ± 10 2: Nuts 100 Nm ± 10
3: Torque see ta ble
Component
Thread size M5 M6 M8 M10
Torque [Nm] 2 4.8 10 17
Quantity Description
1 1 Elastomer part
2 1 Hub
4 1 Coupling ange
5
10
7 2
Cap screws DIN EN ISO 4762
Setscrews DIN EN ISO 4029
© Danfoss | DCS (im) | 2021.05 AN220686503013en-000901 | 180R9368 | 521B1392 | 5
Instruction | APP Pump Instruction APP 53-92
3.3.1 Mounting
1. Mount the coupling ange (component 4) in front of the elastomer part (component
1) and screw the components together with a tightening torque of 120 Nm. Lubricate inside the coupling hubs (not the shafts).
If used in potentially explosive atmos­pheres the setscrews to fasten the hubs as well as all screw connections must be secured against working loose addition­ally, e.g. conglutinating with Loctite (average strength).
Please observe the manufacturer’s instructions regarding the use of adhe­sives. Do not apply glue on the rubber surfaces.
2. Mount the bell housing on pump. Secure nuts with the right torque.
3. Push the coupling part all the way down to the shoulder of with right torque on the locking screws. Measure the distance “a” from the end of the bell housing to the end of the toothing of the coupling.
4. Mount the coupling on motor shaft without using hammer. If needed then polish motor shaft/key and inside coupling hub.
5. On the motor shaft position the coupling so that the length from the end of the coupling to the end of the motor flange is
“b= a+32.5 mm” ± 2 mm.
6. Secure coupling on motor shaft with the right torques on the locking screws.
7. Connect carefully pump/bell housing to motor. Turn motor shaft so coupling tooths can interact.
8. Mount motor flange bolts to bell housing and tighten with the right torque.
9. Check coupling space. The pump coupling should be in a position so there is still 3-7 mm space.
If alternative mounting is desired, please contact Danfoss High Pressure Pumps.
Please take care to observe the recommended length tolerances of the chosen coupling, as an axial force on the pump will damage the pump.
the pump shaft and secure
b = a + 32.5 mm ± 2 mm
6 | © Danfoss | DCS (im) | 2021.05 AN220686503013en-000901 | 180R9368 | 521B1392
Instruction | APP Pump Instruction APP 53-92
3-5 mm [0.12-0.20 inch]
3.4 Direction of rotation
Is indicated by an arrow engraved in the ange of the pump.
3.5 Orientation
APP 53-92 can be mounted/orientated in steps of
The opening characteristics of the valve must not result in peak pressures higher than 100 barg (1450 psig).
The valve should be placed as close to the pump as possible.
45 degrees. Please see Data sheet 521B1340.
We recommend to install exible soft hoses both
3.6 Protection from too high pressures
in the inlet and outlet lines.
The pump should be protected against too high pressure by means of a safety valve or a pressure relief valve.
The valve outlet must not be connected directly to the pump suction line. It must be connected directly to the drain.
Outlet
Outlet Inlet
4. Building up the pump unit with jaw coupling
D
Inlet
A: Elastic coupling B: Bell housing C: Motor shaft D: Pump ange
4.1 Mounting
1. Mount the coupling ush with the pump shaft end or maximum 1 mm oset from the pump shaft end. Ensure an air gap between coupling parts of 3-5 mm (0.12-0.2 inch).
2. Mount the bell housing on pump. Secure nuts with the right torque.
3. Measure the longest distance “A” from top of bell housing to the button of coupling claw.
IMPORTANT
When using jaw coupling it is critiacal that the recommended measure­ments are kept.
max. 0. 25 mm
max. 0. 01 inch
4. Mount the coupling on motor shaft. Ensure the coupling and motor ange are not in contact with each other.
5. Measure from motor ange to the top of the coupling. That measurement “B” shall be 3-5 mm (0.12-0.2 inch) shorter than the measurement “A”.
(“A” and “B” can be found on the next
page).
© Danfoss | DCS (im) | 2021.05 AN220686503013en-000901 | 180R9368 | 521B1392 | 7
Instruction | APP Pump Instruction APP 53-92
Bolts and nuts torque
6. Adjust respectively, verify the measure­ment, and secure both couplings with the right torques on the locking screws (see coupling operation & mounting instruction).
7. Mount the elastic gear ring and mount the bell housing/pump on the motor. After mounting it must be possible to move the elastic gear ring 3-5 mm (0.12 - 0.2 inch) axial “C”. The check can be done through the inspection hole of bell housing. Secure ange bolts with the right torque.
1: Bolts 100 Nm ± 10 2: Nuts 100 Nm ± 10 3: Torque se table below
75 Nm ± 5 Nm
1
2
C
If alternative mounting is desired, please contact Danfoss High Pressure Pumps.
Choose proper tolerances to ensure an easy mounting of the elastic coupling without use of tools.
Please take care to observe the recommended length tolerances of the chosen coupling, as an axial force on the pump will damage the pump.
3
4.2 Connections
To prevent stray current corrosion we recom­mend grounding of the pump and all other parts in the system. All parts in the system must be electrical potential equalized to a single reference point (grounding point). It is recommended that the electrical resistance in the grounding cable is equal to or below 0.25 Ohm towards the grounding point.
Thread size
Torque [Nm]
M5 M6 M8 M10
2 4.8 10 17
8 | © Danfoss | DCS (im) | 2021.05 AN220686503013en-000901 | 180R9368 | 521B1392
Instruction | APP Pump Instruction APP 53-92
5. Initial start-up
1. Flush inlet line before connecting the pump, to remove possible impurities from pipes, hoses etc.
2. Connect pump inlet to inlet line and ush the pump for 5 min. by means of the internal ushing valve, to remove possible impurities from pipes, hoses etc.
3. Loosen top bleeding plug (see item 3.5) using an allen key (only plugs with internal hexagon sockets). Retighten the plug, when water appears from the bleeding plug.
4. Make sure that the direction of rotation of the electric motor corresponds to the direc­tion of rotation of the pump, show on the pump ange.
5. Now the pump is ready for start-up.
WARNING Make sure that the direction of rotation of the electric motor corresponds to the direction of rotation of the pump. Otherwise the pump will be damaged if a check valve is placed between pump and feed pump.
O
I
Internal ushing valve
© Danfoss | DCS (im) | 2021.05 AN220686503013en-000901 | 180R9368 | 521B1392 | 9
Instruction | APP Pump Instruction APP 53-92
6. Operation
6.1 Te mperat u re
Fluid temperature: Min. +2°C to max. +50°C (Min. +35.6°F to max. +122°F)
Ambient temperature: Min. +2°C to max. +50°C (Min. +35.6°F to max. +122°F)
In case of lower operating temperatures, please contact Danfoss High Pressure Pumps.
NaCl vs. temperature
º
C
80
Duplex
70
60
50
316L
40
The chart below illustrates the corrosive resistance of dierent types of stainless steel related to NaCl concentration and temperature.
The APP water pump is made of Duplex and Super Duplex.
If the water pump is operated above the Super Duplex line, always ush water pump with fresh water at operation stop in order to minimize the risk of crevice corrosion.
Super Duplex
30
20
100
1000
160 1600
6.2 Pressure
The inlet pressure shall be min. 2 barg (30 psig) and max. 5 barg (72.5 psig). At lower pressures the pump will cavitate, resulting in damage of the pump.
Max. inlet pressure peak (e.g. in case the pump stops momentarily) up to 10 barg (145 psig) are acceptable.
Max. pressure on the pump’s outlet line shall be limited at 80 barg (1160 psig) continuously.
For APP 86 min. inlet pressure shall be 2.5 barg (36 psig) and max. outlet pressure shall be 70 barg (1015 psig).
For APP 92 min. inlet pressure shall be 3.5 barg (50 psig) and max. outlet pressure shall be 70 barg (1015 psig).
-
10 000
16000
6.3 Dry running
When running, the pump must always be connected to the water supply in order to avoid damage if it should run dry.
6.4 Disconnection
If the inlet line is disconnected from the water supply, the pump will be emptied of water through the disconnected inlet line.
When starting up again, follow the bleeding procedure described under section 4: Initial start up.
100 000
160000
CI ppm
NaCI ppm
Note: The pump unit should include a pressure gauge on the high-pressure side.
10 | © Danfoss | DCS (im) | 2021.05 AN220686503013en-000901 | 180R9368 | 521B1392
Instruction | APP Pump Instruction APP 53-92
6.5 Storage
Storage temperature: Min. -40°C to max. +70°C (Min. -40°F to max. +158°F)
When preparing the pump for long-term storage at temperatures below the freezing point, ush the pump with an anti-freeze medium type monopropylene glycol to prevent internal corrosion or frost in the pump.
For further information on anti-freeze media, please contact Danfoss High Pressure Pumps.
Recommended procedure:
1. Disconnect the water supply to the pump.
2. Through the lower bleeding plug, empty the pump housing of water and close it again.
3. Connect the pump to a tank containing anti-freeze additive. Connect a hose to the inlet port of the pump and via another hose return the ow from the outlet port to the tank with antifreeze additives.
4. Quickly start and stop the pump. Make sure that the pump does not run dry.
The pump is now protected against
internal corrosion and frost.
Storage:
Storage of pump that have been in operation: For shorter periods of storage ush the pump with permeate by rotating the pump for 10 sec. empty permeate and store. For long term storage (more than 2 months) Danfoss recommends servicing the product and clean any biological growth of the surfaces. Store the pump without water inside.
7. Service and warranty
Warranty
Danfoss APP pumps are designed for long operation, low maintenance and reduced lifecycle costs.
Provided that the pump has been running according to the Danfoss specications, Danfoss guarantees 8,000 hours service-free operation, however, max. 18 months from date of production.
If Danfoss recommendations concerning system-design are not followed, it will strongly inuence the life of the APP pumps. Other factors that aect pump performance and lifetime include:
- Insucient ltration
- Insucient bleeding and venting
- Running the pump at speed outside specications.
- Supplying the pump with water at temperature higher than recommended.
- Running the pump at inlet pressure outside specications.
- Running the pump at outlet pressure outside the specications.
- Wrong direction of rotation.
Pump shutdown:
The APP pumps are made of Duplex/Super Duplex materials with excellent corrosion properties. It is, however, always recommended to ush the pump with freshwater when the system is shut down. When stopping the pump for more than 1 day ush the pump with permeate by rotating the pump for 10 sec. Flushing through the ashing valve of the pump without rotating the pump is not enough for cleaning the inside of the pump. The pump can be ushed with biocide like the membranes. The biocide must be compatible with the materials used in our pump (materials can be found in the parts list in the Service guide and Operating manual).
Repair
In case of irregular function of the APP pump, please contact Danfoss High Pressure Pumps.
Maintenance
After 8,000 hours of operation it is strongly recommended to inspect the pump and change any worn parts, e.g. pistons and shaft seal. This is done in order to prevent a potential breakdown of the pump. If the parts are not replaced, more frequent inspection is recommended according to our guidelines.
© Danfoss | DCS (im) | 2021.05 AN220686503013en-000901 | 180R9368 | 521B1392 | 11
Danfoss A/S
High Pressure Pumps DK-6430 Nordborg Denmark
© Danfoss | DCS (im) | 2021.05
AN220686503013en-000901 | 180R9368 | 521B1392 | 12
Loading...